FRIGIDAIRE Q4SE Series Single Packaged Heat Pump Owner’s Manual
- June 15, 2024
- Frigidaire
Table of Contents
- Introduction
- WARRANTY
- FEATURES AND BENEFITS
- MODEL IDENTIFICATION CODE
- DIMENSIONS
- SPECIFICATIONS
- ELECTRICAL DATA
- BLOWER PERFORMANCE
- HEATER APPLICATION MATRIX
- EXPANDED COOLING PERFORMANCE – 14 SEER H.P.
- Q4SE ACCESSORIES
- GENERAL TERMS OF LIMITED WARRANTY
- Customer Support
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
FRIGIDAIRE Q4SE Series Single Packaged Heat Pump
Introduction
Q4SE-14 SEER
2 – 5 Ton Units
Cooling: 23,600 to 56,500 Btuh
Heating: 22,200 to 55,500 Btuh
The Q4SE Series single packaged heat pumps are high efficiency self contained cooling and heating units that can
be installed on a roof or on a slab. The convertible unit design makes installations simple in all applications. Units are ETL and ETLc listed.
WARRANTY
- This product offers a 10-year All-Parts Warranty.
- This product offers a 10 year Quality Pledge to replace the entire unit, if the unit’s major component (heat exchanger or compressor) fails within the first 10 years of operation, to the original owner.
- Consumer product registration required for both 1 0 year All Parts Warranty and Quality Pledge within a limited period of time after the installation. See current warranty document or visit our consumer web site listed on the back of this document for warranty details.
FEATURES AND BENEFITS
- Copeland Ultra-Tech Compressor: State of the art 2 stage scroll compressor is standard equipment.
- Quiet Operation and Low Vibration: Compressor sound blanket is standard. Swept-wing fan blade combined with custom Venturi condenser fan.
- R-41 0A Refrigerant: Earth friendly non-ozone depleting refrigerant.
- Wire guard coated with Earth Friendly Epoxy and plastic mesh hail guard: A guard that will never rust and protects the units coil from being damaged.
- Copper Tube/Aluminum Fin Coils: Both indoor and outdoor coils are designed to optimize heat transfer, minimize size and cost, and increase durability and reliability.
- Designed using Galvanized Steel: with a polyester urethane coat finish. The 950 hour salt spray finish is 1.5 mil thick and resists corrosion 50% better than comparable units.
- Permanently Lubricated Condenser Motor: A heavy duty PSC motor for long lasting reliability and quiet operation. Requires no maintenance and is completely protected from rain and snow.
- Thermostatic Expansion Valves: Factory installed externally equalized thermostatic expansion valves provides precise refrigerant control under varying load conditions.
- Hi/Low Pressure Switches: Ensure long compressor life.
- Externally Accessible, High Flow Service Ports: Quick access to refrigeration system.
- Liquid Line Filter Driers: Factory installed at a convenient location for service.
- Suction Accumulator: Protection from liquid flood back and future compressor failures.
- Low voltage Transformer: Includes 3 Amp fuse to protect low voltage circuit.
- Corrosion-Resistant Drain Pan: Quickly drains away evaporator condensate.
- ECM Variable Speed Blower Motor: Advanced technology allows the motor to automatically adjust to different static loads. The variable speed motor allows for extra quiet operation and improved air quality.
- Demand Defrost Standard: Provides additional energy savings in heating by defrosting only when necessary.
- Three Minute Restart Time Delay: When the unit shuts down, a three minute delay keeps the unit from restarting, eliminating the highest cause for compressor failure.
- Heavy-Gauge, Full Perimeter Base Rails: Facilitates forklift handling and curb mounting.
- Convertible Air Delivery: Horizontal or downflow to accommodate rooftop or horizontal applications.
- Easy Compressor and Control Access: Designed to make servicing easier for the contractor, access panels are provided to all controls and the compressor from the side of the unit.
- Easy access: to the evaporator coil for cleaning and general maintenance.
- Removable Top Grille Assembly: Allows ease of service to the fan motor.
- Duct Flanges: reduce installation costs.
- Optional Electric Heat: Field installed 5 – 20 KW.
- Proven, Industry Standard Components: Easier service and availability.
MODEL IDENTIFICATION CODE
DIMENSIONS
- Top View
MODEL NUMBER
143%-
|
5NIT 7EIGHT
|
#ENTER OF ‘RAVITY
|
(EIGHT (IN INCHES)
#
|
---|---|---|---|---
!| “|
WITH BASE RAILS
|
WITHOUT BASE RAILS
|
X24| 450| 28.0| 25.5| 39.0| 35.3|
X36| 460| 28.0| 25.5| 39.0| 35.3|
X48| 570| 29.5| 26.0| 43.0| 39.3|
X60| 580| 29.5| 26.0| 43.0| 39.3|
-
Side View
-
Back (Duct) View
SPECIFICATIONS
MODEL NUMBER | 143( )- |
---|
824+
|
836+
|
848+
|
860+
PERFORMANCE| | | |
Capacity – Heating BTUH| 22,200| 33,000| 42,500| 55,500
Efficiency – HSPF| 8.0| 8.0| 8.0| 8.0
Capacity – Cooling BTUH| 23,600| 34,000| 44,000| 56,500
Efficiency – SEER| 14.20| 14.00| 14.50| 14.00
EER (Btuh/watt)| 11.0| 11.0| 11.0| 11.0
ELECTRICAL RATING – 60 (Z| | | |
Phase| 1| 1| 1| 1
Operating Voltage Range| 187-253| 187-253| 187-253| 187-253
COMPRESSOR DATA| | | |
Volts| 208-230| 208-230| 208-230| 208-230
Rated Load Amps| 11.4| 19.0| 24.0| 26.0
Lock Rotor Amps| 52| 82| 96| 118
INDOOR BLOWER| | | |
Type| Var. Sp.| Var. Sp.| Var. Sp.| Var. Sp.
Motor HP| 1/2| 1/2| 3/4| 3/4
Motor RPM Range| 490-740| 490-740| 645-950| 645-950
Motor – Amps| 4.3| 4.3| 6.8| 6.8
OUTDOOR &AN| | | |
Motor – HP / RPM| 1/4 – 825| 1/4 – 1100| 1/4 – 1100| 1/3 – 1000
Motor – Amps| 1.4| 1.2| 1.2| 1.5
Fan Diameter / CFM| 20 / 3200| 20 / 3800| 20 / 3800| 20 / 4000
REFRIGERANT CHARGE – OZ.| 112.0| 126.4| 264| 236.8
NET WEIGHT LBS.| 450| 460| 570| 580
SHIPPING WEIGHT LBS.| 460| 470| 580| 590
ELECTRICAL DATA
Model Number | Heater kw | Single Circuit | Multiple Supply Circuit Option |
---|---|---|---|
MCA | Rec, Wire Gage (90°C Cu) | MOP | Circuit A (Compressor, Blower & Fan) |
Circuit B (Heater Only) | Circuit C (Heater Only) | ||
MCA | Rec, Wire Gage (90°C Cu) | MOP | MCA |
Rec, Wire Gage (90°C Cu) | MOP | ||
Q4SE-X24K | 0 | 20 | 12 |
5 | 45 | 8 | 50 |
8 | 60 | 6 | 60 |
10 | 70 | 6 | 70 |
Q4SE-X36K | 0 | 29 | 10 |
5 | 54 | 8 | 60 |
8 | 69 | 6 | 70 |
10 | 79 | 4 | 80 |
15 | 104 | 3 | 110 |
Q4SE-X48K | 0 | 38 | 8 |
5 | 63 | 6 | 80 |
8 | 78 | 4 | 90 |
10 | 88 | 4 | 100 |
15 | 113 | 2 | 125 |
20 | 138 | 1 | 150 |
Q4SE-X60K | 0 | 41 | 8 |
5 | 66 | 6 | 80 |
8 | 80 | 4 | 90 |
10 | 91 | 4 | 100 |
15 | 116 | 2 | 125 |
20 | 141 | 1 | 150 |
BLOWER PERFORMANCE
Basic Air-Flow Settings
1/2 HP Motor | 1/2 HP Motor | 3/4 HP Motor |
---|---|---|
SWITCH | Nominal | |
# &- | 1 | 2 |
2 | 3 | 4 |
4.0 | 5.0 | |
720 | 0 | 0 |
TON | 1080 | 0 |
800 | 0 | 0 |
TON
810| 1| 0| 0| 1| 1215| 1| 0| 0| 1| 3
TON| 1550| 0| 0| 0| 0
880| 0| 0| 1| 0| 1260| 0| 1| 0| 1| 1620| 0| 1| 0| 1| 5
TON
900| 1| 0| 0| 0| 1320| 0| 0| 1| 0| 1650| 1| 0| 0| 0
945| 0| 1| 0| 1| 1350| 1| 0| 0| 0| 1705| 0| 0| 1| 0
990| 1| 0| 1| 0| 1395| 1| 1| 0| 1| 1710| 1|
1| 0| 1
1035| 1| 1| 0| 0| | 1400| 0| 1| 0| 0| 1800| 0| 1| 0| 0
1050| 0| 1| 0| 0| 1485| 1| 0| 1| 0| 1815| 1| 0| 1| 0
1150| 1| 1| 0| 0| 1540| 0| 1| 1| 0| 1900| 1| 1| 0| 0|
1155| 0| 1| 1| 0| 1550| 1| 1| 0| 0| | 1980| 0| 1| 1| 0
1265| 1| 1| 1| 0| 1705| 1| 1| 1| 0| 2090| 1| 1| 1| 0|
Note : 1=ON, 0=OFF
Air Flow Selection for Variable Speed Motors
Delay Description | Switch Number |
---|---|
1 | 2 |
0-5 | 500 |
6-10 | 700 |
11-15 | 900 |
16-20 | 1100 |
Note : 1=ON, 0=OFF
Minimum Electric Heat Airflow (all models)
Delay Description | Switch Number |
---|---|
1 | 2 |
Delay A | |
Delay B | |
No Delay | |
De-Hum. |
Note : 1=ON, 0=OFF
Delay Settings (all models)
HEATER APPLICATION MATRIX
MODEL NUMBER| H3HK-005H-01 B| H3HK-008H-01 B| H3HK-010H-01 B| H3HK-
015H-01 B| H3HK-020H-01 B| H3HK-015H-21 B| H3HK-020H-21 B
---|---|---|---|---|---|---|---
917166″| 917167″| 917168″| 917169″| 917170″|
917172″| 917173″
Q4S( )-X24K| X| X(2)| X(2)| NA| NA| X| NA
Q4S( )-X36K| X| X(2)| X(2)| X(2)| NA| X| NA
Q4S( )-X48K| X(2)| X(2)| X(2)| X(3)| X(3)| X(1)| X(1)
Q4S( )-X60K| X(2)| X(2)| X(2)| X(3)| X(3)| X(1)| X(1)
NA = Not Applicable.
() = Number of internal circuit breaker kits required.
MODEL IDENTIFICATION CODE
EXPANDED COOLING PERFORMANCE – 14 SEER H.P.
Q4SE-X24K
O.D.T | 85°F | 95 °F | 105 °F | 115 °F |
---|---|---|---|---|
CFM | E.D.B. | E.W.B. | T.C. | S.C. |
S.C. | K.W. | T.C. | S.C. | K.W. |
700 | 80 | 62 | 22.2 | 18.8 |
2.47
80| 67| 24.5| 15.4| 1.73| 23.3| 15.0| 1.92| 22.0| 14.5| 2.13| 20.5| 14.0| 2.37
80| 72| 26.4| 11.8| 1.75| 25.0| 11.4| 1.95| 23.6| 10.9| 2.16| 22.0| 10.4| 2.40
75| 63| 22.8| 15.2| 1.72| 21.7| 15.2| 1.90| 20.5| 15.0| 2.11| 19.1| 14.7| 2.35
850| 80| 62| 23.1| 20.8| 1.82| 22.0| 20.9| 2.02| 20.8| 20.3| 2.24| 19.5| 19.5|
2.49
80| 67| 25.3| 17.1| 1.74| 24.0| 16.6| 1.93| 22.6| 16.1| 2.14| 21.1| 15.5| 2.38
80| 72| 27.2| 12.8| 1.76| 25.8| 12.3| 1.95| 24.2| 11.8| 2.17| 22.5| 11.3| 2.41
75| 63| 23.6| 17.4| 1.73| 22.4| 17.2| 1.91| 21.1| 16.9| 2.12| 19.6| 16.4| 2.36
1000| 80| 62| 24.1| 22.3| 1.83| 23.0| 21.8| 2.03| 21.7| 21.7| 2.25| 20.3|
20.3| 2.51
80| 67| 25.9| 18.7| 1.75| 24.6| 18.2| 1.94| 23.1| 17.6| 2.15| 21.5| 17.0| 2.39
80| 72| 27.7| 13.7| 1.77| 26.2| 13.2| 1.96| 24.6| 12.7| 2.18| 22.9| 12.1| 2.42
75| 63| 24.1| 19.7| 1.73| 22.9| 19.2| 1.92| 21.5| 18.7| 2.13| 20.0| 18.0| 2.36
Q4SE-X36K
O.D.T | 85 °F | 95 °F | 105 °F | 115 °F |
---|---|---|---|---|
CFM | E.D.B. | E.W.B. | T.C. | S.C. |
S.C. | K.W. | T.C. | S.C. | K.W. |
1200 | 80 | 62 | 32.7 | 28.1 |
27.4 | 3.64 | |||
80 | 67 | 35.3 | 22.7 | 2.73 |
80 | 72 | 37.7 | 17.3 | 2.77 |
75 | 63 | 32.4 | 23.8 | 2.70 |
1350 | 80 | 62 | 33.5 | 29.5 |
28.4 | 3.66 | |||
80 | 67 | 35.9 | 24.1 | 2.74 |
80 | 72 | 38.3 | 18.2 | 2.78 |
75 | 63 | 33.0 | 25.9 | 2.70 |
1500 | 80 | 62 | 34.1 | 31.6 |
29.1 | 3.67 | |||
80 | 67 | 36.4 | 25.1 | 2.75 |
80 | 72 | 38.8 | 19.0 | 2.78 |
75 | 63 | 33.5 | 28.2 | 2.71 |
Q4SE-X48K
O.D.T | 85 °F | 95 °F | 105 °F | 115 °F |
---|---|---|---|---|
CFM | E.D.B | E.W.B. | T.C. | S.C. |
S.C. | K.W. | T.C. | S.C. | K.W. |
1500 | 80 | 62 | 48.9 | 22.6 |
23.4 | 4.80 | |||
80 | 67 | 45.7 | 29.7 | 3.65 |
80 | 72 | 48.9 | 22.6 | 3.70 |
75 | 63 | 41.9 | 30.7 | 3.59 |
1650 | 80 | 62 | 49.5 | 23.5 |
24.6 | 4.81 | |||
80 | 67 | 46.4 | 31.2 | 3.66 |
80 | 72 | 49.5 | 23.5 | 3.71 |
75 | 63 | 42.6 | 33.4 | 3.60 |
1800 | 80 | 62 | 50.1 | 25.6 |
25.3 | 4.82 | |||
80 | 67 | 47.0 | 32.6 | 3.67 |
80 | 72 | 50.1 | 24.3 | 3.72 |
75 | 63 | 43.1 | 36.3 | 3.61 |
Q4SE-X60K
O.D.T | 85 °F | 95 °F | 105 °F | 115 °F |
---|---|---|---|---|
# &- | E.D.B. | E.W.B. | T.C. | S.C. |
T.C. | S.C. | K.W. | T.C. | S.C. |
1600 | 80 | 62 | 52.0 | 41.5 |
41.7 | 6.03 | |||
80 | 67 | 56.3 | 34.3 | 4.55 |
80 | 72 | 61.5 | 26.3 | 4.64 |
75 | 63 | 51.7 | 35.5 | 10.59 |
10.55
1800| 80| 62| 53.2| 44.2| 4.49| 50.6| 45.6| 4.97| 47.7| 45.2| 5.49| 44.5|
44.5| 6.06
80| 67| 57.6| 36.5| 4.57| 54.6| 35.5| 5.05| 51.4| 34.4| 5.58| 47.8| 33.2| 6.15
80| 72| 62.1| 27.7| 4.66| 59.0| 26.8| 5.14| 55.4| 25.8| 5.67| 51.6| 24.6| 6.25
75| 63| 52.9| 39.2| 10.59| 50.2| 38.8| 10.58| 47.3| 37.6| 10.58| 44.0| 36.6|
10.58
2000| 80| 62| 54.4| 48.0| 4.51| 51.7| 47.8| 4.99| 48.6| 48.6| 5.51| 45.7|
45.7| 6.09
80| 67| 58.6| 38.7| 4.59| 55.5| 37.6| 5.06| 52.2| 36.5| 5.60| 48.6| 34.7| 6.17
80| 72| 63.2| 29.0| 4.68| 59.9| 28.1| 5.16| 56.2| 27.0| 5.69| 52.3| 25.9| 6.27
75| 63| 54.0| 42.5| 10.56| 51.2| 41.7| 10.56| 48.1| 40.5| 10.56| 44.7| 39.1|
10.56
Q4SE X24
| OUTDOOR TEMPERATURE (Deg. F)
---|---
CFM| lndoor T. Deg.F| 10| 17| 20| 30| 40|
47| 50| 60
MBH| COP| kW| MBH| COP| kW| MBH| COP| kW| MBH| COP| kW| MBH| COP| kW| MBH|
COP| kW| MBH| COP| kW| MBH| COP| kW
700| 60| 10.0| 1.88| 1.57| 12.6| 2.31| 1.60| 13.7| 2.49| 1.61| 17.3| 3.06|
1.66| 21.0| 3.61| 1.70| 23.5| 3.98| 1.73| 24.6| 4.13| 1.75| 28.2| 4.62| 1.79
70| 9.5| 1.83| 1.52| 11.9| 2.22| 1.57| 12.9| 2.38| 1.59| 16.3| 2.88| 1.66|
19.7| 3.34| 1.73| 22.1| 3.64| 1.78| 23.1| 3.77| 1.80| 26.5| 4.16| 1.86
80| 8.9| 1.74| 1.50| 11.1| 2.10| 1.55| 12.1| 2.24| 1.58| 15.2| 2.69| 1.66|
18.4| 3.10| 1.73| 20.6| 3.37| 1.79| 21.5| 3.48| 1.81| 24.7| 3.82| 1.89
850| 60| 10.1| 1.82| 1.63| 12.8| 2.25| 1.66| 13.9| 2.43| 1.67| 17.6| 3.01|
1.71| 21.3| 3.57| 1.75| 23.9| 3.94| 1.78| 25.1| 4.09| 1.80| 28.8| 4.59| 1.84
70| 9.7| 1.78| 1.60| 12.1| 2.16| 1.64| 13.1| 2.32| 1.66| 16.6| 2.83| 1.72|
20.1| 3.30| 1.79| 22.5| 3.61| 1.83| 23.5| 3.73| 1.85| 27.0| 4.14| 1.91
80| 9.1| 1.70| 1.56| 11.4| 2.05| 1.62| 12.3| 2.20| 1.64| 15.6| 2.65| 1.72|
18.8| 3.06| 1.80| 21.1| 3.33| 1.86| 22.1| 3.44| 1.88| 25.3| 3.79| 1.96
1000| 60| 10.4| 1.80| 1.69| 13.0| 2.22| 1.72| 14.1| 2.40| 1.73| 17.9| 2.98|
1.76| 21.7| 3.53| 1.80| 24.3| 3.91| 1.83| 25.5| 4.07| 1.84| 29.2| 4.58| 1.87
70| 9.8| 1.75| 1.65| 12.3| 2.13| 1.69| 13.4| 2.29| 1.71| 16.9| 2.80| 1.77|
20.5| 3.27| 1.84| 23.0| 3.58| 1.88| 24.0| 3.71| 1.90| 27.6| 4.13| 1.96
80| 9.3| 1.67| 1.63| 11.6| 2.02| 1.68| 12.6| 2.16| 1.70| 15.8| 2.61| 1.78|
19.1| 3.01| 1.86| 21.4| 3.28| 1.92| 22.4| 3.39| 1.94| 25.7| 3.74| 2.02
Q4SE X36
| OUTDOOR TEMPERATURE (Deg. F)
---|---
CFM| lndoor T. Deg.F| 10| 17| 20| 30| 40| 47|
50| 60
MBH| COP| kW| MBH| COP| kW| MBH| COP| kW| MBH| COP| kW| MBH| COP| kW| MBH|
COP| kW| MBH| COP| kW| MBH| COP| kW
1200| 60| 15.0| 1.96| 2.24| 18.6| 2.38| 2.29| 20.1| 2.55| 2.31| 25.2| 3.09|
2.39| 30.3| 3.60| 2.47| 33.9| 3.94| 2.52| 35.4| 4.08| 2.55| 40.5| 4.53| 2.62
70| 14.3| 1.83| 2.29| 17.8| 2.21| 2.36| 19.2| 2.36| 2.39| 24.1| 2.85| 2.48|
29.0| 3.31| 2.57| 32.4| 3.61| 2.64| 33.9| 3.73| 2.66| 38.8| 4.13| 2.76
80| 13.8| 1.70| 2.37| 17.0| 2.04| 2.44| 18.4| 2.18| 2.47| 23.1| 2.63| 2.57|
27.8| 3.04| 2.68| 31.0| 3.31| 2.75| 32.4| 3.43| 2.78| 37.1| 3.78| 2.88
1350| 60| 15.1| 1.94| 2.29| 18.7| 2.35| 2.34| 20.3| 2.52| 2.36| 25.5| 3.08|
2.43| 30.7| 3.60| 2.50| 34.4| 3.94| 2.55| 35.9| 4.09| 2.58| 41.1| 4.55| 2.65
70| 14.5| 1.81| 2.35| 18.0| 2.19| 2.41| 19.5| 2.35| 2.44| 24.5| 2.84| 2.52|
29.4| 3.31| 2.61| 32.9| 3.61| 2.67| 34.4| 3.74| 2.70| 39.4| 4.15| 2.78
80| 13.9| 1.68| 2.43| 17.3| 2.03| 2.49| 18.7| 2.17| 2.52| 23.4| 2.62| 2.62|
28.2| 3.04| 2.72| 31.5| 3.32| 2.78| 32.9| 3.44| 2.81| 37.7| 3.80| 2.91
1500| 60| 15.2| 1.91| 2.34| 18.9| 2.33| 2.38| 20.5| 2.50| 2.40| 25.8| 3.06|
2.47| 31.1| 3.59| 2.54| 34.8| 3.94| 2.59| 36.3| 4.08| 2.61| 41.6| 4.56| 2.68
70| 14.7| 1.80| 2.40| 18.2| 2.18| 2.45| 19.7| 2.34| 2.48| 24.8| 2.84| 2.56|
29.8| 3.31| 2.65| 33.4| 3.62| 2.70| 34.9| 3.75| 2.73| 39.9| 4.16| 2.81
80| 14.1| 1.67| 2.48| 17.5| 2.02| 2.54| 18.9| 2.16| 2.57| 23.7| 2.61| 2.66|
28.5| 3.04| 2.75| 31.9| 3.32| 2.82| 33.3| 3.43| 2.85| 38.1| 3.80| 2.94
Q4SE X48
| OUTDOOR TEMPERATURE (Deg. F)
---|---
CFM| lndoor T. Deg.F| 10| 17| 20| 30| 40|
47| 50| 60
MBH| COP| kW| MBH| COP| kW| MBH| COP| kW| MBH| COP| kW| MBH| COP| kW| MBH|
COP| kW| MBH| COP| kW| MBH| COP| kW
1500| 60| 16.5| 1.91| 2.54| 21.6| 2.40| 2.64| 23.8| 2.60| 2.68| 31.0| 3.22|
2.83| 38.2| 3.78| 2.97| 43.3| 4.14| 3.07| 45.5| 4.29| 3.11| 52.7| 4.75| 3.25
70| 15.8| 1.75| 2.65| 20.7| 2.21| 2.76| 22.9| 2.39| 2.81| 29.9| 2.96| 2.96|
36.9| 3.47| 3.12| 41.8| 3.80| 3.23| 43.9| 3.93| 3.28| 51.0| 4.35| 3.44
80| 15.3| 1.61| 2.78| 20.0| 2.03| 2.89| 22.1| 2.20| 2.95| 28.9| 2.72| 3.12|
35.7| 3.19| 3.29| 40.5| 3.48| 3.40| 42.5| 3.61| 3.46| 49.3| 3.99| 3.63
1650| 60| 16.7| 1.89| 2.59| 21.8| 2.38| 2.68| 24.0| 2.58| 2.72| 31.3| 3.21|
2.86| 38.6| 3.79| 2.99| 43.8| 4.16| 3.09| 46.0| 4.31| 3.13| 53.3| 4.79| 3.26
70| 16.0| 1.74| 2.70| 21.0| 2.20| 2.80| 23.1| 2.38| 2.85| 30.2| 2.96| 3.00|
37.3| 3.48| 3.15| 42.3| 3.82| 3.25| 44.4| 3.95| 3.30| 51.5| 4.39| 3.45
80| 15.4| 1.60| 2.82| 20.3| 2.02| 2.94| 22.3| 2.19| 2.99| 29.2| 2.72| 3.15|
36.1| 3.20| 3.31| 40.9| 3.51| 3.42| 43.0| 3.63| 3.47| 49.9| 4.03| 3.63
1800| 60| 16.8| 1.87| 2.63| 22.0| 2.37| 2.72| 24.2| 2.57| 2.76| 31.6| 3.20|
2.89| 39.0| 3.78| 3.02| 44.2| 4.16| 3.12| 46.4| 4.31| 3.16| 53.8| 4.80| 3.29
70| 16.2| 1.74| 2.74| 21.3| 2.19| 2.84| 23.4| 2.38| 2.88| 30.6| 2.96| 3.03|
37.7| 3.49| 3.17| 42.8| 3.83| 3.27| 44.9| 3.97| 3.32| 52.1| 4.41| 3.46
80| 15.6| 1.60| 2.87| 20.5| 2.02| 2.98| 22.6| 2.19| 3.02| 29.5| 2.72| 3.18|
36.5| 3.21| 3.33| 41.3| 3.52| 3.44| 43.4| 3.65| 3.49| 50.4| 4.05| 3.65
Q4SE X60
| OUTDOOR TEMPERATURE (Deg. F)
---|---
CFM| lndoor T. Deg.F| 10| 17| 20| 30| 40| 47|
50| 60
MBH| COP| kW| MBH| COP| kW| MBH| COP| kW| MBH| COP| kW| MBH| COP| kW| MBH|
COP| kW| MBH| COP| kW| MBH| COP| kW
1600| 60| 27.3| 2.85| 2.81| 32.8| 3.10| 3.10| 35.1| 3.20| 3.22| 42.9| 3.47|
3.63| 50.7| 3.69| 4.04| 56.2| 3.81| 4.32| 58.5| 3.86| 4.44| 66.3| 4.01| 4.85
70| 26.4| 2.61| 2.97| 31.8| 2.84| 3.28| 34.1| 2.93| 3.41| 41.7| 3.18| 3.85|
49.4| 3.37| 4.29| 54.8| 3.49| 4.60| 57.0| 3.53| 4.73| 64.7| 3.67| 5.17
80| 25.9| 2.42| 3.15| 31.1| 2.62| 3.48| 33.4| 2.70| 3.63| 40.8| 2.91| 4.11|
48.2| 3.08| 4.59| 53.4| 3.18| 4.92| 55.7| 3.22| 5.07| 63.1| 3.34| 5.55
1800| 60| 27.6| 2.82| 2.87| 33.1| 3.10| 3.14| 35.5| 3.20| 3.26| 43.4| 3.49|
3.65| 51.4| 3.73| 4.04| 56.9| 3.87| 4.31| 59.3| 3.93| 4.43| 67.2| 4.09| 4.82
70| 26.8| 2.60| 3.03| 32.2| 2.84| 3.32| 34.5| 2.94| 3.45| 42.3| 3.21| 3.87|
50.0| 3.42| 4.29| 55.4| 3.55| 4.58| 57.7| 3.60| 4.71| 65.5| 3.74| 5.13
80| 26.2| 2.39| 3.21| 31.5| 2.61| 3.53| 33.7| 2.70| 3.66| 41.3| 2.94| 4.12|
48.8| 3.13| 4.57| 54.1| 3.24| 4.89| 56.4| 3.29| 5.03| 63.9| 3.42| 5.48
2000| 60| 27.7| 2.78| 2.91| 33.3| 3.07| 3.18| 35.7| 3.18| 3.30| 43.8| 3.49|
3.68| 51.8| 3.75| 4.06| 57.5| 3.90| 4.32| 59.9| 3.96| 4.44| 68.0| 4.14| 4.82
70| 27.1| 2.58| 3.08| 32.6| 2.84| 3.37| 34.9| 2.94| 3.49| 42.7| 3.22| 3.89|
50.5| 3.45| 4.30| 56.0| 3.59| 4.58| 58.3| 3.64| 4.70| 66.1| 3.80| 5.11
80| 26.5| 2.38| 3.27| 31.8| 2.61| 3.57| 34.1| 2.70| 3.70| 41.7| 2.96| 4.14|
49.3| 3.16| 4.57| 54.6| 3.29| 4.88| 56.9| 3.33| 5.01| 64.5| 3.48| 5.44
Q4SE ACCESSORIES
DESCRIPTION | PART NUMBER |
---|---|
Roof Curb (8”) | 547830 |
Roof Curb (14”) | 547831 |
Roof Curb (18”) | 547850 |
Roof Curb (24”) | 547851 |
Supply/return transition, 16” | 547834 |
Supply/return transition, 18” | 547835 |
Concentric diffuser, flush, 16” | 547836 |
Concentric diffuser, flush, 18” | 547837 |
Concentric diffuser, step down 16” | 547838 |
Concentric diffuser, step down 18” | 547839 |
HOOD TYPE HAIL GUARD 34” X 76” Q4SEX24, X36 | 547846 |
HOOD TYPE HAIL GUARD 38” X 76” Q4SEX48, X60 | 547847 |
DUCT SMOKE DETECTOR PHOTO ELEC | 558863 |
MULTI SIGNAL CONTROL | 547893 |
SAMPLING TUBE DST3, 2-4′ | 558864 |
SAMPLING TUBE DST5, 4-8′ | 558865 |
Filter Rack, All Downflow Applications (not required with economizer) | 547885 |
Horizontal Filter Kit (not required with economizer) Q4SEX24, X36 | 547888 |
Horizontal Filter Kit (not required with economizer) Q4SEX48, X60 | 547889 |
Low Ambient Kit | 918837 |
Outdoor Thermostat Kit | 913852 |
Economizer, downflow w/filter (does not require filter kit) modulating | 558870 |
Economizer, horizontal modulating | 547841 |
Power Exhaust, horizontal economizer (special order) 208/230 | 547843 |
Power Exhaust, downflow economizer (special order) 208/230 | 547842 |
Skirt Trim Kit | 919729 |
Extreme High Wind Kit – Roof Curb Mount | 903696 |
Extreme High Wind Kit – Ground Mount | 903695 |
Duct Adopter, 14″ Round (2 each) | 913812A |
Control, CO2 Sensor, Wall Mount | 920317 |
Control, CO2 Sensor, Duct Mount | 920318 |
Freezestat Kit | 917108 |
Heater Kit – 4 – Pole single Circuit Adapter | 913350 |
Heater Kit – 6 Pole Single Circuit Adaptor | 913556 |
Heater Kit – Circuit Breaker Single Phase (2-Pole) | 913554 |
GENERAL TERMS OF LIMITED WARRANTY
NORDYNE will furnish a replacement for any part of this product which fails in
normal use and service in accordance with the terms of the warranty.
For complete details of the Limited Warranty, including applicable terms and
conditions, see your local installer or contact the NORDYNE warranty
department for a copy.
8000 Phoenix Parkway I O’Fallon, MO 63368-3827
Specifications and illustrations subject to change without notice and without incurring obligations. Printed in U.S.A (07/2010)
Customer Support
204D-071 0 (Replaces 204D-0210)
www.frigidairehvac.com
FRIGIDAIRE is a registered trademark of Electrolux Home Products Inc. and used
under a license from Electrolux Home Products, Inc. © Nortek Global HVAC, LLC.
All Rights Reserved.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>