P S CS8375 3P4W Flanged Inlet

WIRING INSTRUCTIONS

50 AMPERE FLANGED INLET WIRING INSTRUCTIONS

WARNING: To prevent electrocution, make sure power is off, and cannot be turned back on while installing the inlet.

  • Inlets must be installed by a qualified electrician.
  • Failure to comply with the following instructions could cause an electrical failure or fire.
  • Make sure the inlet has the proper electrical rating for the system on which it is being installed.
  • Wire size and type must comply with appropriate local electrical codes. The intent is designed for #10 through #4 AWG.
  • Strip the wire insulation 5/8″.
  • Use copper wire only. Make sure the wire is clean, and a bright copper colour.
  • Do not solder the ends of the wire.
  • Insert each wire into the appropriate wire terminal. Make sure there is no wire insulation in any terminal, and tighten the terminal screws to 25 inch-pounds torque.P-S-CS8375-3P4W-Flanged-Inlet-FIG-1 \(1\)

PASS & SEYMOUR

PASS & SEYMOUR 50A. WIRING DEVICES

P-S-CS8375-3P4W-Flanged-Inlet-FIG-1 \(2\)

THE DEVICES ARE FOR REPLACEMENT USE ONLY IN EXISTING INSTALLATIONS WE RECOMMEND THAT THEY NOT BE USED IN NEW INSTALLATIONS.