VENTS PL-10 Fire Resisting Duct Damper User Manual
- June 15, 2024
- VENTS
Table of Contents
- VENTS PL-10 Fire Resisting Duct Damper
- Product Information
- Product Usage Instructions
- FAQ
- INTRODUCTION
- SAFETY REQUIREMENTS
- PURPOSE
- DELIVERY SET
- DESIGNATION KEY
- TECHNICAL DATA
- DESIGN AND OPERATING PRINCIPLE
- MOUNTING AND SET-UP
- CONNECTION TO POWER MAINS
- TECHNICAL MAINTENANCE
- STORAGE AND TRANSPORTATION REGULATIONS
- MANUFACTURER’S WARRANTY
- CERTIFICATE OF ACCEPTANCE
- SELLER INFORMATION
- INSTALLATION CERTIFICATE
- WARRANTY CARD
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
VENTS PL-10 Fire Resisting Duct Damper
Product Information
Specifications
- The KP/PL-10 series fire dampers are designed for automatic closing of process openings and air duct penetrations in intermediate floors, walls, and partitions. They are also used for closing openings in supply and exhaust ducts of smoke ventilation systems. However, they are not suitable for installation in air ducts and ducts of premises with a rated explosion and fire safety category A and B, as well as in flammable and explosive mixture intakes.
- The KP/PL-10 fire dampers are designed, manufactured, and tested in accordance with the following standards:
- EN 15650:2019 Ventilation for buildings. Fire dampers (EN 15650:2010, IDT)
- EN 13501-3:2016 Fire classification of construction products and building elements. Part 3: Classification using data from fire resistance tests on products and elements used in building service installations: fire resisting ducts and fire dampers (EN 13501-3:2005+A1:2009, IDT)
- EN 1366-2:2013 Fire resistance tests for service installations. Fire dampers (EN 1366-2:1999, IDT)
Delivery Set
Name | Number |
---|---|
Damper | 1 pc. |
User’s manual | 1 pc. |
Packing box | 1 pc. |
Designation Key
- The designation key provides information about the design and features of the fire-resisting damper. Here is an example of a designation: KP-2-250×250-1-72S-VN-1 Series.
- The key breaks down as follows:
- KP – Fire-resisting damper for square and rectangular ventilation ducts
- 2 – Fire resistance of 2 hours
- 250×250 – Damper flow area width and height of 250mm
- 1 – One flange
- 72S – Actuator location outside
- VN – Design variant inside (except for dampers with a height and width of less than 300mm)
- 1 – Ordinary damper design (simplified damper design for KP-2 only)
Technical Data
The technical data provides information about the overall and connecting
dimensions of the KP-1…72S dampers with a return spring. Here are some
examples:
Model | Dimensions [mm] | Weight |
---|---|---|
KP-1-200×200-2-72S-SN | 200, 220, 240, 200 | B1, B2, deposits |
KP-1-250×200-2-72S-SN | 250, 270, 290, 200 | B1, B2, deposits |
KP-1-250×250-2-72S-SN | 250, 270, 290, 250 | B1, B2, deposits |
Product Usage Instructions
Installation
- Choose a suitable location for the fire damper installation.
- Ensure that the installation area is free from obstructions and debris.
- Follow the provided user’s manual for step-by-step installation instructions.
- Secure the damper in place using appropriate fasteners and mounting brackets.
- Connect the damper to the ventilation system according to the specified duct dimensions.
Maintenance
To ensure optimal performance and longevity of the fire damper, regular
maintenance is required. Follow these maintenance guidelines:
- Inspect the damper periodically for any signs of damage or wear.
- Clean the damper and surrounding area to remove dust and debris.
- Check the operation of the damper by testing the closing and opening mechanism.
- Replace any worn-out components or damaged parts immediately.
Troubleshooting
If you encounter any issues with the KP/PL-10 fire damper, refer to the
troubleshooting section of the user’s manual. It provides guidance on common
problems and their solutions.
FAQ
-
Can the fire damper be installed in air ducts with a rated explosion and fire safety category A or B?
No, the KP/PL-10 fire dampers are not suitable for installation in air ducts and ducts of premises with a rated explosion and fire safety category A and B. -
How can I dispose of the fire damper at the end of its service life?
The product must be disposed of separately at the end of its service life. Do not dispose of the unit as unsorted domestic waste.
INTRODUCTION
- This user’s manual is a main operating document intended for technical, maintenance, and operating staff.
- The manual contains information about purpose, technical details, operating principle, design, and installation of the KP/PL-10 unit and all its modifications.
- Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country.
SAFETY REQUIREMENTS
- All operations described in this manual must be performed by qualified personnel only, properly trained and qualified to install, make electrical connections and maintain ventilation units.
- Do not attempt to install the product, connect it to the mains, or perform maintenance yourself. This is unsafe and impossible without special knowledge.
- Disconnect the power supply prior to any operations with the unit.
- All user’s manual requirements as well as the provisions of all the applicable local and national construction, electrical, and technical norms and standards must be observed when installing and operating the unit.
- Disconnect the unit from the power supply prior to any connection, servicing, maintenance, and repair operations.
- Connection of the unit to power mains is allowed by a qualified electrician with a work permit for the electric units up to 1000 V after careful reading of the present user’s manual.
- Check the unit for any visible damage of the impeller, the casing, and the grille before starting installation. The casing internals must be free of any foreign objects that can damage the impeller blades.
- While mounting the unit, avoid compression of the casing! Deformation of the casing may result in motor jam and excessive noise.
- Misuse of the unit and any unauthorised modifications are not allowed.
- Do not expose the unit to adverse atmospheric agents (rain, sun, etc.).
- Transported air must not contain any dust or other solid impurities, sticky substances, or fibrous materials.
- Do not use the unit in a hazardous or explosive environment containing spirits, gasoline, insecticides, etc.
- Do not close or block the intake or extract vents in order to ensure the efficient air flow.
- Do not sit on the unit and do not put objects on it.
- The information in this user’s manual was correct at the time of the document’s preparation. The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments. Never touch the unit with wet or damp hands.
- Never touch the unit when barefoot.
BEFORE INSTALLING ADDITIONAL EXTERNAL DEVICES, READ THE RELEVANT USER MANUALS.
PURPOSE
-
The KP/PL-10 series fire dampers are intended for automatic closing of process openings and air duct penetrations in intermediate floors, walls and partitions, as well as closing of openings in supply and exhaust ducts of smoke ventilation systems.
-
The dampers of this particular design are not suitable for installation in air ducts and ducts of premises with rated explosion and fire safety category A and B and in flammable and explosive mixture intakes.
-
The KP/PL-10 fire dampers are designed, manufactured and tested in accordance with the following standards:
EN 15650:2019 Ventilation for buildings. -
Fire dampers (EN 15650:2010, IDT);
EN 13501-3:2016 Fire classification of construction products and building elements. -
Part 3: Classification using data from fire resistance tests on products and elements used in building service installations:
fire resisting ducts and fire dampers (EN 13501-3:2005+A1:2009, IDT). -
Product performance has been confirmed by tests in accordance with EN 1366-2:2013 Fire resistance tests for service installations.
-
Fire dampers (EN 1366-2:1999, IDT).
DELIVERY SET
- Damper 1 pc.
- User’s manual 1 pc.
- Packing box 1 pc.
DESIGNATION KEY
TECHNICAL DATA
- The dampers are designed for operation in spaces with non aggressive environment, the air temperature ranging from 0 °C to +60 °C and relative humidity up to 80 %.
- Durability test:
- 50 cycles / manual actuation;
- 10,000 cycles / electric actuator with return spring.
- Ingress protection rating against access to hazardous parts and water ingress is IPX4.
- In terms of electric shock hazard the products belong to the following categories of electrical appliances:
- Class III (low voltage) for the dampers with 24 V electric actuator power supply.
- Class II (complete insulation) for the dampers with 230 V electric actuator power supply.
- The dampers may not be integrated:
- Into air ducts and on premises rated explosion and fire safety category A and B.
- Into air ducts of local intakes for flammable and explosive mixtures.
- Into systems which do not undergo periodic cleaning pursuant to an approved schedule to prevent the build-up of combustible deposits.
- The damper undergoes continuous improvement. Therefore, some models may slightly differ from the ones described herein.
Overall and connecting dimensions of KP-1…72S dampers with a return spring
Overall and connecting dimensions of KP-1…PNP/KP-1…PVP/KP-1…PSP dampers with electric actuators
Overall and connecting dimensions of KP-2…72S dampers with a mechanical actuator
Overall and connecting dimensions of KP-2…PNP/KP-2…PVP/KP-2…PSP dampers with electric actuators
Overall and connecting dimensions of KP-2…PNP…-1/KP-2…PVP…-1/KP-2…PSP…-1 dampers with electric actuators
The PL-10-1A fire safety damper with a mechanical actuating unit, a thermal fuse and a return spring
The PL-10…PNP/PL-10…PVP/PL-10…PSP fire safety damper with an electric actuator and a thermally sensitive breaker
Main technical specifications of Belimo electric actuators with a return spring and a thermal breaker
Main technical specifications of Nenutec electric actuators with a return spring and a thermal breaker
Main technical specifications of Siemens electric actuators with a return spring and a thermal breaker
DESIGN AND OPERATING PRINCIPLE
KP-1…72S fire safety damper with a mechanical actuating unit with a thermal fuse and a return spring
KP-1…PNP/KP-1…PVP/KP-1…PSP fire safety damper with electric actuator and a thermoelectric breaker
The KP-2…72S fire safety damper with a mechanical actuating unit with a thermal fuse and a return spring
The KP-2…PNP/KP-2…PVP/KP-2…PSP fire safety damper with electric actuator and thermoelectric breaker
The KP-2…PNP…-1/KP-2…PVP…-1/KP-2…PSP…-1 fire safety damper with a Belimo electric actuator and thermoelectric reaker
The PL-10…-1A fire safety damper with a mechanical ctuating unit, a thermal fuse and a return spring
The PL-10…PNP/PL-10…PVP/PL-10…PSP fire safety damper with an electric actuator and a thermoelectric breaker
MOUNTING AND SET-UP
The dampers are installed into square or rectangular (KP-1, KP-2 series) and
round (PL-10 series) air ducts of ventilation systems, and the apertures of
ventilation shafts, division walls and fire partitions.
The installation of the dampers into ventilation systems must be carried out
in consideration of the air flow direction. While installing electrically
actuated dampers provide for sufficient space for the actuator inspection.
- When preparing the fire-safety dampers for installation the damper casing must be fitted with wooden spreader bars to prevent deformation, torsional twisting or geometry perturbation of the casing which may result in flap jamming and, eventually, loss of the damper functionality.
- Following the damper installation into the shaft, wall or ceiling filler structure section and upon complete curing (immobilization) of the mortar make sure to remove the wooden spreader bars. The damper must open and close freely without excessive friction.
- To install the dampers into the apertures of wall or ceiling slabs fill up the gaps between the damper casing and the aperture. The gaps are filled with fire-resistant mortar.
- The damper design enables its attachment to air ducts and other ventilation system components by means of flanges as well as its installation into filler structures. Under any installation scenario the mating structure fire-resistance level must be upgraded by using extra fire insulation to at least match that of the filler structure of the respective fire-safety zone.
- According to EN 15650, each fire damper must be installed in accordance with the mounting instructions provided by the manufacturer!
KP-1, KP-2 DAMPER INSTALLATION
- The dampers can be installed in any position into vertical and horizontal channels of fire-protection structures. The damper installation openings must be made in such a way so as to prevent the transfer of loads caused by the fire-protection structures to the damper casing. The adjoining air duct must be suspended in such a way so as to prevent the transfer of air duct load to the damper flange. There must be at least 350 mm of unrestricted clearance for accessing the control elements. Make sure to arrange an inspection hole. While carrying out the installation mind size K. When two or more dampers are installed into the same fire-protection separation structure the distance between the two adjacent dampers must be at least 200 mm.
- The damper must be installed in such a way that the damper flap lies in the fire-protection divider structure plane while closed. If such installation is not possible, the damper casing part between the fire-protection separation structure and the damper flap must be insulated with a suitable material pursuant to the applicable standards.
- The damper control mechanism must be protected against damage and contamination. Avoid damper casing deformation during the embedding. After the installation the flap must not catch against the damper casing while opening or closing.
- Fire-safety dampers can be integrated into a tight wall structure – e.g. made of conventional concrete work of minimum width W = 100 mm or into a plasterboard wall of the necessary fire resistance class or into a tight ceiling structure – e.g. made of conventional concrete of minimum width W = 150 mm.
- The recommended values for construction openings are given below.
INSTALLATION RECOMMENDATIONS FOR KP-1…72S DAMPERS WITH A THERMAL FUSE AND A RETURN SPRING
INSTALLATION RECOMMENDATIONS FOR KP-1…PNP/KP-1…PVP/KP-1…PSP FIRE SAFETY DAMPERS WITH ELECTRIC ACTUATOR
INSTALLATION RECOMMENDATIONS FOR KP-2…72S DAMPERS WITH A THERMAL FUSE AND A RETURN SPRING
INSTALLATION RECOMMENDATIONS FOR KP-2…PNP/KP-2…PVP/KP-2…PSP FIRE SAFETY DAMPERS WITH ELECTRIC ACTUATOR
INSTALLATION RECOMMENDATIONS FOR KP-2…PNP…-1/KP-2…PVP…-1/KP-2…PSP…-1 FIRE SAFETY DAMPERS WITH ELECTRIC ACTUATOR
PL-10 DAMPER INSTALLATION
- Fire-safety dampers can be installed into solid walls with the minimum width of W = 150 mm, into both round and square apertures, minimum intermediate layer thickness S = 50 mm. The walls can be made of concrete, brick or foam concrete blocks. The intermediate layer can be made of concrete or mortar. While carrying out the installation mind size K. When installing the dampers into thicker walls add an extender section on one of the damper sides.
- The electric actuator can be positioned freely on either side of the fire control sector (space) wall.
- Fire-safety dampers can be installed into solid ceiling panels with the minimum thickness of W = 150 mm, minimum intermediate layer thickness S = 50 mm. The ceiling panels are made of concrete. The intermediate layer can be made of concrete or mortar. While carrying out the installation mind size K.
- When installing the dampers into thicker walls add an extender section on one of the damper sides.
- The electric actuator can be positioned freely above or below the ceiling panel of the fire control sector (space).
Permissible positions for fire-safety damper installation
The damper axle and actuation mechanism can be installed in any position –
from horizontal to vertical.
CONNECTION TO POWER MAINS
- The actuators featuring a return spring are designed to control fire-resisting dampers and smoke-extraction dampers installed in ventilation and air-conditioning systems.
- The return spring is cocked upon setting the damper flap to the horizontal position. In case of a power failure, the damper flap is re-set to the protective position by the energy stored in the spring.
- The damper does not require any limit switches and is overload-proof.
- The thermally sensitive breaker Tf1 actuates upon ambient temperature exceeding 72 °C. The renewable thermally sensitive breakers Tf2 and Tf3 actuate upon the air duct temperature exceeding 72 °C. The operation of the renewable thermally sensitive breakers interrupts the electric power supply in such a way that it prevents actuator re-activation without their replacement.
- The button on the thermally sensitive breaker body enables testing the damper functionality.
- The actuator is equipped with two fixed microswitches which signal the end positions.
- Intermediate positions of the damper are shown by the mechanical indicator (needle).
- The BF24-T and BFN24-T actuators are connected via an insulated transformer unit .
- The damper can also be controlled manually and fixed in any position. The unit can be unlocked either manually using a hex wrench (included) or automatically upon power-up.
- The actuator connections (cables and wires) must be durable, insulated and heat-resistant.
- The recommended minimum conductor cross-section is 0.75 mm2. The conductor cross-section selection must account for the maximum permissible wire heating which depends on the wire type, its insulation, length and installation method (i.e. overhead, in cable channels or inside walls).
Electrical connection of the basic models of Belimo and Nenutec electric actuators, as well as Belimo and Nenutec models with increased torque
Electrical connection of Belimo electric actuators with the highest torque, as well as Siemens electric actuators
TECHNICAL MAINTENANCE
- The damper technical maintenance includes routine inspections and functionality checks.
- The damper technical maintenance frequency must comply with the established technical maintenance frequency of the fire safety equipment complex of the facility.
- Recommended inspection steps according to EN 15650:
- Identification of the damper.
- Date of the inspection.
- Check the electrical connection of the actuating mechanism (if any).
- Check the damper for cleanliness and the need for cleaning (if necessary).
- Check the condition of the blade and seal, perform correction and registration actions (if necessary).
- Check that the damper is able to close properly.
- Check the functionality of the damper: opening and closing using the control system, physical inspection of the blade behaviour, perform correction and registration actions (if necessary).
- Check the functionality of the limit switches in the open and closed position, perform correction and registration actions if necessary.
- Check that the damper is operating as intended as part of the control system (if necessary).
- Check the standard operating position of the damper.
- The damper usually operates as a part of the system.
- In this case, it is necessary to check the entire system as described in the requirements for its operation defined by the system developer.
STORAGE AND TRANSPORTATION REGULATIONS
- Store the unit in the manufacturer’s original packaging box in a dry closed with temperature range from -20 °C to +50 °C.
- Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
- Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
- Follow the handling requirements applicable for the particular type of cargo.
- The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
- Avoid sharp blows, scratches, or rough handling during loading and unloading.
- Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least
3- 4 hours.
MANUFACTURER’S WARRANTY
- The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby declare that the product complies with the provisions of Electromagnetic Compatibility (EMC) Directive 2014/30/EU of the European Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council and CE-marking Council Directive 93/68/EEC. This certificate is issued following test carried out on samples of the product referred to above.
- The manufacturer hereby warrants normal operation of the unit for 24 months after the retail sale date provided the user’s observance of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation through the Manufacturer’s fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component.
The warranty repair does not include:
- routine technical maintenance
- unit installation/dismantling
- unit setup
To benefit from warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.
The manufacturer’s warranty does not apply to the following cases:
- User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
- Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
- User’s failure to ensure timely technical maintenance of the unit.
- External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
- Redesign or engineering changes to the unit.
- Replacement and use of any assemblies, parts and components not approved by the manufacturer.
- Unit misuse.
- Violation of the unit installation regulations by the user.
- Violation of the unit control regulations by the user.
- Unit connection to power mains with a voltage different from the one stated in the user’s manual.
- Unit breakdown due to voltage surges in power mains.
- Discretionary repair of the unit by the user.
- Unit repair by any persons without the manufacturer’s authorization.
- Expiration of the unit warranty period.
- Violation of the unit transportation regulations by the user.
- Violation of the unit storage regulations by the user.
- Wrongful actions against the unit committed by third parties.
- Unit breakdown due to circumstances of insuperable force (flood, earthquake, war, hostilities of any kind, blockades).
- Missing seals if provided by the user’s manual.
- Failure to submit the user’s manual with the unit purchase date stamp.
- Missing payment paperwork certifying the unit purchase.
The manufacturer shall not accept any claims with regards to the condition of the paint-and-lacquer coating (hereinafter PLC) in the following cases:
- Dents, cracks, scratches and abrasions of the PLC sustained during handling, mounting and assembly operations.
- Progress of corrosion on areas damaged with stones, sand, and roof coat tar during the performance of roofing work.
- Signs of direct exposure of the PLC to excessive temperatures, which occurred during the performance of roofing work.
- Violation of regulations on transportation, storage, installation, and operation of the unit.
- Presence of damage caused by exposure to industrial and chemical emissions, acidic or alkaline pollution, sap or other factors not related to normal operating conditions.
- FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE-FREE OPERATION OF THE UNIT
- USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE STAMP
CERTIFICATE OF ACCEPTANCE
SELLER INFORMATION
INSTALLATION CERTIFICATE
WARRANTY CARD
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>