Noark Ex9S Manual Motor Starters Instruction Manual
- June 15, 2024
- NoarK
Table of Contents
- Ex9S Manual Motor Starters
- Features
- Certifications
- Standards Compliance
- Product Selection Guide
- Ex9S SPECIFICATIONS
- Technical Data
- IEC Motor Power
- IEC Interrupting Capacity
- UL Motor Power
- Short-Circuit Current Rating
- UL Motor Power
- Temperature Derating Factor
- Technical Data
- Electrical Diagram
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Manual Motor Starters
Ex9S
Ex9S Manual Motor Starters
Features
Ex9S Manual Motor Starters provide manual isolation, manual motor control, and overcurrent protection. They are electro-mechanical devices combining the functions below in one unit.
- Disconnect for Motor Branch Circuit
- Manual Motor Control (automatic when used with contactor)
- Branch-Circuit Short Circuit Protection (Magnetic Protection)
- Overload Protection (Thermal Protection) – Trip Class 10
The National Electrical Code requires an individual Motor Branch Circuit to be
protected by a UL/CSA Listed Fuse, Circuit breaker or Self-Protected
Combination Motor Controller.
Available as:
- Up to 80A @600Vac
- UL 60947-4-1 Type E Self Protection-Ex9S32 and Ex9S80
- UL 60947-4-1 Type F Group Motor Protection-Ex9S32
- Built-in fault indication
- Full range of accessories
- Lockable handle
Certifications
Ex9S Manual Motor Starters provide manual isolation, manual motor control, and overcurrent protection. They are electro-mechanical devices combining the functions below in one unit.
- UL listed
- CCC Certified
- NOM Certified
- RoHs Compliant
Standards Compliance
- L 60947-1; UL 60947-4-1
- IEC/EN 60947-1, IEC/EN 60947-2, IEC/EN 60947-4-1,IEC/EN 60947 -5-1
- GB 14048.1, GB 14048.2, GB 14048.4
- CSA 22.2 NO. 60947-1,CSA 22.2 NO. 60947-4-1
Label
- Brand
- Adjustable Current Range
- Rotary Handle with Padlock
- Test Button
- Product Selection
- Rated Current
Product Selection Guide
Ex9S SPECIFICATIONS
Ex9S32
Rated Current Amp (Min-Max) | Thermal Magnetic protection |
---|
Product ………………………………………… Part Number
0.10~0.16| Ex9S32A0.16A| 1600046
0.16~0.25| Ex9S32A0.25A| 1600047
0.25~0.40| Ex9S32A0.4A| 1600048
0.40~0.63| Ex9S32A0.63A| 1600049
0.63~1| Ex9S32A1A| 1600050
1~1.6| Ex9S32A1.6A| 1600051
1.6~2.5| Ex9S32A2.5A| 1600052
2.5~4| Ex9S32A4A| 1600053
Rated Current Amp (Min-Max)| Thermal Magnetic protection
Product ……………………………………. Part Number
4~6.3| Ex9S32A6.3A| 1600054
6~10| Ex9S32A10A| 1600055
9~14| Ex9S32A14A| 1600056
13~18| Ex9S32A18A| 1600057
17~23| Ex9S32A23A| 1600058
20~25| Ex9S32A25A| 1600059
24~32| Ex9S32A32A| 1600060
Ex9S80
Rated Current Amp (Min-Max) | Thermal Magnetic protection |
---|---|
Product | Part Number |
14~20 | Ex9S80A20A |
18~25 | Ex9S80A25A |
23~32 | Ex9S80A32A |
30~40 | Ex9S80A40A |
38~50 | Ex9S80A50A |
48~63 | Ex9S80A63A |
60~72 | Ex9S80A72A |
70~80 | Ex9S80A80A |
Rated Current Amp (Min-Max) | Magnetic protection |
Product | Part Number |
14~20
18~25
| Ex9S80A20AM| 1600185
Ex9S80A25AM| 1600186
23~32| Ex9S80A32AM| 1600187
30~40| Ex9S80A40AM| 1600188
38~50| Ex9S80A50AM| 1600189
48~63| Ex9S80A63AM| 1600190
60~72| Ex9S80A72AM| 1600191
70~80| Ex9S80A80AM| 1600192
Rated Current Amp (Min-Max)| Thermal Magnetic protection
Product| Part Number
14~20| Ex9S80A20B| 1600178
18~25| Ex9S80A25B| 1600179
23~32| Ex9S80A32B| 1600180
30~40| Ex9S80A40B| 1600181
38~50| Ex9S80A50B| 1600182
48~63| Ex9S80A63B| 1600183
60~72| Ex9S80A72B| 1600184
Rated Current Amp (Min-Max)| Magnetic protection
Product| Part Number
14~20| Ex9S80A20BM| 1600193
18~25| Ex9S80A25BM| 1600194
23~32| Ex9S80A32BM| 1600195
30~40| Ex9S80A40BM| 1600196
38~50| Ex9S80A50BM| 1600197
48~63| Ex9S80A63BM| 1600198
60~72| Ex9S80A72BM| 1600199
Certifications IEC/EN 60947-4-1
Technical Data
Description………………………………………………….Ex9S32…………………………….Ex9S80
Rated operational current le (A) | 32A | 80A |
---|---|---|
Conventional rated thermal current lth (A) | 0.16~32A | 14-80A |
Tripping Class | 10 | |
Rated insulation voltage Ui (Vac) | 690/lEC; 600/UL, CSA | |
Rated operational voltage Ue (AC) | 230/240, 400/415, 460/480, 575/600 | |
Rated impulse withstand voltage Uimp (AC) | 6,000V | |
Rated Operational Frequency (Hz) | 50/60Hz | |
Resistance to shock | 30 gn -11 ms | |
Resistance to vibrations | 5gn (5 -150Hz) |
Enviornmental Temperature
| Transportation or Storage| -40°F to 176°F (-40°C to 80°C)¹
Working at| -4°F to 140°F (-20°C to 60°C)²
Testing at| 59°F to 77°F (15°C to 25°C)
lnstantaneous limit| -31°F to 158°F (-35°C to 70°C)
Altitude ft (m)| Not to exceed 6,562 (2,000)
Ambient Conditions| At mounting site, relative humidity not exceed 90% at the
temperature 104°F (40°C), higher relative humidity is allowable under lower
temperature
Pollution Grade| lll
Mounting Conditions| The inclination between the mounting plane and the
vertical plane shall not exceed 30°; The product shall be installed and
operated at a place without obvious shock, impact and vibration.
Service life* (cycles)
| Electrical| 50,000| 50,000 (up to 63A) ;30,000( 72A&80A)
Mechanical| 100,000| 50,000 (up to 72A) ;30,000( 80A)
Duty Class (cycles/hr)| 30, max. operating rate
Degree of Protection| lP 20
1: 24 hours max. at the ultimated temperature
2: with temperature reduction factor
*: close/open operation, and 30 cycles/hr for AC-3 Duty@400/415Vac
Overload Protection Properties
Overload Protection Properties
| Multiple of Setting Current| Initial Status| Time| Expected Results|
Ambient Temperature
1| 1.05| Cold Status| t³2h| Non-Tripping| 68°F to ±35.6°F (+20°C to ±2°C)
2| 1.25| Heat Status (right after test 1)| t<2h| **** Tripping
3| 1.50| t<4 min
4| 7.20| Cold Status| 4s<t£10s|
Phase Failure Protection Properties
| Multiple of Setting Current| Initial Status| Time| Expected Results|
Ambient Temperature
Any 2 Phase| The Other Phase
1| 1.0| 0.9| Cold Status| t³2h| Non-Tripping| 68°F to ±35.6°F (+20°C to ±2°C)
2| 1.15| 0| Heat Status (right after test 1)| t<2h| Tripping
Temperature Compensation Properties
| Multiple of Setting Current| Initial Status| Time| Expected Results|
Ambient Temperature
1| 1.0| Cold Status| t³2h| Non-Tripping| 104°F to ±35.6°F (+40°C to ±2°C)
2| 1.25| Heat Status (right after test 1)| t<2h| Tripping
3| 1.05| Cold Status| t³2h| Non-Tripping| -23°F to ±35.6°F (-5°C to ±2°C)
4| 1.3| Heat Status (right after test 1)| t<2h| Tripping
IEC Motor Power
Manual self- protected starter
Ex9S32A0.16A
| Overload Trip Range| Standard rated power of three-phase motor (kW)
AC-3,50Hz/60Hz
---|---|---
230/240Vac| 400/415Vac| 500Vac| 690Vac
0.1 – 0.16A| –| –| 0.06| 0.06
Ex9S32A0.25A| 0.16- 0.25A| –| 0.06| 0.09| 0.12
Ex9S32A0.4A| 0.25 – 4A| 0.06| 0.09| 0.12| 0.18
Ex9S32A0.63A| 0.4 – 0.63A| 0.09| 0.18| 0.18| 0.25
Ex9S32A1A| 0.63 – 1A| 0.18| 0.25| 0.37| 0.55
Ex9S32A1.6A| 1 – 1.6A| 0.25| 0.55| 0.75| 1.1
Ex9S32A2.5A| 1.6 – 2.5A| 0.37| 0.75| 1.1| 1.5
Ex9S32A4A| 2.5 – 4A| 0.75| 1.5| 2.2| 3
Ex9S32A6.3A| 4 – 6.3A| 1.5| 2.2| 3| 4
Ex9S32A10A| 6 – 10A| 2.2| 4| 5.5| 7.5
Ex9S32A14A| 9 – 14A| 3| 5.5| 7.5| 11
Ex9S32A18A| 13 – 18A| 4| 7.5| 11| 15
Ex9S32A23A| 17 – 23A| 5.5| 11| 15| 18.5
Ex9S32A25A| 20 – 25A| 5.5| 11| 15| 22
Ex9S32A32A| 24 – 32A| 7.5| 15| 18.5| 22
Ex9S80A20A(M)| 14- 20A| 4| 7.5| 11| 15
Ex9S80A20B(M)| 14- 20A| 4| 7.5| 11| 15
Ex9S80A25A(M)| 18- 25A| 5.5| 11| 15| 22
Ex9S80A25B(M)| 18- 25A| 5.5| 11| 15| 22
Ex9S80A32A(M)| 23- 32A| 7.5| 15| 18.5| 30
Ex9S80A32B(M)| 23- 32A| 7.5| 15| 18.5| 30
Ex9S80A40A(M)| 30- 40A| 11| 18.5| 22| 37
Ex9S80A40B(M)| 30- 40A| 11| 18.5| 22| 37
Ex9S80A50A(M)| 38- 50A| 11| 22| 30| 45
Ex9S80A50B(M)| 38- 50A| 11| 22| 30| 45
Ex9S80A63A(M)| 48- 63A| 15| 30| 37| 55
Ex9S80A63B(M)| 48- 63A| 15| 30| 37| 55
Ex9S80A72A(M)| 60- 72A| 18.5| 37| 45| 65
Ex9S80A72B(M)| 60- 72A| 18.5| 37| 45| 65
Ex9S80A80A(M)| 70- 80A| 22| 45| 50| 70
IEC Interrupting Capacity
400 Vac
690 Vac
Manual self- protected starter
Ex9S32A0.16A
| Overload Trip Range| | FUSE| | FUSE
---|---|---|---|---|---
Icu (kA)| Ics (kA)| aM| gl/gG| Icu (kA)| Ics (kA)| aM| gl/gG
0.1 – 0.16A| 100| 100| –| –| 100| 100| –| –
Ex9S32A0.25A| 0.16- 0.25A| 100| 100| –| –| 100| 100| –| –
Ex9S32A0.4A| 0.25 – 4A| 100| 100| –| –| 100| 100| –| –
Ex9S32A0.63A| 0.4 – 0.63A| 100| 100| –| –| 100| 100| –| –
Ex9S32A1A| 0.63 – 1A| 100| 100| –| –| 100| 100| –| –
Ex9S32A1.6A| 1 – 1.6A| 100| 100| –| –| 100| 100| –| –
Ex9S32A2.5A| 1.6 – 2.5A| 100| 100| –| –| 100| 100| –| –
Ex9S32A4A| 2.5 – 4A| 100| 100| –| –| 6| 4| 25| 32
Ex9S32A6.3A| 4 – 6.3A| 100| 100| –| –| 6| 4| 32| 40
Ex9S32A10A| 6 – 10A| 100| 100| –| –| 6| 4| 32| 40
Ex9S32A14A| 9 – 14A| 100| 100| –| –| 6| 4| 40| 50
Ex9S32A18A| 13 – 18A| 50| 30| 63| 80| 6| 4| 40| 50
Ex9S32A23A| 17 – 23A| 50| 30| 80| 100| 6| 4| 40| 50
Ex9S32A25A| 20 – 25A| 50| 30| 80| 100| 6| 4| 40| 50
Ex9S32A32A| 24 – 32A| 50| 30| 100| 125| 6| 4| 50| 63
Ex9S80A20A(M)| 14- 20A| 100| 100| –| –| 8| 8| 50| 63
Ex9S80A20B(M)| 14- 20A| 100| 100| –| –| 8| 8| 50| 63
Ex9S80A25A(M)| 18- 25A| 100| 100| –| –| 8| 8| 50| 63
Ex9S80A25B(M)| 18- 25A| 100| 100| –| –| 8| 8| 50| 63
Ex9S80A32A(M)| 23- 32A| 100| 100| –| –| 8| 8| 50| 63
Ex9S80A32B(M)| 23- 32A| 100| 100| –| –| 8| 8| 50| 63
Ex9S80A40A(M)| 30- 40A| 50| 50| 125| 160| 8| 8| 63| 80
Ex9S80A40B(M)| 30- 40A| 50| 50| 125| 160| 8| 8| 63| 80
Ex9S80A50A(M)| 38- 50A| 50| 50| 125| 160| 8| 8| 63| 80
Ex9S80A50B(M)| 38- 50A| 50| 50| 125| 160| 8| 8| 63| 80
Ex9S80A63A(M)| 48- 63A| 50| 50| 125| 160| 8| 8| 80| 100
Ex9S80A63B(M)| 48- 63A| 50| 50| 125| 160| 8| 8| 80| 100
Ex9S80A72A(M)| 60- 72A| 50| 50| 160| 200| 8| 8| 100| 125
Ex9S80A72B(M)| 60- 72A| 50| 50| 160| 200| 8| 8| 100| 125
Ex9S80A80A(M)| 70- 80A| 50| 50| 160| 200| 8| 8| 100| 125
UL Motor Power
UL Motor Power (hp)
Manual self- protected starter
Ex9S32A0.16A
| Overload Trip Range| 1PH| 3PH
---|---|---|---
110-120Vac| 220-240Vac| 200Vac| 208Vac| 220-240Vac| 460-480Vac| 575-600Vac
0.1 – 0.16A| –| –| –| –| –| –| –
Ex9S32A0.25A| 0.16- 0.25A| –| –| –| –| –| –| –
Ex9S32A0.4A| 0.25 – 4A| –| –| –| –| –| –| –
Ex9S32A0.63A| 0.4 – 0.63A| –| –| –| –| –| –| –
Ex9S32A1A| 0.63 – 1A| –| –| –| –| –| –| 0.5
Ex9S32A1.6A| 1 – 1.6A| –| 0.1| –| –| –| 0.75| 0.75
Ex9S32A2.5A| 1.6 – 2.5A| –| 0.167| 0.5| 0.5| 0.5| 1| 1.5
Ex9S32A4A| 2.5 – 4A| 0.125| 0.333| 0.75| 0.75| 0.75| 2| 3
Ex9S32A6.3A| 4 – 6.3A| 0.25| 0.5| 1| 1| 1.5| 3| 5
Ex9S32A10A| 6 – 10A| 0.5| 1.5| 2| 2| 3| 5| 7.5
Ex9S32A14A| 9 – 14A| 0.75| 2| 3| 3| 3| 10| 10
Ex9S32A18A| 13 – 18A| 1| 3| 5| 5| 5| 10| 15
Ex9S32A23A| 17 – 23A| 1.5| 3| 5| –| 7.5| 15| 20
Ex9S32A25A| 20 – 25A| 2| –| –| –| 7.5| 15| 20
Ex9S32A32A| 24 – 32A| 2| 5| 7.5| 7.5| 10| 20| 25
Ex9S80A20A(M)| 14- 20A| 1| 3| 5| 5| 5| 10| 15
Ex9S80A20B(M)| 14- 20A| 1| 3| 5| 5| 5| 10| 15
Ex9S80A25A(M)| 18- 25A| 2| –| –| 7.5| 7.5| 15| 20
Ex9S80A25B(M)| 18- 25A| 2| –| –| 7.5| 7.5| 15| 20
Ex9S80A32A(M)| 23- 32A| 2| 5| 7.5| 7.5| 10| 20| 25
Ex9S80A32B(M)| 23- 32A| 2| 5| 7.5| 7.5| 10| 20| 25
Ex9S80A40A(M)| 30- 40A| 3| –| 10| 10| –| 25| 30
Ex9S80A40B(M)| 30- 40A| 3| –| 10| 10| –| 25| 30
Ex9S80A50A(M)| 38- 50A| –| –| 15| 15| 15| 30| 40
Ex9S80A50B(M)| 38- 50A| –| –| 15| 15| 15| 30| 40
Ex9S80A63A(M)| 48- 63A| 5| 10| 15| 20| 20| 40| 50
Ex9S80A63B(M)| 48- 63A| 5| 10| 15| 20| 20| 40| 50
Ex9S80A72A(M)| 60- 72A| –| –| 20| –| 25| 50| 60
Ex9S80A72B(M)| 60- 72A| –| –| 20| –| 25| 50| 60
Ex9S80A80A(M)| 70- 80A| –| –| 25| 25| –| 60| 75
- Manual Motor Control and Motor Disconnect only, not applied in Combination Motor Control.
Short-Circuit Current Rating
Type E: Self-Protected Combination Motor Controller
UL Motor Power
Manual selfprotected
starter| Overload
Trip Range| Type E| Type E| Type E| Matching
accessories
---|---|---|---|---|---
SCCR (kA)| 240Vac| SCCR (kA)| 480Y/277Vac| SCCR (kA)| 600Y/347Vac
Ex9S32A0.16A| 0.1 – 0.16A| 65| 65| 65| 65| 10| 10| CCE51, AL5111
Ex9S32A0.25A| 0.16- 0.25A| 65| 65| 65| 65| 10| 10
Ex9S32A0.4A| 0.25 – 0.4A| 65| 65| 65| 65| 10| 10
Ex9S32A0.63A| 0.4 – 0.63A| 65| 65| 65| 65| 10| 10
Ex9S32A1A| 0.63 – 1A| 65| 65| 65| 65| 10| 10
Ex9S32A1.6A| 1 – 1.6A| 65| 65| 65| 65| 10| 10
Ex9S32A2.5A| 1.6 – 2.5A| 65| 65| 65| 65| 10| 10
Ex9S32A4A| 2.5 – 4A| 65| 65| 65| 65| 10| 10
Ex9S32A6.3A| 4 – 6.3A| 65| 65| 65| 65| 10| 10
Ex9S32A10A| 6 – 10A| 65| 65| 65| 65| 10| 10
Ex9S32A14A| 9 – 14A| 65| 65| 65| 65| 10| 10
Ex9S32A18A| 13 – 18A| 42| 42| 42| 42| –| –
Ex9S32A23A| 17 – 23A| 42| 42| 42| 42| –| –
Ex9S32A25A| 20 – 25A| 42| 42| 42| 42| –| –
Ex9S32A32A| 24 – 32A| 42| 42| 42| 42| –| –
Ex9S80A20A/B| 14 – 20A| 42| 42| 42| 42| 30| 30| AL5111
Ex9S80A25A/B| 18 – 25A| 42| 42| 42| 42| 30| 30
Ex9S80A32A/B| 23 – 32A| 42| 42| 42| 42| 30| 30
Ex9S80A40A/B| 30 – 40A| 42| 42| 42| 42| 18| 18
Ex9S80A50A/B| 38 – 50A| 42| 42| 42| 42| 18| 18
Ex9S80A63A/B| 48 – 63A| 42| 42| 42| 42| 10| 10
Ex9S80A72A/B| 60 -72A| 42| 42| 42| 42| 10| 10
Ex9S80A80A| 70 – 80A| 10| 10| 10| 10| 10| 10
UL Motor Power
Manual Self- Protected Starter| Associated Cable, AWG 75°C, Cu|
Type of Contactor Required| Overload Trip Range(A)| SCCR
(kA)| Fault Signaling Accessory| Combination Block| Mounting
Bracket
---|---|---|---|---|---|---|---
240V| 480YS
277V| 600YS 347V
Ex9S32A0.16A| 14| Ex9CS06/09 Ex9C09| 0.1-0.16| 65| 10| AL5111| CC51/CC52|
DRA51
Ex9S32A0.25A| 0.16-0.25
Ex9S32A0.4A| 0.25-0.4
Ex9S32A0.63A| 0.4-.63
Ex9S32A1A| 0.63-1
Ex9S32A1.6A| 1-1.6
Ex9S32A2.5A| 1.6-2.5
Ex9S32A4A| 2.5-4
Ex9S32A6.3A| 4-6.3
Ex9S32A10A| Ex9CS12/9C12| 6-10
Ex9S32A14A| 12| Ex9C18| 9-14| CC52
Ex9S32A18A| Ex9C25| 13-18| 42| –| CC53
Ex9S32A23A| 10| 17-23
Ex9S32A25A| Ex9C38/32| 20-25
Ex9S32A32A| 8| 24-32
Temperature Derating Factor
Device
| -20℃≤T≤0℃| 0℃<T<30℃| 30℃≤T≤40℃| 40℃<T≤60℃
---|---|---|---|---
single| group| single| group| single| group| single| group
Ex9S32A0.16A| 1.05| 1| 1| 1| 1| 1| 1| 0.98
Ex9S32A0.25A| 1.05| 1| 1| 1| 1| 0.99| 0.98| 0.97
Ex9S32A0.4A| 1.05| 1| 1| 1| 1| 0.96| 0.96| 0.93
Ex9S32A0.63A| 1.05| 1| 1| 1| 1| 0.97| 0.96| 0.94
Ex9S32A1A| 1.05| 1| 1| 1| 1| 0.96| 0.96| 0.91
Ex9S32A1.6A| 1.05| 1| 1| 1| 1| 0.96| 0.96| 0.93
Ex9S32A2.5A| 1.05| 1| 1| 1| 1| 1| 1| 0.99
Ex9S32A4A| 1.05| 1| 1| 0.98| 1| 0.98| 0.98| 0.96
Ex9S32A6.3A| 1.05| 1| 1| 0.97| 1| 0.96| 0.96| 0.95
Ex9S32A10A| 1.05| 1| 1| 0.96| 1| 0.94| 0.94| 0.91
Ex9S32A14A| 1.05| 1| 1| 0.96| 1| 0.94| 0.94| 0.90
Ex9S32A18A| 1.05| 1| 1| 0.96| 1| 0.93| 0.92| 0.90
Ex9S32A23A| 1.05| 1| 1| 0.95| 1| 0.94| 0.93| 0.90
Ex9S32A25A| 1.05| 1| 1| 0.95| 1| 0.94| 0.93| 0.90
Ex9S32A32A| 1.05| 1| 1| 0.92| 1| 0.91| 0.91| 0.87
Ex9S80A20A/B| 1.05| 1| 1| 1| 1| 0.98| 1| 0.96
Ex9S80A25A/B| 1.05| 1| 1| 1| 1| 0.98| 1| 0.96
Ex9S80A32A/B| 1.05| 1| 1| 1| 1| 0.98| 1| 0.96
Ex9S80A40A/B| 1.05| 1| 1| 0.98| 1| 0.98| 1| 0.96
Ex9S80A50A/B| 1.05| 1| 1| 0.97| 1| 0.96| 0.96| 0.93
Ex9S80A63A/B| 1.05| 1| 1| 0.95| 1| 0.93| 0.92| 0.9
Ex9S80A72A/B| 1.05| 1| 1| 0.95| 1| 0.93| 0.93| 0.9
Ex9S80A80A| 1.05| 1| 1| 0.94| 1| 0.9| 0.9| 0.88
- Please refer to derating table for multiple use of electromagnetic product or use single unit above 40°C
Manual Motor Starters
Ex9S SPECIFICATIONS
Manual self-protected
starter| Setting Current (A)| Magnetic Trip Rating (A)
---|---|---
Ex9S32A0.16A| Minimun| Maximum| A| B
Ex9S32A0.25A| 0.1| 0.16| 2.1| –
Ex9S32A0.4A| 0.16| 0.25| 3.2| –
Ex9S32A0.63A| 0.25| 4| 4.8| –
Ex9S32A1A| 0.4| 0.63| 7.2| –
Ex9S32A1.6A| 0.63| 1| 11| –
Ex9S32A2.5A| 1| 1.6| 20| –
Ex9S32A4A| 1.6| 2.5| 30| –
Ex9S32A6.3A| 2.5| 4| 50| –
Ex9S32A10A| 4| 6.3| 72.5| –
Ex9S32A14A| 6| 10| 130| –
Ex9S32A18A| 9| 14| 175| –
Ex9S32A23A| 13| 18| 230| –
Ex9S32A25A| 17| 23| 280| –
Ex9S32A32A| 20| 25| 322| –
Ex9S80A20A(M)| 24| 32| 416| –
Ex9S80A20A(M)| 14| 20| 310| 400
Ex9S80A20B(M)| 14| 20| 310| 400
Ex9S80A25A(M)| 18| 25| 375| 500
Ex9S80A25B(M)| 18| 25| 375| 500
Ex9S80A32A(M)| 23| 32| 445| 680
Ex9S80A32B(M)| 23| 32| 445| 680
Ex9S80A40A(M)| 30| 40| 560| 800
Ex9S80A40B(M)| 30| 40| 560| 800
Ex9S80A50A(M)| 38| 50| 700| 960
Ex9S80A50B(M)| 38| 50| 700| 960
Ex9S80A63A(M)| 48| 63| 950| 1150
Ex9S80A63B(M)| 48| 63| 950| 1150
Ex9S80A72A(M)| 60| 72| 1000| 1150
Ex9S80A72B(M)| 60| 72| 1000| 1150
Ex9S80A80A(M)| 70| 80| 1150| –
Manual
Motor Starters
Ex9S32 DIMENSIONS Manual Motor Starters
EX9S80 DIMENSIONS Ex9S ACCESSORIES: SPECIFICATIONS
Manual Motor Starters Auxiliary Contact Blocks
Applies to Ex9S32 and Ex9S80
AX51 | 11 |
---|---|
Description | Auxiliary Contact |
AX51: Auxiliary contact (front mount only) | 11: 1NO+1NC (AX51,AX52,AL51, AX53) |
AX52: Auxiliary contact (left side only) | 20: 2NO (AX51,AX52) |
AX53: Auxiliary contact (front mount only) | 02: 2NC (AX52) |
AL51: Fault Signaling Contact (left side only) | |
Description | Mounting Location |
number
---|---|---|---|---
Instantaneous auxiliary
contacts| Front| 1| NO+NC| AX5111
NO+NO| AX5120
NO+NC| AX5311
Left Side| 2| NO+NC| AX5211
NO+NO| AX5220
NC+NC| AX5202
Fault Signaling Contact| 1| NO+NC| AL5111
Electrical Trip Unit
Applies to Ex9S32 and Ex9S80
UVT51 | G | SHT51 | G |
---|---|---|---|
Description | Rated Voltage | Description | Rated Voltage |
UVT51:
Undervoltage release
(right side only)| A: 110~120V 60Hz(UVT51)
B: 110~120V 50Hz & 127V
60Hz(UVT51)
C: 208V 60Hz(UVT51)
D: 240V 60Hz(UVT51)
E: 480V 60Hz(UVT51)
F: 600V 60Hz(UVT51)
G: 220~240V 50Hz(UVT51)
H: 380~415V 50Hz(UVT51)| SHT51:
Shunt release (right side only)| A: 100~130V 50/60Hz(SHT51)
B: 190~330V 50/60Hz(SHT51)
C: 330~440V 50/60Hz(SHT51)
D: 480~500V 50/60Hz(SHT51)
E: 575~600V 50/60Hz(SHT51)
Description | Mounting Location | Voltage | Hz | Catalog number |
---|---|---|---|---|
Undervoltage Release | Right Side | 110-120V | 60 | UVT51A |
127V | 60 | UVT51B | ||
110-120V | 50 | UVT51B | ||
208V | 60 | UVT51C | ||
240V | 60 | UVT51D | ||
480V | 60 | UVT51E | ||
600V | 60 | UVT51F | ||
220-240V | 50 | UVT51G | ||
380-415V | 50 | UVT51H | ||
Shunt Release | Right Side | 100-130V | 50/60 | SHT51A |
190-330V | 50/60 | SHT51B | ||
330-440V | 50/60 | SHT51C | ||
480-500V | 50/60 | SHT51D | ||
575-600V | 50/60 | SHT51E |
Manual Motor Starters
Ex9S ACCESSORIES: SPECIFICATIONS
Busbars
Applies to Ex9S32
Description| No. of Ex9S32
Starter| No. of Side- Mounted Aux
Contact on each Ex9S32
starter| Busbar Pitch (mm)| Catalog number
---|---|---|---|---
Sets of 3-pole,
63A Busbar| 2| None| 45| BBUM 245
1 of AX52, AL51| 54| BBUM 254
2 of AX52 or 1 UVT51,
SHT51| 63| BBUM 263
3| None| 45| BBUM 345
1 of AX52, AL51| 54| BBUM 354
2 of AX52 or 1 UVT51,
SHT51| 63| BBUM 363
4| None| 45| BBUM 445
1 of AX52, AL51| 54| BBUM 454
2 of AX52 or 1 UVT51,
SHT51| 63| BBUM 463
5| None| 45| BBUM 545
1 of AX52, AL51| 54| BBUM 554
2 of AX52 or 1 UVT51,
SHT51| 63| BBUM 563
Wiring Accessories
Applies to Ex9S32
Description | Application | Catalog number |
---|---|---|
Terminal Cover | Terminal cover for Ex9S32 for use in type E application | CCE51 |
Input Terminal for CBB51 Busbar | Terminal block for power supply to one or | |
more CBB51 bus bar | FD51 | |
Protective end cover | For unused busbar outlets | PC51 |
Enclosures
Applies to Ex9S32
WPB | 51 | B |
---|---|---|
Description | Type | Color of Handle |
Waterproof Enclosure | 51: for Ex9S32 | B: Black/Gray |
Y: Yellow/Red
Description| Type| Color| Rating| Catalog number
---|---|---|---|---
Waterproof Enclosure;
Ex9S32 Protectors| Operation by rotary
handle| Black/ Gray| NEMA 4X/4, IP 65| WPB51B
Yellow/ Red| WPB51Y
Ex9S ACCESSORIES: SPECIFICATIONS
Operation Handle
Applies to Ex9S32 and Ex9S80
ERH | 51 | B |
---|---|---|
Description | Type | Color of Handle |
Extended Rotary Handle | 51: for Ex9S | B: Black/Gray |
Y: Yellow/Red
Description| Type| Color| Rating| Catalog number
---|---|---|---|---
Extended Rotary Handle| 9 inch (230mm) shaft,
with bracket| Black/ Gray| NEMA 4X/4, IP65| ERH51B
Yellow/ Red| ERH51Y
The extended rotary handie makes it possible for a door-mounted rotary handle
to operate starter installed on the inside back panel of an enclosure. The
extended rotary handle consists of the following:
– a set of screws onto the handle of the starter
– an assembly (handle and front plate) that fits on the enclosure door
– an extension shaft which must be adjusted according to the distance between
the mounting surface and the door: 9 inch (230 mm)
– a bracket that install with starter and the shaft through
Mounting Accessories
Applies to Ex9S32
DRA | 51 |
---|---|
Description | Type |
Mounting Bracket | 51: for mounting Ex9S32 with Ex9C 09-38A |
CC | 51 |
Description | Type |
Combination Block | 51: between Ex9S32 and Ex9CS 09-12A |
Description | Application |
--- | --- |
Combination Block | Between Ex9S32 and Ex9C Mini Type Contactor, 09-12A |
Between Ex9S32 and Ex9C Standard Type Contactor, 09-18A | CC52 |
Between Ex9S32 and Ex9C Standard Type Contactor, 25-38A | CC53 |
Mounting Bracket | For mounting a Ex9S32 to a Ex9C Standard Type Contactor, |
09-38A | DRA51 |
Manual Motor Starters
Ex9S ACCESSORIES: SPECIFICATIONS
Technical Data
| Auxiliary contacts AX51| Auxiliary contacts AX52| Auxiliary
contacts AX53| Auxiliary contacts AX51
---|---|---|---|---
Rated operational voltage Ue| 300V| 600V| 60VAC、24VDC| 600V
Rated frequency| 50/60Hz| 50/60Hz| –| 50/60Hz
Rated impulse withstand voltage Uimp| 2500V| 6000V| 800V| 6000V
Conventional rated thermal current (lth)”| 2.5A| 5A| 1A| 5A
Mechanical life (C-O operations)| 100000| 100000| 100000| 100000
Electrical Rating| C300,Q300| B600,Q300| AC-12:60V/0.1A DC-12:24V/1A|
B600,Q300
Minimum connection Load| 5mA @24Vac/dc| 8mA @24Vac/dc| 2mA @12Vac/dc 3mA
@5Vdc| 8mA @24Vac/dc
Terminal Wiring
| Ex9S32| Ex9S80
---|---|---
Screw Type| M4, Phil-Slot head| M8, Phil-Hex head
Pull wire length inch (mm)| 0.4 (10)| 0.59 (15)
Wire range AWG| (1)x14-(2)x8| 14~3
Torques lb•in (N.m)| 22 (2.5)| 53 (6)
Model| Wire Ranges(AWG)| Torques lb•in (N.m)| Screw Type
---|---|---|---
Phil-Slot Head
| AX51| (1)x18-(2)x12| 7 (0.8)| M3
AX52| (1)x18-(2)x12| 7 (0.8)| M3
AX53| (1)x18-(2)x14| 7 (0.8)| M3
AL51| (1)x18-(2)x12| 7 (0.8)| M3
UVT51| (1)x18-(2)x12| 15 (1.7)| M3.5
SHT51| (1)x18-(2)x12| 15 (1.7)| M3.5
Electrical Diagram
Manual Motor Starters
Ex9S ACCESSORY DIMENSIONS Note: NOARK Electric reserves the
right to make technical changes or modify the contents of this document
without prior notice. With regard to purchase orders, the agreed particulars
shall prevail. NOARK Electric nor any of its af昀椀liates or subsidiaries shall
be responsible or liable for potential errors or possible lack of information
in this document. NOARK Electric reserves all rights in this document and in
the subject matter and illustrations contained therein. Any reproduction,
disclosure to third parties or utilization of its contents – in whole or in
parts – is forbidden without prior written consent of NOARK Electric.
NOARK Electric USA
2188 Pomona Blvd.
Pomona, CA 91768
626-330-7007
nasales@noark-electric.com
NOARK Electric Canada
975 Bleams Rd. Unit 3
Kitchener, ON N2E 3Z5
519-790-0605
casales@noark-electric.com
na.noark-electric.com
2023 NOARK Electric
A ll Rights Reserved
ICMMS202305NA
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>