VENTIA C8 Controller Modbus User Manual
- June 15, 2024
- VENTIA
Table of Contents
Description of C8
controller Modbus
C8 Controller Modbus
This manual is compatible with C8 controller firmware version x.x.x.4 and
above (X – does not matter).
C8 controller supports Modbus RTU and Modbus TCP protocols. Both protocols are
using main commands to read and preset registers. Supported Modbus commands
are presented in Table 1.
Table 1. Supported Modbus commands
Function code | Description |
---|---|
03 | Read Holding Registers |
06 | Preset Single Register |
16 | Preset Multiple Registers |
Modbus RTU protocol works via RS-485 interface. Default interface settings are
presented in Table 2. Default in- terface settings and Modbus RTU protocol ID
can be changed using the website. To change settings, connect air handling
unit (AHU) to your network. Default AHU IP address is 192.168.0.60. Go to your
browser and type default AHU IP address. You should see „Login“ window (Fig.
1). To login type username and password. Default username: „user“ and
password: „user“.
Table 2. Default settings of RS485 interface
Baudrate | 19200 |
---|---|
Word length | 8 |
Parity | EVEN |
Stop bits | 1 |
To find RS-485 interface settings and Modbus RTU protocol ID go to „SETTINGS“ and „CONNECTIVITY“ (Fig. 2). If you logged in, but can’t open „SETTINGS“ window make sure, that JavaScript in your web browser is enabled (activated).
If you can’t see „Login“ window, make sure that:
- your device and air handling unit are connected in the same network;
- your device and air handling unit are in the same subnet;
- your proxy server and firewall isn’t blocking connection;
- you typed correct IP address.
If your device is connected directly to C8 controller, make sure, that your DHCP server is disabled and your static IP is in same subnet. If you are using PC and Windows operating system, go to „Local Area Connection Properties“, go to „Internet Protocol Version 4 (TCP/IPv4) Properties“ (Fig. 3), check „Use the following IP address“ and type your static parameters, for example:
- IP address: 192.168.0.61;
- Subnet Mask: 255.255.255.0;
- Default gateway: 192.168.0.1.
UAB KOMFOVENT we reserve the right to make changes without prior notice
Modbus_connection_C8_23-11
The air handling unit has external connection terminals in the control box,
inside the air handling unit. Modbus A and B communication wires can be
connected to 1 and 2 terminals of connection for external elements (Fig. 4,
Fig. 5). To connect devices use twisted pair cable. Maximum cable length is
150 m. C8 controller ground point (any GND terminal from connection too
external elements – 4, 7, 10, 12) and other device should be connected
together, if distance between the RS-485 interfaces is more than 10 m. (Fig.
4, Fig. 5).
- Ethernet connection of computer network or Internet
- Controller panel connection
- Connection of external elements
Fig. 4. Controller with the connection terminals
1
2| A| Modbus RTU| RS485
---|---|---|---
B
3| +24V| Air quality sensor / Humidity sensor| B8
4| GND
5| 0..10V
6| +24V| Water mixing valve actuator /| AOUT
7| GND| DX control
8| 0..10V| Frost protection
9| NTC| Supply air| B1
10| GND| temperature sensor
11| NTC| Return water| B5
12| GND| temperature sensor
13| C| General| DIN
14| NC| Fire alarm
15| NO| Priority
16| C| General| DOUT
17| NO| Heating
18| NO| Cooling
19| | Air damper actuators Max 15W| FG1
20| ~230V
21| N
Fig. 5. Connection diagram for external elements
Modbus TCP protocol works via Ethernet interface, connection is provided
to RJ-45 socket on the C8 controller (Fig. 4). Default IP address is
192.168.0.60, and port is 502. To connect C8 controller via Modbus TCP make
sure, that proxy servers or firewall isn’t blocking device destination IP
address and 502 port is opened. Controller IP address can be changed using the
website (Fig. 2). Instructions how to connect and login to website was
presented at Modbus RTU section. IP address and subnet mask also can be
changed using C6.1 touch panel. To find these settings click touch C6.1 panel
screen, click „Menu“ button, click „Settings“ button and don’t release it, for
more than 5 seconds, after that „Advanced settings“ window will pop-up. Click
„Connectivity“ button and here you will find IP address and subnet mask (Fig.
6). If you want to change one of these parameters, just click on it and edit.
For connection the CAT5 category cable should be used. The maximum cable length between device and controller C8 is 100 m. C8 controller Modbus registers with descriptions are presented in Table 3.
Table 3
Alarm codes (registers 600-861)
Code | Text | Message |
---|---|---|
Hex | Dec | |
03 | 3 | F3 |
04 | 4 | F4 |
05 | 5 | F5 |
06 | 6 | F6 |
07 | 7 | F7 |
08 | 8 | F8 |
09 | 9 | F9 |
0A | 10 | F10 |
0B | 11 | F11 |
0C | 12 | F12 |
0D | 13 | F13 |
0E | 14 | F14 |
0F | 15 | F15 |
10 | 16 | F16 |
13 | 19 | F19 |
14 | 20 | F20 |
15 | 21 | F21 |
Code | Text | Message |
--- | --- | --- |
Hex | Dec | |
16 | 22 | F22 |
17 | 23 | F23 |
18 | 24 | F24 |
19 | 25 | F25 |
1A | 26 | F26 |
1C | 28 | F28 |
1D | 29 | F29 |
1E | 30 | F30 |
1F | 31 | F31 |
28 | 40 | F40 |
29 | 41 | F41 |
2A | 42 | F42 |
2B | 43 | F43 |
2C | 44 | F44 |
2D | 45 | F45 |
2E | 46 | F46 |
2F | 47 | F47 |
30 | 48 | F48 |
31 | 49 | F49 |
32 | 50 | F50 |
33 | 51 | F51 |
81 | 129 | W1 |
82 | 130 | W2 |
83 | 131 | W3 |
84 | 132 | W4 |
85 | 133 | W5 |
86 | 134 | W6 |
SERVICE AND SUPPORT
LITHUANIA
UAB KOMFOVENT
Phone: +370 5 200 8000
[email protected]
www.komfovent.com
FINLAND
Komfovent Oy
Muuntotie 1 C1
FI-01 510 Vantaa, Finland
Phone: +358 20 730 6190
[email protected]
www.komfovent.com
GERMANY
Komfovent GmbH
Konrad-Zuse-Str. 2a,
42551 Velbert, Deutschland
Phone: +49 0 2051 6051180
[email protected]
www.komfovent.de
LATVIA
SIA Komfovent
Bukaišu iela 1, LV-1004 Riga, Latvia
Phone: +371 24 66 4433
[email protected]
www.komfovent.com
Vidzemes filiāle
Alejas iela 12A, LV-4219 ValmiermuižaValmieras pagasts, Burtnieku novads
Phone: +371 29 358 145
[email protected]
www.komfovent.com
SWEDEN
Komfovent AB
Ögärdesvägen 12A
433 30 Partille, Sverige
Phone: +46 31 487 752
[email protected]
www.komfovent.se
UNITED KINGDOM
Komfovent Ltd
Unit C1 The Waterfront
Newburn Riverside
Newcastle upon Tyne NE15 8NZ, UK
Phone: +447983 299 165
[email protected]
www.komfovent.com
PARTNERS
AT| J. PICHLER Gesellschaft m. b. H.|
www.pichlerluft.at
---|---|---
BE| Ventilair group
ACB Airconditioning|
www.ventilairgroup.com
www.acbairco.be
CZ| REKUVENT s.r.o.| www.rekuvent.cz
CH| WESCO AG
SUDCLIMATAIR SA
CLIMAIR GmbH| www.wesco.ch
www.sudclimatair.ch
www.climair.ch
DK| Øland A/S| www.oeland.dk
EE| BVT Partners| www.bvtpartners.ee
FR| ATIB| www.atib.fr
HR| Microclima| www.microclima.hr
HU| AIRVENT Légtechnikai Zrt.
Gevent Magyarország Kft.
Merkapt| www.airvent.hu
www.gevent.hu
www.merkapt.hu
IE| Lindab| www.lindab.ie
IR| Fantech Ventilation Ltd| www.fantech.ie
IS| Blikk & Tækniþjónustan ehf
Hitataekni ehf| www.bogt.is
www.hitataekni.is
IT| Icaria srl| www.icariavmc.it
NL| Ventilair group
DECIPOL-Vortvent
CLIMA DIRECT BV| www.ventilairgroup.com
www.vortvent.nl
www.climadirect.com
NO| Ventilution AS
Ventistål AS
Thermo Control AS| www.ventilution.no
www.ventistal.no
www.thermocontrol.no
PL| Ventia Sp. z o.o.| www.ventia.pl
SE| Nordisk Ventilator AB|
www.nordiskventilator.se
SI| Agregat d.o.o| www.agregat.si
SK| TZB produkt, s.r.o.| www.tzbprodukt.sk
UA| TD VECON LLC| www.vecon.ua
Documents / Resources
|
VENTIA C8 Controller
Modbus
[pdf] User Manual
C8 Controller Modbus, C8, Controller Modbus, Modbus
---|---
References
- Domov - Agregat
- Airvent Légtechnikai Zrt.
- Solutions de ventilation et de traitement d’air | ATIB
- Blikk - og tækniþjónustan ehf. - Heim
- BVT | BVT
- Clima Direct: making it comfortable
- CLIMAIR
- Elta Ireland | Air Movement & Air Quality
- GEVENT Magyarország
- Hitatækni | Sérþekking á sviði loftræsinga
- ICARIA VMC
- Home | Komfovent
- Startseite | Komfovent
- Hemsida | Komfovent
- Welcome to Lindab Ireland
- Merkapt Zrt. – Épületgépészeti kereskedések
- Sistemi za klimatizaciju, grijanje, rashladna tehnika i regulacija | Microclima d.o.o.
- Nordisk Ventilator AB |
- Velkommen hos Øland A/S
- Home Pichler - Pichlerluft - Wohnraumlüftung, Luftförderung, Luftführung, Luftverteilung
- Rekuvent | Rekuperace, vzduchotechnika, řízené větrání
- SUDCLIMATAIR - Votre Air, Notre Expertise
- Totalleverandør av kjølemaskiner og varmepumper > Thermo Control
- TZB produkt
- Vecon
- VENTIA | Strona główna
- Ventilution AS
- Hjem - Ventistål
- Vind hier luchtbehandeling voor uw bedrijf - Vortvent
- Ihr Spezialist für Lüftung & Luftfiltration - WESCO