LENNOX LGM-LCM092U Gas and Cooling Packaged Units Instruction Manual
- June 15, 2024
- Lennox
Table of Contents
- LENNOX LGM-LCM092U Gas and Cooling Packaged Units
- Product Information
- Parts Arrangement
- Safety
- Unit Support
- High Altitude Derate
- Blower Operation
- Cooling Start-Up
- Electric Heat Start-Up (Cooling Units)
- Cooling Operation
- Service
- Factory Unit Controller Settings
- FAQ
- IMPORTANT
- INSTALLATION INSTRUCTIONS
- SIDE VIEW
- CONDENSER COIL
- UNIT CLEARANCES
- RIGGING
- MOUNTING FRAME
- FILTER ACCESS DOOR
- BOTTOM CONDENSATE DRAIN
- Electrical Connections – Control Wiring
- F-Compressor Controls
- Cooling Operation
- REMOVE FILTERS
- SHEET METAL END STOP
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
LENNOX LGM-LCM092U Gas and Cooling Packaged Units
Product Information
Specifications
- Model: LGM/LCM092U (7.5 TON), LGM/LCM102U (8.5 TON), LGM/LCM120U (10 TON), LGM/LCM150U (12.5 TON)
- Type: Gas and Cooling Packaged Units
- Part Number: 508116-01
- Dimensions: Please refer to the diagram below for detailed dimensions.
Parts Arrangement
The parts of the product are arranged as shown in the diagram below:
Shipping and Packing List
The product is shipped with the following items:
- Product unit
- Factory-installed accessories (if applicable)
- User manual and instructions
Safety
It is important to follow safety guidelines to prevent property damage, personal injury, or loss of life. The following safety precautions should be taken:
- All installation, adjustment, alteration, service, and maintenance must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier.
- Before performing any maintenance, ensure proper lock-out and tag-out procedures are followed.
- Disable power to the blower and set all controllers and thermostats to the OFF position before performing maintenance.
- Avoid contact with moving parts and sharp sheet metal edges. Always wear gloves and protective clothing when handling the equipment.
Unit Support
The product unit should be properly supported to ensure stability and safety. Follow the manufacturer’s guidelines for unit support.
Duct Connection
Connect the product unit to the duct system using appropriate duct
connections. Ensure proper sealing to prevent air leaks.
Rigging Unit for Lifting
If lifting the product unit is necessary, use the designated lifting holes
or forklift slots as indicated in the diagram below. Follow proper rigging
procedures and guidelines.
Condensate Drains
Proper condensate drainage is important for the operation and efficiency of
the product unit. Install condensate drains as per manufacturer’s
instructions.
Connect Gas Piping (Gas Units)
If using a gas unit, connect the gas piping following appropriate
guidelines and codes. Ensure proper sealing and leak testing.
Pressure Test Gas Piping (Gas Units)
Before operating a gas unit, it is important to perform a pressure test on
the gas piping to ensure there are no leaks. Follow the manufacturer’s
instructions for pressure testing.
High Altitude Derate
In high altitude areas, the product unit may require derating. Refer to the manufacturer’s guidelines for derating instructionsspecific to your altitude.
Download Mobile Service App
The product unit is compatible with a mobile service app that allows for
remote control and configuration. Follow the steps below to download and set
up the app:
- Use your smartphone to scan the QR code provided in the unit control area or refer to the manual for the QR code.
- Download and install the mobile service app from the appropriate iOS or Android store.
- Follow the prompts in the app to pair it with the unit control system and configure the unit.
- For detailed instructions, refer to the “Download Mobile App” section in the user manual and the Setup Guide provided with the unit.
Electrical Connections – Power Supply
Ensure proper electrical connections for the power supply of the product
unit. Follow local electrical codes and guidelines. If unsure, consult a
licensed professional.
Electrical Connections – Control Wiring
Connect the control wiring according to the manufacturer’s instructions.
Follow proper wiring practices and ensure secure connections.
Blower Operation
The blower is a critical component of the product unit. Follow the manufacturer’s instructions for blower operation, maintenance, and troubleshooting.
Direct Drive Blower Start-Up
If the product unit has a direct drive blower, follow these steps for
start-up:
- Ensure all power to the unit is off.
- Inspect the blower for any obstructions or damage.
- If necessary, lubricate the blower motor according to the manufacturer’s instructions.
- Turn on the power to the unit and set the thermostat to the desired settings.
- Observe the blower operation for any abnormalities or unusual noises.
Cooling Start-Up
To start the cooling operation of the product unit, follow these steps:
- Ensure all power to the unit is off.
- Inspect the cooling components for any obstructions or damage.
- Check the refrigerant level and make adjustments if necessary.
- Turn on the power to the unit and set the thermostat to the desired cooling temperature.
- Observe the cooling operation for any abnormalities or insufficient cooling.
Prognostic & Diagnostic Sensors
The product unit is equipped with prognostic and diagnostic sensors to
monitor and detect any issues. These sensors provide valuable information for
maintenance and troubleshooting. Refer to the manufacturer’s instructions for
details on sensor operation and interpretation of sensor data.
Gas Heat Start-Up (Gas Units)
To start the gas heating operation of the product unit, follow these steps:
- Ensure all power to the unit is off.
- Inspect the gas heat components for any obstructions or damage.
- Check the gas supply and ensure it is connected properly.
- Turn on the power to the unit and set the thermostat to the desired heating temperature.
- Observe the gas heating operation for any abnormalities or insufficient heating.
Heating Operation and Adjustments
For heating operation and adjustments, follow the manufacturer’s
instructions specific to your product unit model. This may include settings
for temperature control, fan speed, and other heating-related parameters.
Electric Heat Start-Up (Cooling Units)
If the product unit has electric heat for cooling operation, follow these steps for start-up:
- Ensure all power to the unit is off.
- Inspect the electric heat components for any obstructions or damage.
- Check the electrical connections for the electric heat elements.
- Turn on the power to the unit and set the thermostat to the desired cooling temperature.
- Observe the electric heating operation for any abnormalities or insufficient heating.
SCR Electric Heat Controller (LCM Units)
If your product unit is equipped with an SCR electric heat controller (LCM
units), follow the manufacturer’s instructions for operation and adjustments
specific to the controller. This may include settings for temperature control,
fan speed, and other heating-related parameters.
Cooling Operation
For cooling operation, follow the manufacturer’s instructions specific to your product unit model. This may include settings for temperature control, fan speed, and other cooling-related parameters.
Modulating Hot Gas Reheat Start-Up and Operation
If your product unit has a modulating hot gas reheat system, follow the
manufacturer’s instructions for start-up and operation. This system is
designed to provide precise control of reheat temperature for optimal comfort
and energy efficiency.
Service
For servicing the product unit, refer to the manufacturer’s instructions. Only perform maintenance and repairs that are within your capabilities. If unsure, consult a licensed professional HVAC technician.
Field-Installed Accessories
If you have installed any field accessories in addition to the factory-
installed accessories, refer to the manufacturer’s instructions for operation
and maintenance of those accessories.
Factory Unit Controller Settings
The factory unit controller settings are pre-configured for optimal performance. Avoid making unnecessary changes to the controller settings unless instructed by the manufacturer or a licensed professional.
FAQ
Q: Can I install the product unit myself?
A: No, installation must be performed by a licensed professional HVAC
installer or equivalent, service agency, or the gas supplier.
Q: Where can I download the mobile service app?
A: The mobile service app can be downloaded from the appropriate iOS or
Android store. Look for the following icon:
Q: How can I prevent personal injury while handling the equipment?
A: Take care while handling the equipment and always wear gloves and
protective clothing. Avoid contact with sharp sheet metal edges.
IMPORTANT
Improper installation, adjustment, alteration, ser vice or maintenance can cause property damage, personal injury or loss of life. Installation and ser vice must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier
INSTALLATION INSTRUCTIONS
LGM/LCM092U (7.5 TON)
LGM/LCM102U (8.5 TON)
LGM/LCM120U (10 TON)
LGM/LCM150U (12.5 TON)
GAS AND COOLING PACKAGED UNITS
508116-01 10/2023 Supersedes 4/2022
Cooling Operation
26
Modulating Hot Gas Reheat Start-Up and Operation 27
Service
28
Field-Installed Accessories
35
Factory Unit Controller Settings
35
WARNING
To prevent serious injury or death:
1- Lock-out. tag-out before performing maintenance.
2- If system power is required (e.g., smoke detector maintenance), disable
power to blower, remove fan belt where applicable, and ensure all controllers
and thermostats are set to the OFF position before performing maintenance.
3- Always keep hands, hair clothing, jewelery, tools, etc., away from moving
parts.
RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCES
Attention!
Use this QR code to download the mobile service app. Follow the prompts to
pair the app with the unit control system and configure the unit. Refer to the
“Download Mobile App” section in this manual and the Setup Guide provided with
this unit. The QR code is also available in the unit control area.
The app can be downloaded from the appropriate iOS or Android store. Look for the following icon.
WARNING
As with any mechanical equipment, contact with sharp sheet metal edges can
result in personal in jury. Take care while handling this equipment and wear
gloves and protective clothing.
LGM/LCM092, 102, 120, 150 DIMENSIONS in. – Gas heat section shown
6-1/8 (156)
AA
5-5/8 (143) BOTTOM SUPPLY
AIR OPENING
BB
58-1/8 (1476)
6-1/8 (156)
24 (610)
10-3/4
28
(273) 20 (711)
(508)
60-1/8 (1527) BASE
BOTTOM POWER ENTRY 5-1/2 (140) Dia.
27 (686)
BOTTOM RETURN AIR OPENING
EE
CENTER OF GRAVITY
FF
7 (178)
6-5/8 (168)
DD
BOTTOM
CC
7 (178)
CONDENSATE
34-7/8 (886)
101-1/4 BASE (2572)
TOP VIEW
OPTIONAL DISCONNECT (FACTORY INSTALLED)
99-1/4 (2521)
60-1/8 (1527)
END VIEW
46-7/8 (1191) 43-3/8 (1102)
3-1/2 (89)
1 (25) ELECTRIC INLETS
15-1/2 (394)
CONDENSATE DRAIN (FRONT)
GAS SUPPLY INLET
5-3/8 (137)
18-1/2 (470)
FLUE OUTLET
46-7/8 (1191)
34-7/8 (886)
39-7/8 (1013)
FORKLIFT SLOTS (BOTH SIDES) LIFTING HOLES (FOR RIGGING)
101-1/4 (2572)
SIDE VIEW
15-1/2 (394)
1-5/8 (41)
HORIZONTAL SUPPLY AIR
OPENING
HORIZONTAL RETURN AIR
OPENING
30 (762)
12-1/8 (308)
CONDENSATE
6-1/8
DRAIN (BACK)
5-3/8
(156)
(137)
31-1/2
30
Important – Do not install
(800)
66-3/8 (1686)
(762)
horizontal economizers on this opening. Refer to
SIDE VIEW
economizer instructions for proper installation.
(Horizontal Openings)
Page 2
LGM092, 102, 120, 150 PARTS ARRANGEMENT
FILTERS (FOUR – 20 X 25 X 2″)
EVAPORATOR COIL
REHEAT COIL BLOWER (OPTIONAL) (DIRECT DRIVE)
CONDENSER FANS
CONDENSER COIL
COMPRESSOR INVERTER
(BEHIND THE HINGED PANEL)
ECONOMIZER (OPTIONAL)
WIFI ANTENNA
UNIT CONTROLLER
WIRELESS BOARD
COMPRESSORS
GAS VALVE
CONDENSATE DRAIN
COMBUSTION AIR INDUCER
BURNERS
IGNITION CONTROL
LCM092, 102, 120, 150 PARTS ARRANGEMENT
FILTERS (FOUR – 20 X 25 X 2″)
EVAPORATOR COIL
REHEAT COIL (OPTIONAL)
BLOWER (DIRECT DRIVE)
CONDENSER FANS
COMPRESSOR INVERTER
(BEHIND THE HINGED PANEL)
ECONOMIZER (OPTIONAL)
WIFI ANTENNA
UNIT CONTROLLER
WIRELESS BOARD
COMPRESSORS
CONDENSATE DRAIN
ELECTRIC HEAT (OPTIONAL)
CONDENSER COIL
Page 3
Shipping and Packing List
Package 1 of 1 contains:
1 – Assembled unit
Check unit for shipping damage. Receiving party should contact last carrier
immediately if shipping damage is found.
General
These instructions are intended as a general guide and do not supersede local
codes in any way. Authorities having jurisdiction should be consulted before
installation.
The LGM092, 102, 120, & 150 gas/electric packaged rooftop unit is available in
130,000, 180,000, or 240,000 Btuh heating inputs. The LCM092, 102, 120, & 150
cooling packaged rooftop unit is the same basic design as the LGM unit except
for the heating section. Optional electric heat is factory- or field-installed
in LCM units. Units are equipped with fin/tube condenser coils. Units are
available with an optional hot gas reheat coil which provides dehumidifying
modes of operation. Refer
to Reheat Operation section.
Units are equipped with direct drive blowers. The blower will operate at lower
speeds when demand is low and increase to higher speeds when demand is high.
Refer to the Direct Drive Start-Up section.
The following examples show the model numbers of ten ton units with blower
options.
LGM/LCM120U4E Single Zone VAV Direct Drive
LGM/LCM120U4P VAV Direct Drive
All units are available using R410A, an ozone-friendly HFC refrigerant. Refer
to the Cooling Start-Up section for precautions when installing unit.
Safety
See TABLE 1 for unit clearances.
WARNING
Electric shock hazard and danger of explosion. Can cause injury, death or
product or property damage. Turn off gas and electrical power to unit before
performing any maintenance or servicing operations on the unit. Follow
lighting instructions attached to unit when putting unit back into operation
and after service or maintenance.
Optional Outdoor Air Hood
UNIT CLEARANCES
C
B D
A
FIGURE 1
TABLE 1 UNIT CLEARANCES
¹ Unit
A
B
C
D
Top
Clearance in.(mm) in.(mm) in.(mm) in.(mm) Clearance
Service Clearance
60 (1524)
36 (914)
36 (914)
60 (1524)
Unobstructed
Clearance to
36
1
1
1
Unob-
Combustibles (914)
(25)
(25)
(25)
structed
Minimum Operation Clearance
36 (914)
36 (914)
36 (914)
36 (914)
Unobstructed
NOTE – Entire perimeter of unit base requires support when elevated above mounting surface.
¹ Service Clearance – Required for removal of serviceable parts Clearance to Combustibles – Required clearance to combustible material (gas units). On LCM units, see clearance to combustible materials as outlined of neater rating plate. Minimum Operation Clearance – Required clearance for proper unit operation.
NOTICE
Roof Damage!
This system contains both refrigerant and oil. Some rubber roofing material
may absorb oil, causing the rubber to swell. Bubbles in the rubber roofing
material can cause leaks. Protect the roof surface to avoid exposure to
refrigerant and oil during service and installation. Failure to follow this
notice could result in damage to roof surface.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFC’s
and HCFC’s) as of July 1, 1992. Approved methods of recovery, recycling or
reclaiming must be followed. Fines and/or incarceration may be levied for non-
compliance.
Page 4
Use of this unit as a construction heater or air conditioner is not
recommended during any phase of construction. Very low return air
temperatures, harmful vapors and operation of the unit with clogged or
misplaced filters will damage the unit.
If this unit has been used for heating or cooling of buildings or structures
under construction, the following conditions must be met or the warranty will
be void:
· A room thermostat or zone air temperature sensor must control the unit. The
use of fixed jumpers that will provide continuous heating or cooling is not
allowed.
· A pre-filter must be installed at the entry to the return air duct.
· The return air duct must be provided and sealed to the unit.
· Return air temperature range between 55°F (13°C) and 80°F (27°C) must be
maintained.
· Air filters must be replaced and pre-filters must be removed upon
construction completion.
· The input rate and temperature rise must be set per the unit rating plate.
· The heat exchanger, components, duct system, air filters and evaporator coil
must be thoroughly cleaned following final construction clean-up.
· The unit operating conditions (including airflow, cooling operation,
ignition, input rate, temperature rise and venting) must be verified according
to these installation instructions.
This appliance is not to be used by persons with reduced physical, sensory or
mental capabilities, or lack of experience and knowledge, unless they have
been given supervision or instruction.
This appliance should not be used by children. Children should be supervised
to ensure they do not play with the appliance.
Unit Support
In downflow discharge installations, install the unit on a non-combustible
surface only. Unit may be installed on combustible surfaces when used in
horizontal discharge applications or in downflow discharge applications when
installed on an C1CURB7*B roof mounting frame.
NOTE – Securely fasten roof frame to roof per local codes.
CAUTION
To reduce the likelihood of supply / return air by pass and promote a proper
seal with the RTU, duct work / duct drops / diffuser assemblies must be
supported independently to the building structure.
A-Downflow Discharge Application Roof Mounting with C1CURB7B
1 – The C1CURB7B roof mounting frame must be installed, flashed and sealed in
accordance with the instructions provided with the frame.
2 – The C1CURB7B roof mounting frame should be square and level to 1/16″ per
linear foot (5mm per linear meter) in any direction.
3 – Duct must be attached to the roof mounting frame and not to the unit;
supply and return plenums must be installed before setting the unit.
Installer’s Roof Mounting Frame
Many types of roof frames can be used to install the unit depending upon
different roof structures. Items to keep in mind when using the building frame
or supports are:
1 – The base is fully enclosed and insulated, so an enclosed frame is not
required.
2 – The frames or supports must be constructed with non-combustible materials
and should be square and level to 1/16″ per linear foot (5mm per linear meter)
in any direction.
3 – Frame or supports must be high enough to prevent any form of moisture from
entering unit. Recommended minimum frame height is 14″ (356mm).
4 – Duct must be attached to the roof mounting frame and not to the unit.
Supply and return plenums must be installed before setting the unit.
5 – Units require support along all four sides of unit base. Supports must be
constructed of steel or suitably treated wood materials.
NOTE – When installing a unit on a combustible surface for downflow discharge
applications, an C1CURB7B roof mounting frame is required.
Page 5
B-Horizontal Discharge Applications 1 – Units installed in horizontal airflow
applications must use a horizontal conversion kit K1HECK00.
2 – Specified installation clearances must be maintained when installing
units. Refer to FIGURE 1.
3 – Top of support slab should be approximately 4″ (102mm) above the finished
grade and located so no run-off water from higher ground can collect around
the unit.
4 – Units require support along all four sides of unit base. Supports must be
constructed of steel or suitably treated wood materials.
Duct Connection
All exterior ducts, joints and openings in roof or building walls must be
insulated and weather-proofed with flashing and sealing compounds in
accordance with applicable codes. Any duct passing through an unconditioned
space must be insulated.
CAUTION
In downflow applications, do not drill or punch holes in base of unit. Leaking
in roof may occur if unit base is punctured.
Rigging Unit for Lifting
Rig unit for lifting by attaching four cables to holes in unit base rail. See
FIGURE 2.
1 – Detach wooden base protection before rigging. NOTE – Remove all 7 (5
brackets on units with three outdoor fans) base protection brackets before
setting unit.
2 – Connect rigging to the unit base using both holes in each corner.
3 – All panels must be in place for rigging.
4 – Place field-provided H-style pick in place just above top edge of unit.
Frame must be of adequate strength and length. (H-style pick prevents damage
to unit.)
Condensate Drains
Make drain connection to the 1″ N.P.T. drain coupling provided on unit.
NOTE – The drain pan is made with a glass reinforced engineered plastic
capable of withstanding typical joint torque but can be damaged with excessive
force. Tighten pipe nipple hand tight and turn an additional quarter turn.
A trap must be installed between drain connection and an open vent for proper condensate removal. See FIGURE 3 or FIGURE 4. It is sometimes acceptable to drain condensate onto the roof or grade; however, a tee should be fitted to the trap to direct condensate downward. The condensate line must be vented. Check local codes concerning condensate disposal. Refer to page 1 and page 2 for condensate drain location.
RIGGING
Unit
*Weight
Lbs.
Kg.
LGM LCM
1401
636
1366
620
*Maximum weight with all available factory-installed accessories.
CAUTION – Do not walk on unit.
IMPORTANT – ALL PANELS MUST BE IN PLACE FOR RIGGING.
LIFTING POINT SHOULD BE DIRECTLY ABOVE CENTER OF GRAVITY
FIGURE 2
CONDENSATE SIDE DRAIN CONNECTION
CAULK AROUND CONDENSATE COUPLING
NOTE – Allow clearance to open doors when installing condensate piping.
Minimum Pitch 1″ (25 mm) per 10′ (3 m) of line
OPEN VENT
UNIT
FIGURE 3
MOUNTING FRAME
Page 6
CONDENSATE BOTTOM DRAIN CONNECTION
UNIT
DRAIN PAN CAULK AROUND CONDENSATE COUPLING
OPEN VENT
MOUNTING FRAME
Minimum Pitch 1″ (25 mm) per 10′
(3 m) of line
FIGURE 4
Units are shipped with the drain coupling facing the front of the unit.
Condensate can be drained from the back or bottom of the unit with the
following modifications. The unit can be installed in either downflow or
horizontal air discharge regardless of condensate drain location.
Rear Drain Connection
1 – Open blower and heat access doors. See FIGURE 5.
FILTER ACCESS DOOR
BLOWER ACCESS DOOR
2 – Remove six screws from filter access door. Refer to FIGURE 6.
UNITS WITH HINGED PANELS
FILTER DOOR
CONDENSATE DRAIN MULLION
REMOVE THREE SCREWS (PER HINGE)
FIGURE 6 3 – Open filter access door hinges and carefully remove
door. 4 – Remove eight screws holding condensate drain
mullion and remove mullion. 5 – Lift front edge of the drain pan (to clear
bottom drain
plug) and slide drain pan out of unit. See FIGURE 7.
HEAT ACCESS DOOR CONDENSATE DRAIN MULLION
FIGURE 5
DRAIN PAN
FIGURE 7 6 – Make sure the cap over the unit bottom drain hole
is secure. 7 – Rotate the drain pan until the downward slope is
toward the back of the unit. Slide the drain pan back into the unit. Be
careful not to dislodge the cap over the bottom drain hole. 8 – From the back
side of the unit, pull the drain pan coupling through the rear condensate
opening. 9 – Replace the condensate drain mullion and reinstall eight screws.
10 – Reinstall filter door on hinges.
Page 7
Bottom Drain Connection
1 – Open blower and heat access doors. See FIGURE 5.
2 – Remove six screws from filter access door. Refer to FIGURE 6.
3 – Open filter access door hinges and carefully remove door.
4 – Remove eight screws holding condensate drain mullion and remove mullion.
5 – Lift front edge of the drain pan (to clear bottom drain plug) and slide
drain pan out of unit. See FIGURE 7.
6 – Turn the drain pan upside down and drill a pilot hole through the bottom
of the drain pan in the center of the coupling. See FIGURE 8.
BOTTOM CONDENSATE DRAIN
CAUTION: Be careful not to damage the coupling threads
when drilling the hole.
DRILL A PILOT HOLE IN CENTER
OF COUPLING
Connect Gas Piping (Gas Units)
Before connecting piping, check with gas company or authorities having
jurisdiction for local code requirements. When installing gas supply piping,
length of run from gas meter must be considered in determining pipe size for
0.5″ w.c. (.12kPa) maximum pressure drop. Do not use supply pipe smaller than
unit gas connection. For natural gas units, operating pressure at the unit gas
connection must be a minimum of 4.7″ w.c. (1.17kPa) and a maximum of 10.5″
(2.60kPa) w.c. For LP/propane gas units, operating pressure at the unit gas
connection must be a minimum of 10.5″ w.c. (2.61kPa) and a maximum of 13.0″
w.c. (3.23kPa).
When making piping connections a drip leg should be installed on vertical pipe
runs to serve as a trap for sediment or condensate. A 1/8″ N.P.T. plugged tap
is located on gas valve for test gauge connection. Refer to Heating Start-Up
section for tap location. Install a ground joint union between the gas control
manifold and the main manual shut-off valve. See FIGURE 9 for gas supply
piping entering outside the unit. FIGURE 10 shows bottom gas entry piping
through the curb. FIGURE 11 shows bottom gas entry piping through the unit.
Compounds used on threaded joints of gas piping shall be resistant to the
action of liquefied petroleum gases.
OUTSIDE OF UNIT GAS PIPE CONNECTION
After drilling the pilot hole, drill a 7/8″ hole from
the inside of the pan.
FIGURE 8
7 – From the inside of the pan, use a Vari-Bit® bit to enlarge the hole to
7/8″. Do not damage coupling threads.
8 – Remove the cap over the unit bottom drain hole.
9 – Slide the drain pan back into the unit.
10 – From the back side of the unit, pull the drain pan coupling through the
rear condensate opening.
11 – From the front side of the unit, move the drain pan until the bottom
coupling settles into the unit bottom drain opening. Once in place, check to
make sure the coupling is still positioned through the rear condensate drain
hole.
12 – Use a field-provided 1″ plug to seal side drain connection.
13 – Replace the condensate drain mullion and reinstall eight screws.
14 – Reinstall filter door on hinges.
GROUND JOINT UNION
TO GAS SUPPLY
TO GAS VALVE
GAS PIPING SUPPORT
MANUAL MAIN SHUT-OFF VALVE
DRIP LEG
(REFER TO LOCAL CODES)
FIGURE 9
Page 8
BOTTOM ENTRY GAS PIPING THROUGH THE CURB
MULLION BETWEEN
SOR SECTIONS
4″ NIPPLE
4″ NIPPLE
TO GAS VALVE
GROMMET ALL ELBOWS ARE 3/4″
MANUAL MAIN SHUT-OFF VALVE
5″ NIPPLE
7-1/2″ NIPPLE GROUND JOINT UNION
4″ NIPPLE
TO GAS SUPPLY
10″ NIPPLE ROOF MOUNTING FRAME
FIGURE 10
3-1/2″ NIPPLE
3″ NIPPLE DRIP LEG
BOTTOM GAS ENTRY THROUGH THE UNIT
ALL ELBOWS ARE 3/4″
MULLION BETWEEN
10″ NIPPLE GROMMET
GROMMET 7-1/2″ NIPPLE
SOR SECTIONS 5″ NIPPLE
4″ NIPPLE
4″ NIPPLE
TO GAS VALVE
7″ NIPPLE
TO GAS SUPPLY
GROUND JOINT UNION
ALTERNATE KNOCKOUTS
ROOF MOUNTING FRAME
DRIP LEG
4″ NIPPLE MANUAL MAIN SHUT-OFF VALVE
3-1/2″ NIPPLE
3″ NIPPLE
Pressure Test Gas Piping (Gas Units)
When pressure testing gas lines, the gas valve must be disconnected and
isolated. Gas valves can be damaged if subjected to more than 0.5 psig
(3.48kPa). See FIGURE 12. NOTE – Codes may require that manual main shut-off
valve and union (furnished by installer) be installed in gas line external to
unit. Union must be of the ground joint type. After all connections have been
made, check all piping connections for gas leaks. Also check existing unit gas
connections up to the gas valve; loosening may occur during installation. Use
a leak detection solution or other preferred means. Do not use matches candles
or other sources of ignition to check for gas leaks. NOTE – In case emergency
shut down is required, turn off the main manual shut-off valve and disconnect
main power to unit. These devices should be properly labeled by the installer.
PRESSURE TEST GAS LINE
MANUAL MAIN SHUT-OFF VALVE
GAS VALVE
CAP
FIGURE 12
CAUTION
Some soaps used for leak detection are corrosive to certain metals. Carefully
rinse piping thoroughly after leak test has been completed. Do not use
matches, candles, flame or other sources of ignition to check for gas leaks.
WARNING
Danger of explosion. Can cause injury or product or property damage. Do not
use matches, candles, flame or other sources of ignition to check for leaks.
FIGURE 11
Page 9
High Altitude Derate
Locate the high altitude conversion sticker in the unit literature bag. Fill
out the conversion sticker and affix next to the unit nameplate. High altitude
kits are available for field-installation.
Refer to TABLE 2 for high altitude adjustments.
TABLE 2 HIGH ALTITUDE DERATE
Altitude Ft.*
Gas Manifold Pressure
2000-4500
See Unit Nameplate
4500 and Above
Derate 4% / 1000 Ft. above Sea Leavel
*Units installed at 0-2000 feet do not need to be modified.
NOTE – This is the only permissible derate for these units.
Download Mobile Service App
A-Mobile Device Requirements
· Android hardware requires 2GB RAM and a 2Ghz core processor. Tablets are
supported.
· Minimum Android 6.0 (Marshmallow) or higher. Recommend Android 10 and Apple
products require iOS version 11 or higher.
B-New Installations
Once the app is downloaded, refer to the Setup Guide provided with this unit
to pair the app to the unit control system. Follow the setup wizard prompts to
configure the unit. See FIGURE 13 for the app menu overview. If a mobile
device is unavailable or not pairing, refer to the Unit Controller Setup Guide
for start-up instructions.
Electrical Connections – Power Supply
Route field wiring in conduit between bottom power entry disconnect. See
FIGURE 14. This does not supersede local codes or authorities having
jurisdiction.
Do not apply power or close disconnect switch until installation is complete.
Refer to start-up directions. Refer closely to unit wiring diagram.
Refer to unit nameplate for minimum circuit ampacity and maximum fuse size.
1 – 230/460/575 volt units are factory wired. For 208V supply, disconnect the
orange wire (230V) at all control power transformer(s). Reconnect the red wire
(208V). Tape the exposed end of the 230V orange wire.
2 – Route power through the bottom power entry area. On gas units or units
with electric heat, connect power wiring to TB2. On cooling only units,
connect power to F4. If unit contains an optional factoryinstalled circuit
breaker or disconnect switch, connect line voltage to CB10 or S48. See unit
wiring diagram.
3 – Connect separate 120v wiring to optional GFCI outlet. Route field wiring
in conduit between bottom power entry and GFCI. See FIGURE 14.
MOBILE SERVICE APP MENU OVERVIEW
MENU
RTU MENU
SETUP
INSTALL
NETWORK INTEGRATION
TEST AND BALANCE
ALARM HISTORY DATA TRENDING
FACTORY RUNTIMES
SYSTEM DATA / SENSORS / OUTPUTS
SERVICE
COMPONENT TEST
REPORT
ADVANCED CONTROL FIRMWARE UPDATE
SETTINGS
FIGURE 13
RTU OPTION INSTALL
FIELD WIRE ROUTING
SIDE ENTRY KNOCKOUTS
MAKE-UP BOX
OPTIONAL 120V GFI
SEAL WATERTIGHT
RUN FIELD WIRING IN
VIDED CONDUIT
BOTTOM POWER ENTRY
FIGURE 14
Page 10
Electrical Connections – Control Wiring
NOTE – Optional wireless sensors are available for use with this unit. Refer
to the instructions provided with each sensor.
CAUTION
Electrostatic discharge can affect electronic components. Take precautions
during unit installation and service to protect the electronic controls.
Precautions will help to avoid control exposure to electrostatic discharge by
putting the unit, the control and the technician at the same electrostatic
potential. Neutralize electrostatic charge by touching hands and all tools on
an unpainted unit surface, such as the gas valve or blower deck, before
performing any service procedure.
A-Thermostat Location
Applied to units in default thermostat control mode only.
Room thermostat mounts vertically on a standard 2″ X 4″ handy box or on any
non-conductive flat surface. Locate thermostat approximately 5 feet (1524mm)
above the floor in an area with good air circulation at average temperature.
Avoid locating the room thermostat where it might be affected by:
· drafts or dead spots behind doors and in corners · hot or cold air from
ducts · radiant heat from sun or appliances · concealed pipes and chimneys
B-Control Wiring
The Unit Controller will operate the unit from a thermostat or zone sensor
based on the System Mode. The default System Mode is the thermostat mode.
Refer to the Unit Controller Setup Guide to change the System Mode. Use the
mobile service app menu and select Settings > Install.
Thermostat Mode
1 – Route thermostat cable or wires from subbase to control area above
compressor (refer to unit dimensions to locate bottom and side power entry).
IMPORTANT – Unless field thermostat wires are rated for maximum unit voltage,
they must be routed away from line voltage wiring. Use wire ties located near
the lower left corner of the controls mounting panel to secure thermostat
cable.
Use18 AWG wire for all applications using remotely installed electro-
mechanical and electronic thermostats. 2 – Install thermostat assembly in
accordance with instructions provided with thermostat.
3 – Connect thermostat wiring to Unit Controller on the lower side of the
controls hat section.
4 – Wire as shown in FIGURE 15 for electromechanical and electronic
thermostats. If using other temperature control devices or energy management
systems see instructions and wiring diagram provided by manufacturer.
IMPORTANT – Terminal connections at the Unit Controller must be made securely.
Loose control wire connections may allow unit to operate but not with proper
response to room demand.
Zone Sensor Mode
The Unit Controller will operate heating and cooling based on the Unit
Controller internal setpoints and the temperature from the A2 room sensor. An
optional Network Control Panel (NCP) can also be used to provide setpoints. A
thermostat or return air sensor can be used as a back-up mode. Make room
sensor wiring connections as shown in FIGURE 16.
C-Hot Gas Reheat Units Only
1 – Install humidity sensor in accordance with instructions provided with
sensor. A DDC input may be used to initiate dehumidification instead of a
sensor.
2 – Make wiring connections as shown in FIGURE 15 for Thermostat Mode or
FIGURE 16 for Zone Sensor Mode. In addition, connect either a humidity sensor
or a dehumidification input. See FIGURE 18 or FIGURE 19 for humidity sensor
wiring or FIGURE 17 for dehumidification input wiring.
24 VOLT FIELD WIRING IN THERMOSTAT MODE
P262 J262C
24 V POWER
J297A P297
R
1
A55
10
C
2
B
11
G
3
W1
4
W1
W2
5
W2
12
Y1
6
Y2
7
OCP
8
C
9
10
D
FIGURE 15
Page 11
FIELD WIRING IN ZONE SENSOR MODE (Zone Sensor Mode)
UNIT CONTROLLER
24VAC SENSOR SENSOR IAQ
INPUTS
R C AI1
HUM TMP AI2 C R
J298
A2 SENSOR
FIGURE 16
FIELD WIRING HOT GAS REHEAT UNITS (Using A Dehumidification Switch)
J299
7
R
DEHUMIDIFICATION SWITCH
8
DI-4
9
C
10
Use 24 VAC (R) from any terminal available on J299-2, -5, or -7.
FIGURE 17
Humidity Sensor Cable Applications:
Wire runs of 50 feet (mm) or less:
Use two separate shielded cables containing 20AWG minimum, twisted pair
conductors with overall shield. Belden type 8762 or 88760 (plenum) or
equivalent. Connect both cable shield drain wires to the Unit Controller as
shown in FIGURE 18.
Wire runs of 150 feet (mm) or less:
Use two separate shielded cables containing 18AWG minimum, twisted pair
conductors with overall shield. Belden type 8760 or 88760 (plenum) or
equivalent. Connect both cable shield drain wires to the Unit Controller as
shown in FIGURE 18.
Wire runs over 150 feet (mm)
Use a local, isolated 24VAC transformer such as Lennox cat #18M13 (20VA
minimum) to supply power to RH sensor as shown in figure 19. Use two shielded
cables containing 20AWG minimum, twisted pair conductors with overall shield.
Belden type 8762 or 88760 (plenum) or equivalent.
FIELD WIRING HOT GAS REHEAT UNITS (Using A
Humidity Sensor With Less Than 150 Ft. Wire
NOT CONNECTED
Runs) J298A 1
A55 UNIT CONTROLLER
P298 R
A91 VIN
2
C
B
3
AI1
4
C
5
HUM
GND
DRAIN
VO
6
7
TMP
D
8
AI2
9
C
10
R
NOT
UNUSED
FIGURE 18
FIELD WIRING HOT GAS REHEAT UNITS (Using
A Humidity Sensor With More than 150Ft. Wire
NOT
Runs)
CONNECTED ISOLATED 24V
TRANSFORMER
A55 UNIT
CONTROLLER
J298A 1 P298 R
A91
DRAIN
2
B
VIN
NOT
3
CONNECTED
4 C
5
C AI1
HUM
GND VO
6
7
TMP
D
8
AI2
9
C
10
R
FIGURE 19
Page 12
Blower Operation
Units are equipped with variable speed, direct drive blowers. The installer is
able to enter the design-specified supply air CFM into the Unit Controller for
optimal efficiency. The Unit Controller calibrates the supply air volume which
eliminates the need to manually take duct static measurements. Refer to
C-Adjusting Unit CFM Ultra High Efficiency Direct Drive Blowers.
IMPORTANT
Compressor two is the only component that must be checked to ensure proper
phasing. Follow “COOLING START-UP” section of installation instructions to en
sure proper compressor and blower operation.
The Unit Controller checks the incoming power during start-up. If the voltage
or phase is incorrect, the Unit Controller will display an alarm and the unit
will not start.
A-Blower Operation
Refer to the Unit Controller Setup Guide to energize blower. Use the mobile
service app menu; see SERVICE > TEST.
In thermostat control mode, the Unit Controller will stage the blower between
low and high speed. In zone sensor control mode, the Unit Controller will vary
(VAV) the blower between low and high speed.
WARNING
1- Make sure that unit is installed in accordance with the installation
instructions and applicable codes.
2- Inspect all electrical wiring, both field and factoryinstalled, for loose
connections. Tighten as required.
3- Check to ensure that refrigerant lines do not rub against the cabinet or
against other refrigerant lines.
4- Check voltage at disconnect switch. Voltage must be within range listed on
nameplate. If not, consult power company and have voltage condition corrected
before starting unit.
5- Make sure filters are new and in place before start-up.
Initiate blower only (G) demand at thermostat according to instructions
provided with thermostat. Unit will cycle on thermostat demand. The following
steps apply to applications using a typical electro-mechanical thermostat.
1 – Blower operation is manually set at the thermostat subbase fan switch.
With fan switch in ON position, blowers will operate continuously.
2 – With fan switch in AUTO position, the blowers will cycle with demand.
Blowers and entire unit will be off when system switch is in OFF position.
NOTE – Blower operation mode can also be initiated by the mobile service app.
Direct-drive motor may not immediately stop when power is interrupted to the
Unit Controller. Disconnect unit power before opening the blower compartment.
The Controller’s digital inputs must be used to shut down the blower. See Unit
Controller manual for operation sequences.
B-Blower Access
The blower assembly is secured to a sliding frame which allows the blower
assembly to be pulled out of the unit. See FIGURE 21.
1 – Loosen the reusable wire tie which secures the controls and high voltage
blower wiring to the blower housing. Disconnect the pressure sensor low
voltage wire harness.
2 – Remove and retain screws on either side (and on the front for direct
drive) of sliding frame. Use the metal handle to pull frame toward outside of
unit.
3 – Slide frame back into original position when finished servicing. Reattach
the blower wiring in the previous location using the wire tie. Reconnect
pressure sensor low voltage wire harness.
4 – Replace retained screws.
Page 13
LOCATION OF STATIC PRESSURE READINGS
INSTALLATIONS WITH DUCTWORK
INSTALLATIONS WITH CEILING DIFFUSERS
ROOFTOP UNIT
ROOFTOP UNIT
RETURN AIR READING LOCATION
SUPPLY TURN
MAIN DUCT RUN
FIRST BRANCH OFF OF MAIN RUN
SUPPLY AIR READING LOCATION
SUPPLY AIR READING LOCATION
FIGURE 20
DIRECT DRIVE BLOWER ASSEMBLY
SUPPLY TURN
DIFFUSER
BLOWER HOUSING
RETURN AIR READING LOCATION
BLOWER MOTOR SECURED TO THIS SIDE OF HOUSING
REMOVE TWO SCREWS ON EACH SIDE TO SLIDE
BLOWER OUT OF UNIT
INLET GRID
FIGURE 21
Page 14
Direct Drive Blower Start-Up
The supply CFM can be adjusted by changing Unit Controller settings. Refer to
TABLE 3 for menu paths and default settings. Record any CFM changes on the
parameter settings label located on the inside of the compressor access panel.
IMPORTANT
The BLOWER CALIBRATION process starts the in door blower at operational speeds
and moves the economizer damper blades. Before starting this process, replace
any access panels and close all unit doors except compressor compartment door.
Blower calibration is required only on units that are newly installed or if
there is a change in the duct work or air filters after installation. Use the
mobile service app to navigate to the SETUP>TEST & BALANCE>BLOWER menu.
After the new CFM values are entered, select START CALIBRATION. The blower
calibration status is displayed as a % complete. Upon successful completion,
the mobile service app will display CALIBRATION SUCCESS and go back to the
blower calibration screen.
IMPORTANT – The default value for Cooling Low CFM is lower than a traditional
singe- or two-speed unit. If operating the unit with a 2- or 3-stage
controller (2- or 3-stage thermostat, DDC controller, etc.), it is recommended
to increase the Cooling Low CFM default value to a suitable level for part
load cooling (typically 60% of full load CFM).
TABLE 3 DIRECT DRIVE PARAMETER SETTINGS
Parameter
Factory Setting 092 102 120 150
Field Setting
Description
NOTE – Any changes to Smoke CFM setting must be adjusted before the other CFM settings. Use SETTINGS > RTU OPTIONS > EDIT PARAMETERS = 12
BLOWER SMOKE CFM
3000 3400 4000 5000
CFM Smoke blower speed
SETUP > TEST & BALANCE > BLOWER
BLOWER HEATING HIGH CFM BLOWER COOLING HIGH CFM
3000 2625
3400 2975
4000 3500
5000 4375
CFM Heating blower speed CFM High cooling blower speed
BLOWER COOLING LOW CFM BLOWER VENTILATION CFM
800 800 875 1100 800 800 875 1100
CFM Low cooling blowr speed CFM Ventilation blower speed
SETUP > TEST & BALANCE > DAMPER BLOWER HIGH CFM DAMPER POS % 0% 0% 0% 0%
% Minimum damper position for high speed blower operation.
BLOWER LOW CFM DAMPER POS % 0% 0% 0% 0%
% Minimum damper position for low speed operation.
BLOWER EXHAUST DAMPER POS % 50% 50% 50% SETTINGS > RTU OPTIONS > EDIT PARAMETERS = 216
50%
% Minimum damper position for power exhaust operation.
POWER EXHAUST DEADBAND %
10% 10% 10% 10%
% Deadband % for power exhaust operation.
SETTINGS > RTU OPTIONS > EDIT PARAMETER = 10 (Applies to Thermostat Mode ONLY)
FREE COOLING STAGE-UP DELAY
300 300 300 300 sec, sec. sec. sec.
sec
Number of seconds to hold indoor blower at low speed before switching to indoor blower at high speed.
Installer – Circle applicable unit model number and record any parameter changes under “Field Setting” column. Settings need to be recorded by installer for use when Unit Controller is replaced or reprogrammed.
Page 15
BLOWER DATA
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY (NO HEAT SECTION) WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 – Wet indoor coil air resistance of selected unit. 2 – Any factory installed
options air resistance (heat section, Economizer, etc.) 3 – Any field
installed accessories air resistance (duct resistance, diffuser, etc.) See
page 17 for wet coil and option/accessory air resistance data. See page 17 for
minimum air volume required for use with optional electric heat.
Maximum Static Pressure With Gas Heat – 2.0 in. w.g.
Minimum Air Volume Required For Different Gas Heat Sizes: Standard – 2150 cfm;
Medium – 2250 cfm; High – 2600 cfm
Total Air Volume
cfm
0.2 RPM Watts
0.4 RPM Watts
Total Static Pressure – in. w.g.
0.6
0.8
1.0
RPM Watts RPM Watts RPM Watts
1.2 RPM Watts
1.4 RPM Watts
1750
759 223 864 298 961 359 1049 420 1128 508 1199 607 1260 704
2000
846 271 943 345 1035 410 1117 488 1189 598 1255 704 1313 804
2250
945 303 1030 391 1111 476 1184 577 1247 697 1310 806 1367 905
2500
1035 366 1109 476 1180 583 1245 688 1306 797 1368 903 1426 1008
2750
1113 476 1182 601 1248 715 1310 809 1371 902 1432 1011 1491 1129
3000
1195 596 1261 718 1324 827 1385 922 1444 1024 1503 1146 1559 1279
3250
1282 711 1346 827 1406 935 1464 1044 1521 1167 1576 1306 1629 1460
3500
1372 821 1432 940 1489 1060 1544 1192 1598 1337 1650 1494 1700 1663
3750
1461 949 1517 1081 1571 1221 1624 1373 1675 1532 1725 1700 1773 1875
4000
1549 1109 1602 1256 1653 1413 1703 1576 1753 1743 1801 1916 1847 2091
4250
1637 1298 1687 1458 1735 1625 1784 1795 1831 1966 1877 2139 1923 2310
4500
1724 1510 1772 1678 1818 1851 1864 2023 1910 2195 1955 2365 2000 2530
4750
1811 1738 1856 1910 1901 2083 1946 2254 1990 2423 2034 2587 2079 2746
5000
1897 1973 1941 2144 1985 2314 2028 2480 2071 2644 2114 2805 2158 2959
5250
1983 2205 2026 2373 2069 2538 2111 2699 2153 2860 2195 3017 – – – – – –
5500
2070 2428 2112 2595 2153 2756 2194 2912 – – – – – – – – – – – – – – – – – –
5750
2156 2643 2197 2809 – – – – – – – – – – – – – – – – – – – – – – – – – – – – – –
Total Air Volume
cfm
1.6 RPM Watts
1.8 RPM Watts
Total Static Pressure – in. w.g.
2.0
2.2
2.4
RPM Watts RPM Watts RPM Watts
2.6 RPM Watts
1750
1316 793 1373 875 1432 963 1491 1064 1548 1175 1604 1300
2000
1368 894 1425 982 1483 1081 1540 1196 1596 1322 1650 1458
2250
1423 1001 1480 1101 1537 1216 1593 1344 1647 1483 1700 1629
2500
1483 1117 1539 1236 1594 1368 1648 1509 1700 1657 1752 1810
2750
1547 1256 1601 1394 1654 1539 1705 1690 1756 1846 1806 2004
3000
1612 1425 1664 1577 1715 1734 1765 1893 1815 2053 1864 2213
3250
1680 1623 1729 1787 1778 1949 1828 2110 1876 2269 1925 2426
3500
1748 1835 1796 2003 1844 2165 1893 2324 1942 2479 1991 2633
3750
1819 2048 1866 2214 1914 2374 1963 2530 2012 2684 2061 2837
4000
1893 2260 1940 2423 1988 2581 2036 2737 2084 2891 2134 3044
4250
1969 2475 2016 2634 2063 2790 2111 2945 2159 3098 – – – – – –
4500
2046 2689 2093 2844 2140 2998 2187 3153 – – – – – – – – – – – –
4750
2124 2900 2170 3053 – – – – – – – – – – – – – – – – – – – – – – – –
5000
2203 3111 – – – – – – – – – – – – – – – – – – – – – – – – – – – – – –
5250
— — — — — — — — — — — —
5500
— — — — — — — — — — — —
Page 16
BLOWER DATA
POWER EXHAUST FAN PERFORMANCE Return Air System Static Pressure in. w.g. 0 0.05 0.10 0.15 0.20 0.25 0.30 0.35
Air Volume Exhausted cfm 3175 2955 2685 2410 2165 1920 1420 1200
MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT
Electric Heat kW
Minimum cfm
7.5
1750
15
2750
22.5
2750
30
2750
45
2750
60
3500
FACTORY INSTALLED OPTIONS/FIELD INSTALLED ACCESSORY AIR RESISTANCE – in. w.g.
Air
Wet Indoor Coil
Gas Heat Exchanger
Volume
Standard Medium High
cfm 092, 102 120, 150 Heat
Heat Heat
Electric Heat
Econo mizer
Condensor Reheat Coil
1750 0.04 0.04
0.06
0.02
0.02
0.03
0.05
0.02
2000 0.05 0.05
0.07
0.05
0.06
0.03
0.06
0.02
2250 0.06 0.06
0.07
0.07
0.08
0.04
0.08
0.02
2500 0.07 0.07
0.09
0.10
0.11
0.04
0.11
0.03
2750 0.08 0.08
0.09
0.11
0.12
0.05
0.12
0.03
3000 0.10 0.09
0.11
0.12
0.13
0.06
0.13
0.03
3250 0.11 0.10
0.12
0.15
0.16
0.06
0.15
0.04
3500 0.12 0.11
0.12
0.16
0.17
0.09
0.15
0.04
3750 0.14 0.13
0.14
0.19
0.20
0.09
0.15
0.05
4000 0.15 0.14
0.14
0.21
0.22
0.09
0.19
0.05
4250 0.17 0.15
0.14
0.24
0.28
0.13
0.19
0.06
4500 0.19 0.17
0.15
0.26
0.32
0.14
0.22
0.07
4750 0.20 0.18
0.16
0.29
0.37
0.17
0.25
0.07
5000 0.22 0.20
0.16
0.34
0.43
0.20
0.29
0.08
5250 0.24 0.22
0.16
0.37
0.47
0.22
0.32
0.08
5500 0.25 0.23
0.18
0.44
0.54
0.25
0.34
0.09
5750 0.27 0.25
0.19
0.49
0.59
0.31
0.45
0.10
6000 0.29 0.27
0.20
0.54
0.64
0.33
0.52
0.10
MERV 8
0.01 0.01 0.01 0.01 0.02 0.02 0.02 0.03 0.03 0.04 0.04 0.04 0.05 0.06 0.06
0.07 0.07 0.08
Filters MERV 13 MERV 16
0.03
0.05
0.03
0.06
0.04
0.07
0.05
0.08
0.05
0.09
0.06
0.10
0.06
0.11
0.07
0.12
0.08
0.13
0.08
0.14
0.09
0.15
0.09
0.17
0.10
0.18
0.10
0.19
0.11
0.20
0.12
0.22
0.12
0.23
0.13
0.24
Return Air
Adaptor Plate 0.00 0.00 0.00 0.00 0.00 0.02 0.02 0.04 0.07 0.09 0.11 0.12 0.16
0.18 0.19 0.22 0.25 0.27
Page 17
Cooling Start-Up
IMPORTANT – The crankcase heater must be energized for 24 hours before
attempting to start compressor. Set thermostat so there is no demand to
prevent compressors from cycling. Apply power to unit. A-Start-Up
1 – Initiate full load cooling operation using the following mobile service
app menu path:
RTU MENU > SERVICE > COMPONENT TEST > COOLING > COOL 4
2 – Refer to Cooling Operation section for cooling startup.
3 – Units have two refrigerant circuits. See FIGURE 22.
4 – Each refrigerant circuit is charged with R410A refrigerant. See unit
rating plate for correct amount of charge.
5 – Refer to Refrigerant Check and Charge section for proper method to check
refrigerant charge.
B-R410A Refrigerant
Units charged with R410A refrigerant operate at much higher pressures than
R22. The expansion valve and liquid line drier provided with the unit are
approved for use with R410A. Do not replace them with components designed for
use with R22.
R410A refrigerant is stored in a pink cylinder.
Manifold gauge sets used with systems charged with R410A refrigerant must be
capable of handling the higher system operating pressures. The gauges should
be rated for use with pressures of 0-800 on the high side and a low side of
30″ vacuum to 250 psi with dampened speed to 500 psi. Gauge hoses must be
rated for use at up to 800 psi of pressure with a 4000 psi burst rating.
IMPORTANT
Mineral oils are not compatible with R410A. If oil must be added, it must be a
polyol ester oil.
C-Refrigerant Charge and Check
WARNING-Do not exceed nameplate charge under any condition.
This unit is factory charged and should require no further adjustment. If the
system requires additional refrigerant, reclaim the charge, evacuate the
system, and add required nameplate charge.
NOTE – System charging is not recommended below 60°F (15°C). In temperatures
below 60°F (15°C) , the charge must be weighed into the system.
If weighing facilities are not available, or to check the charge, use the
following procedure:
REFRIGERANT STAGES TRADITIONAL FIN/TUBE COIL
CONDENSER COIL STAGES 1 & 2
(BOTH FANS ARE ENERGIZED WITH A Y1 DEMAND)
EVAPORATOR COIL STAGE 2
B4 B5
2
1
EVAPORATOR COIL STAGE 1
FIGURE 22
1 – Attach gauge manifolds to discharge and suction lines. With the economizer disabled, operate the unit in cooling mode at high speed using the following mobile service app menu path:
SERVICE > COMPONENT TEST > COOLING > COOL 4
2 – Use a thermometer to accurately measure the outdoor ambient temperature.
3 – Apply the outdoor temperature to TABLE 4 through 11 to determine normal
operating pressures. Pressures are listed for sea level applications at 80°F
dry bulb and 67°F wet bulb return air.
4 – Compare the normal operating pressures to the pressures obtained from the
gauges. Minor variations in these pressures may be expected due to differences
in installations. Significant differences could mean that the system is not
properly charged or that a problem exists with some component in the system.
Correct any system problems before proceeding.
5 – If discharge pressure is high, remove refrigerant from the system. If
discharge pressure is low, add refrigerant to the system.
· Add or remove charge in increments. · Allow the system to stabilize each
time refrigerant is
added or removed. 6 – Use the following subcooling method along with the
normal operating pressures to confirm readings.
Page 18
Outdoor Coil
Entering Air Temp
65° F
75° F
85° F
95° F
105° F
115° F
TABLE 4 581027-01 LGM/LCM092U No Reheat
CIRCUIT 1
CIRCUIT 2
Discharge Suction + Discharge Suction +
+ 10 psig
5 psig
+ 10 psig
5 psig
252
140
269
137
293
143
311
139
335
146
354
142
382
148
403
144
434
150
454
147
490
153
508
150
Outdoor Coil
Entering Air Temp
65° F
75° F
85° F
95° F
105° F
115° F
TABLE 5 581028-01 LGM/LCM092U Reheat
CIRCUIT 1
CIRCUIT 2
Discharge Suction + Discharge Suction +
+ 10 psig
5 psig
+ 10 psig
5 psig
258
140
269
136
301
139
308
137
344
141
349
139
392
143
398
142
445
145
447
144
504
148
501
147
Outdoor Coil
Entering Air Temp
65° F
75° F
85° F
95° F
105° F
115° F
TABLE 6 581029-01 LGM/LCM102U No Reheat
CIRCUIT 1
CIRCUIT 2
Discharge Suction + Discharge Suction +
+ 10 psig
5 psig
+ 10 psig
5 psig
256
140
259
139
294
143
300
141
333
147
341
143
381
149
388
146
433
151
438
149
487
155
491
153
Outdoor Coil
Entering Air Temp
65° F
75° F
85° F
95° F
105° F
115° F
TABLE 7 581030-01 LGM/LCM102U Reheat
CIRCUIT 1
CIRCUIT 2
Discharge Suction + Discharge Suction +
+ 10 psig
5 psig
+ 10 psig
5 psig
264
140
266
137
301
139
300
139
349
141
341
141
399
144
390
144
450
146
440
147
508
149
494
150
Outdoor Coil
Entering Air Temp
65° F
75° F
85° F
95° F
105° F
115° F
TABLE 8 581031-01 LGM/LCM120U No Reheat
CIRCUIT 1
CIRCUIT 2
Discharge Suction + Discharge Suction +
+ 10 psig
5 psig
+ 10 psig
5 psig
258
132
263
131
296
137
302
133
337
139
344
135
383
141
389
137
439
142
438
140
490
145
494
143
Outdoor Coil
Entering Air Temp
65° F
75° F
85° F
95° F
105° F
115° F
TABLE 9 581032-01 LGM/LCM120U Reheat
CIRCUIT 1
CIRCUIT 2
Discharge Suction + Discharge Suction +
+ 10 psig
5 psig
+ 10 psig
5 psig
272
131
255
133
309
135
294
135
350
138
335
137
396
139
381
139
452
141
430
142
503
144
485
145
Outdoor Coil
Entering Air Temp
65° F
75° F
85° F
95° F
105° F
115° F
TABLE 10 581033-01 LGM/LCM150U No Reheat
CIRCUIT 1
CIRCUIT 2
Discharge Suction + Discharge Suction +
+ 10 psig
5 psig
+ 10 psig
5 psig
267
122
270
113
308
128
313
120
355
133
363
127
399
136
407
130
448
139
456
132
503
142
510
136
Outdoor Coil
Entering Air Temp
65° F
75° F
85° F
95° F
105° F
115° F
TABLE 11 581034-01 LGM/LCM150U Reheat
CIRCUIT 1
CIRCUIT 2
Discharge Suction + Discharge Suction +
+ 10 psig
5 psig
+ 10 psig
5 psig
313
123
259
113
353
129
302
121
401
134
351
127
445
137
396
130
493
140
445
133
548
143
499
137
Page 19
Charge Verification – Subcooling Method – AHRI Testing
1 – Attach gauge manifolds to discharge and suction lines. With the economizer
disabled, operate the unit in cooling mode at high speed using the following
mobile service app menu path:
RTU MENU > SERVICE > COMPONENT TEST > COOLING > COOL 4
2 – Use the liquid line pressure and a PT chart to determine the saturated
liquid temperature.
3 – Measure the liquid line temperature at the condenser outlet.
Subcooling Temperature = Liquid Saturated Temperature Minus Liquid Temperature
4 – Refer to TABLE 12 for subcooling temperatures. A subcooling temperature
greater than this value indicates an overcharge. A subcooling temperature less
than this value indicates an undercharge.
TABLE 12 SUBCOOLING TEMPERATURE
Liquid Temp. Minus Ambient Temp.
Unit
1st Stage
2nd Stage
092
12°F + 1 (6.7°C + 0.5) 15°F + 1 (8.3°C + 0.5)
092 Reheat 17°F + 1 (9.4°C + 0.5) 15°F + 1 (8.3°C + 0.5)
102
11°F + 1 (6.1°C + 0.5) 14°F + 1 (7.7°C + 0.5)
102 Reheat 19°F + 1 (6.7°C + 0.5) 14°F + 1 (7.7°C + 0.5)
120
9°F + 1 (5.0°C + 0.5) 13°F + 1 (7.2°C + 0.5)
120 Reheat 15°F + 1 (8.3°C + 0.5) 8°F + 1 (4.4°C + 0.5)
150
10°F + 1 (5.6°C + 0.5) 11°F + 1 (6.1°C + 0.5)
150 Reheat 22°F + 1 (12°C + 0.5) 8°F + 1 (4.4°C + 0.5)
F-Compressor Controls
See unit wiring diagram to determine which controls are used on each unit.
1 – High Pressure Switch (S4)
The compressor circuit is protected by a high pressure switch which opens at 640 psig + 10 psig (4413 kPa + 70 kPa) and automatically resets at 475 psig + 20 psig (3275kPa + 138 kPa).
2 – Low Pressure Switch (S87, S88)
The compressor circuit is protected by a loss of charge switch. Switch opens
at 40 psig + 5 psig (276 + 34 kPa) and automatically resets at 90 psig + 5
psig (621 kPa + 34 kPa).
3 – Crankcase Heater (HR1, HR2)
Compressors have belly band compressor oil heaters which must be on 24 hours
before running compressors. Energize by setting thermostat so that there is no
cooling demand, to prevent compressor from cycling, and apply power to unit.
4 – Thermal Protector (S5)
The compressors are thermally protected with automatic temperature switches.
5 – Prognostics and Diagnostics Sensors (RT42RT49) Eight thermistors are
located on specific points in the refrigeration circuit. The thermistors
provide constant temperature feedback to the Unit Controller to protect the
compressor. Thermistors take the place of the freezestat and low ambient
pressure switch.
Prognostic & Diagnostic Sensors
Units are equipped with eight factory-installed thermistors (RT42 – RT49)
located on different points on the refrigerant circuit.
The thermistors provide the Unit Controller with constant temperature readings
of four specific locations on the refrigeration circuit. These temperatures
are used as feedback in certain modes of unit operation. In addition, the Unit
Controller uses these temperatures to initiate alarms such as loss of
condenser or evaporator airflow and loss of charge.
Each thermistor must be specifically placed for proper unit operation and to
initiate valid alarms. See TABLE 13 for proper locations.
TABLE 13 THERMISTOR LOCATION
RT42, 43, 46, 47
RT44 & RT45
RT48 & 49
FIGURE 23
FIGURE 24
FIGURE 25
Page 20
THERMISTOR LOCATION RT42, 43, 46, 47 (EVAPORATOR COIL VIEW FROM FRONT SIDE OF UNIT)
RT47
RT42
RT46
TXV BULB
RT42/43
SUCTION LINE
RT43
FIGURE 23 Page 21
THERMISTOR LOCATION RT44 & 45 (VIEW FROM FRONT SIDE OF UNIT)
092, 102 CONDENSER COIL
120, 150 CONDENSER COIL
RT44 & 45
RT44 RT45
RT45
RT44
FIGURE 24 Page 22
THERMISTOR LOCATION RT48 & 49 (VIEW FROM FRONT SIDE OF UNIT)
092, 102 CONDENSER COIL
120, 150 CONDENSER COIL
RT48
RT49
FIGURE 25 Page 23
Gas Heat Start-Up (Gas Units)
FOUR YOUR SAFETY READ BEFORE LIGHTING
WARNING
Electric shock hazard. Can cause injury or death. Do not use this unit if any
part has been under water. Immediately call a qualified service technician to
inspect the unit and to replace any part of the control system and any gas
control which has been under water.
WARNING
Danger of explosion. Can cause injury or product or property damage. If over
heating occurs or if gas supply fails to shut off, shut off the manual gas
valve to the appliance before shutting off electrical supply.
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform
any service or maintenance, turn the electrical power to unit OFF at
disconnect switch(es). Unit may have multiple power supplies.
WARNING
SMOKE POTENTIAL The heat exchanger in this unit could be a source of smoke on
initial firing. Take precautions with respect to building occupants and
property. Vent initial supply air outside when possible. BEFORE LIGHTING smell
all around the appliance area for gas. Be sure to smell next to the floor
because some gas is heavier than air and will settle on the floor. Use only
your hand to push in or turn the gas control knob. Never use tools. If the
knob will not push in or turn by hand, do not try to repair it, call a
qualified service technician. Force or attempted repair may result in a fire
or explosion.
WARNING
Danger of explosion. Can cause injury or death. Do not attempt to light
manually. Unit has a direct spark ignition system.
This unit is equipped with an automatic spark ignition system. There is no
pilot. In case of a safety shutdown, move thermostat switch to OFF and return
the thermostat switch to HEAT to reset ignition control.
A-Placing Unit In Operation
WARNING
Danger of explosion and fire. Can cause injury or product or property damage.
You must follow these instructions exactly.
Gas Valve Operation for Honeywell VR8205Q/VR8305Q and White Rodgers 36H54
(FIGURE 26 and FIGURE 27).
WHITE RODGERS 36H54 GAS VALVE
INLET
Two-Stage
PRESSURE TAP
MANIFOLD PRESSURE
TAP
HIGH FIRE ADJUSTMENT
LOW FIRE ADJUSTMENT
GAS VALVE SWITCH SHOWN IN ON POSITION.
FIGURE 26
HONEYWELL VR8205Q/VR8305Q GAS VALVE
HIGH FIRE ADJUSTMENT
LOW FIRE ADJUSTMENT
MANIFOLD PRESSURE
TAP
INLET PRESSURE
TAP
GAS VALVE KNOB IS SHOWN IN OFF POSITION.
FIGURE 27 1 – Set thermostat to lowest setting. 2 – Turn off all electrical
power to appliance. 3 – This appliance is equipped with an ignition device
which automatically lights the burner. Do not try to light the burner by hand.
4 – Open or remove the heat section access panel.
Page 24
5 – Turn gas valve switch to OFF. See FIGURE 26. On Honeywell VR8305Q gas
valves, turn the knob on the gas valve clockwise to OFF. Do not force. See
figure 27.
6 – Wait five (5) minutes to clear out any gas. If you then smell gas, STOP!
Immediately call your gas supplier from a neighbor’s phone. Follow the gas
supplier’s instructions. If you do not smell gas, go to the next step.
7 – Turn gas valve switch to ON. See FIGURE 26. On Honeywell VR8305Q gas
valves, turn the knob on the gas valve counterclockwise to ON. Do not force.
See FIGURE 27.
8 – Close or replace the heat section access panel.
9 – Turn on all electrical power to appliance.
10 – Set thermostat to desired setting.
11 – The ignition sequence will start.
12 – If the appliance does not light the first time (gas line not fully
purged), it will attempt up to two more ignitions before locking out.
13 – If lockout occurs, repeat steps 1 through 10.
14 – If the appliance will not operate, follow the instructions “Turning Off
Gas to Appliance” and call your service technician or gas supplier.
Turning Off Gas to Unit 1 – If using an electromechanical thermostat, set to
the lowest setting.
2 – Before performing any service, turn off all electrical power to the
appliance.
3 – Open or remove the heat section access panel.
4 – Turn gas valve switch to OFF. On Honeywell VR8305Q gas valves, turn the
knob on the gas valve clockwise to OFF. Do not force.
5 – Close or replace the heat section access panel.
WARNING
Danger of explosion. Can cause injury or death. Do not attempt to light
manually. Unit has a direct spark ignition system.
Heating Operation and Adjustments
(Gas Units) A-Heating Sequence of Operation
1 – On a heating demand the combustion air inducer starts immediately.
2 – Combustion air pressure switch proves inducer operation. After a 30-second
pre-purge, power is allowed to ignition control. Switch is factory set and
requires no adjustment.
3 – Spark ignitor energizes and gas valve solenoid opens.
4 – Spark ignites gas, ignition sensor proves the flame and combustion
continues.
5 – If flame is not detected after first ignition trial, ignition control will
repeat steps 3 and 4 two more times before locking out the gas valve.
6 – For troubleshooting purposes, an ignition attempt after lock out may be
re-established manually. Move thermostat to OFF and return thermostat switch
to HEAT position.
B-Limit Controls
Limit controls are factory-set and are not adjustable. The primary limit is
located on the blower deck to the right of the blower housing.
C-Heating Adjustment
Main burners are factory-set and do not require adjustment.
The following manifold pressures are listed on the gas valve.
Natural Gas Units – Low Fire – 1.6″ w.c. (not adjustable) Natural Gas Units –
High Fire – 3.7″ w.c. LP Gas Units – Low Fire – 5.5″ w.c. (not adjustable) LP
Gas Units – High Fire – 10.5″ w.c.
Electric Heat Start-Up (Cooling Units)
Factory or Field-Installed Option
Electric heat will stage on and cycle with thermostat demand. Number of stages
of electric heat will vary depending on electric heat assembly. See electric
heat wiring diagram on unit for sequence of operation.
SCR Electric Heat Controller (LCM Units)
Optional factory-installed SCR (A38) will provide small amounts of power to
the electric heat elements to efficiently maintain warm duct air temperatures
when there is no heating demand. The SCR maintains duct air temperature based
on input from a field-provided and installed thermostat (A104) and duct sensor
(RT20). SCR is located in the electric heat compartment in front of the
elements. Use only with a thermostat.
Use the instructions provided with the thermostat to set DIP switches as
follows: S1 On, S2 Off, S3 Off. Use the instructions provided with the duct
sensor to install sensor away from electric element radiant heat and in a
location where discharge air is a mixed average temperature.
Once power is supplied to unit, zero SCR as follows:
1 – Adjust thermostat (A104) to minimum position.
2 – Use a small screwdriver to slowly turn the ZERO potentiometer on the SCR
until the LED turns solid red.
3 – Very slowly adjust the potentiometer the opposite direction until the LED
turns off.
Cooling Operation
This is a summary of cooling operation. Refer to the sequence of operation
provided in the Engineering Handbook or Service Manual for more detail.
NOTE – Free cooling is locked-out during reheat operation. Refer to hot gas
reheat start-up and operation section for details.
A-Two-Stage Thermostat
1 – Economizer With Outdoor Air Suitable
Y1 Demand –
Compressors Off Blower Cooling Low Dampers modulate NOTE – If dampers are at
maximum open for five minutes, compressors are energized and blower stays on
cooling high.
Y2 Demand –
Compressors Modulate Blower Cooling High Dampers Maximum Open
2 – No Economizer or Outdoor Air Not Suitable
Y1 Demand –
Compressors Modulate Blower Cooling Low Dampers Minimum Position
Y2 Demand –
Compressors Modulate Blower Cooling High Dampers Minimum Position
B-Three-Stage Thermostat
1 – Economizer With Outdoor Air Suitable
Y1 Demand –
Compressors Off Blower Cooling Low Dampers Modulate NOTE – If dampers are at
maximum open for five minutes, compressors are energized and blower stays on
cooling high.
Y2 Demand –
Compressors Modulate Blower Cooling Intermediate Dampers Maximum Open
Y3 Demand –
Compressors Modulate Blower Cooling High Dampers Maximum Open
C-Room Sensor
1 – Economizer With Outdoor Air Suitable
Compressors Off Blower Modulates Dampers modulate NOTE – If dampers are at
maximum open for five minutes, compressors are energized and the blower
modulates. 2 – No Economizer or Outdoor Air Not Suitable
Compressors Modulate Blower Modulates Dampers Minimum Position
Page 26
Modulating Hot Gas Reheat Start-Up and Operation
General
Hot gas reheat units provide a dehumidifying mode of operation. These units
contain a reheat coil adjacent to and downstream of the evaporator coil.
Reheat coil solenoid valve, L14, routes hot discharge gas from the compressor
to the reheat coil. Return air pulled across the evaporator coil is cooled and
dehumidified; the reheat coil adds heat to supply air. See FIGURE 28 for
reheat refrigerant routing and FIGURE 29 for standard refrigerant routing.
L14 Reheat Coil Solenoid Valve
When Unit Controller input (Unit Controller J298-5 or J2998) indicates room
conditions require dehumidification, L14 reheat valve is energized (Unit
Controller J394-1) and refrigerant is routed to the reheat coil.
Reheat Setpoint
Reheat is factory-set to energize when indoor relative humidity rises above
60% (default).
The reheat setpoint can be adjusted by changing mobile service app Settings –
Control menu. A setting of 100% will operate reheat from an energy management
system digital output.
The reheat setpoint can also be adjusted using an optional Network Control
Panel (NCP). Reheat will terminate when the indoor relative humidity falls 3%
(57% default) or the digital output de-energizes. The reheat deadband can be
adjusted at Settings – Control menu.
Check-Out
Test hot gas reheat operation using the following procedure.
1 – Make sure reheat is wired as shown in wiring section.
2 – Make sure unit is in local thermostat mode.
3 – Select:
RTU MENU > SERVICE > COMPONENT TEST >
DEHUMIDIFICATION The blower and compressor 1 (reheat) should be operating.
DEHUMIDIFIER 1 ON will appear.
4 – Press STOP to discontinue the testing mode. Compressor 1 (reheat) and
blower should de-energize.
REHEAT MODE REFRIGERANT ROUTING
FIGURE 28 Page 27
COOLING MODE REFRIGERANT ROUTING
FIGURE 29
Default Reheat Operation
TABLE 14 Reheat Operation – Two Cooling Stages – Default
T’stat and Humidity Demands
Operation
Reheat Only
Compressor 1 Reheat
Reheat & Y1
Compressor 1 & 2 Enhanced Dehumidification at Low CFM
Reheat & Y1 & Y2
Compressor 1 & 2 Enhanced Dehumidification at High CFM
*If there is no reheat demand and outdoor air is suitable, free cooling will operate.
**If there is no reheat demand and outdoor air is suitable, free cooling and compressor 1 will operate.
Service
The unit should be inspected once a year by a qualified service technician.
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors
can cause improper and dangerous operation. Verify proper operation after
servicing.
A-Filters
Units are equipped with four 20 X 25 X 2′ filters. Filters should be checked
monthly and replaced when necessary with filters of like kind and size. Take
note of air flow direction marking on filter frame when reinstalling filters.
See FIGURE 30.
NOTE – Filters must be U.L.C. certified or equivalent for use in Canada.
B-Lubrication
All motors are lubricated at the factory. No further lubrication is required.
C-Burners (Gas Units)
Periodically examine burner flames for proper appearance during the heating
season. Before each heating season examine the burners for any deposits or
blockage which may have occurred.
Clean burners as follows:
1 – Turn off both electrical power and gas supply to unit.
2 – Remove burner compartment access panel.
3 – Remove screws securing burner assembly to burner support and remove
assembly. See figure 31. Clean as necessary.
4 – Locate the ignitor under the left burners. Check ignitor spark gap with
appropriately sized twist drills or feeler gauges. See FIGURE 32.
Page 28
REMOVE FILTERS
PULL TO REMOVE FILTERS
GAS VALV
E
FIGURE 30
BURNER BOX ASSEMBLY 240KBTUH SHOWN BURNER ASSEMBLY SECURED WITH MULTIPLE
SCREWS
GAS MANIFOLD
FIGURE 31 IGNITOR
SPARK GAP SHOULD BE 1/8″
(3mm)
FIGURE 32
5 – Check the alignment of the ignitor and the sensor as shown in FIGURE 33 and TABLE 15.
TABLE 15
Dimensions
Unit Btuh Input
Length – in. (mm)
Ignitor
Sensor
A
130K
7-3/4 (197)
11 (279)
B
180K
5 (127)
5-1/2 (140)
C
240K
2-1/4 (57)
2-3/4 (70)
6 – Replace burners and screws securing burner.
7 – Replace access panel.
8 – Restore electrical power and gas supply. Follow lighting instructions attached to unit and use inspection port in access panel to check flame.
WARNING
Danger of explosion. Can cause injury or death. Do not overtighten main burner
mounting screws. Snug tighten only.
D-Combustion Air Inducer (Gas Units)
A combustion air proving switch checks combustion air inducer operation before
allowing power to the gas controller. Gas controller will not operate if
inducer is obstructed.
Under normal operating conditions, the combustion air inducer wheel should be
checked and cleaned prior to the heating season. However, it should be
examined periodically during the heating season to establish an ideal cleaning
schedule. With power supply disconnected, the condition of the inducer wheel
can be determined by looking through the vent opening.
Clean combustion air inducer as follows:
1 – Shut off power supply and gas to unit.
2 – Disconnect pressure switch air tubing from combustion air inducer port.
3 – Remove and retain screws securing combustion air inducer to flue box.
Remove vent connector. See FIGURE 34.
4 – Clean inducer wheel blades with a small brush and wipe off any dust from
housing. Clean accumulated dust from front of flue box cover.
5 – Return combustion air inducer motor and vent connector to original
location and secure with retained screws. It is recommended that the
combustion air inducer gasket be replaced during reassembly.
6 – Clean combustion air inlet louvers on heat access panel using a small
brush.
Page 29
IG NIT O R
A B C
IGNITOR AND SENSOR POSITION TOP VIEW
S E NS OR
A B C
S IDE VIE W IGNITOR
Gas Flow
S IDE VIE W S E NS OR
Gas Flow
1-3/8″ (35mm)
1-3/4″ (45mm)
13/16″ (21mm)
BURNER BOX FIGURE 33
3/8″ (10mm)
HEAT EXCHANGER ASSEMBLY
HEAT EXCHANGER
TUBE COMBUSTION AIR INDUCER
VENT CONNECTOR
G-Supply Air Blower Wheel
Annually inspect supply air blower wheel for accumulated dirt or dust. Turn
off power before attempting to remove access panel or to clean blower wheel.
H-Condenser Coil
Clean condenser coil annually with detergent or commercial coil cleaner and
inspect monthly during the cooling season. Access panels are provided on front
and back of condenser section.
J-Needlepoint Bipolar Ionizer
The ionizer was designed for low maintenance. The device should be checked
semi-annually to confirm the brushes are clean for maximum output. The ionizer
is located on the blower deck. See FIGURE 36.
BIPOLAR IONIZER
GAS VALVE
BURNER
FIGURE 34
E-Flue Passageway and Flue Box (Gas Units)
1 – Remove combustion air inducer assembly as described in section D.
2 – Remove flue box cover. Clean with a wire brush as required.
3 – Clean tubes with a wire brush.
4 – Reassemble the unit. The flue box cover gasket and combustion air inducer
gasket should also be replaced during reassembly.
F-Evaporator Coil
Inspect and clean coil at beginning of each cooling season. Clean using mild
detergent or commercial coil cleaner. Flush coil and condensate drain with
water taking care not to get insulation, filters and return air ducts wet.
IONIZER ASSEMBLY
FIGURE 35
Page 30
K-UVC Light
When field-installed, use only UVC Light Kit assembly 106882-01 (21A93) with
this appliance.
Factory-Installed UVC Light
When the UVC light is factory installed, the lamp is shipped in a foam sleeve.
The lamp is attached to the UVC light assembly on the blower deck. See FIGURE
37. Remove the lamp and install into the UVC light assembly as shown in steps
2 through 11.
Annual Lamp Replacement
WARNING
Personal Burn Hazard Personal injury may result from hot lamps. During
replacement, allow lamp to cool for 10 minutes be fore removing lamp from
fixture. The lamp should be replaced every 12 months, as UVC energy production
diminishes over time.
1 – Obtain replacement lamp 101087-01 for your germicidal light model.
2 – Disconnect power to the rooftop unit before servicing the UVC kit.
UVC ASSEMBLY
UVC LAMP UVC ASSEMBLY
DOOR SWITCH
FIGURE 36
ASSEMBLY SECURED WITH 3 SCREWS
Page 31
3 – Open the blower access door. 4 – Remove the screw in wire tie from the UVC
assembly and disconnect the 4-pin connector from the lamp end. 5 – Remove and
retain the (3) screws securing the UVC assembly. Carefully slide the complete
UVC assembly out through the blower access door. See FIGURE 37.
INSTALL LAMP IN HOLDER CLIPS
UVC Sub-Assembly
BANDS (see Note below)
DETAIL A
SHEET METAL END STOP
LAMP FLANGE
4-PIN CONNECTOR
LAMP
HOLDER CLIPS (2)
NOTE – The bands around the lamp should be evenly spaced as shown in the diagram .
FIGURE 37
6 – Allow 10 minutes before touching the lamps. Then, carefully remove the old lamp from the lamp holder clips.
7 – Wear cotton gloves or use a cotton cloth when handling the new lamp. Place the new lamp in the holder clips of the UVC assembly. Verify that the lamp flange at the connector end is sandwiched between the lamp holder clip and the sheet-metal end stop (see FIGURE 38).
8 – Carefully place the UVC assembly on the blower deck. Line up the mounting holes on the UVC assembly with the mounting holes on the blower deck See FIGURE 37. Use the retained screws provided to attach the UVC assembly in place.
9 – Close the blower access door.
10 – Reconnect power to the rooftop unit.
11 – Open the filter access door and look through the view port in the
triangular sheet-metal panel to
verify that the UVC light is on.
If UVC lamp does not come on:
1 – Check Power Wiring: Disconnect 1/4″ QC (quick connects) of the UVC cable
near the UVC assembly. With Power ON, use multimeter to test 110-230V at the
1/4″QC quick connects from the control panel.
2 – Check Lamp: Carefully remove the UVC assembly out of the rooftop unit. Use
multimeter to test for continuity across each pair of pins at each end of the
lamp.
3 – Check Lamp Installation: Make sure that lamp’s pins snap properly into the
lamp holder.
LED(s) not illuminated
Power status LED not lit–Check that the lamp unit is connected to the proper
power source and is wired correctly.
Lamp status LED(s) not lit
1 – Check that lamp 4-pin connectors are properly engaged.
2 – Ohm-check across the lamp pins to check for continuity of lamp filaments
(see FIGURE 40).
Troubleshooting charts are provided to aid in determining the cause of any
problems encountered (FIGURE 39 and FIGURE 40).
Lamp Disposal
Hg-LAMP Contains Mercury – Manage in accordance with local, state and federal
disposal laws. Refer to www. lamprecycle.org or call
800-953-6669.
Proper Clean-up Technique in Case of Lamp Breakage
Wear protective gloves, eye wear and mask.
Sweep the broken glass and debris into a plastic bag, seal the bag, and
dispose of properly. Contact your local waste management office for proper
disposal. Do not use a vacuum cleaner. Do not incinerate.
Maintenance
· For all maintenance, contact a qualified HVAC technician.
· Read the maintenance instructions before opening unit panels.
· Unintended use of the unit or damage to the unit housing may result in the
escape of dangerous UVC radiation. UVC radiation may, even in small doses,
cause harm to the eyes and skin.
· Do not operate units that are obviously damaged. · Do not discard the
triangular UVC light shield or any
barriers with an ultraviolet radiation symbol. · Do not override the door
interlock switch that inter-
rupts power to the UVC light. · Do not operate the UVC light outside of the
unit.
Page 32
DANGER
Ultraviolet (UVC) Radiation hazard. Any exposure will cause significant eye
damage and may cause skin damage. DO NOT look into UVC light source. Access
panels must be in place during appliance operation.
UVC LIGHT TROUBLESHOOTING – POWER
UVC LAMP NOT OPERATING
POWER LED
LIT?
NO
YES
CHECK LAMP LEDS
DONE
YES
NO LAMP LEDS
LIT?
USE MULTIMETER TO TEST 110-230V AT
BALLAST INPUT LEADS
CORRECT VOLTAGE PRESENT? NO
YES
CHECK POWER
LEDS
FIRST TURN THE POWER OFF
;
CHECK THE WIRING
TURN POWER BACK ON
POWER LED YES LIT NOW?
NO GO TO LAMP LED TROUBLESHOOTING
FIGURE 38
REPLACE BALLAST
LAMP LEDS NOT LIT
UVC LIGHT TROUBLESHOOTING – LAMP
FIRST TURN THE POWER OFF. BE SURE THAT THE 4-PIN
CONNECTORS FOR ALL THE LAMPS ARE PROPERLY ENGAGE.D
TURN POWER ON; CHECK LAMP LEDS
DETAIL A
CALL LENNOX TECH SUPPORT 1-800-453-6669
NO
DONE
LAMPS BLACK ON
ENDS?
YES NO
YES LAMP LEDS LIT?
CHECK FOR CONTINUITY
TWO PAIR, PIN TO PIN ON EACH PAIR (SEE DETAIL A)
CONTINUITY YES PRESENT?
NO
REPLACE LAMPS; TURN POWER ON
LAMP LEDS
YES
LIT?
NO
BANDS
AROUND LAMP
YES
INTACT?
NO
BANDS
NOTE – CHECK FOR CONTINUITY ON THE SETS OF PINS CLOSEST TOGETHER
CHECK FOR CONTINUITY
DETAIL B
FIGURE 39 Page 33
Field-Installed Accessories
When field-installing the following accessories, refer to the latest online
installation instructions.
Accessory Economizer Outdoor Air Damper Electric Heat Smoke Detector
TABLE 16
Instruction # 507227-XX 506340-XX 507250-XX 506437-XX
Factory Unit Controller Settings
Use the mobile service app to adjust parameters; menu paths are shown in each
table. Refer to the Unit Controller manual provided with each unit.
TABLE 14 through TABLE 20 show blower factory settings. Record any field-
adjusted settings in the blank column.
TABLE 21 through TABLE 23 show control options. When applicable, record field-
specific information on the label located inside the compressor access panel.
When field installing optional kits and accessories, the Unit Controller must
be configured to identify the option before it will function. Refer to FIGURE
41 and FIGURE 42 to determine whether the Unit Controller configuration I.D.
must change. To configure the option, use RTU MENU > SETUP > INSTALL menu
path. Press NEXT until CONFIGURATION ID 1 or 2 appears depending on the option
installed. Change the appropriate character in the configuration I.D. For
example, when an economizer is installed using a single enthalpy sensor,
change configuration I.D. 1, the second character, to “S”.
TABLE 17
LGM/LCM 092U4E (2-Compressor) Staged Direct Drive
Parameter
Factory Setting
Field Setting
Description
NOTE – Any changes to Smoke CFM setting must be adjusted be fore the other CFM settings. Use SETTINGS > RTU OPTIONS > EDIT PARAMETERS
12
3000 CFM CFM
Blower CFM during smoke detection.
SETUP > TEST & BALANCE (can also use SETTINGS > RTU OPTIONS > BLOWER > SPEEDS)
3000 CFM CFM
Clower CFM during heating.
2625 CFM CFM
Blower CFM during high speed cooling (2 compressor) operation.
300 CFM CFM
Blower CFM during low speed cooling (1 compressor) operation.
800 CFM CFM
Blower CFM during ventilation.
1195 CFM RPM*
Adjust RPM based on unit stattic and blower tables to reach target CFM.
*Once all four blower settings are entered, the target (highest of the heating and cooling settings) CFM will be displayed. Once the RPM is saved for the target CFM, all other blower RPM values are set by the Unit Controller according to the field CFM setting..
SETUP > TEST & BALANCE (can also use SETTINGS > RTU OPTIONS > DAMPER)
0%
%
Damper min. position during LOW blower operation.
0%
%
Damper min. position during HIGH blower operation.
50%
%
Min. damper % for stage 1 power exhaust operation.
SETTINGS > RTU OPTIONS > EDIT PARAMETERS
Damper minimum position
during G blower operation.
29
101%
% Open
(Setting parameter 29 to “101” disables parameter
29 and passes control to
parameter 9 or 132).
216
10%
%
Deadband % for stage 1 power exhaust operation.
SETTINGS > RTU OPTIONS > EDIT PARAMETER
Compressor 1 low temp
85
0°F
°F
lockot. Settings lower than
0°F could void warranty.
Compressor 2 low temp
86
0°F
°F
lockout. Settings lower than
0°F could void warranty.
Page 34
TABLE 18
LGM/LCM 102U4E (2-Compressor) Staged Direct Drive
Parameter
Factory Setting
Field Setting
Description
NOTE – Any changes to Smoke CFM setting must be adjusted be fore the other CFM settings. Use SETTINGS > RTU OPTIONS > EDIT PARAMETERS
12
3400 CFM CFM
Blower CFM during smoke detection.
SETUP > TEST & BALANCE (can also use SETTINGS > RTU OPTIONS > BLOWER > SPEEDS)
3400 CFM CFM
Clower CFM during heating.
2675 CFM CFM
Blower CFM during high speed cooling (2 compressor) operation.
800 CFM CFM
Blower CFM during low speed cooling (1 compressor) operation.
800 CFM CFM
Blower CFM during ventilation.
1285 CFM RPM*
Adjust RPM based on unit stattic and blower tables to reach target CFM.
*Once all four blower settings are entered, the target (highest of the heating and cooling settings) CFM will be displayed. Once the RPM is saved for the target CFM, all other blower RPM values are set by the Unit Controller according to the field CFM setting..
SETUP > TEST & BALANCE (can also use SETTINGS > RTU OPTIONS > DAMPER)
0%
%
Damper min. position during LOW blower operation.
0%
%
Damper min. position during HIGH blower operation.
50%
%
Min. damper % for stage 1 power exhaust operation.
SETTINGS > RTU OPTIONS > EDIT PARAMETERS
Damper minimum position
during G blower operation.
29
101%
% Open
(Setting parameter 29 to “101” disables parameter
29 and passes control to
parameter 9 or 132).
216
10%
%
Deadband % for stage 1 power exhaust operation.
SETTINGS > RTU OPTIONS > EDIT PARAMETER
Compressor 1 low temp
85
0°F
°F
lockot. Settings lower than
0°F could void warranty.
Compressor 2 low temp
86
0°F
°F
lockout. Settings lower than
0°F could void warranty.
TABLE 19
LGM/LCM 120U4E (2-Compressor) Staged Direct Drive
Parameter
Factory Setting
Field Setting
Description
NOTE – Any changes to Smoke CFM setting must be adjusted be fore the other CFM settings. Use SETTINGS > RTU OPTIONS > EDIT PARAMETERS
12
4000 CFM CFM
Blower CFM during smoke detection.
SETUP > TEST & BALANCE (can also use SETTINGS > RTU OPTIONS > BLOWER > SPEEDS)
4000 CFM CFM
Clower CFM during heating.
3500 CFM CFM
Blower CFM during high speed cooling (2 compressor) operation.
875 CFM CFM
Blower CFM during low speed cooling (1 compressor) operation.
875 CFM CFM
Blower CFM during ventilation.
1425 CFM RPM*
Adjust RPM based on unit stattic and blower tables to reach target CFM.
*Once all four blower settings are entered, the target (highest of the heating and cooling settings) CFM will be displayed. Once the RPM is saved for the target CFM, all other blower RPM values are set by the Unit Controller according to the field CFM setting..
SETUP > TEST & BALANCE (can also use SETTINGS > RTU OPTIONS > DAMPER)
0%
%
Damper min. position during LOW blower operation.
0%
%
Damper min. position during HIGH blower operation.
50%
%
Min. damper % for stage 1 power exhaust operation.
SETTINGS > RTU OPTIONS > EDIT PARAMETERS
Damper minimum position
during G blower operation.
29
101%
% Open
(Setting parameter 29 to “101” disables parameter
29 and passes control to
parameter 9 or 132).
216
10%
%
Deadband % for stage 1 power exhaust operation.
SETTINGS > RTU OPTIONS > EDIT PARAMETER
Compressor 1 low temp
85
0°F
°F
lockot. Settings lower than
0°F could void warranty.
Compressor 2 low temp
86
0°F
°F
lockout. Settings lower than
0°F could void warranty.
Page 35
TABLE 20
LGM/LCM 150U4E (2-Compressor) Staged Direct Drive
Parameter
Factory Setting
Field Setting
Description
NOTE – Any changes to Smoke CFM setting must be adjusted be fore the other CFM settings. Use SETTINGS > RTU OPTIONS > EDIT PARAMETERS
12
5000 CFM CFM
Blower CFM during smoke detection.
SETUP > TEST & BALANCE (can also use SETTINGS > RTU OPTIONS > BLOWER > SPEEDS)
5000 CFM CFM
Clower CFM during heating.
4375 CFM CFM
Blower CFM during high speed cooling (2 compressor) operation.
1100 CFM CFM
Blower CFM during low speed cooling (1 compressor) operation.
1100 CFM CFM
Blower CFM during ventilation.
1655 CFM RPM*
Adjust RPM based on unit stattic and blower tables to reach target CFM.
*Once all four blower settings are entered, the target (highest of the heating and cooling settings) CFM will be displayed. Once the RPM is saved for the target CFM, all other blower RPM values are set by the Unit Controller according to the field CFM setting..
SETUP > TEST & BALANCE (can also use SETTINGS > RTU OPTIONS > DAMPER)
0%
%
Damper min. position during LOW blower operation.
0%
%
Damper min. position during HIGH blower operation.
50%
%
Min. damper % for stage 1 power exhaust operation.
SETTINGS > RTU OPTIONS > EDIT PARAMETERS
Damper minimum position
during G blower operation.
29
101%
% Open
(Setting parameter 29 to “101” disables parameter
29 and passes control to
parameter 9 or 132).
216
10%
%
Deadband % for stage 1 power exhaust operation.
SETTINGS > RTU OPTIONS > EDIT PARAMETER
Compressor 1 low temp
85
0°F
°F
lockot. Settings lower than
0°F could void warranty.
Compressor 2 low temp
86
0°F
°F
lockout. Settings lower than
0°F could void warranty.
TABLE 21 581024-01
Units With Hot Gas Reheat
RTU Menu > Settings “RTU Options” > Dehumidifier
Parameter
Factory Setting
Field Setting
Description
105
7
Factory Setting 7: Reheat mode en abled without prerequisite conditions. Controlled by RH sensor (A91) con nected to input A55_P298_5 and set point set at parameter 106 (default 60%).
TABLE 22 581037-01
Units with LonTalk Settings
Use menu RTU Menu > Network Integration > Network Setup Wiz ard > Set
“LONTALK”
TABLE 23 581038-01
Units With BACnet Settings
RTU Menu > Network Integration > Network Setup Wizard > BACnet MS/TP > See
BACnet MAC Address
BACNET MAC ADDRESS:
Units With Room Sensor, CPC/LSE Gateway Settings
RTU Menu > Network Integration > Network Setup Wizard > SBUS > Set SBUS
Address
LCONN ADDRESS:
Page 36
Configuration ID 1
1 2 3 4 5 6 7 8
Humiditrol [1] Not Installed = N Humiditrol Installed = H
Unconfigured = U
Economizer [2] Not Installed = N Motorized Outdoor Air
Damper Only = M Economizer – Temperature = T
Economizer Global = G Economizer – Single Enthalpy = S
Economizer – Dual Enthalpy = D Unconfigured = U
Power Exhaust [3] Not Installed = N Single-Stage = S
Dual-Stage = D Unconfigured = U
Power Exhaust Control 4] Not Installed = N Damper Position = A A34 Pressure
Sensor = C
[8] Outdoor Air Velocity Control
N = Not applicable (for future use) L = Outdoor Air Control Installed
with A24 Sensor set for low range. M = Outdoor Air Control Installed with
A24 Sensor set for medium range. H = Outdoor Air Control Installed with
A24 Sensor set for high range.
[7] Reserved
N = Reserved for future use.
[6] Blower Variable Frequency Drive Bypass
N = Not Installed A = Automatic Bypass M = Manual Bypass U = Unconfigured
[5] Network Module
N = Not Installed L = LonTalk (Lennox)
FIGURE 40 Page 37
Configuration ID 2
1 2 3 4 5 6 7 8 9 10
Air Flow Proving [1] Switch (S52)
Not Installed = N Installed on M4 = C Installed on DDC
Controller = D
Dirty Filter Switch (S27) [2] Not Installed = N Installed on M4 = C Installed
on DDC Controller = D
Overflow Switch [3] (S149 / S179)
Not Installed = N Installed = Y
Reserved [4] Reserved = N
[10] Reserved
N = Reserved
[9] Electric Heat (Field-Installed)
N = Not Installed Y = Installed
[8] Load Shedding
N = Not Installed G = Global (P297 – pin 9) 2 = Installed on DI-2 3 =
Installed on DI-3
[7] Zone Bypass Damper
N = Not Installed Y = Installed
Phase / Voltage Detection * [5] N = Not Installed 1 = Enabled Internal
(Lennox) 2 = External (A42) Phase Detection
on DI-2 3 = External (A42) Phase Detection
on DI-3
[6] IAQ Options
N = Not Installed
1 = UV Lamp Installed
2 = Bipolar Ionizer Installed 3 = UV Lamp and
Bipolar Ionizer Installed
- When phase detection and voltage monitoring is enabled and wired incorrectl y, the system will go into demand hold status and restart after six minutes.
FIGURE 41 Page 38
START-UP REPORT
Job Name:___
Inspections and Checks
Store No.___Start-Up Date:__
Damage?
Yes No
R22 R410A
Address:_____
If yes, reported to:____
City:__State:__ Start-Up Contractor:____ Technician: Model No.: Serial No.:____ RTU No.:____ Catalog No.:__
Verify factory and field-installed accessories.
Check electrical connections. Tighten if necessary.
Supply voltage: L1-L2__L1-L3L2-L3
If unit contains a 208-230/240 volt transformer: Check primary transformer tap
Transformer secondary voltage: __
Cooling Checks
Compressor Rotation Ambient Temp.____Return Air Temp.____ Supply Air Temp.____
Compressor Amps
Compressor Volts
Pressures Condenser Fan Amps CC Heater Amps
L1
L2
L3 L1-L2 L1-L3 L2-L3 Disch. Suct. L1
L2
L3
L1
1
2
3
4
Blower Checks
Pulley/Belt Alignment Set Screws Tight
Blower Rotation Belt Tension
Nameplate Amps:_ Volts:___
Motor
Amps L1 L2 L3_____
Volts L1-L2 L1-L3 L2-L3_____
Heating Checks – Gas
Fuel type: Nat. LP Inlet Pressure:_in. w.c. Return Air Temp.:__ Supply Air Temp.:_ Altitude:____ Primary Limits Operate:
CO2%: Gas Valve GV1 GV2
Manifold Pressure
Low Fire
High Fire
Control Type
Heating Checks – Electric
Return Air Temp.:__ Supply Air Temp.:__ Limits Operate:
Amps
L1 L2 L3
L1 L2 L3
1
10
2
11
3
12
4
13
5
14
6
15
7
16
8
17
9
18
Accessory Checks
Power Exhaust Amps
1 _____ 2 ____ None
Min. Pos.
Economizer Operation Motor travel full open/close
Page 39
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>