S P TD EVO 100 Ecowatt Diagonal Energy Saving Duct Fan Installation Guide
- June 15, 2024
- S P
Table of Contents
- TD EVO 100 Ecowatt Diagonal Energy Saving Duct Fan
- TRANSPORT AND MANIPULATION
- STORAGE
- SAFETY DURING INSTALLATION
- START UP
- PUTTING OUT OF SERVICE AND RECYCLING
- PUTTING OUT OF SERVICE AND RECYCLING
- INFORMATION REQUIREMENTS FOR RVU
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
TD EVO 100
TD EVO 125
Installation Guide
TD EVO 100 Ecowatt Diagonal Energy Saving Duct Fan
|
---|---
|
|
|
FIG. 1
TD EVO VAR operating with an external ON/OFF switch “S”, at a predetermine
speed situated between RPMmax and RPMmin, and preset with the internal
potentiometer PT1.
FIG. 2
TD EVO VAR runing continuously at a predetermine speed situated between
RPMmax and RPMmin, preset with the internal potentiometer PT1 and going to
maximum speed (BOOST) with an external switch “S”.
FIG. 3
TD EVO VAR runing continuously at a predetermine speed situated between
RPMmax and RPMmin, preset with the internal potentiometer PT1 and going to
maximum speed (BOOST) with an external switch “S” plus an adjustable run on
timer.
FIG. 4
TD EVO VAR controlled with a REB ECOWATT or REB-CVF, for start-up and
manual speed regulation.
FIG. 5
TD EVO VAR runing continuously at a predetermine speed situated between
RPMmax and RPMmin, preset with the REB ECOWATT or REB-CVF potentiometer and
going to maximum speed (BOOST) with an external switch “S”.
FIG. 6
TD EVO VAR runing continuously at a predetermine speed situated between
RPMmax and RPMmin, preset with the REB ECOWATT or REB-CVF potentiometer and
going to maximum speed (BOOST) with an external switch “S” plus an adjustable
run on timer.
FIG. 7
TD EVO VAR runing continuously at a predetermine speed situated between
RPMmax and RPMmin, preset with the internal potentiometer PT1 and going to
maximum speed (BOOST) with an AIRSENS sensor.
FIG. 8
TD EVO VAR runing continuously at a predetermine speed situated between RPMmax
and RPMmin, preset with the REB ECOWATT or REB-CVF potentiometer and going to
maximum speed (BOOST) with an AIRSENS sensor.
FIG. 9
TD EVO VAR running continuously at a speed proportional to the analog 0-10V
or 4-20mA signal from an AIRSENS sensor.
| | (m3/h)| Dn,e,w (ctr)
---|---|---|---
EC-N 22| 22| 35
EC-N 30| 30| 34
EC-N 45| 45| 33
| | (m3/h)| Dn,e,w (ctr)
---|---|---|---
ECA 22| 22| 39
ECA 30| 30| 39
ECA 36| 36| 38
ECA 45| 45| 37
| | (m3/h)| Dn,e,w (ctr)
---|---|---|---
ECA-RA 22| 22| 41
ECA-RA 30| 30| 41
ECA-RA 36| 36| 39
ECA-RA 45| 45| 39
| | (m3/h)| Dn,e,w (ctr)
---|---|---|---
SILEM KIT 22| 22| 47
SILEM KIT 30| 30| 47
| | (m3/h)| Dn,e,w (ctr)
---|---|---|---
EC-HY 6/45| 6/45| 33
ECA-HY 6/45| 6/45| 37
ECA-HY 6/45 RA| 6/45| 39
SILEM KIT HY 125| 6/45| 39
| | | (m3/h)
---|---|---|---
BEHC 10/40/90| 10| -40| -90
BEHC 10/45/105| 10| -45| -105
BEHC 10/45/120| 10| -45| -120
BEHC 10/45/135| 10| -45| -135
| | (m3/h)
---|---|---
BEHW 5/30| 5 – 30
| | (m3/h)
---|---|---
BEHS 5/40| 5| -40
BEHS 5/45| 5| -45
BEHS 10/40| 5| -40
BEHS 10/45| 5| -45
| | (m3/h)
---|---|---
BEHT 15/30| 15| -30
BEHT 15/50| 15| -50
BEHT 15/75| 15| -75
BEHT 15/100| 15| -100
This instruction manual contains important information and must be read carefully by competent persons prior to any handling, transport, inspection or installation of this product. Every care has been taken in the preparation of the instructions and information; however, it is the responsibility of the installer to ensure the system complies with relevant national and international regulations, especially safety. The manufacturer, Soler & Palau Sistemas de Ventilación S.L.U. accepts no responsibility for breakages, accidents or any inconvenience caused by failure to comply with the instructions contained in this manual. The fan units referred to in this manual have been manufactured in accordance with rigorous quality control and International standard ISO 9001. Once the product has been installed, this manual to be retained by the end user.
TRANSPORT AND MANIPULATION
The packaging used for this fan unit has been designed to support normal transporting conditions. The fan unit must always be transported in its original packaging as not doing so could deform or damage the product. Do not accept delivery if the fan is not in its original packaging or shows clear signs of having been damaged. The product should be stored in a dry place in its original packaging, protected from dust and dirt until it is installed in its fi nal location. Do not place heavy weights on the packed product and avoid impact damage. Any lifting equipment must be safe and of suitable capacity for weight and size. Special attention may be required to ensure fan assembly does not distort or tilt as weight distribution may vary. Never lift a product by pulling it by the wires or terminal casing. Likewise, no pressure should be applied on the propeller, turbine or safety grid while manipulating the product.
STORAGE
Storage must be in a safe, fl at, controlled environment to prevent damage,
especially from water, sand, dust, moisture, corrosion, temperature. Recommend
that duct connections (infl ow and outfl ow) are closed to avoid dust/debris
entering the equipment.
These data may also apply to an installed fan, which is not put into operation
for extended period.
IMPORTANT INFORMATION FOR THE SAFETY OF INSTALLERS AND USERS
- Installation must be carried out by qualifi ed persons acting in accordance with all safety precautions applicable and as required by law, regulations and standards in the country applicable.
- All fan units are designed and manufactured in accordance with EC Directive. Safety guard accessories are available from S&P if required due to specifi c installation.
- Working ambient temperature for fan unit equipment should not be exceeded typically this will be within -20°C to +40°C, unless stated otherwise.
- This fan unit must not be used in explosive or corrosive atmospheres.
- Precautions must be taken to avoid the back-fl ow of gases into the room from the open fl ue of gas or other fuel-burning appliances.
- This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
- Means for disconnection must be incorporated in the fi xed wiring according with the wiring rules. An external disconnecting device, which will function as the “designated” disconnect device must be provided, and:
- It shall disconnect the “Line”, while disconnection of the “Neutral” is optional;
- Its OFF-position shall be clearly marked;
- Not to position the equipment so that it is diffi cult to operate it; and
- The protection current device must be at least 10A, 250V, curve Type C.
SAFETY DURING INSTALLATION
Fan unit equipment should be electrically isolated and locked out before any
work started.
The Installer, User is responsible for ensuring that the fan unit is
installed, operated and serviced by qualifi ed personnel, acting in accordance
with all safety precautions applicable and as required by law, regulations and
standards in the country applicable.
Safety protective clothing, equipment, hearing protection, and tools may be
required.
Before any installation work is started, ensure that fan unit equipment
iscorrect for application. Location for installation is solid, level, flat and
suitable for mounting fan unit assembly. Fan unit should be located in
position, and assembled with any accessory equipment supplied, on relevant
mounting, anti-vibration mountings, safety protection guards, on a solid level
base to avoid any distortion and misalignment and with correct air direction
as shown on nameplate.
Fan unit should then be levelled on any anti-vibration mountings. Flexible
connectors must be taught toensure no disruption to air flow,especially on
inlet to fan unit.
Make sure there are no loose elements near the fan unit. When the fan unit is
mounted in a duct, check that it is clean of any elements and exclusively used
for ventilation system.
The electrical installation must include a double pole switch with a contact
clearance of at least 3 mm, correctly sized and in accordance with the
electrical standards of the country of installation.
For electrical connections follow the wiring diagram “A” indicated in this
manual.
The fan unit classifi ed as Residential Ventilation Unit with control factor
0,65 have to comply with the requirements of the European Directive 2009/125
and must be installed following the local demand control definition given in
the regulation nº1253/2014 (See fig.B as example).
START UP
- Check fan unit equipment name plate data is appropriate to the location electrical supply, especially Voltage, Frequency, Phase, Amps, speed are correct.
- Check earth connections, electrical terminations and terminal box lid, with any seals, if fi tted, are correct.
- In compliance with Machine Directive, if the fan unit is accessible to operators and is a health and safety risk, adequate protection must be fi tted, information for safety equipment, including guards, can be found in S&P accessories catalogue.
- Check all rotating parts have free, unobstructed movement.
- Check there are no foreign bodies inside the fan unit or that can be drawn into, or fall into fan unit.
- Check the structure is complete and has no damage. Check installation and area is safe and energise fan unit and start motor.
- Check that the impeller and airfl ow direction is correct, and there are no unusual vibrations.
- Check current does not exceed fan equipment nameplate data.
- If any of the electrical safety devices blow, the fan unit must be quickly disconnected from the mains supply. The whole installation should be carefully checked before trying to start up the fan again. After two hours of operation, check that all fi xings are tight and adjust if necessary.
PUTTING OUT OF SERVICE AND RECYCLING
Maintenance/repairs must be carried out by competent and local regulations.
Fan unit equipment should be electrically isolated and locked out before any
work started.
Fan unit equipment should be regularly cleaned, frequency depending upon
service load and application, but no less than every year. Cleaning should
include all areas where dust can accumulate in the fan equipment. Special
attention should be made to any unusual sounds, vibration or temperature.
If any problems are detected the fan unit equipment should be stopped
immediately and cause inspected. The impeller and blades should be regularly
checked for damage that could cause imbalance in the moving parts.
PUTTING OUT OF SERVICE AND RECYCLING
EEC legislation and our consideration of future generations mean that we
should always recycle materials where possible; please do not forget to
deposit all packaging in the appropriate recycling bins. If your device is
also labeled with this symbol, please take it
to the nearest Waste Management Plant at the end of its servicable life.
The fan unit is mainly made of steel, copper, ferrite, aluminium and plastic.
These components should be recycling in the following categories:
- Steel and iron
- Aluminium
- Non-ferrous metals
- Plastics
- Insulating materials
- Cables
- Electronic scrap
To clarify any questions regarding S&P products contact your local distributor. For its location and to obtain the EU Declaration of Conformity certifi edtechnical data sheet and copy of this instruction manual, see our web site www.solerpalau.com
INFORMATION REQUIREMENTS FOR RVU
a .Trade mark
b. Identifi er
c. SEC average climate (kWh/(m 2 .an)) SEC class SEC cold climate (kWh/(m 2
.an)) SEC warm climate (kWh/(m 2 .an))
d. Typology
e. Type of drive
f. Type of HRC
g .Thermal effi ciency (%)
h. Maximum flow rate (m 3 /h)
i. Electrical power input at maximum flow rate (W)
j. Sound power level (LWA) k Reference fl ow rate (m 3 /s)
l. Reference pressure difference (Pa)
m. SPI (W/m 3 /h)
n. Control factor Control typology
o. Maximum internal leakage for BVU (%) Maximum external leakage for BVU and
UVU (%)
p. Mixing rate for BVU without duct connection (%)
q. Position of visual filter warning description of visual fi lter warning
r. Instructions to install supply grilles Instructions to install exhaust
grilles
s. Internet address
t. Airflow sensitivity to pressure variation
u. Indoor/outdoor air tighness (m 3 /h)
v. Annual electricity consumption – Average climat (kWh/a) Annual electricity
consumption – Warm climat (kWh/a) Annual electricity consumption – Cold climat
(kWh/a)
w. Annual heating saved – Average climat (kWh/a) Annual heating saved – Warm
climat (kWh/a) Annual heating saved – Cold climat (kWh/a)
| TD EVO-100| TD EVO-100 T| TD EVO-100 VAR| TD
EVO-125| TD EVO-125 T| TD EVO-125 VAR
---|---|---|---|---|---|---
a| S &P| S &P
b| | | | | |
c| -26,8| -13,4| -26,8| -26,6| -13,3| -26,6
NA| NA| NA| NA| NA| NA
-53,8| -53,8| -29,8| -53,8| -53,7| -29,7
-11,3| -11,3| -4,0| -11,3| -11,1| -3,9
d| RVU UVU| RVU UVU| RVU UVU| RVU UVU| RVU UVU| RVU UVU
e| VSD| VSD| VSD| VSD| VSD| VSD
f| None| None| None| None| None| None
g| NA| NA| NA| NA| NA| NA
h| 141| 141| 141| 220| 220| 220
i| 16,1| 16,1| 16,1| 29,2| 29,2| 29,2
j| 33| 33| 33| 37| 37| 37
k| 0,028| 0,028| 0,028| 0,043| 0,043| 0,043
l| 30| 34| 30| 36| 28| 36
m| 0,116| 0,12| 0,116| 0,129| 0,124| 0,129
n| 0,65| 1| 0,65| 0,65| 1| 0,65
n1| Local demand| Manual| Local demand| Local demand| Manual
o| NA| NA| NA| NA| NA| NA
0,4| 0,4| 0,4| 0,4| 0,1| 0,1
p| NA| NA| NA| NA| NA| NA
q| NA| NA| NA| NA| NA| NA
NA| NA| NA| NA| NA| NA
r|
| | | | |
| | | | | **
s| [ www.solerpalau.com](http://www.solerpalau.com/)| [
www.solerpalau.com**](http://www.solerpalau.com/)
t| NA| NA| NA| NA| NA| NA
u| NA| NA| NA| NA| NA| NA
v| 61| 151| 61| 68| 155| 68
| 61| 151| 61| 68| 155| 68
| 61| 151| 61| 68| 155| 68
w| 2830| 1715| 2830| 2830| 1715| 2830
| 1280| 776| 1280| 1280| 776| 1280
| 5536| 3355| 5536| 5536| 3355| 5536
S &P SISTEMAS DE VENTILACIÓN, S.L.U.
C. Llevant, 4
Polígono Industrial Llevant
08150 Parets del Vallès
Barcelona – España
Tel. +34 93 571 93 00
Fax +34 93 571 93 01
www.solerpalau.com Ref. 9023038303-01
References
- Ventilation Systems – S&P
- Μηχανήματα Εξαερισμού - Ε. ΚΑΦΦΕΣ Α.Ε.|Εναλλάκτες θερμότητας/συστηματα ψυξης-θερμανσης/εξαεριστηρες
- Ventilation Systems – S&P
- Ventilation Systems – S&P