legrand PSDS30AX Series Stainless Disconnect Instruction Manual

June 16, 2024
Legrand

No: 341199 ­ 02/17
Pass & Seymour®
Stainless Steel Disconnect Switch ­ 30, 60, 100 Amperes
Installation Instructions
Catalog Number(s) : PSDS30, PSDS60, PSDS60HP, PSDS100

Country of Origin: Made in USA

READ AND SAVE THESE INSTRUCTIONS!

  1. NOTICE: For installation only by a qualified electrician in accordance with the National Electrical Code, local codes and the instructions provided on this document.
  2. CAUTION: RISKS OF ELECTRICAL SHOCK. More than one disconnect switch may be required to de-energize the connected equipment before servicing. Disconnect all power supplies to this disconnect switch before removing cover and exposing interior.
  3. Short Circuit Ratings: Suitable for use on circuits capable of delivering not more than (see chart below for cat no.) RMS symmetrical amperes, 600 VAC maximum.
    Cat No.| kA| Fuse/Breaker| Max Size
    ---|---|---|---
    PSDS30 (AX)(SR)| 10| RK1| –
    65| Class J| 40A
    PSDS60 (AX)(SR)| 10| RK1| 125A
    65| Class J| 70A
    PSDS60HP (AX)(SR)
    PSDS100 (AX)(SR)| 10| RK1| –
    10| SFHA36AT0250| –
    65| Class J| 100A
  4. NOTICE: Separate over-current protection must be provided in accordance with National Electrical Code, article 220 or Canadian Electrical Code, section B, as appropriate.
  5. This enclosure includes a provision for locking the switch handle in the “OFF” position. This feature accepts up to a 5/16 inch (8 mm) diameter padlock shackle. This lockout  feature is designed to isolate power from the connected equipment in order to comply with OSHA lockout/tagout regulation 29 CFR part 1910.147. This feature DOES NOT isolate power supplied to this disconnect switch during internal servicing of this disconnect switch.
  6. This disconnect switch must NOT be used as a junction box for feed-thru connections.
  7. The switch in this device was available with or without a “pre-break” auxiliary contact. If the device was purchased with an auxiliary contact, the auxiliary contact’s rating is  600VAC, 10 amps. The pre-break feature allows the auxiliary contact to open slightly prior to the main contacts opening. This is useful for signaling computer controlled equipment that power will be disconnected. The auxiliary contact can be wired with one normally opened or one normally closed contact, (see diagram at right for wiring).
  8. Consult Pass & Seymour/Legrand distributor for auxiliary contact availability.

OUTDOOR/INDOOR: TYPE 4X WATERTIGHT, CORROSION RESISTANT
IP66/IP67/IP69 (HIGH PRESSURE, HIGH TEMPERATURE, & DUST)
INDOOR: TYPE 12 DUST TIGHT

  1. Loosen four (4) enclosure cover screws and lift off cover.
  2. Enclosure must be mounted by means of mounting feet. DO NOT drill mounting holes through enclosure.
  3. Mounting feet will accept up to 5/16″ dia. screws (not provided). Device must be mounted with label reading “TOP” in upward direction. See Figure 1 for mounting dimensions.
    Mounting Pattern Table – Inches (mm)

    | A| B
    30 Amp| 3.30 [84]| 8.40 [213]
    60/100 Amp| 5.50 [140]| 11.60 [295]
    30 Amp (SR)| 4.24 [108]| 10.50 [267]
    60/100 Amp (SR)
    | 6.70 [170]| 14.03 [356]

  4. Drill or punch appropriate hole size (see chart below) at the desired conduit entry location. Drill centers are provided on the enclosure.
    NOTE: Use appropriately rated conduit hub for required environmental rating of the application.
    NOTE: Back feed is NOT permitted in Type 12 applications. Back feed IS permitted in Type 4X applications.

| 30 AMP| 60/100 AMP| 60/100 AMP
---|---|---|---
HUB TRADE SIZE| 3/4″| 1″| 1-1/4″
APPROXIMATE HOLE SIZE| 1-1/18″ (28 MM)| 1-3/8″ (34.99 MM)| 1-3/4″ (44.4 MM)
5. Install conduit hub (not provided) with sealing ring between hub and enclosure. Tighten conduit nut securely to ensure watertight seal and ground connection. 6. Mount disconnect switch as intended on equipment, wall or other location after pre-drilling for screws per the dimensions provided in Figure 1. 7. Installing conduit directly above the switch is not recommended in applications where condensation can occur in the conduit. When using top feed entrance drip loops must always be used as in Figures 2 and 3.

WIRING INSTRUCTIONS

Wire size may vary with application. Select conductors in accordance with the 75°C column of ampacity table 310-16 of the National Electric Code or Table 2 of the Canadian Electrical Code.

  1. CAUTION: Use copper conductors only.
  2. Terminals will accept the wire sizes listed in Table 1 below.
  3. Cleanly cut and strip 1/2” (13mm) of insulation from end of cable. DO NOT TIN CONDUCTORS.
  4. Connected equipment electrical rating must not exceed the rating of this device.
  5. Select the correct wiring diagram from wiring diagram chart and wire switch as illustrated, making sure to provide condensation drip loop as shown in Figures 2 and 3. Insert stripped cables fully into terminal openings, tighten terminal screws per Table 1.
  6. With switch in “OFF” position, replace enclosure cover. Tighten enclosure cover screws according to Table 1, being sure that the sealing O-rings are properly seated under each screw head.

WIRING DIAGRAMS

legrand PSDS30AX Series Stainless Disconnect - WIRING INSTRUCTIONS
2

NOTE:
“G” designates grounding wire (bare, green or green with yellow stripe and green/yellow grounding buss).
“N” designates the blue neutral (grounded) terminal.
“W” designates the white neutral (grounded) wire.
THIS MANUAL MOTOR CONTROLLER CARRIES A MAXIMUM HORSE POWER RATING ACCORDING TO THE CHARTS BELOW.

30A (PSDS30)| 600 VAC| 60A (PSDS60)| 600 VAC| 60A (PSDS6OHP)| 600 VAC| 100A (PSDS100)| 600 VAC
---|---|---|---|---|---|---|---
1.5 HP| 120 VAC| 3 HP| 120 VAC| 5 HP| 120 VAC| 5 HP| 120 VAC
3 HP| 208 VAC| 7.5 HP| 240 VAC| 10 HP| 240 VAC| 15 HP| 240 VAC
5 HP| 240 VAC| 7.5 HP| 277 VAC| 15 HP| 277 VAC| 15 HP| 277 VAC
5 HP| 277 VAC| 15 HP| 480 VAC| 20 HP| 480 VAC| 30 HP| 480 VAC
7.5 HP| 480 VAC| 15 HP| 600 VAC| 30 HP| 600 VAC| 30 HP| 600 VAC
7.5 HP| 600 VAC| 15 HP| 3o 240 VAC| 25 HP| 3o 240 VAC| 25 HP| 3o 240 VAC
10 HP| 3o 240 VAC| 30 HP| 3o 480 VAC| 50 HP| 3o 480 VAC| 50 HP| 3o 480 VAC
20 HP| 3o 480 VAC| 40 HP| 30 600 VAC| 50 HP| 30 600 VAC| 50 HP| 30 600 VAC
25 HP| 3o 600 VAC| | | | | |

legrand PSDS30AX Series Stainless Disconnect - Table 1

800.223.4185
1.877.BY.LEGRAND
www.legrand.us
www.legrand.ca

341199 – 02/17
© Copyright 2017 Legrand All Rights Reserved.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals