577C-K Ultra Low NOx Air Conditioner and Gas Furnace System
577C–K Ultra Low NOx: Product Data
577C–K Ultra Low NOx LegacyTM13.4 SEER2 Single-Packaged Air Conditioner and Gas Furnace System with Puron® (R-410A) Refrigerant Single Phase 2-5 Nominal Tons (Sizes 24-60) Three Phase 3-5 Nominal Tons (Sizes 36-60)
Product Data
Fig. 1 Unit 577C
A09033
Single-Packaged Products with Energy-Saving Features and Puron® R-410A refrigerant.
· 13.4 SEER2
· 10.6 EER2
· 81.0% AFUE (Single phase and three phase models)
· ECM Blower Motor-Standard
· Direct Spark Ignition
· Low Sound Levels
· Dehumidification Feature
· Louvered Condenser Coil Guard-Standard
Features/Benefits
One-piece heating and cooling units with low sound levels, easy installation,
low maintenance, and dependable performance.
Puron is Bryant’s unique refrigerant designed to be environmentally balanced.
Puron is an HFC refrigerant which does not contain chlorine that can harm the
ozone layer. The most important advantage of Puron refrigerant is that it has
not been banned in future air conditioning systems as the traditional
refrigerant R-22 has been. Puron refrigerant is in service in millions of
systems proving highly reliable and is non-ozone depleting.
Easy Installation
Factory-assembled package is a compact, fully self-contained, combination gas
heating/electric cooling unit that is prewired, pre-piped, and pre-charged for
minimum installation expense. These units are available in a variety of
standard and optional heating/ cooling size combinations with voltage options
to meet residential and light commercial requirements. Units are lightweight
and install easily on a rooftop or at ground level. The high tech composite
base eliminates rust problems associated with ground level applications.
Innovative Unit Base Design
On the inside a high-tech composite material will not rust and incorporates a
sloped drain pan which improves drainage and helps inhibit mold, algae and
bacterial growth. On the outside metal base rails provide added stability as
well as easier handling and rigging.
Convertible Duct Configuration
Unit is designed for use in either downflow or horizontal applications. Each
unit is converted from horizontal to downflow and includes two horizontal duct
covers. Downflow operation is provided in the field to allow vertical ductwork
connections. The basepan seals on the bottom openings to ensure a positive
seal cin the vertical airflow mode.
Efficient operation high-efficiency design offers SEER2 (Seasonal Energy
Efficiency Ratios) of 13.4, 10.6 EER2, and AFUE (Annual Fuel Utilization
Efficiency) ratings of 81.0%.
Energy-saving, direct spark ignition saves gas by operating only when the room
thermostat calls for heating. Standard units are furnished with natural gas
controls.
Ultra Low NOx units meet California air quality district standards requiring
NOx emissions no more than 14ng/J.
Durable, Dependable Components
Turbo-tubularTM heat exchangers are constructed of stainless steel for
corrosion resistance and optimum heat transfer for improved efficiency. The
tubular design permits hot gases to make multiple passes across the path of
the supply air.
In addition, dimples located on the heat exchanger walls force the hot gases
to stay in close contact with the walls, improving heat transfer.
ECM Blower Motor is standard on all models.
Direct-drive PSC (Permanent Split Capacitor) condenser-fan motors are designed
to help reduce energy consumption and provide for cooing operation down to
40°F (4.4°C) outdoor temperature. Motormaster® II low ambient kit is available
as a field-installed accessory.
Thermostat Controls
Time Guard® II anti-short cycle protection circuitry. If a non-corporate
thermostat without anti-short cycle protection is used the Time Guard II
field-installed anti-short cycle kit is recommended.
Refrigerant system is designed to provide dependability. Liquid filter driers
are used to promote clean, unrestricted operation. Each unit leaves the
factory with a full refrigerant charge. Refrigerant service connections make
checking operating pressures easier.
High pressure switch provides added reliability for the compressor.
Indoor and outdoor coils are computer-designed for optimum heat transfer and
efficiency. The indoor coil is fabricated from aluminum tube and aluminum fins
and is located inside the unit for protection against damage. The outdoor coil
is internally mounted on the top tier of the unit.
Low sound ratings ensure a quiet indoor and outdoor environment with sound
ratings as low as 70.7 dBA.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 1
577C–K Ultra Low NOx: Product Data
Easy to service cabinets provide easy 3-panel accessibility to serviceable
components during maintenance and installation. The basepan with integrated
drain pan provides easy ground level` installation with mounting pad. A
nesting feature ensures a positive basepan to roof curb seal when the unit is
roof mounted. A convenient 3/4-in. (19.05 mm) wide perimeter flange makes
frame mounting on a rooftop easy. Standard horizontal metal duct covers with
insulation come with the unit and cover the horizontal duct openings. These
can be left in place if the units are converted to downflow.
Table of Contents
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . 1 Model Number Nomenclature . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . 3 AHRI Capacities . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Unit
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 7 Unit Dimensions . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . 8 Performance Data . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 25 Electrical Data. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . 26 Connection Wiring
Schematic 208/230-1-60 . . . . . . . . . . . . . . . . . . . . 27 Controls. .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . 31 Guide Specifications . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . 32
Integrated Gas Control (IGC) board provides safe and efficient control of
heating and simplifies trouble-shooting through its built-in diagnostic
function.
Cabinets are constructed of heavy duty, phosphated, zinc-coated prepainted
steel capable of withstanding 500 hours in salt spray. Interior surfaces of
the evaporator/heat exchanger compartment are insulated with cleanable semi-
rigid insulation board, which keeps the conditioned air from being affected by
the outdoor ambient temperature and provides improved indoor air quality.
(Conforms to American Society of Heating, Refrigeration and Air Conditioning
Engineers 62.2.) The sloped drain pan minimizes standing water in the drain.
An external drain is provided.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 2
577C–K Ultra Low NOx: Product Data
Model Number Nomenclature
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in
the program For verification of certification for individual products, go to
www.ahridirectory.org.
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 3
577C–K Ultra Low NOx: Product Data
AHRI* Capacities Cooling Capacities and Efficiencies
UNIT SIZE
24 30 36 42 48 60
NOMINAL TONS
2 2.5 3 3.5 4 5
STANDARD CFM
750 950 1150 1350 1600 1750
COOLING
CAPACITY 22800 28000 33800 39000 47000
EER2
10.6 10.6 10.6 10.6 10.6 10.6
*. Air Conditioning, Heating & Refrigeration Institute. . Rated in accordance with U.S. Government DOE Department of Energy) test procedures and/or AHRI Standards 210/240. . At “A” conditions-80°F (26.7°C) indoor db/67°F (19.4°C) indoor wb & 95°F (35°C) outdoor db. **. Rated in accordance with AHRI Standard 270. Notes: 1. Ratings are net values, reflecting the effects of circulating fan heat. Ratings are based on: Cooling Standard: 80°F (26.7°C) db, 67°F wb (19.4°C) indoor entering-air temperature and 95°F db (35°C) outdoor entering-air temperature. 2. Before purchasing this appliance, read important energy cost and efficiency information available from your retailer. LEGEND dB-Sound Levels (decibels) db–Dry Bulb SEER–Seasonal Energy Efficiency Ratio wb–Wet Bulb COP-Coefficient of Performance
Gas Heating Capacities and Efficiencies, Single and Three Phase Models
Unit Size
Heating Input (Btuh)
Output Capacity (Btuh) Temperature Rise Range °F (°C)
24040 30040
45,000
37,000
25-55 (14-31)
24060 30060 36060 42060
60,000
49,000
25-55 (14-31)
42090 48090 60090
89,000
73,000
35-65 (19-36)
LEGEND
AFUE–Annual Fuel Utilization Efficiency
NOTE: Before purchasing this appliance, read important energy cost and
efficiency information available from your retailer.
A-Weighted Sound Power Level
UNIT SIZE
STANDARD RATING (dBA)
125
TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)
250
500
1000
2000
4000
24
70.7
59.4
58.5
58.3
60.4
56.7
52.6
30
73.4
53.8
59.9
62.3
64.0
61.4
53.8
36
74.8
67.1
60.3
64.3
63.8
61.9
57.1
42
74.9
62.5
63.1
63.7
65.5
61.5
57.5
48
75.4
64.1
61.0
65.5
63.7
61.8
60.1
60
NOTE: Tested in compliance with AHRI 270 but not listed with AHRI.
SEER2** 13.4 13.4 13.4 13.4 13.4 13.4
AFUE (%) 81.0
81.0
81.0
8000 46.9 45.6 50.8 53.5 56.1
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 4
577C–K Ultra Low NOx: Product Data
COIL FILTE R
ECONOMIZER
ECONOMIZER
SIDE VIEW COIL
CAULK BOTTOM CORNER OF ECONOMIZER ON EACH SIDE
FI LTER
ECONOMIZER
FLANGE ON BASE
BASE DETAIL
Vertical Economizer
FILTER RACK
BEND FLANGE AT 90° -SCREW TO DIVIDER WITH 1-IN. (25 mm)SCREW TOP FILTER RACK
EV APORATOR COIL
BOTTOM FILTER RACK
Horizontal Economizer
MANUAL OUTSIDE AIR DAMPER
REPLACEMENT PANEL
MANUAL OUTSIDE AIR HOOD
DAMPER BLADE
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 5
A09375
577C–K Ultra Low NOx: Product Data
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 6
Physical Data
UNIT SIZE
NOMINAL CAPACITY (ton)
SHIPPING WEIGHT lb. SHIPPING WEIGHT (kg)
COMPRESSOR / QUANTITY
REFRIGERANT (R-410A) Quantity lb. Quantity (kg)
REFRIGERANT METERING DEVICE
ORIFICE ID in. / mm
OUTDOOR COIL Rows…Fins/in. Face Area (sq ft)
OUTDOOR FAN Nominal CFM Diameter in. Diameter (mm) Motor Hp (Rpm)
INDOOR COIL Rows…Fins/in. Face Area (sq ft)
INDOOR BLOWER Nominal Cooling Airflow (CFM) Size in. Size (mm.) Motor HP (RPM)
FURNACE SECTION* Burner Orifice No. (Qty…Drill Size) 1 & 3 Phase Ultra Low NOx
Natural Gas (Factory Installed)
HIGH-PRESSURE SWITCH (psig) Cut-out Reset (Auto)
LOSS-OF-CHARGE / LOW-PRESSURE SWITCH (Liquid Line) (psig) cut-out Reset (auto)
24040 2
339 154
6.4 2.9
.059 / 1.5
1..21 11.9
2500 24
609.6 1/12 (810)
3…17 3.7
750 10×10 254×254 1/2 (1050)
1…0.125″ size
RETURN-AIR FILTERS Throwaway Size in. (mm)
24060 2
339 154
30040 2-1/2
348 158
30060
36060
2-1/2
3
348
394
158
179
Scroll / 1
42060 3-1/2
428 194
42090 3-1/2
428 194
48090 4
481 218
6.4 2.9
.059 / 1.5
6.0 2.7
.063 / 1.60
6.0
5.75
2.7
2.6
Orifice
.063 / 1.60 .070 / 1.78
6.0
6.0
2.7
2.7
.073 / 1.85 .073 /1.85
9.0 4.1
.080 / 2.03
1…21 11.9
1…21 13.6
1…21 13.6
1…21 13.6
1…21 13.6
1…21 13.6
1…21 23.3
2500 24
609.6 1/12 (810)
3200 24
609.6 1/5 (810)
3200 24
609.6 1/5 (810)
3500 26
660.4 1/2 (810)
3500 26
660.4 3/4 (810
3500 26
660.4 3/4 (810)
3500 26
660.4 1/5 (810)
3…17 3.7
3…17 3.7
3…17 3.7
2…17 5.6
3…17 4.7
3…17 4.7
3…17 5.6
750 10×10 254×254 1/2 (1050)
950 10×10 254×254 1/2 (1050)
950 10×10 254×254 1/2 (1050)
1150 11×10 279.4×254 3/4 (1000)
1350 11×10 279.4×254 1/2 (1050)
1350 11×10 279.4×254 1/2 (1050)
1600 11×10 279.4×254 1.0 (1075)
1…#28
1…0.125″ size
2 each 20x12x1 508x305x25
1…#28
1…#28
650 +/- 15 420 +/- 25
NA
1 each 24x16x1 610x406x25 24x18x1 610x457x25
1…#28
1…#18
1…#18
1 each 24x14x1 610x356x25 24x16x1 610x406x25
1 each 24x16x1 610x406x25 24x18x1 610x457x25
60090
*. Based on altitude of 0 to 2000 ft (0-610 m). . Required filter sizes shown are based on the larger of the AHRI (Air Conditioning Heating and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 to 350 ft/minute for
throwaway type. Air filter pressure drop for non-standard filters must not
exceed 0.08 IN. W.C. . If using accessory filter rack refer to the filter rack
installation instructions for correct filter sizes and quantity NA – Not
Available
577C–K Ultra Low NOx: Product Data
Unit Dimensions 24-30
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 7
577C–K Ultra Low NOx: Product Data
Unit Dimensions 36-60
A221498
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 8
A221499
577C–K Ultra Low NOx: Product Data
SMALL/COMMON CURB
SUPPLY AIR
SMALL BASE UNIT
RETURN AIR
LARGE BASE UNIT
UNIT PLACEMENT ON COMMON CURB
LARGE CURB
SMALL OR LARGE BASE UNIT
Accessory Dimensions
A180216
Unit Size Catalog Number
A IN. (mm)
B (small / common base)
IN. (mm)*
B (large base) IN. (mm)*
C IN. (mm)
D IN. (mm)
E IN. (mm)
F IN. (mm)
G IN. (mm)
H IN. (mm)
Small or Large
CPRFCURB011B00 14 (356)
Large CPRFCURB013B00 14 (356)
10 (254) 14 (356)
14 (356)
16 (406)
47.8 (1214)
32.4 (822)
43.9 (1116)
30.6 (778) 2.7 (69)
42.2 (1072)
46.1 (1170)
- Part Number CPRCURB011B00 can be used on both small and large basepan units. The cross supports must be located based on whether the unit is a small basepan or a large basepan. NOTES:
1. Roof curb must be set up for unit being installed. 2. Seal strip must be applied, as required, to unit being installed. 3. Roof curb is made of 16-gauge steel. 4. Attach ductwork to curb (flanges of duct rest on curb). 5. Insulated panels: 1-in. (25.4 mm) thick fiberglass 1 lb. density.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 9
577C–K Ultra Low NOx: Product Data
Selection Procedure (With Example)
DETERMINE COOLING AND HEATING REQUIREMENTS AT DESIGN CONDITIONS: Given:
Required Cooling Capacity (TC) …………………………………46,000 Btuh Sensible Heat Capacity
(SHC)…………………………………….34,000 Btuh Required Heating Capacity
…………………………………………72,000 Btuh Condenser Entering Air Temperature ………………………….
95°F (35°C) Indoor-Air Temperature ………………80°F (27°C) edb 67°F (19°C) ewb
Evaporator Air Quantity………………………………………………. 1600 CFM External Static Pressure
………………………………………… 0.440 IN. W.C. Electrical Characteristics
……………………………………………….. 208-1-60 SELECT UNIT BASED ON REQUIRED COOLING CAPACITY
Enter Net Cooling Capacities table at condenser entering temperature of 95°F
(35°C). Unit 48 at 1600 CFM and 67°F (19°C) ewb (entering wet bulb) will
provide a total capacity of 47,000 Btuh and a SHC of 35,000 Btuh. Calculate
SHC correction, if required, using Note 4 under Cooling Capacities tables.
SELECT ELECTRIC HEAT
In the Gas Heating Capacities and Efficiencies table, note that the 48090 unit will provide 73,000 Btuh with an input of 89,000 Btuh.
DETERMINE FAN SPEED AND POWER REQUIREMENTS AT DESIGN CONDITIONS.
Before entering the air delivery tables, calculate the total static pressure required. From the given example, the Wet Coil Pressure Drop Table, and the Filter Pressure Drop Table:
External Static Pressure
0.30 IN. W.C
Filter
0.06 IN. W.C
Wet Coil Pressure Drop
0.07 IN. W.C
Total Static Pressure
0.43 IN. W.C
At 0.43 IN. W.C. ESP (external static pressure) and MED speed the motor delivers between 1664 CFM and 1627 cfm. Interpolation estimates 1653 CFM at .43 IN. W.C. Thus, MED delivers CFM needed.
SELECT UNIT THAT CORRESPONDS TO POWER SOURCE AVAILABLE.
The Electrical Data Table shows that the unit is designed to operate at 208-1-60.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 10
577C–K Ultra Low NOx: Product Data
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 11
Performance Data 24 Size
Evaporator Air
CFM
EWB °F(°C)
75 (23.9) Capacity MBtuh
Total Sens
Total Sys KW**
57 (13.8)
23.62
23.62
1.55
62 (16.6)
24.47
21.38
1.56
700
63* (17.2)
24.99
17.43
1.56
67 (19.4)
27.02
18.13
1.55
72 (22.2)
29.59
14.70
1.55
57 (13.8)
24.74
24.74
1.57
62 (16.6)
25.14
23.06
1.57
800
63* (17.2)
25.59
18.60
1.57
67 (19.4)
27.63
19.36
1.56
72 (22.2)
30.16
15.42
1.56
57 (13.8)
25.69
25.69
1.58
62 (16.6)
25.74
25.74
1.58
900
63* (17.2)
26.07
19.72
1.58
67 (19.4)
28.08
20.52
1.58
72 (22.2)
30.58
16.10
1.58
85 (29.4) Capacity MBtuh Total Sens
Total Sys KW**
21.90 21.90 1.75
22.45 20.24 1.75
22.88 16.39 1.76
24.79 17.09 1.76
27.20 13.77 1.76
22.92 22.92 1.77
23.07 21.80 1.78
23.43 17.53 1.77
25.32 18.28 1.77
27.69 14.48 1.77
23.77 23.77 1.79
23.81 23.81 1.79
23.84 18.62 1.79
25.72 19.42 1.79
28.07 15.15 1.79
Condenser Entering Air Temperatures °F (°C)
95 (35)
105 (40.6)
Capacity MBtuh Total Sens
Total Sys KW**
Capacity MBtuh Total Sens
Total Sys KW**
20.07 20.07 1.95 17.88 17.88 2.14
20.32 19.02 1.96 17.92 17.92 2.14
20.71 15.32 1.96 18.05 14.06 2.15
22.51 16.03 1.98 19.92 14.86 2.20
24.84 12.86 1.99 22.48 11.95 2.24
21.02 21.02 1.99 18.78 18.78 2.19
21.05 21.05 1.99 18.81 18.81 2.19
21.18 16.43 1.99 18.51 15.14 2.18
23.00 17.20 2.00 20.41 16.03 2.24
25.27 13.55 2.01 22.88 12.64 2.26
21.80 21.80 2.01 19.55 19.55 2.23
21.84 21.84 2.01 19.58 19.58 2.23
21.55 17.49 2.01 18.84 16.17 2.20
23.37 18.31 2.02 20.82 17.17 2.26
25.58 14.21 2.02 23.17 13.29 2.28
115 (46.1)
Capacity MBtuh Total Sens
Total Sys KW**
15.87 15.87 2.38
15.90 15.90 2.38
15.56 12.87 2.36
17.28 13.67 2.42
19.68 10.89 2.51
16.65 16.65 2.42
16.68 16.68 2.42
15.93 13.90 2.39
17.67 14.78 2.45
20.12 11.62 2.53
17.32 17.32 2.46
17.35 17.35 2.46
16.24 14.87 2.42
17.98 15.84 2.48
20.45 12.30 2.56
125 (51.7)
Capacity MBtuh Total Sens
Total Sys KW**
14.01 14.01 2.64
14.03 14.03 2.64
13.28 11.77 2.61
14.91 12.59 2.67
17.14 9.92
2.77
14.70 14.70 2.69
14.72 14.72 2.69
13.61 12.73 2.64
15.25 13.64 2.71
17.47 10.60 2.80
15.29 15.29 2.73
15.31 15.31 2.73
13.92 13.92 2.67
15.54 14.63 2.74
17.73 11.25 2.83
577C–K Ultra Low NOx: Product Data
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 12
Performance Data 30 Size
Evaporator Air
CFM
EWB °F(°C)
75 (23.9)
Capacity MBtuh
Total
Sens
Total Sys KW**
Condenser Entering Air Tempeatures °F (°C)
85 (29.4)
95 (35)
105 (40.6)
Capacity MBtuh
Total
Sens
Total Sys KW**
Capacity MBtuh
Total
Sens
Total Sys KW**
Capacity MBtuh
Total
Sens
Total Sys KW**
115 (46.1)
Capacity MBtuh
Total
Sens
Total Sys KW**
57 (13.9)
27.39
27.39
1.98
26.29
26.29
2.20
25.01
25.01
2.44
23.52
23.52
2.69
21.57
21.57
2.94
62 (16.7)
28.22
26.10
1.99
26.84
25.48
2.20
25.28
24.73
2.45
23.38
23.38
2.68
21.59
21.59
2.94
875
63* (17.2)
28.70
21.18
1.99
27.33
20.58
2.20
25.77
19.89
2.45
23.74
19.00
2.69
21.18
17.90
2.93
67 (19.4)
30.96
21.97
2.00
29.59
21.44
2.22
28.06
20.82
2.46
26.21
20.08
2.74
23.74
19.09
3.02
71 (21.7)
33.22
18.60
2.02
31.86
18.10
2.24
30.33
17.53
2.48
28.62
16.90
2.76
26.55
16.13
3.08
57 (13.9)
28.61
28.61
2.01
27.47
27.47
2.22
26.20
26.20
2.47
24.68
24.68
2.75
22.66
22.66
3.00
62 (16.7)
28.93
28.00
2.01
27.59
27.35
2.23
26.34
26.18
2.47
24.72
24.72
2.75
22.70
22.70
3.00
1000
63* (17.2)
29.30
22.46
2.01
27.91
21.89
2.23
26.32
21.22
2.47
24.35
20.38
2.73
21.72
19.26
2.97
67 (19.4)
31.55
23.29
2.03
30.16
22.79
2.24
28.60
22.20
2.49
26.76
21.49
2.77
24.30
20.55
3.06
71 (21.7)
33.80
19.48
2.05
32.41
19.01
2.26
30.84
18.46
2.51
29.10
17.84
2.79
27.04
17.11
3.11
57 (13.9)
29.58
29.58
2.03
28.44
28.44
2.25
27.15
27.15
2.50
25.62
25.62
2.78
23.61
23.61
3.06
62 (16.7)
29.56
29.56
2.03
28.82
27.88
2.25
27.19
27.19
2.50
25.66
25.66
2.78
23.65
23.65
3.06
1125
63* (17.2)
29.76
23.65
2.04
28.33
23.11
2.25
26.76
22.46
2.50
24.80
21.66
2.77
22.16
20.54
3.01
67 (19.4)
31.99
24.51
2.05
30.58
24.06
2.27
29.00
23.49
2.51
27.19
22.82
2.79
24.77
21.94
3.11
71 (21.7)
34.23
20.29
2.07
32.81
19.85
2.29
31.24
19.31
2.54
29.45
18.71
2.82
27.39
18.01
3.13
577C–K Ultra Low NOx: Product Data
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 13
Performance Data 36 Size
Evaporator Air
CFM
EWB °F(°C)
75 (23.9) Capacity MBtuh
Total Sens
Total Sys KW**
57 (13.8)
34.58
34.58
2.40
62 (16.6)
36.10
31.44
2.41
1000
63* (17.2)
36.53
25.60
2.42
67 (19.4)
39.44
26.70
2.43
72 (22.2)
43.05
21.95
2.46
57 (13.8)
36.19
36.19
2.46
62 (16.6)
37.15
33.84
2.46
1150
63* (17.2)
37.52
27.28
2.47
67 (19.4)
40.47
28.51
2.48
72 (22.2)
44.12
23.06
2.51
57 (13.8)
37.56
37.56
2.51
62 (16.6)
38.06
35.99
2.51
1300
63* (17.2)
38.23
28.87
2.51
67 (19.4)
41.26
30.24
2.53
72 (22.2)
44.94
24.09
2.56
85 (29.4) Capacity MBtuh Total Sens
Total Sys KW**
32.46 32.46 2.66
33.65 29.92 2.67
34.01 24.25 2.67
36.74 25.34 2.69
40.11 20.71 2.72
33.98 33.98 2.71
34.60 32.19 2.72
34.89 25.86 2.72
37.67 27.07 2.74
41.04 21.76 2.77
35.24 35.24 2.77
35.47 34.14 2.77
35.57 27.41 2.77
38.33 28.73 2.79
41.77 22.75 2.82
Condenser Entering Air Temperatures °F (°C)
95 (35)
105 (40.6)
Capacity MBtuh Total Sens
Total Sys KW**
Capacity MBtuh Total Sens
Total Sys KW**
30.31 30.31 2.94 28.08 28.08 3.27
31.16 28.38 2.95 28.62 26.75 3.27
31.48 22.90 2.95 28.86 21.49 3.28
34.00 23.95 2.97 31.20 22.53 3.30
37.12 19.45 3.00 34.07 18.16 3.32
31.67 31.67 3.00 29.30 29.30 3.32
32.03 30.46 3.00 29.42 29.41 3.32
32.23 24.43 3.01 29.50 22.95 3.33
34.80 25.60 3.03 31.88 24.11 3.35
37.93 20.44 3.06 34.77 19.10 3.38
32.79 32.79 3.05 30.30 30.30 3.38
32.84 32.84 3.05 30.34 30.34 3.38
32.80 25.90 3.05 29.99 24.35 3.38
35.38 27.20 3.08 32.36 25.62 3.40
38.55 21.38 3.11 35.28 19.98 3.43
115 (46.1)
Capacity MBtuh Total Sens
Total Sys KW**
25.78 25.78 3.65
26.05 25.03 3.65
26.20 20.05 3.65
28.34 21.07 3.67
30.95 16.85 3.69
26.84 26.84 3.70
26.90 26.90 3.70
26.72 21.43 3.70
28.91 22.56 3.72
31.54 17.73 3.74
27.71 27.71 3.75
27.75 27.75 3.75
27.14 22.76 3.75
29.31 24.01 3.76
31.96 18.56 3.79
125 (51.7)
Capacity MBtuh Total Sens
Total Sys KW**
23.44 23.44 4.08
23.48 23.48 4.08
23.49 18.58 4.08
25.45 19.58 4.09
27.81 15.51 4.11
24.34 24.34 4.12
24.38 24.38 4.12
23.92 19.88 4.12
25.90 20.99 4.14
28.28 16.32 4.16
25.08 25.08 4.17
25.12 25.12 4.17
24.25 21.11 4.17
26.22 22.34 4.18
28.62 17.10 4.21
577C–K Ultra Low NOx: Product Data
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 14
Performance Data 42 Size
Evaporator Air
75 (23.9)
85 (29.4)
Condenser Entering Air Temperatures °F (°C)
95 (35)
105 (40.6)
115 (46.1)
125 (51.7)
CFM 1175 1350 1525
EWB °F(°C)
57 (13.8)
62 (16.6)
63 (17.2)
67 (19.4)
72 (22.2)
57 (13.8)
62 (16.6)
63 (17.2)
67 (19.4)
72 (22.2)
57 (13.8)
62 (16.6)
63* (17.2)
67 (19.4)
72 (22.2)
Capacity MBtuh Total Sens 38.66 38.66 40.29 35.16 41.08 28.70 44.34 29.79 48.52 24.17 40.50 40.50 41.38 37.85 42.06 30.61 45.33 31.78 49.45 25.33 41.99 41.99 42.32 40.26 42.81 32.42 46.08 33.66 50.14 26.41
Total Sys KW** 2.51 2.54 2.54 2.59 2.66 2.58 2.59 2.60 2.64 2.72 2.63 2.64 2.65 2.70 2.78
Capacity MBtuh Total Sens 36.66 36.66 37.87 33.90 38.62 27.55 41.80 28.66 45.92 23.18 38.39 38.39 38.93 36.52 39.52 29.42 42.72 30.67 46.79 24.36 39.82 39.82 39.90 39.90 40.22 31.23 43.40 32.57 47.44 25.44
Total Sys KW** 2.87 2.90 2.92 2.97 3.05 2.95 2.96 2.97 3.03 3.12 3.02 3.02 3.02 3.08 3.18
Capacity MBtuh Total Sens 34.60 34.60 35.39 32.59 36.06 26.34 39.16 27.52 43.20 22.16 36.24 36.24 36.44 36.11 36.90 28.24 40.00 29.50 44.00 23.33 37.59 37.59 37.64 37.64 37.53 30.01 40.64 31.35 44.60 24.44
Total Sys KW** 3.30 3.32 3.34 3.42 3.52 3.40 3.41 3.41 3.48 3.58 3.47 3.47 3.47 3.54 3.64
Capacity MBtuh Total Sens 32.45 32.45 32.82 31.18 33.40 25.10 36.41 26.33 40.37 21.10 34.01 34.01 34.06 34.06 34.16 26.96 37.18 28.29 41.11 22.27 35.28 35.28 35.33 35.33 34.76 28.74 37.75 30.14 41.64 23.37
Total Sys KW** 3.80 3.82 3.84 3.95 4.06 3.92 3.92 3.92 4.01 4.13 4.01 4.01 3.99 4.07 4.20
Capacity MBtuh Total Sens 30.07 30.07 30.12 30.12 30.40 23.73 33.45 25.06 37.44 20.00 31.54 31.54 31.59 31.59 31.10 25.56 34.18 27.02 38.09 21.17 32.78 32.78 32.82 32.82 31.66 27.29 34.73 28.86 38.57 22.27
Total Sys KW** 4.39 4.39 4.40 4.57 4.70 4.51 4.52 4.49 4.64 4.78 4.63 4.64 4.56 4.70 4.85
Capacity MBtuh Total Sens 27.19 27.19 27.24 27.24 26.65 22.06 29.97 23.59 34.27 18.84 28.67 28.67 28.72 28.72 27.35 23.86 30.76 25.56 34.91 20.01 29.92 29.92 29.97 29.97 27.97 25.57 31.38 27.42 35.35 21.11
Total Sys KW** 5.02 5.03 4.98 5.21 5.44 5.17 5.17 5.08 5.32 5.52 5.31 5.31 5.17 5.42 5.59
577C–K Ultra Low NOx: Product Data
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 15
Performance Data 48 Size
Evaporator Air
75 (23.9)
85 (29.4)
Condenser Entering Air Temperatures °F (°C)
95 (35)
105 (40.6)
115 (46.1)
125 (51.7)
CFM 1400 1550 1800
EWB °F(°C)
57 (13.8)
62 (16.6)
63 (17.2)
67 (19.4)
72 (22.2)
57 (13.8)
62 (16.6)
63 (17.2)
67 (19.4)
72 (22.2)
57 (13.8)
62 (16.6)
63* (17.2)
67 (19.4)
72 (22.2)
Capacity MBtuh Total Sens 45.45 45.45 47.27 42.17 48.20 34.32 52.06 35.63 56.98 28.79 47.02 47.02 48.16 44.46 49.02 35.96 52.88 37.35 57.73 29.76 49.14 49.14 49.49 47.88 50.04 38.56 53.94 40.13 58.67 31.28
Total Sys KW** 3.10 3.13 3.13 3.15 3.18 3.17 3.17 3.18 3.20 3.23 3.25 3.25 3.25 3.28 3.31
Capacity MBtuh Total Sens 42.83 42.83 44.15 40.29 45.02 32.66 48.74 34.02 53.50 27.36 44.27 44.27 45.01 42.51 45.75 34.27 49.49 35.71 54.20 28.31 46.25 46.25 46.34 46.34 46.70 36.84 50.43 38.42 55.06 29.83
Total Sys KW** 3.46 3.49 3.50 3.52 3.56 3.54 3.55 3.55 3.57 3.61 3.63 3.63 3.63 3.65 3.69
Capacity MBtuh Total Sens 40.16 40.16 41.03 38.39 41.76 30.98 45.33 32.35 49.89 25.89 41.50 41.50 41.85 40.45 42.41 32.55 46.00 34.00 50.51 26.84 43.34 43.34 43.39 43.39 43.27 35.06 46.85 36.63 51.26 28.32
Total Sys KW** 3.89 3.91 3.92 3.95 3.99 3.96 3.97 3.98 4.00 4.04 4.06 4.06 4.06 4.08 4.12
Capacity MBtuh Total Sens 37.26 37.26 37.61 36.29 38.24 29.20 41.77 30.64 46.16 24.36 38.53 38.53 38.60 38.60 38.87 30.75 42.38 32.25 46.68 25.28 40.29 40.29 40.34 40.34 39.66 33.20 43.16 34.80 47.34 26.73
Total Sys KW** 4.36 4.36 4.38 4.44 4.48 4.44 4.44 4.45 4.49 4.53 4.55 4.55 4.54 4.57 4.62
Capacity MBtuh Total Sens 33.52 33.52 33.57 33.57 33.54 26.93 37.35 28.63 42.23 22.80 34.79 34.79 34.83 34.83 34.15 28.45 38.03 30.31 42.70 23.71 36.55 36.55 36.60 36.60 34.96 30.85 38.95 32.92 43.27 25.12
Total Sys KW** 4.82 4.83 4.82 4.96 5.04 4.92 4.92 4.89 5.04 5.09 5.07 5.07 5.00 5.12 5.18
Capacity MBtuh Total Sens 29.80 29.80 29.84 29.84 28.81 24.65 32.39 26.38 37.37 21.00 30.91 30.91 30.95 30.95 29.32 26.09 32.93 27.95 37.92 21.96 32.46 32.46 32.49 32.49 30.05 28.30 33.66 30.41 38.61 23.50
Total Sys KW** 5.37 5.37 5.33 5.46 5.64 5.46 5.46 5.40 5.53 5.70 5.60 5.61 5.51 5.65 5.78
577C–K Ultra Low NOx: Product Data
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 16
Performance Data 60 Size
Evaporator Air
75 (23.9)
85 (29.4)
Condenser Entering Air Temperatures °F (°C)
95 (35)
105 (40.6)
115 (46.1)
125 (51.7)
CFM 1750 2000 2250
EWB °F(°C)
57 (13.8)
62 (16.6)
63 (17.2)
67 (19.4)
72 (22.2)
57 (13.8)
62 (16.6)
63 (17.2)
67 (19.4)
72 (22.2)
57 (13.8)
62 (16.6)
63* (17.2)
67 (19.4)
72 (22.2)
Capacity MBtuh Total Sens 57.04 57.04 58.59 49.98 59.69 40.44 64.43 42.04 70.39 33.58 59.44 59.44 60.04 53.50 60.84 43.04 65.61 44.79 71.45 35.11 61.37 61.37 61.42 61.42 61.75 45.60 66.46 47.42 72.23 36.56
Total Sys KW** 3.68 3.70 3.70 3.73 3.78 3.78 3.78 3.78 3.81 3.87 3.86 3.86 3.86 3.89 3.95
Capacity MBtuh Total Sens 53.71 53.71 54.72 48.26 55.67 38.90 60.26 40.56 66.06 32.25 55.93 55.93 56.07 56.07 56.74 41.49 61.36 43.29 67.02 33.78 57.76 57.76 57.83 57.83 57.57 43.99 62.10 45.93 67.73 35.23
Total Sys KW** 4.20 4.22 4.23 4.26 4.31 4.31 4.31 4.31 4.34 4.40 4.39 4.40 4.39 4.43 4.48
Capacity MBtuh Total Sens 50.37 50.37 50.83 46.41 51.62 37.32 56.00 39.00 61.55 30.87 52.41 52.41 52.48 52.48 52.56 39.87 56.95 41.68 62.40 32.37 54.09 54.09 54.15 54.15 53.29 42.29 57.67 44.25 63.02 33.84
Total Sys KW** 4.81 4.82 4.83 4.87 4.93 4.92 4.92 4.92 4.96 5.02 5.01 5.01 5.00 5.04 5.11
Capacity MBtuh Total Sens 46.94 46.94 47.02 47.02 47.50 35.70 51.67 37.39 56.94 29.39 48.83 48.83 48.90 48.90 48.32 38.18 52.51 40.02 57.67 30.89 50.36 50.36 50.42 50.42 48.99 40.55 53.13 42.53 58.17 32.33
Total Sys KW** 5.51 5.51 5.52 5.57 5.64 5.62 5.62 5.62 5.66 5.73 5.72 5.72 5.71 5.75 5.82
Capacity MBtuh Total Sens 42.94 42.94 43.00 43.00 42.48 33.69 47.05 35.71 52.21 27.88 44.92 44.92 44.98 44.98 43.48 36.25 47.83 38.30 52.81 29.36 46.38 46.38 46.44 46.44 44.27 38.64 48.44 40.74 53.23 30.78
Total Sys KW** 6.27 6.28 6.25 6.38 6.45 6.44 6.44 6.39 6.47 6.55 6.54 6.54 6.52 6.56 6.65
Capacity MBtuh Total Sens 38.22 38.22 38.29 38.29 36.58 31.27 41.05 33.47 47.19 26.29 39.97 39.97 40.04 40.04 37.36 33.66 41.86 36.09 47.75 27.77 41.44 41.44 41.51 41.51 38.08 35.80 42.58 38.56 48.12 29.19
Total Sys KW** 7.08 7.08 7.00 7.21 7.37 7.26 7.26 7.13 7.35 7.47 7.43 7.43 7.26 7.48 7.57
577C–K Ultra Low NOx: Product Data
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 17
Performance Data
- At 75F (24C) entering dry bulb-Tennessee Valley Authority (TVA) rating conditions; all others at 80F dry bulb. } Sensible capacities shown are based on 80F (27C) entering air at the indoor coil. For sensible capacities at other than 80F (27C), deduct 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80F (27C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree above 80F (27C). ** System KW is total of indoor and outdoor unit kilowatts. LEGEND BF– Bypass Factor edb– Entering Dry—Bulb Ewb– Entering Wet—Bulb kW — Total Unit Power Input SHC– Sensible Heat Capacity (1000 Btuh) TC — Total Capacity (1000 Btuh) (net) rh–Relative Humidity COOLING NOTES: 1. Ratings are net; they account for the effects of the evaporator —fan motor power and heat. 2. Direct interpolation is permissible. Do not extrapolate. 3. The following formulas may be used:
4. The SHC is based on 80_F (26.6_C) edb temperature of air enteringevaporator coil. Below 80_F (26.6_C) edb, subtract (corr factor x cfm) from SHC. Above 80_F (26.6_C) edb, add (corr factor x cfm) to SHC. Correction Factor = 1.10 x (1 + BF) x (edb — 80). 5. Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.
577C–K Ultra Low NOx: Product Data
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 18
Gas Adjustment Natural Gas Orifice Sizes and Manifold Pressure – Single and Three Phase Models
Nameplate Input (Btu/hr)
45,000 60,000 89,000 *. Altitude of 2001ft and above is not allowed.
Orifice No. (Qty) Manifold Press. (in. W.C.)
Orifice No. (Qty) Manifold Press. (in. W.C.)
Orifice No. (Qty) Manifold Press. (in. W.C.)
Altitude of Installation (FT. Above Sea Level) U.S.A.*
0 to 2000 (0-610 m) 0.125-in.
3.2~3.8 28 (1) 3.2~3.8 18 (1) 3.2~3.8
577C–K Ultra Low NOx: Product Data
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 19
Dry Coil Air Delivery* – Horizontal and Downflow Discharge Sizes 24-60
Unit Size
Heating Rise oF (oC)
Motor Speed
Tap
Allowable Functions
ESP (in. W.C.)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
CFM
640
553
454
310
—
—
—
—
—
—
Low
BHP
0.07
0.08
0.08
0.09
—
—
—
—
—
—
Blue
Alternate Heating
Gas Heat Rise (oF)
52
NA
NA
NA
NA
NA
NA
NA
NA
NA
Gas Heat Rise (oC)
29
NA
NA
NA
NA
NA
NA
NA
NA
NA
CFM
830
758
688
607
514
393
254
—
—
—
Med-Low
Pink
Heating
BHP
0.12
0.13
0.13
0.13
0.14
0.14
0.15
—
Alternate Cooling
Gas Heat Rise (oF)
40
44
49
55
NA
NA
NA
NA
–NA
–NA
Gas Heat Rise (oC)
22
25
27
31
NA
NA
NA
NA
NA
NA
24040
25 – 55 (14 – 31)
Medium**
Red
CFM
1080
1025
969
910
852
787
718
638
541
457
Cooling
BHP
0.21
0.22
0.23
0.23
0.24
0.24
0.25
0.25
0.26
0.27
Alternate Heating
Gas Heat Rise (oF)
31
33
35
37
39
43
47
52
NA
NA
Gas Heat Rise (oC)
17
18
19
20
22
24
26
29
NA
NA
CFM
1101
1046
993
936
878
816
749
676
599
498
Med-High
Orange
Alternate Cooling Alternate Heating
BHP
0.22
Gas Heat Rise (oF)
30
0.23 32
0.24 34
0.24 36
0.25 38
0.26 41
0.26 45
0.27 50
0.27 NA
0.28 NA
Gas Heat Rise (oC)
17
18
19
20
21
23
25
28
NA
NA
High
Black High Static Cooling Only
CFM BHP
1222
1173
1123
1072
1021
967
912
853
787
712
0.29
0.29
0.30
0.31
0.31
0.32
0.33
0.34
0.34
0.34
CFM
640
553
454
310
—
—
—
—
—
—
Low
Blue
BHP
0.07
0.08
0.08
0.09
—
—
—
—
—
—
Gas Heat Rise (oF)
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
Gas Heat Rise (oC)
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
CFM
830
758
688
607
514
393
254
—
—
—
Med-Low
Pink
Alternate Cooling
BHP
0.12
0.13
0.13
0.13
0.14
0.14
0.15
—
Alternate Heating
Gas Heat Rise (oF)
54
NA
NA
NA
NA
NA
NA
NA
–NA
–NA
Gas Heat Rise (oC)
30
NA
NA
NA
NA
NA
NA
NA
NA
NA
24060
25 – 55 (14 – 31)
Medium**
Red
CFM
1080
1025
969
910
852
787
718
638
541
457
Cooling
BHP
0.21
0.22
0.23
0.23
0.24
0.24
0.25
0.25
0.26
0.27
Alternate Heating
Gas Heat Rise (oF)
41
44
46
49
52
NA
NA
NA
NA
NA
Gas Heat Rise (oC)
23
24
26
27
29
NA
NA
NA
NA
NA
CFM
1101
1046
993
936
878
816
749
676
599
498
Med-High Orange
Heating Alternate Cooling
BHP
0.22
Gas Heat Rise (oF)
41
0.23 43
0.24 45
0.24 48
0.25 51
0.26 55
0.26 NA
0.27 NA
0.27 NA
0.28 NA
Gas Heat Rise (oC)
23
24
25
26
28
30
NA
NA
NA
NA
High
Black High Static Cooling Only
CFM BHP
1222
1173
1123
1072
1021
967
912
853
787
712
0.29
0.29
0.30
0.31
0.31
0.32
0.33
0.34
0.34
0.34
577C–K Ultra Low NOx: Product Data
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 20
Dry Coil Air Delivery* – Horizontal and Downflow Discharge Sizes 24-60
Unit Size
Heating Rise oF (oC)
Motor Speed
Tap
Allowable Functions
ESP (in. W.C.)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
CFM
643
552
455
348
225
—
—
—
—
—
Low
BHP
0.09
0.10
0.11
0.11
0.11
—
—
—
—
—
Blue
Alternate Heating
Gas Heat Rise (oF)
52
NA
NA
NA
NA
NA
NA
NA
NA
NA
Gas Heat Rise (oC)
29
NA
NA
NA
NA
NA
NA
NA
NA
NA
CFM
817
744
673
597
516
431
325
190
—
—
Med-Low
Pink
Heating
BHP
0.14
0.15
0.15
0.16
0.17
0.17
0.18
0.18
—
Alternate Cooling
Gas Heat Rise (oF)
41
45
50
NA
NA
NA
NA
NA
NA
–NA
Gas Heat Rise (oC)
23
25
28
NA
NA
NA
NA
NA
NA
NA
30040
25 – 55 (14 – 31)
Medium
CFM
1159
1104
1045
990
937
878
821
759
693
618
Red
Alternate Cooling
BHP
0.31
0.32
0.33
0.33
0.34
0.35
0.36
0.37
0.37
0.38
Alternate Heating
Gas Heat Rise (oF)
29
30
32
34
36
38
41
44
48
54
Gas Heat Rise (oC)
16
17
18
19
20
21
23
25
27
30
CFM
1201
1147
1095
1037
987
934
877
818
755
671
Med-High** Orange
Cooling Alternate Heating
BHP
0.34
Gas Heat Rise (oF)
28
0.35 29
0.36 31
0.37 32
0.37 34
0.38 36
0.39 38
0.40 41
0.41 44
0.40 50
Gas Heat Rise (oC)
15
16
17
18
19
20
21
23
25
28
High
Black High Static Cooling Only
CFM BHP
1291
1236
1181
1131
1080
1033
978
909
792
661
0.41
0.42
0.43
0.43
0.44
0.45
0.46
0.45
0.43
0.40
CFM
643
552
455
348
225
—
—
—
—
—
Low
Blue
BHP
0.09
0.10
0.11
0.11
0.11
—
—
—
—
—
Gas Heat Rise (oF)
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
Gas Heat Rise (oC)
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
CFM
817
744
673
597
516
431
325
190
—
—
Med-Low
Pink
Alternate Cooling
BHP
0.14
0.15
0.15
0.16
0.17
0.17
0.18
0.18
—
Alternate Heating
Gas Heat Rise (oF)
55
NA
NA
NA
NA
NA
NA
NA
NA
–NA
Gas Heat Rise (oC)
30
NA
NA
NA
NA
NA
NA
NA
NA
NA
30060
25 – 55 (14 – 31)
Medium
Red
CFM
1159
1104
1045
990
937
878
821
759
693
618
Heating
BHP
0.31
0.32
0.33
0.33
0.34
0.35
0.36
0.37
0.37
0.38
Alternate Cooling
Gas Heat Rise (oF)
39
40
43
45
48
51
54
NA
NA
NA
Gas Heat Rise (oC)
21
22
24
25
26
28
30
NA
NA
NA
CFM
1201
1147
1095
1037
987
934
877
818
755
671
Medium-High** Orange
Cooling Alternate Heating
BHP
0.34
Gas Heat Rise (oF)
37
0.35 39
0.36 41
0.37 43
0.37 45
0.38 48
0.39 51
0.40 55
0.41 NA
0.40 NA
Gas Heat Rise (oC)
21
22
23
24
25
27
28
30
NA
NA
High
Black High Static Cooling Only
CFM BHP
1291
1236
1181
1131
1080
1033
978
909
792
661
0.41
0.42
0.43
0.43
0.44
0.45
0.46
0.45
0.43
0.40
577C–K Ultra Low NOx: Product Data
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 21
Dry Coil Air Delivery* – Horizontal and Downflow Discharge Sizes 24-60
Unit Size
Heating Rise oF (oC)
36060
25 – 55 (14 – 31)
42060
25 – 55 (14 – 31)
Motor Speed Low
Med-Low Medium
Med-High High Low
Med-Low
Medium
Med-High High
Tap
Allowable Functions
Blue Pink Red Orange Black Blue Pink
Red
Orange Black
Alternate Cooling, Alternate Gas Heating
Gas Heating, Alternate Cooling
Alternate Cooling, Alternate Gas Heating
Cooling, Alternate Gas Heating High Static Cooling Only
Alternate Heating
Heating Alternate Cooling
Alternate Cooling Alternate Heating
Cooling Alternate Heating
High Static Cooling Only
CFM BHP Gas Heat Rise (oF) Gas Heat Rise (oC) CFM BHP Gas Heat Rise (oF) Gas
Heat Rise (oC) CFM BHP Gas Heat Rise (oF) Gas Heat Rise (oC) CFM BHP Gas Heat
Rise (oF) Gas Heat Rise (oC) CFM BHP CFM BHP Gas Heat Rise (oF) Gas Heat Rise
(oC)
CFM
BHP Gas Heat Rise (oF) Gas Heat Rise (oC)
CFM
BHP Gas Heat Rise (oF) Gas Heat Rise (oC)
CFM
BHP Gas Heat Rise (oF) Gas Heat Rise (oC)
CFM BHP
0.1
1096 0.14 41 23 1151 0.16 39 22 1299 0.22 34 19 1382 0.26 32 18 1530 0.33 956
0.13 47 26
1201
0.21 37 21
1443
0.32 31 17
1529
0.37 29 16 1604 0.42
0.2
1044 0.15 43 24 1103 0.17 40 22 1252 0.23 36 20 1335 0.27 33 19 1485 0.35 899
0.13 50 28
1153
0.22 39 22
1402
0.33 32 18
1491
0.39 30 17 1565 0.44
0.3
994 0.16 45 25 1056 0.18 42 23 1204 0.24 37 21 1292 0.28 35 19 1442 0.36 843
0.14 53 29
1107
0.22 40 22
1361
0.34 33 18
1451
0.40 31 17 1529 0.45
ESP (in. W.C.)
0.4
0.5
945 0.18 47
26 1002 0.19
45
25 1155 0.25
39
21 1246 0.29
36
20 1398 0.37 786 0.15 NA
NA
892 0.19 50
28 953 0.20 47
26 1106 0.26
40
22 1202 0.30
37
21 1354 0.38 729 0.16 NA
NA
1060
1012
0.23
0.24
42
44
23
25
1322
0.35 34 19
1284
0.36 35 19
1411
1376
0.41 32
18 1490 0.46
0.42 32
18 1455 0.47
0.6
837 0.19 53 30 897 0.21 50 28 1059 0.27 42 23 1152 0.31 39 22 1309 0.39 676
0.16 NA NA
965
0.25 46 26
1243
0.37 36 20
1338
0.43 33 19 1421 0.48
0.7
780 0.20 NA NA 845 0.22 53 29 1007 0.28 44 25 1106 0.32 40 22 1263 0.40 621
0.17 NA NA
917
0.26 49 27
1204
0.38 37 21
1300
0.44 34 19 1385 0.49
0.8
717 0.21 NA NA 788 0.23 NA NA 959 0.29 47 26 1058 0.33 42 23 1217 0.41 558
0.18 NA NA
871
0.27 51 28
1164
0.39 38 21
1261
0.45 35 20 1348 0.50
0.9
664 0.22 NA NA 729 0.24 NA NA 905 0.30 49 27 1007 0.34 44 25 1169 0.42 504
0.18 NA NA
828
0.28 54 30
1124
0.40 40 22
1223
0.46 36 20 1310 0.51
1
612 0.23 NA NA 678 0.25 NA NA 844 0.31 53 29 957 0.35 47 26 1120 0.43 435 0.19
NA NA
782
0.29 NA NA
1084
0.42 41 23
1185
0.47 38 21 1274 0.52
577C–K Ultra Low NOx: Product Data
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 22
Dry Coil Air Delivery* – Horizontal and Downflow Discharge Sizes 24-60
Unit Size
Heating Rise oF (oC)
42090
35 – 65 (19 – 36)
48090
35 – 65 (19 – 36)
Motor Speed Low
Med-Low Medium Med-High
High Low Med-Low Medium Med-High High
Tap
Allowable Functions
Blue Pink Red Orange Black Blue Pink Red Orange Black
Alternate Cooling Alternate Heating
Heating Alternate Cooling
Cooling Alternate Heating High Static Cooling Only
Heating Alternate Cooling
Cooling Alternate Heating
Alternate Cooling Alternate Heating High Static Cooling Only
CFM BHP Gas Heat Rise (oF) Gas Heat Rise (oC) CFM BHP Gas Heat Rise (oF) Gas Heat Rise (oC) CFM BHP Gas Heat Rise (oF) Gas Heat Rise (oC) CFM BHP Gas Heat Rise (oF) Gas Heat Rise (oC) CFM BHP CFM BHP Gas Heat Rise (oF) Gas Heat Rise (oC) CFM BHP Gas Heat Rise (oF) Gas Heat Rise (oC) CFM BHP Gas Heat Rise (oF) Gas Heat Rise (oC) CFM BHP Gas Heat Rise (oF) Gas Heat Rise (oC) CFM BHP
0.1
956 0.13 NA
NA 1201 0.21
56
31 1443 0.32
46
26 1529 0.37
44
24 1604 0.42 641 0.05 NA
NA 1437 0.29
47
26 1771 0.51
38
21 1928 0.64
35
19 2212 0.97
0.2
899 0.13 NA
NA 1153 0.22
58
32 1402 0.33
48
27 1491 0.39
45
25 1565 0.44 551 0.06 NA
NA 1395 0.30
48
27 1735 0.52
39
21 1897 0.65
35
20 2167 0.99
0.3
843 0.14 NA
NA 1107 0.22
60
34 1361 0.34
49
27 1451 0.40
46
26 1529 0.45 462 0.06 NA
NA 1351 0.31
50
28 1699 0.53
39
22 1862 0.67
36
20 2124 1.00
ESP (in. W.C.)
0.4
0.5
786 0.15 NA
NA 1060 0.23
63
35 1322 0.35
51
28 1411 0.41
47
26 1490 0.46 385 0.07 NA
NA 1307 0.32
51
28 1664 0.55
40
22 1830 0.68
37
20 2061 0.97
729 0.16 NA
NA 1012 0.24 NA
NA 1284 0.36
52
29 1376 0.42
49
27 1455 0.47 289 0.07 NA
NA 1265 0.33
53
29 1627 0.56
41
23 1796 0.69
37
21 1976 0.95
0.6
676 0.16 NA
NA 965 0.25 NA
NA 1243 0.37
54
30 1338 0.43
50
28 1421 0.48 216 0.08 NA
NA 1221 0.34
55
30 1592 0.57
42
23 1764 0.71
38
21 1892 0.91
0.7
621 0.17 NA
NA 917 0.26 NA
NA 1204 0.38
56
31 1300 0.44
52
29 1385 0.49 163 0.08 NA
NA 1176 0.35
57
32 1557 0.58
43
24 1732 0.72
39
21 1794 0.86
0.8
558 0.18 NA
NA 871 0.27 NA
NA 1164 0.39
58
32 1261 0.45
53
29 1348 0.50 115 0.09 NA
NA 1132 0.36
59
33 1522 0.59
44
24 1698 0.73
39
22 1699 0.82
0.9
504 0.18 NA
NA 828 0.28 NA
NA 1124 0.40
60
33 1223 0.46
55
30 1310 0.51
—-NA
NA 1084 0.37
62
34 1486 0.61
45
25 1620 0.71
41
23 1567 0.77
1
435 0.19 NA
NA 782 0.29 NA
NA 1084 0.42
62
34 1185 0.47
57
31 1274 0.52
—-NA
NA 1039 0.38
64
36 1450 0.62
46
26 1512 0.66
44
25 1438 0.71
577C–K Ultra Low NOx: Product Data
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 23
Dry Coil Air Delivery* – Horizontal and Downflow Discharge Sizes 24-60
Unit Size
60090
Heating Rise Motor Speed Tap oF (oC)
Allowable Functions
CFM
Low
Blue
Alternate Heating
BHP Gas Heat Rise (oF)
Gas Heat Rise (oC)
CFM
Med-Low
Pink
Heating Alternate Cooling
BHP Gas Heat Rise (oF)
Gas Heat Rise (oC)
35 – 65
CFM
(19 – 36)
Medium**
Red
Cooling Alternate Heating
BHP Gas Heat Rise (oF)
Gas Heat Rise (oC)
CFM
Med-High
Orange
Alternate Cooling Alternate Heating
BHP Gas Heat Rise (oF)
Gas Heat Rise (oC)
High
Black High Static Cooling Only
CFM BHP
Shaded areas indicate speed/static combinations that are not permitted for dehumidification speed.
0.1
641 0.05 NA
NA 1437 0.29
47
26 1914 0.62
35
19 1928 0.64
35
19 2212 0.97
- Air delivery values are without air filter and are for dry coil (See Wet Coil Pressure Drop Table). Factory-shipped continuous fan speed Factory-shipped heating speed ** Factory-shipped cooling speed “High Static Cooling” = Only to be used for cooling function (not allowed for heating function) NOTE: Deduct field-supplied air filter pressure drop and wet coil pressure drop to obtain static pressure available for ducting.
Wet Coil Pressure Drop (IN. W.C.)
0.2
551 0.06 NA
NA 1395 0.30
48
27 1881 0.64
36
20 1897 0.65
35
20 2167 0.99
0.3
462 0.06 NA
NA 1351 0.31
50
28 1848 0.65
36
20 1862 0.67
36
20 2124 1.00
Unit Size 24 30 36 42 48 60
Standard CFM (SCFM)
600
700
800
900
1000
1100
1200
1300
1400
1500
0.03
0.04
0.04
0.05
0.06
0.05
0.06
0.07
0.08
0.11
0.02
0.03
0.03
0.04
0.05
0.05
0.05
0.05
0.06
0.07
0.08
0.08
0.04
0.05
0.05
0.06
0.06
ESP (in. W.C.)
0.4
0.5
385 0.07 NA
NA 1307 0.32
51
28 1814 0.67
37
21 1830 0.68
37
20 2061 0.97
289 0.07 NA
NA 1265 0.33
53
29 1780 0.68
38
21 1796 0.69
37
21 1976 0.95
1600
1700
0.09
0.09
0.07
0.07
0.07
0.01
0.6 216 0.08 NA NA 1221 0.34 55 30 1748 0.69 38 21 1764 0.71 38 21 1892 0.91
1800
0.11 0.08 0.08
Economizer with 1-in. Filter Pressure Drop (IN. W.C.)
Filter Size in. (mm)
600-1400 CFM 12x20x1+12x20x1 (305x508x25+305x508x25)
1200-1800CFM 16x24x1+14x24x1 (406x610x25+356x610x25)
1500-2200CFM 16x24x1+18x24x1 (406x610x25+457x610x25)
Cooling Tons 2.0, 2.5
3.5
3.0, 4.0, 5.0
Standard CFM (SCFM) 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700
–
–
0.08 0.09 0.10 0.11 0.11 0.13 0.14
–
–
–
–
–
–
–
–
0.09 0.09 0.10 0.12 0.13 0.15 0.17
–
–
–
–
–
–
–
–
–
0.15 0.17 0.18
0.7
163 0.08 NA
NA 1176 0.35
57
32 1716 0.71
39
22 1732 0.72
39
21 1794 0.86
0.8
115 0.09 NA
NA 1132 0.36
59
33 1681 0.72
40
22 1698 0.73
39
22 1699 0.82
0.9
—-NA
NA 1084 0.37
62
34 1619 0.71
41
23 1620 0.71
41
23 1567 0.77
1
—-NA
NA 1039 0.38
64
36 1512 0.66
44
25 1512 0.66
44
25 1438 0.71
1900
2000
2100
2200
0.09
0.14
0.09
0.10
0.12
0.13
1800 1900 2000 2100 2200
–
–
–
–
–
0.17 0.19 0.21
–
–
0.20 0.21 0.22 0.23 0.23
577C–K Ultra Low NOx: Product Data
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 24
Filter Pressure Drop Table (IN. W.C.)
Filter Size in. (mm)
600-1400CFM 12x20x1+12x20x1 (305x508x25+305x508x25
1200-1800 CFM 16x24x1+14x24x1 (406x610x25+356x610x25)
1100-2200 CFM 16x24x1+18x24x1 (406x610x25+457x610x25)
Cooling Tons 2.0, 2.5
3.5
3.0 4.0 5.0
Standard CFM (SCFM) 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200
0.03 0.05 0.06 0.08 0.10 0.11 0.13 0.14 0.16
–
–
–
–
–
–
–
–
–
–
–
–
–
–
0.07 0.08 0.09 0.09 0.10 0.11 0.12
–
–
–
–
–
–
–
–
–
0.02 0.02 0.03 0.03 0.04 0.06 0.08 0.10 0.11 0.13 0.14 0.15
577C–K Ultra Low NOx: Product Data
Typical Piping and Wiring
ROOF-MOUNTING CURB
SUPPLY-AIR FLEXIBLE DUCT
ROOF
RETURN-AIR FLEXIBLE DUCT
CONCENTRIC DIFFUSER BOX (FIELD-SUPPLIED)
CEILING
RETURN AIR
TOP COVER
INDOOR THERMOSTAT
FROM POWER SOURCE
A09230
Application Data
Condensate trap — A 2-in. (50.8 mm) condensate trap must be field supplied.
Ductwork — Secure downflow discharge ductwork to roof curb. For horizontal
discharge applications, attach ductwork to unit with flanges.
To convert a unit to downflow discharge — Units are equipped with factory-
installed inserts in the down-flow openings. Removal of the inserts is similar
to removing an electrical knock-out. Use the duct cover to seal the horizontal
discharge openings in the unit. Units installed in horizontal discharge
orientation do not require duct covers.
Airflow — Units are draw-thru in the cooling mode and blow-thru in the heating
mode.
FROM GAS LINE
DISCONNECT PER NEC*
*NEC – NATIONAL ELECTRICAL CODE
A09231
Maximum cooling airflow — To minimize the possibility of condensate blow-off
from the evaporator, airflow through the units should not exceed 450 CFM per
ton.
Minimum cooling airflow — Minimum cooling airflow is 350 cfm per ton.
Minimum ambient cooling operation temperature — All standard units have a
minimum ambient operating temperature of 40_F (4_C). With accessory low
ambient temperature kit, units can operate at temperatures down to 0_F
(-17_C).
Minimum temperature — Air entering the heat exchanger in heating mode must be
a minimum of 50_F (10_C) continuous and/or 45_F (7_C) intermittent.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 25
577C–K Ultra Low NOx: Product Data
Electrical Data
MODEL
NOMINAL V-PH-HZ
VOLTAGE RANGE
MIN
MAX
COMPRESSOR
RLA
LRA
OFM FLA
IFM FLA
IDM FLA
POWER SUPPLY
MCA
MOCP
24040, 24060
208/230-1-60
197
253
11.1
59.5
0.6
3.9
0.7
18.4
25
30040, 30060
208/230-1-60
197
253
14.1
67.9
1.05
3.9
0.7
22.6
30
36060 208/230-1-60
197
253
14.7
75
1.05
3.8
0.7
23.3
35
36060 208/230-3-60
197
253
8.5
70
1.05
3.8
0.7
15.5
25
42060, 42090
208/230-1-60
197
253
16.7
109
1.05
5.8
0.7
27.8
40
42060, 42090
208/230-3-60
197
253
11.2
84
1.05
5.8
0.7
20.9
30
48090 208/230-1-60
197
253
19.6
130
1.05
6.9
0.7
32.5
50
48090 208/230-3-60
197
253
13.7
83.1
1.05
6.9
0.7
25.1
35
LEGEND
FLA – Full Load Amps IDM – Inducer Motor IFM – Indoor Fan Motor LRA -Locked
Rotor Amps MCA – Minimum Circuit Amps MOCP – Maximum Over Current Protection
OFM – Outdoor Fan Motor RLA – Rated Load Amps
A06564
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 26
577C–K Ultra Low NOx: Product Data
Connection Wiring Schematic 208/230-1-60
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 27
A221593
577C–K Ultra Low NOx: Product Data
Ladder Wiring Schematic 208/230-1-60
A221594 Manufacturer reserves the right to change, at any time, specifications
and designs without notice and without obligations.
28
577C–K Ultra Low NOx: Product Data
Connection Wiring Schematic 208/230-3-60
A221591 Manufacturer reserves the right to change, at any time, specifications
and designs without notice and without obligations.
29
577C–K Ultra Low NOx: Product Data
Ladder Wiring Schematic 208/230-3-60
A221592 Manufacturer reserves the right to change, at any time, specifications
and designs without notice and without obligations.
30
577C–K Ultra Low NOx: Product Data
Controls
Operating Sequence
Heating Sequence of Operation (Ultra Low NOx Single and Three Phase Models)
On a call for heating, terminal W of the thermostat is energized, starting the
induced-draft motor for a 30 second pre-purge at intermediate speed. When the
pressure switch senses that the induced-draft motor is moving sufficient
combustion air, the burner sequence begins. This function is controlled by the
integrated gas unit controller (IGC).
After 30 sec of pre-purge is complete, the pressure switch checks for
sufficient combustion. Then, the gas valve energizes and the system attempts
to ignite with igniter being energized. The igniter energizes for 5 sec and
integrated gas controller (IGC) allows system to sense flame for 2 sec at the
end of 5 sec of ignition trial. On first successful ignition, system stays at
the intermediate inducer speed for 10 sec and gradually ramps up to the high
speed for steady-state operation. The system uses the same logic for 2nd
ignition trial. If a 3rd or 4th ignition attempt is needed, the inducer speed
is decreased to the low speed. On a successful light on the 3rd or 4th
attempt, the inducer speed is increased to the intermediate speed for about 10
seconds and then gradually ramps up to the high speed for steady-state
operation. In case the 4th attempt fails, the system will lock out for 1 hr.
After 1 hr. lock out period, the system starts with normal operating sequence.
Once flame is established and proven successfully, indoor (evaporator) fan
motor is energized after 30 seconds. When the thermostat is satisfied and W is
de-energized, the pre-mix burner will stop firing and the indoor (evaporator)
fan motor shuts off after a 90 second time-off delay. Please note that the IGC
has the capability to automatically decrease the indoor (evaporator) fan motor
“ON” delay and increase the indoor (evaporator) fan motor “OFF” delay in the
event of high duct static and/or partially-clogged filter.
Cooling Sequence of Operation
With the room thermostat SYSTEM switch in the COOL position and the FAN switch
in the AUTO position, the cooling sequence of operation is as follows:
1. When the room temperature rises to a point that is slightly above the
cooling control setting of the thermostat, the thermostat completes the
circuit between thermostat terminal R to terminals Y and G.
2. The normally open contacts of energized contactor (C) close and complete
the circuit through compressor motor (COMP) to condenser (outdoor) fan motor
(OFM). Both motors start instantly.
3. The set of normally open contacts on the interface fan board (IFB) are
closed which energizes a circuit to the indoor fan motor (IFM).
NOTE: Once the compressor has started and then stopped, it should not be
started again until 5 minutes have elapsed. The cooling cycle remains on until
the room temperature drops to a point that is slightly below the cooling
control setting of the room thermostat. At this point, the thermostat breaks
the circuit between thermostat terminal R to terminals Y and G. These open
circuits deenergize contactor coil C. The condenser and compressor motors
stop. After a 60-sec. delay, the blower motor stops. The unit is in a standby
condition, waiting for the next call for cooling from the room thermostat.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 31
577C–K Ultra Low NOx: Product Data
Guide Specifications Packaged Gas Heating/Electric Cooling Units Constant
Volume Application HVAC Guide Specifications
Size Range:2 to 5 Tons, Nominal Cooling
60,000 to 90,000 Btuh,
Nominal Heating Input
General
SYSTEM DESCRIPTION
Outdoor rooftop mounted, gas heating/electric cooling unit utilizing a
hermetic scroll compressor for cooling duty. Unit shall discharge supply air
vertically or horizontally as shown on contract drawings. Condenser fan/coil
section shall have a draw-thru design with vertical discharge for minimum
sound levels.
QUALITY ASSURANCE Unit shall be rated in accordance with AHRI Standards
210/240 and 270-1995. Unit shall be designed in accordance with UL Standard
1995 and ANSI Z 21.47. Unit shall be manufactured in a facility registered
to ISO 9001 manufacturing quality standard. Unit shall be UL listed and c-UL
certified as a total package for safety requirements. Roof curb shall be
designed to conform to NRCA Standards. Insulation and adhesives shall meet
NFPA 90.1 requirements for flame spread and smoke generation. Cabinet
insulation shall meet ASHRAE Standard 62.2.
DELIVERY, STORAGE AND HANDLING Unit shall be stored and handled per
manufacturer’s recommendations.
Products
EQUIPMENT
General:
Factory-assembled, single-piece, heating and cooling unit. Contained within
the enclosure shall be all factory wiring, piping, controls, refrigerant
charge with R-410A refrigerant, and special features required prior to field
start-up.
Unit Cabinet: Unit cabinet shall be constructed of phosphated, zinc-coated,
pre-painted steel capable of with-standing 500 hours in salt spray. Normal
service shall be through 3 removable cabinet panels. The unit shall be
constructed on a rust proof unit base that has an externally trapped,
integrated sloped drain. Evaporator fan compartment top surface shall be
insulated with a minimum 1/2-in. (12.7 mm) thick, flexible fiberglass
insulation, coated on the air side and retained by adhesive and mechanical
means. The evaporator wall sections will be insulated with a minimum semi-
rigid foil-faced board capable of being wiped clean. Aluminum foil-faced
fiberglass insulation shall be used in the entire indoor air cavity section.
Unit shall have a field-supplied condensate trap.
Fans: The evaporator fan shall be a multi-speed, direct-drive, as shown on
equipment drawings. Fan wheel shall be made from steel, be double-inlet type
with forward curved blades with corrosion resistant finish. Fan wheel shall be
dynamically balanced. Condenser fan shall be direct drive propeller type
with aluminum blades riveted to corrosion resistant steel spiders, be
dynamically balanced, and discharge air vertically.
Compressor: Fully hermetic compressors with factory-installed vibration
isolation.
Coils:
Evaporator and condenser coils shall have aluminum plate fins mechanically
bonded to seamless copper tubes with all joints brazed. Tube sheet openings
shall be belled to prevent tube wear.
Heating Section: Induced-draft combustion type with energy saving direct
spark ignition system and redundant main gas valve. Induced-draft motors
shall provide adequate airflow for combustion. The heat exchangers shall be
constructed of stainless steel for corrosion resistance. Pre-mixed burners
shall be stainless steel and other alloys. All gas piping and electric power
shall enter the unit cabinet at a single location.
Refrigerant Components:
Refrigerant expansion device shall be of the TXV (thermostatic expansion
valve) or fixed orifice type.
Filters:
Filter section shall consist of field-installed, throwaway, 1-in. (25 mm)
thick fiberglass filters of commercially available sizes.
Controls and Safeties: Unit controls shall be complete with a self-contained
low voltage control circuit. Compressors shall incorporate a solid-state
compressor protector that provides reset capability.
Operating Characteristics: Unit shall be capable of starting and running at
125_F (51_C) ambient outdoor temperature per maximum load criteria of AHRI
Standard 210. Compressor with standard controls shall be capable of
operation down to 40_F (4_C) ambient outdoor temperature. Units shall be
provided with fan time delay to prevent cold air delivery before the heat
exchanger warms up. Unit shall be provided with 60-second fan time delay
(single phase models) after the thermostat is satisfied.
Electrical Requirements:
All unit power wiring shall enter the unit cabinet at a single location.
Motors: Compressor motors shall be of the refrigerant-cooled type with line-
break thermal and current overload protection. All fan motors shall have
permanently lubricated bearings, and inherent, automatic reset, thermal
overload protection. Condenser fan motor shall be totally enclosed.
Evaporator Fan Motor to be ECM Motor.
Compressor Protection:
Solid-state control shall protect compressor by preventing “short cycling.”
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 32
577C–K Ultra Low NOx: Product Data
Guide Specifications (Continued)
Ultra Low NOx:
Shall provide NOx reduction to meet 14ng/J NOx emissions requirements as
shipped from the factory.
Special Features Available:
1. Coil Options Base unit with tin plated indoor coil hairpins available as a
factory installed option.
2. Compressor Start Kit (single phase units only): Shall provide additional
starting torque for single-phase compressors.
3. Thermostat: To provide for one-stage heating and cooling in addition
manual or automatic changeover and indoor fan control.
4. Crankcase Heater: Shall provide anti-floodback protection for low-load
cooling applications.
5. Economizer: (Horizontal – Field installed accessory) (Vertical – Field
installed accessory) a. Economizer controls capable of providing free cooling
using outside air. b. Equipped with low leakage dampers not to exceed 3%
leakage, at 1.0 IN. W.C. pressure differential. c. Spring return motor shuts
off outdoor damper on power failure.
6. Filter Rack Kit: Shall provide filter mounting for downflow applications.
Offered as a field installed accessory.
7. Flat Roof Curb: Curbs shall have seal strip and a wood nailer for flashing
and shall be installed per manufacturer’s instructions.
8. Flue Discharge Deflector Directs flue gas exhaust; 90 degrees upward from
current discharge.
9. Low Ambient Package: Shall consist of a solid-state control and condenser
coil temperature sensor for controlling condenser-fan motor operation, which
shall allow unit to operate down to 0_F (-18_C) outdoor ambient temperature
when properly installed.
10. Manual Outdoor Air Damper: Package shall consist of damper, birdscreen,
and rainhood which can be preset to admit outdoor air for year-round
ventilation.
11. Square-To-Round Duct Transitions (24-48 models): Shall have the ability
to convert the supply and return openings from rectangular to round.
12. Time Guard II Automatically prevents the compressor from restarting for
at least 4 minutes and 45 seconds after shutdown of the compressor. Not
required when a corporate programmable thermostat is applied or with a RTU-MP
control. Offered as a field installed accessory.
13. Low Pressure Switch Kit Kit is designed for use when a low pressure
control in desired. This kit provides added reliability for the compressor.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 33
577C–K Ultra Low NOx: Product Data
© 2022 Carrier. All rights reserved. A Carrier Company
Edition Date: 12/22
Catalog No: PDS577C-ULN-08 Replaces: PDS577C-ULN-07
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
34