P S CS8375 3P4W Flanged Inlet Instructions

June 16, 2024
P S

P S CS8375 3P4W Flanged Inlet

WIRING INSTRUCTIONS

50 AMPERE FLANGED INLET WIRING INSTRUCTIONS

WARNING: To prevent electrocution, make sure power is off, and cannot be turned back on while installing the inlet.

  • Inlets must be installed by a qualified electrician.
  • Failure to comply with the following instructions could cause an electrical failure or fire.
  • Make sure the inlet has the proper electrical rating for the system on which it is being installed.
  • Wire size and type must comply with appropriate local electrical codes. The intent is designed for #10 through #4 AWG.
  • Strip the wire insulation 5/8″.
  • Use copper wire only. Make sure the wire is clean, and a bright copper colour.
  • Do not solder the ends of the wire.
  • Insert each wire into the appropriate wire terminal. Make sure there is no wire insulation in any terminal, and tighten the terminal screws to 25 inch-pounds torque.P-S-CS8375-3P4W-Flanged-Inlet-FIG-1 \(1\)

PASS & SEYMOUR

PASS & SEYMOUR 50A. WIRING DEVICES

P-S-CS8375-3P4W-Flanged-Inlet-FIG-1 \(2\)

THE DEVICES ARE FOR REPLACEMENT USE ONLY IN EXISTING INSTALLATIONS WE RECOMMEND THAT THEY NOT BE USED IN NEW INSTALLATIONS.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals