Gibson G7SD High Efficiency Single Stage Condensing Upflow Gas Owner’s Manual

June 15, 2024
Gibson

Gibson G7SD High Efficiency Single Stage Condensing Upflow Gas

PRODUCT INFORMATION

Technical Specifications

  • Model: (*)G7SD
  • Type: High Efficiency, Single Stage, Condensing Upflow Gas Furnace
  • AFUE: Up to 95.0
  • Btuh Input: 38,000 – 115,000

Features and Benefits

  • Can be installed free standing in a utility room, basement, or enclosed in an alcove or closet
  • Extended flush jacket for a pleasing appliance appearance
  • Not compliant with SCAQMD Rule 1111 or SJVPACD Rule 4905 NOx emission limit (14 ng/J) for California installations

Gas Furnace Components

  • Flame Sensor
  • Finish Flange
  • Roll-Out Switch
  • Main Air Limit Switch
  • Inducer Limit Switch
  • Pressure Switch (Inducer)
  • Inducer Assembly
  • Blower Door Switch
  • Burner Assembly
  • Igniter Gas Valve Furnace Control Board
  • Pressure Switch (Condensate)
  • Transformer
  • Motor Choke
  • Motor Control Board
  • Blower Assembly

Dimensions

Model # Dim. -A Dim. -B Dim. -C
038D-T24B 17 1/2 inches 15 7/8 inches 16 1/8 inches
054D-T24B 21 inches 19 3/8 inches 19 5/8 inches
072D-T35C 24 1/2 inches 22 7/8 inches 23 1/8 inches
090D-T35C
108D-T45D
120D-T45D

FAQ

  • Q: Is this furnace compliant with SCAQMD regulations?
    A: No, this furnace does not meet the SCAQMD Rule 1111 or SJVPACD Rule 4905 NOx emission limit (14 ng/J).

INSTRUCTION

The high efficiency upflow gas furnace may be installed free standing in a utility room, basement, or enclosed in an alcove or closet. The extended flush jacket provides a pleasing “appliance appearance.” For California installations in SCAQMD only: This furnace does not meet the SCAQMD Rule 1111 or SJVPACD Rule 4905 NOx emission limit (14 ng/J).

FEATURES and BENEFITS

  • 100% fired and tested: All units and each component are tested on the manufacturing line.
  • Best packaging in the industry: Unique corner post design assures product will arrive to the homeowner dent free.
  • 30 second blower delay at start-up assures a warm duct temperature at furnace start-up. Adjustable blower off settings (60, 90, 120 and 180 seconds).
  • 30 second post purge increases life of heat exchanger.
  • Hot surface igniter: Innovative application of a silicon nitride type igniter. Utilizes proven Smartlite® technology.
  • Color coded wire harness: Designed to fit the components, all with quick-connect fittings for ease of service and replacement.
  • Flexible category IV venting system: May be vertically or horizontally vented using either a one-pipe or two-pipe system for maximum flexibility in installation.
  • High Static Blowers: All models equipped with high static blowers.
  • Low Boy Height: Easy to apply in low ceiling applications, works well with taller high SEER coils, easier to handle and install.
  • Tubular primary heat exchanger: Heavy gauge aluminized steel heat exchanger and stainless steel secondary heat exchanger assures a long life.
  • 60 second fixed cooling cycle blower-off delay (TDR) increases cooling performance when matched with a Nortek Global HVAC coil.
  • Multi-speed direct drive blower: Designed to give a wide range of cooling capacities. Dip switches on PCB provide easy motor speed selection.
  • LP convertible: Simple burner orifice and regulator spring change for ease of convertibility.
  • Incorporates integrated control board with connections for electronic air cleaner and humidifier.
  • Two piece door design enhances furnace appearance and uses captured screws to prevent losing door screws.
  • Blower Compartment: Sealed door to reduce air leakage and insulated for ultra quiet operation.
  • Sealed Vestibule reduces burner and inducer sound levels.
  • Furnace Air Leakage: These furnaces comply with Energy Star cabinet air leakage requirement of less than or equal to 2%. Keep the conditioned air flowing to where it’s needed.
  • PolyPro by DuraVent: These furnaces have been tested with and are approved to be installed with DuraVent’s PolyPro venting system.

GAS FURNACE COMPONENTS

Gibson-G7SD-High-Efficiency-Single-Stage-Condensing-Upflow-Gas-
\(1\)

DIMENSIONS

*()G7SD Upflow Furnaces**

Model #’s| Dim. -A-| Dim -B-| Dim -C-
038D-T24B| ****

17 1/2

| ****

15 7/8

| ****

16 1/8

054D-T24B
072D-T35C| ****

21

| ****

19 3/8

| ****

19 5/8

090D-T35C
108D-T45D| ****

24 1/2

| ****

22 7/8

| ****

23 1/8

120D-T45D

Gibson-G7SD-High-Efficiency-Single-Stage-Condensing-Upflow-Gas-
\(2\)

BLOWER PERFORMANCE – (*)G7SD

Gibson-G7SD-High-Efficiency-Single-Stage-Condensing-Upflow-Gas-
\(3\)

NOTES:

  1. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
  2. Data is shown without filter.
  3. Temperature rises in the table are approximate. Actual temperature rises may vary.
  4. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
  5. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
  6. Unit ships with (4) speeds pre-wired. Use of the fifth speed will require changing the appropriate wires at the motor connection. Consult the wiring diagram for more information.

NOTES:

  1. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
  2. Data is shown without filter.
  3. Temperature rises in the table are approximate. Actual temperature rises may vary.
  4. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
  5. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
  6. Unit ships with (4) speeds pre-wired. Use of the fifth speed will require changing the appropriate wires at the motor connection. Consult the wiring diagram for more information.

Gibson-G7SD-High-Efficiency-Single-Stage-Condensing-Upflow-Gas-
\(5\)

NOTES:

  1. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
  2. Data is shown without filter.
  3. Temperature rises in the table are approximate. Actual temperature rises may vary.
  4. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
  5. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
  6. Unit ships with (4) speeds pre-wired. Use of the fifth speed will require changing the appropriate wires at the motor connection. Consult the wiring diagram for more information.

Gibson-G7SD-High-Efficiency-Single-Stage-Condensing-Upflow-Gas-
\(6\)

NOTES:

  1. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
  2. Data is shown without filter.
  3. Temperature rises in the table are approximate. Actual temperature rises may vary.
  4. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
  5. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
  6. Unit ships with (4) speeds pre-wired. Use of the fifth speed will require changing the appropriate wires at the motor connection. Consult the wiring diagram for more information.

Gibson-G7SD-High-Efficiency-Single-Stage-Condensing-Upflow-Gas-
\(7\)

NOTES:

  1. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
  2. Data is shown without filter.
  3. Temperature rises in the table are approximate. Actual temperature rises may vary.
  4. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
  5. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
  6. Unit ships with (4) speeds pre-wired. Use of the fifth speed will require changing the appropriate wires at the motor connection. Consult the wiring diagram for more information.

Gibson-G7SD-High-Efficiency-Single-Stage-Condensing-Upflow-Gas-
\(8\)

NOTES:

  1. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
  2. Data is shown without filter.
  3. Temperature rises in the table are approximate. Actual temperature rises may vary.
  4. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
  5. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
  6. Unit ships with (4) speeds pre-wired. Use of the fifth speed will require changing the appropriate wires at the motor connection. Consult the wiring diagram for more information.

VENTING

All models are approved for vertical non direct (1 pipe) and direct (2 pipe) venting applications. See Vent Table below for specified sizes and allowable lengths.

VENT TABLE

 | SINGLE PIPE LENGTH (FT.)

with 1 long radius elbow*

| DIRECT VENT,

DUEL PIPE LENGTH (ft.) WITH

1 long radius elbow on each pipe*

---|---|---
OUTLET| OUTLET| INLET/OUTLET| INLET/OUTLET
MODELS| 2”| 3”| 2”| 3”
SD038| 50| 70| 50| 70
SD054| 70| 90| 70| 90
SD072| 50| 90| 50| 90
SD090| 60| 90| 60| 90
SD108| N/A| 90| N/A| 90
SD120| N/A| 90| N/A| 90

* NOTE:

  1. Subtract 2.5 ft. for each additional 2″ elbow and 3.5 ft. for each additional 3″ elbow.
  2. Two 45 degree elbows are equivalent to one 90 degree elbow.
  3. One short radius elbow is equivalent to two long radius elbows.
  4. Do not include termination elbows in calculation of vent length.
  5. This table is applicable for elevations from sea level to 2000 ft. For higher elevations decrease vent pipe lengths by 8% per 1000 ft. of altitude.
  6. Only the listed pipe materials are approved for use with FG7 Condensing Furnaces.

MODEL IDENTIFICATION CODE

Gibson-G7SD-High-Efficiency-Single-Stage-Condensing-Upflow-Gas-
\(9\)

SPECIFICATIONS

*()G7SD MODEL NUMBERS:| -038D-T24B1| -054D-T24B1| -072D- T35C1| -090D-T35C1| -108D-T45D1| -120D-T45D1
---|---|---|---|---|---|---
Input – Btuh (a)| 38,000| 54,000| 72,000| 85,000| 108,000| 115,000
Heating Capacity – Btuh| 36,000| 51,000| 68,000| 81,000| 103,000| 109,000
AFUE**| 95.0| 95.0| 95.0| 95.0| 95.0| 95.0
Blower D x W| 10 x 8| 11 x 8| 10 x 10| 11 x 10| 11 x 10| 11 x 10
Motor H.P. – Speed – Type| 3/4 – 5 – ECM| 3/4 – 5 – ECM| 3/4 – 5 – ECM| 1 – 5 – ECM| 1 – 5 – ECM| 1 – 5 – ECM
Motor FLA| 8.8| 8.8| 8.8| 11.5| 11.5| 11.5
Rated Ext. SP – In. W.C.| 0.5| 0.5| 0.5| 0.5| 0.5| 0.5
Temperature Rise Range – ºF| 25 – 55| 30 – 60| 35 – 65| 35 – 65| 35 – 65| 40 – 70
Shipping Weights| 100lbs| 120lbs| 130lbs| 135lbs| 155lbs| 156lbs

NOTE: All models are 115V, 60 Hz. Gas Connections are 1/2″ N.P.T. AFUE = Annual Fuel Utilization Efficiency (a) Ratings to 2,000 ft. Over 2,000 ft. reduce 4% for each 1,000 ft. above sea level.

ACCESSORIES

*()G7SD KITS**

Description| SKU
2″ Concentric vent kit, Canadian and US approved| 904952
3″ Concentric vent kit, Canadian and US approved| 904953
2″ Side wall vent kit| 904617
3″ Side wall vent kit| 904347
U.S. LP Conversion kit (0 to 10,000 ft.)| 905028
Canada LP Conversion kit (0 to 4,500 ft.)| 905029
Bottom return filter 20 per box, “B” cabinet| 904916
Bottom return filter 20 per box, “C” cabinet| 904917
Bottom return filter 20 per box, “D” cabinet| 904918
Side return filter kit| 541036
Neutralizer kit| 902377
Furnace Twinning Kit| 1010035

Gibson-G7SD-High-Efficiency-Single-Stage-Condensing-Upflow-Gas-
\(10\)

GENERAL TERMS OF LIMITED WARRANTY
Nortek Global HVAC, LLC will furnish a replacement for any part of this product which fails in normal use and service within the terms and conditions of the warranty. For complete details of the Limited Warranty, including applicable terms and conditions, see your local installer or contact the Nortek Global HVAC, LLC warranty department for a copy.

Before purchasing this appliance, read important energy cost and efficiency information available from your retailer. Specifications and illustrations subject to change without notice and without incurring obligations. Printed in U.S.A (03/23)

593F-0323 (Replaces 593F-0123)
www.gibsonhvac.com
GIBSON is a pending or registered trademark of Electrolux Home Products Inc. and used under a license from Electrolux Home Products, Inc. © Nortek Global HVAC, LLC. All Rights Reserved.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Gibson User Manuals

Related Manuals