AEMC 6422 Hazmat Grounding and Bonding System Installation Guide

June 15, 2024
AEMC

AEMC 6422 Hazmat Grounding and Bonding System

Product Information

Specifications:

  • Product Name : Static Ground and Bond Test System Kit
  • Catalog Number: Cat. #2155.01

Product Packaging:

  • Ground Tester Model 6422 Cat. #2135.55
  • Set of two, 14.5 T-shaped Auxiliary Ground Electrodes Cat. #2135.39
  • 50 ft Bonding Cable with REB Clamp Cat. #2155.12
  • Lead, Set of 2, color-coated 5 ft (Red and Blue) for Reels Cat. #5000.34
  • Waterproof Utility Case with inserts Cat. #2155.13
  • Ground Rod Driver /Extractor Tool Cat. #2155.11
  • (2 Sets of) 3 Copper Clad Ground Rods with 2 Ground Rod Couplers Cat. #2155.10 (3 Rods & 2 Couplers)
  • (3) 50 ft Ground Cable with REB Clamp on one end and Mueller Clip on the other. Cat. #2155.14 (1 Reel)
  • 30 ft Lead (green) Cat. #5000.01
  • 150 ft Red Wire on Reel Cat. #5000.04
  • 150 ft Blue Wire on Reel Cat. #5000.07
  • Handles supplied with Red and Blue Reels
  • Extra Handle for Reels Cat. #5000.64
  • Ground Tester Calibration Checker For Models 6422/6424 Cat. #5000.92
  • (2 Sets of) 3 10ft Ground Rod Jumper Cables Cat. #2155.15 (1 Set of 3)

Product Usage Instructions

  • Installing the Grounding System
    NOTE: One or more rods may be needed for each grounding system to obtain an acceptable grounding resistance. Multiple rods should be (3 to 6) ft apart and connected to each other via jumper cable.
1. Connect the grounding rods E1, E2, and E3, ensuring they are spaced (3 to 6) ft apart.
2. Connect the grounding rods to each other using the provided jumper cable.
  • Testing the Grounding System
    Conduct independent Fall-of-Potential tests on each of the grounding systems.
1. Insert the auxiliary test electrode H a few inches into the ground and (50 to 80) ft away at a location that is central to the three grounding system E rods.
2. Insert the auxiliary test electrode S a few inches into the ground at a distance approximately (30 to 45) ft from the first ground system E1 and in a straight line with the H electrode.
3. Connect the Red, Blue, and Green test wires to the grounding rod(s), electrodes, and instrument as shown.
4. Press and hold the Test button until reading stabilizes to measure the resistance.
5. Repeat steps 2, 3, and 4 for grounding systems E2 and E3.  

NOTE: Readings should be below 1000 or below 25 as defined by the local authority.

  • Connect to the Grounding System
    Following the diagram, perform the below steps in the following order:
1. Connect a grounding cable to the distressed tanker first and then to its grounding system E1.
2. Connect a grounding cable to the recovery tanker first and then to its ground system E2.
3. Connect a grounding cable to the transfer pump first and then to its grounding system E3. (Note: E3 is not needed if the pump is mounted to a fire truck.)
4. Connect a bonding cable to the distressed tanker first and then to the recovery tanker.
5. Connect the hoses to the pump and tankers.
6. Begin the transfer process.

FAQ (Frequently Asked Questions)

  • What resistance value should the grounding system readings be below?
    The readings should be below 1000 or below 25 as defined by the local authority.

Site Considerations

  • Locate grounding points on the tankers and transfer pump.
  • Make connections to damaged tanker first to avoid a potential spark.
  • When possible, grounding systems should be established up hill and outside of the Hot Zone.
  • Resistance measurement should be compliant with your local jurisdiction which usually follows NFPA 472 @1000 Ω or less or NEC @ 25 Ω or less, lower is always better. Higher resistance means longer static discharge time.

Installing the Grounding System

  • Install/establish three separate static grounding systems, one for the distressed tanker (E1), one for the recovery tanker (E2) and one for the pump (E3). When the pump is not mounted to the fire truck, they should be at least 10 feet apart.
  • The grounding sites should be up hill and up wind as well as outside of the distressed tanker’s hot zone.
    NOTE: One or more rods may be needed for each grounding system to obtain an acceptable grounding resistance. Multiple rods should be (3 to 6) ft apart and connected to each other via jumper cable.

Testing the Grounding System

Conduct independent Fall-of-Potential tests on each of the grounding systems.

  1. Insert the auxiliary test electrode H a few inches into the ground and (50 to 80) ft away at a location that is central to the three grounding system E rods.
  2. Insert the auxiliary test electrode S a few inches into the ground at a distance approximately (30 to 45) ft from the first ground system E1 and in a straight line with the H electrode.
  3. Connect the Red, Blue and Green test wires to the grounding rod(s), electrodes and instrument as shown.
  4. Press and hold the Test button until reading stabilizes to measure the resistance.
  5. Repeat steps 2, 3 and 4 for grounding systems E2 and E3.
    NOTE: Readings should be below 1000 Ω or below 25 Ω as defined by local authority.
    After achieving the acceptable resistance, disconnect the meter and auxiliary rods S and H before Step 3, connecting the tankers and pump to their grounding systems.

Connect to the Grounding System

Following the diagram, perform the below steps in the following order:

  •  Connect a grounding cable to the distressed tanker first and then to its grounding system E1.

  •  Connect a grounding cable to the recovery tanker first and then to its ground system E2.

  •  Connect a grounding cable to the transfer pump first and then to its grounding system E3.
    NOTE: E3 is not needed if the pump is mounted to a fire truck.

  •  Connect a bonding cable to the distressed tanker first and then to the recovery tanker.

  •  Connect the hoses to the pump and tankers.

Begin the transfer process.

PRODUCT PACKAGING

Also Includes:

  • User Manual
  • 6 AA Batteries – Uninstalled
  • Flathead Screwdriver
  • 8 Cable Ties

Accessories (Sold Separately):

ABOUT COMPANY

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals