- 2 Philips and 3/16 (5 mm) & 1/8″ (3.8 mm) Flat-head screwdrivers
MS-003650 SureSine Inverter
Installation and Operations Manual
150 W, 300 W, & 700 W (12 V, 24 V, & 48 V) Models,
1,000 W & 1,250 W, (24 V & 48 V) Models,
2,500 W (48 V Only) Models
(120 V / 60 Hz, 230 V / 50 Hz,
127 V / 60 Hz, and 220 V / 60 Hz)
April 2023 (Rev 2)
About MorningStar:
With well over 4 million products sold in over 100 countries since
1993—functioning in some of the most extreme environments and mission-critical
applications in the world—Morningstar Corporation can truly claim to be “the
leading supplier of solar controllers and inverters.” That success is why
Morningstar has had staying power and stable management for over 27 years,
along with the lowest employee turnover rate.
- Smarter digital design has been pioneered for solar components, for faster, more agile processing onboard. This allows for the maximum performance from the hardware.
- Advanced thermal engineering is used to eliminate cooling fans—the weak link in competitors’ products.
- Finally, internal electronics are laid out for performance and longevity instead of economics—designing for the long-term in order to achieve the industry’s lowest hardware failure rates.
For additional information about Morningstar Corporation, go to: www.morningstarcorp.com
Disclaimer:
The specifi cations and descriptions contained in this document are verifi ed to
be as accurate as possible at the time of publication. However, because
Morningstar Corporation’s products and their performance are constantly
evolving, Morningstar reserves the right to make product or documentation
modifi cations at any time, with or without notice. Due to the wide range of
applications where this product can be used, details may vary by product
version, geography, and site application.
To ensure that you have the most current version of this document, go to:
www.morningstarcorp.com/support.
To communicate any inaccuracies or omissions in this document, please fi ll out
a contact form at:
www.morningstarcorp.com/support.
Reference document #: MS-003650. Rev 2
Contact Information:
Morningstar Corporation
8 Pheasant Run
Newtown, Pennsylvania 18940 USA
Email: | support@morningstarcorp.com |
---|---|
Website: | www.morningstarcorp.com |
Service and Support: |
www.morningstarcorp.com/support
Phone:| +1 215.321.4457
Copyright 2023:
This document and its contents are protected by trade secrets, patent,
copyright, and other applicable laws.
All rights are reserved. Unauthorized use is illegal.
SureSine™ is a trademark of Morningstar Corporation
ModBus™ and ModBus TCP/IP™ are trademarks of ModBus IDA. www.modbus-
ida.org
© 2023 Morningstar Corporation. All rights reserved.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS – This manual contains important safety, installation,
and operating instructions for the Morningstar SureSine Inverter.
The SureSine produces voltages and currents capable of causing severe injury
or death. Extreme caution must be taken when installing and using the
SureSine.
The following symbols are used throughout this manual to indicate potentially
dangerous conditions or important safety instructions.
| WARNING: Indicates a potentially dangerous condition.
Failure to observe this notice could result in severe personal injury or
death.
---|---
| CAUTION: Indicates a critical procedure for safe and proper operation
of the SureSine. Use extreme caution when performing this task. Failure to
observe this notice could result in personal injury or equipment damage.
| NOTE: Indicates a procedure or function that is important to the safe and
proper operation of the SureSine Inverter.
GENERAL SAFETY INFORMATION
Throughout this manual, NEC guidance has been provided in order to meet
general safety requirements and inform best installation practices. It is the
installer’s responsibility to ensure that the Installation complies with all
local safety and code requirements.
- Read all of the instructions and cautions in the manual before starting the installation.
- Ensure that battery power has been disconnected BEFORE installing, servicing, or removing the SureSine Inverter.
- Do not allow water to enter the SureSine.
- Avoid wearing jewelry while installing this equipment.
- Do not smoke near the battery bank.
- Ensure power connections remain tight to avoid excessive heating from a loose connection.
- Recycle the battery when it is replaced.
WIRE AND CABLE SAFETY
Proper wire type and size is required for all installations. Use only UL-
listed Class B or Class C wire rated for 300 volts and 75ºC or higher. Use
stranded wire for the battery circuit and solid or stranded wire for the AC
and Ground circuits.
Copper wire is recommended instead of aluminum due to its ease of use,
superior conductivity, strength and thermal expansion properties.
| WARNING: SHOCK HAZARD
---|---
• Installations must be performed by a qualifi ed person trained in electrical
safety procedures (minimum qualifi cation).
• All wiring must comply with local electric code requirements.
• For all 120 Vac models, the AC neutral output circuit is bonded to the
inverter frame.
The grounding electrode terminal of the chassis frame must be connected to a
grounding electrode in accordance with local codes.
• Ensure all sources of input are disconnected before connecting ANY cabling.
| WARNING: RISK OF FIRE
---|---
All over-current protection devices and wiring must be sized properly, in
accordance with US National Electric Code (NEC) or the local regulations of
the country of installation.
| WARNING: FIRE HAZARD
---|---
A risk of fi re may exist if a 120 Vac power source is wired incorrectly to
120/240 Vac panel containing multi-wire branch circuits.
MOUNTING, CLEARANCE, AND LOCATION SAFETY
| WARNING: EXPLOSION/FIRE HAZARD
---|---
Do not install in a confi ned area where battery gases can accumulate. Battery
gases can create an explosion or fi re hazard if ignited by a spark. Ensure the
enclosure is ventilated well enough to disperse any accumulated gases.
Do not install over an easily combustible surface, since the heat sink may get
hot under certain operating conditions.
| CAUTION: EQUIPMENT DAMAGE
---|---
• Do not mount in zero-clearance compartment. Overheating may result. Ensure
adequate space around the components to ensure suffi cient ventilation around
the equipment.
• Locate the SureSine on a surface that is protected from direct sun, high
temperatures, corrosive fumes, and water.
• Ensure the mounting surface is strong enough to support the weight of the
inverter as well as any other devices that may be attached to it. It may be
necessary to reinforce the surface with plywood to provide additional support
for the equipment.
| CAUTION: HOT SURFACE/BURN HAZARD
---|---
The SureSine inverter models 700 Watts to 2,500 W can become very hot. Install
the SureSine so that it cannot be accidentally touched.
BATTERY SAFETY INFORMATION
| WARNING: SHOCK HAZARD
---|---
• Servicing of batteries should be performed, or supervised, by personnel
knowledgeable about batteries, and the proper safety precautions.
• Have someone nearby to assist in case of an accident.
• Carefully read the battery manufacturer’s instructions before installing /
connecting to, or removing batteries from the SureSine Inverter.
• A battery can present a risk of electrical shock or burn from large amounts
of shortcircuit current, fire, or explosion from vented gases. Observe proper
precautions.
• Remove watches, rings, jewelry and other metal objects before working with
batteries.
• Use tools with insulated handles and avoid placing tools or metal objects on
top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery
terminals.
• Determine if battery is inadvertently grounded. If so, remove the source of
contact with ground. Contact with any part of a grounded battery can result in
electrical shock. The likelihood of such a shock can be reduced if battery
grounds are removed during installation and maintenance (applicable to
equipment and remote battery supplies not having a grounded supply circuit).
| WARNING: RISK OF EXPLOSION
---|---
• Explosive battery gases can be present during charging. Be certain there is
enough ventilation to release the gases.
• Proper disposal of batteries is required. Do not dispose of batteries in fi
re. Refer to local regulations or codes for requirements. Recycle the battery
when it is replaced.
• Never smoke in the battery area.
| WARNING: CORROSION HAZARD/TOXIC FUMES
---|---
• Do not open or mutilate batteries. Released electrolyte is harmful to skin
and may be toxic if inhaled.
• Be very careful when working with large lead-acid batteries. Wear eye
protection and have fresh water available in case there is contact with the
battery acid.
• Wear rubber gloves and boots.
• If battery acid comes into contact with the skin, wash with soap and water.
If the acid contacts the eye, fl ood with fresh water and get medical
attention.
• Recycle the battery when it is replaced.
| CAUTION: EQUIPMENT DAMAGE
---|---
• Ensure the battery voltage matches the DC voltage requirements of the model
of SureSine inverter to be installed.
• Ensure the battery bank consists of batteries of the same type, make and
age.
• Ensure the battery electrolyte level is correct before starting charging. Do
not attempt to charge a frozen battery.
• Ensure that the charging equipment implemented in the system meets the
charging requirements for the battery bank and varied charging.
• The SureSine Low Voltage Disconnect (LVD) and Low Voltage Reconnect (LVR)
presets are generally designed for lead acid batteries. Use custom LVD and LVR
settings required for the type of battery in the system and minimum desired
state of charge (SOC). Note that some battery types may not be compatible.
CERTIFICATIONS:
North American Certifi cations:
- Complies with UL 1741 and CSA-C22.2 No. 107.1
- Complies with FCC Article 15, Class B
- Complies with ICES-003 Issue 4, Feb 2004 (Class B)
European LVD Directive :
- IEC/EN 62109-1:2010 Safety of Power Converters in PV Systems – Part 1: General Requirements
- IEC/EN 62109-2: 2011 Safety of power converters for use in photovoltaic power systems – Part 2: Particular requirements for inverters
European EMC Directive:
- IEC/EN 61000-6-1, IEC/EN 61000-6-2, IEC/EN 61000-6-3, IEC/EN 61000-6-4,
- IEC/EN 55032, IEC/EN55011
INTRODUCTION
The SureSine Inverter is a pure sine wave inverter for industrial and
residential DCto-AC applications which require high quality power. The
SureSine can be used as a standalone system or as an accessory to larger
systems that may include charging sources and
energy storage systems.
1.1 Features
SureSine features include:
-
Pure sine wave conversion produces a highly effi cient AC grid-quality power.
-
DC power to AC power conversion to the following output voltages:
– 120-volt/60 Hz.
– 220-volt/60 Hz.
– 127-volt/60 Hz.
– 230-volt/50 Hz -
Supports 12-volt, 24-volt, or 48-volt DC systems (dependent on model purchased).
-
Extensive electronic protections ensure protection against faults and user mistakes such as short circuits, overloads, high temperatures, and low voltage disconnects.
Recovery from most faults is automatic. -
Two LEDs provide important information to the user regarding battery status and AC output.
-
Remote ON/OFF capability.
-
Eight DIP switches provide easy adjustment of several system parameters.
-
Multiple communication options.
– Mobile devices can connect through Bluetooth
– Other network devices can connect through Ethernet and/or EIA-485
– FUTURE FEATURE: The SureSine Inverter can pair with other Morningstar products that feature MS-CAN Communication for control, adjustments, and monitoring performance
1.2 Components of the 150 W & 300 W Models
Figure 2 shows the components included with the 150 and 300 W models. 1.3
Components of the 700 W Models
Figure 3 shows the components included with the 700 W models. 1.4 Components
of the 1,000 W to 2,500 W Models
Figure 4 shows the components included with the 1,000 W to 2,500 W models.
1.5 Dimensions of the 150 W & 300 W Models
1.6 Dimensions of the 700 W to 2,500 W Models
INSTALLATION
Included in the box:
- Mounting Screws (#10 x4)
- CAN Terminal resistor
- Terminal block connector (for ModBus™, Remote Switch, Auxiliary Power)
2.1 Required Tools
| WARNING: SHOCK HAZARD
---|---
This product can produce hazardous voltage. Use insulated tools while working
with this equipment.
The minimum required tools include the following. Additional tools may be required depending on the site application.
- Wire cutters/strippers
- Drill and 1/8″ (3 mm) drill bit
-
2 Philips and 3/16 (5 mm) & 1/8″ (3.8 mm) Flat-head screwdrivers
- Multimeter
- Crimping Tool
- Wrench
2.2 Additional Hardware Requirements
Depending on the type of installation, additional hardware may be required.
This hardware is NOT provided with the SureSine Inverter. These types of
components include, but are not limited to:
-
Battery or battery bank
– Ensure the battery voltage matches the DC voltage requirements of the model of SureSine inverter to be installed.
– Ensure the battery bank is comprised of batteries of the same type, make, and age. -
All DC and ground cables
-
AC wiring for hardwired (HW) models only
-
Sub panels, circuit breakers, fuses Ground Fault Disconnects etc.
-
Primary Earth Ground connection (e.g., ground rod)
-
Remote Switch (Optional)
Consult the system design diagrams to determine the exact requirements for the installation.
2.3 Mounting
The SureSine may be mounted horizontally on a fl at surface (like a table) or
vertically (on a wall). If mounted vertically (on a wall), the inverter can be
mounted either portrait style or landscape style. Ensure that there is enough
space inside the enclosure for the wiring and ventilation. For optimal
ventilation and cooling, mount in portrait style orientation. Four Keyhole
slots are provided to secure the inverter to the mounting surface.
2.3.1 Safety Considerations for Mounting
| WARNING: EXPLOSION/FIRE HAZARD
---|---
Do not install in a confi ned area where battery gases can accumulate. Battery
gases can create an explosion or fi re hazard if ignited by a spark. Ensure the
enclosure is ventilated well enough to disperse any accumulated gases.
Do not install over an easily combustible surface, since the heat sink may get
hot under certain operating conditions.
| CAUTION: EQUIPMENT DAMAGE
---|---
• Do not mount in a compartment with inadequate clearance. Overheating may
result and cause derated output power or shut off, and may reduce the life
expectancy.
• Locate the SureSine on a surface that is protected from direct sun, high
temperatures, corrosive fumes, and water.
• Ensure the mounting surface is strong enough to support the weight of the
inverter as well as any other devices that may be attached to it. It may be
necessary to reinforce the surface with plywood to provide additional support
for the equipment.
| CAUTION: HOT SURFACE/BURN HAZARD
---|---
The SureSine inverter models 700 W to 2,500 W can become very hot. Install the
SureSine so that it cannot be accidentally touched.
2.3.2 Mounting Procedure
To secure the inverter to the mounting surface:
-
Place the SureSine on the surface where it will be mounted and determine where the wires will enter/exit.
• Be sure there is suffi cient bending room for the wires and other auxiliary connections, as required by local code.
• Verify that the mounting screws will not penetrate wires or other objects located on the opposite side of the surface.
• Ensure the surface is strong enough to support the weight of the inverter and anything else mounted on it. It may require additional support, such as a sheet of plywood. -
With a pencil or pen, mark the mounting hole locations.
-
With a drill and 1/8” (3 mm) bit, drill pilot holes for each of the four mounting screw locations marked on the mounting surface.
-
Place the SureSine onto the surface and align the mounting feet holes with the four pilot holes. Use the #10 screws (included) to secure the SureSine to the surface.
2.4 Adjusting Settings
The SureSine has eight (8) DIP Switches that allow for adjusting specifi c
operational parameters for the inverter. Each switch has an ON/OFF position.
See Section 2.4.2 on page 12 for details on specifi c settings.
| IMPORTANT:
---|---
Check that the DIP Switches are properly confi gured for the designed
installation prior to installing the inverter.
2.4.1 DIP Switch Location
The DIP switches are located on the DC side of all models.
2.4.2 DIP Switch Confi guration Options
DIP Switches control the operational functions of the inverter as follows.
The default position for these switches is OFF.
Table 1: DIP Switch Confi guration
DIP Switch | Function | Status | Control Content |
---|---|---|---|
1 | Operational Control (with AC Switch Down (Remote)) | OFF | AC Output is |
controlled by the Remote ON/OFF Switch
ON| AC Output is controlled by the communication command (digital
command).
2| Alarm Sounds| OFF| Alarm OFF
ON| Alarm ON
3| Not Used| OFF| Not Used – Default is OFF
ON| Not Used – Default is OFF
4| Low Voltage Disconnect| OFF| CUSTOM. LVD is set to the factory-
default values, but can be modified through RS485 communication port or
Bluetooth App. See the factory- default settings in Table 2 for default
values.
ON| PRESETS. LVD is set with the #5 DIP Switch values and cannot be
modified. See the Preset settings in Table 2 for Preset values.
5| Low Voltage Disconnect PRESETS (i.e., Default)
For 12 V
(24 V or 48 V)
Systems| OFF| • Low Voltage Disconnect (LVD) = 10.5 V (21 V or 42 V)
• Low Voltage Reconnect (LVR) = 11.6 V (23.2 V or 46.4 V)
• LVD Alarm = 10.8 V, (21.6 V or 43.2 V)
ON| • Low Voltage Disconnect (LVD) = 11.5 V (23.0 or 46 V)
• Low Voltage Reconnect (LVR) = 12.6 V (25.2 V or 50.4 V)
• LVD Alarm = 11.8 V (23.6 V or 48.4 V)
6| Standby Mode| OFF| AC Output is always ON
ON| AC Output is OFF unless a load > 8 W is detected
7| Ethernet Security (See Section 4.1 on page 36 for details)| OFF| 150
W & 300 W Models: Not Used – Default is OFF 700 W to 2,500 W Models: Ethernet
Write Disabled.
ON| 150 W & 300 W Models: Not Used – Default is OFF 700 W to 2,500 W
Models: Ethernet Write Enabled.
8| Bluetooth Communication*| OFF| Bluetooth Disabled
ON| Bluetooth Enabled
*Note: Requires a power cycle when turning Bluetooth (BT) on with DIP
Switch 8 during operation. BT can be turned off with DIP Switch 8 without a
power cycle. All other DIP Switches can be changed during operation and the
changes will immediately be implemented.
Table 2: Low Voltage Disconnect Settings (DIP 4 & 5)
Low Voltage Disconnect Factory Default & Presets (All Models)| 12-volt
Models| 24-volt Models| 48-volt Models
---|---|---|---
LVD| LVR| Alarm| LVD| LVR| Alarm| LVD| LVR| Alarm
Factory Default Settings (DIP 4 OFF)| 11.8| 12.8| 12.1| 23.6| 25.6| 24.2|
47.2| 51.2| 48.4
Preset Low (DIP 4 ON, DIP 5 OFF)| 10.5| 11.6| 10.8| 21.0| 23.2| 21.6| 42.0|
46.4| 43.2
Preset High (DIP 4 ON, DIP 5 ON) | 11.5| 12.6| 11.8| 23.0| 25.2| 23.6| 46.0|
50.4| 47.2
*Note : DIP 4 in the OFF position allows the factory-default values to be
changed using the RS485 communication port or Bluetooth App, if needed. When
DIP 4 is in the OFF position, it disables DIP 5. So when DIP 4 is in the OFF
position, the position of DIP 5 is irrelevant.
2.5 Pluggable Terminal Block Installation for Remote Switch or
Communications Wiring
If the application includes using a Remote Switch, 12 V Auxiliary Power, or
EIA-485 communications Port, the pluggable terminal block that is included in
the box will need to be installed. This will either be an 4-pin (150 W or 300
W models) or two 8-pin (700 to 2,500 W models) pluggable terminal block(s).
To install the Terminal Block:
- Use a 1/8″ (3.8 mm) fl athead screwdriver to connect the wires to the pluggable terminal block before plugging it in. See Table 3 on page 16 for acceptable wire sizes and torque values.
- Align the pins on the back of the terminal block with the holes in the SureSine Chassis on the DC Side of the unit.
- Press into place. Ensure the terminal block seats fi rmly into place.
2.6 Remote Switch Installation (Optional)
| IMPORTANT:
---|---
Check the AC Output Mode Switch on the AC end of the inverter and ensure it is
in the REMOTE position before wiring. See Figure 28 on page 33.
If the site application requires a Remote ON/OFF Switch or relay dry contact,
the following illustration shows where to connect the wires.
Note: Closed = ON and Open = OFF.
2.7 Auxiliary Power (Optional)
Auxiliary Power for 1 W (Maximum), 12 Vdc applications is available on the 700
W to 2,500 W Models only. These types of applications include:
- EIA-485 Communication Bus.
- Small DC devices (e.g., LEDs).
2.8 Inverter Wiring
This section provides general instructions for connecting all the wiring for
the inverter.
This includes DC, AC, Neutral, and all Ground connections (system and
chassis).
Ensure all connections are made as required by local regulatory code.
| WARNING: SHOCK HAZARD
---|---
• Installations must be performed by a qualifi ed person trained in electrical
safety procedures (minimum qualifi cation).
• All wiring must comply with local electric code requirements.
• Ensure all sources of input are disconnected before connecting ANY cabling.
| WARNING: RISK OF FIRE
---|---
All over-current protection devices and wiring must be sized properly, in
accordance with US National Electric Code (NEC) or the country of
installation’s local regulations.
| CAUTION: EQUIPMENT DAMAGE
---|---
Do not connect the SureSine inverter’s AC Output in parallel with any AC power
sources. The SureSine inverter is not capable of synchronizing AC output
phases.
AC power from utility, generator, and inverter AC power can feed back into the
unit and instantly damage the inverter and may also pose a fi re and safety
hazard.
2.8.1 Terminal Torque Requirements
Tighten all connections as specifi ed in Table 3.
Table 3: Terminal Torque Requirements
Terminal | Terminal Size or Wire Size | Torque to: |
---|---|---|
In-lbs. | Nm | |
DC (+) (–) Input Bolt Terminals (150 – 300 Watt) Note 1 | M8 (~5/16″) | 20 |
2.3
DC (+) (–) Input Bolt Terminals (700 – 2,500 Watt) Note 1| M6 (~1/4″)|
35| 4
AC Output Neutral, Line and Ground Terminals Note 2| M6 (~1/4″)| 20| 2.3
Chassis Ground Lug Note 3| 14 – 2 AWG (2.5 – 10.0 mm2)| 35| 4
ModBus™, Remote Switch, Auxiliary Power Terminals| 16 – 28 AWG (1.0 – 0.1
mm2)| 5| 0.57
Note 1 – Use properly sized ring terminals for DC power connections.
Note 2 – Use properly sized slotted terminals or solid copper wire (#12
maximum) with AC Neutral, Line, and Ground bolt terminals.
Note 3 – Use stranded copper wire with Chassis Ground stud.
2.8.2 Over-current Protection Requirements
| WARNING: RISK OF FIRE
---|---
Fuses or circuit breakers are required in the DC battery circuit (all models)
and in the AC output circuit (HW models) and shall be provided by the
installer.
Locate battery breakers or fused disconnects for easy access and free from
hydrogen gas/sulfuric acid fumes. The battery DC circuit breaker or fuse
should be within 6 inches from the battery bank or as close as possible.
| WARNING: SHOCK HAZARD
---|---
• Fuses, single-pole circuit breakers or single-pole disconnect switches
should NEVER open grounded system conductors. This could create a shock hazard
that could be fatal to personnel and/or damage the equipment.
• Fuses, single-pole circuit breakers, or single-pole disconnect switches must
only be installed on ungrounded system conductors.
• It is acceptable to use double-pole breakers or double-pole disconnect
switches which break both the grounded and ungrounded conductors with
the SureSine inverter.
2.8.2.1 Recommended Battery Over-current Protection Device Sizing
Use Table 4 to determine the size of the over-current protection device
required for the battery conductor.
Table 4: DC Battery Circuit Breaker/Fuse Size
Model Power Rating| Maximum Battery Continuous Current|
Recommended Battery Breaker/ Fuse Rating
---|---|---
Watts| Volts DC
150 W| 12 Vdc| 18 Amps| 30 Amps
24 Vdc| 8 Amps| 12-15 Amps
48 Vdc| 4 Amps| 6-10 Amps
300 W| 12 Vdc| 36 Amps| 60 Amps
24 Vdc| 16 Amps| 25 Amps
48 Vdc| 8 Amps| 12-15 Amps
700 W| 12 Vdc| 84 Amps| 125 Amps
24 Vdc| 38 Amps| 60 Amps
48 Vdc| 18.5 Amps| 30 Amps
1,000 W| 24 Vdc| 54 Amps| 80 Amps
48 Vdc| 26.5 Amps| 40 Amps
1,250 W| 24 Vdc| 68 Amps| 100 Amps
48 Vdc| 33 Amps| 50 Amps
2,500 W| 48 Vdc| 66 Amps| 100 Amps
2.8.2.2 Recommended AC Over-current Protection Device Sizing
Use Table 5 to determine the size of the over-current protection device
required for the AC conductor.
Table 5: AC Circuit Breaker/Fuse Size
Model Power Rating| AC Output Maximum Continuous Current| AC
Circuit Breaker/Fuse Ratings
---|---|---
120 Vac Model| 230 Vac Model| 120 Vac & 127 Vac Models| 220
Vac & 230 Vac Models
150 W| 1.25 Amps| 0.7 Amps| 2 to 5 Amps| 2 to 5 Amps
300 W| 2.5 Amps| 1.3 Amps| 4 to 5 Amps| 3 to 5 Amps
700 W| 5.8 Amps| 3 Amps| 10 Amps| 5 Amps
1,000 W| 8.3 Amps| 4.3 Amps| 15 Amps| 7 to 10 Amps
1,250 W| 10.5 Amps| 5.4 Amps| 15 Amps| 10 Amps
2,500 W| 21.0 Amps| 11 Amps| 30 Amps| 20 Amps
2.8.3 DC and AC Conductor Sizing Requirements
It is critical that the ampacity (or current carrying capacity) of conductors
is suffi cient to handle the maximum current of the power circuits. Ensure that
ring or slotted wire terminals have the proper wire size ratings for the wires
being installed.
Table 6 and Table 7 show the minimum sizing requirements (for 75°C wire) of
each SureSine model when operated at the maximum continuous current rating of
the inverter. These sizing requirements are based on NEC 2021 [Table
310.15(b)(16)], ampacity for not more than three current-carrying conductors
in a raceway, cable, or earth (buried), based on Ambient Temperature of 30°C
(86°F).
Conductors rated for 90°C or in free air have higher ampacities and may
provide smaller wire sizing than indicated in these tables. In addition,
higher ambient temperatures reduce wire ampacity and increase the wire sizing
requirements.
Voltage drops due to longer wire distances is another factor to be considered.
Good system design generally requires larger wire sizes that limit voltage
drop losses to 2% or less.
Use Table 6 to determine the minimum size for the DC Battery cables.
Table 6: Minimum Battery Cable Size – 75°C rated Copper
Model Power Rating | Wire in a Raceway, Cable, or Earth @30°C |
---|---|
12 Vdc Model | 24 Vdc Model |
150 W | 10 AWG |
300 W | 8 AWG |
700 W | 2 AWG |
1,000 W | N/A |
1,250 W | N/A |
2,500 W | N/A |
See Appendix A for more detailed wire sizing information including tables for
90°C copper wire, wiring in free air, higher ambient temperatures, and voltage
drop distance tables for maximum 2% voltage drop in the DC battery cables.
Use Table 7 to determine the minimum size for the AC output wires.
Table 7: Minimum AC Output Wire Size – 75°C rated Copper
Model Power Rating | AC Wire Size |
---|---|
120 Vac & 127 Vac Models | 220 Vac & 230 Vac Models |
150 W | 14 AWG (1 mm2) |
300 W | 14 AWG (1 mm2) |
700 W | 14 AWG (1.5 mm2) |
1,000 W | 14 AWG (1.5 mm2) |
1,250 W | 14 AWG (1.5 mm2) |
2,500 W | 10 AWG (4 mm2) |
2.8.4 Grounding and Bonding Requirements
A proper grounding system is required for safety, equipment protection and
electromagnetic noise reduction.
There must be a DC ground bond and a chassis equipment grounding connection.
See Sections 2.8.5.1 and 2.8.5.2 for equipment ground and DC grounding
electrode conductor wire sizing.
The DC input is isolated from the AC output and chassis so the inverter can
have a positive or negative DC system ground depending on the application. DC
system grounding is the responsibility of the installer.
2.8.4.1 AC Neutral-Ground Bond
An AC neutral-ground bond is required in North America. Therefore, all 120 Vac
/ 60 Hz models include, by default, an internal bond to earth ground as a
factory connection between the AC neutral circuit and the metal chassis.
Note that removing the internal Neutral-Ground bond with a 120 V, 60 Hz model
without an external neutral ground bond will void the certifi cation. For all
other models (127 V, 230 V and 240 V), the AC output is fl oating, isolated
from the chassis, with no neutral to ground bond between the neutral AC
terminal and the metal chassis. If local code requires an AC neutral to ground
bond or is otherwise required for the system with the 127 V, 230 V or 240 V
models, there is an internal neutral-ground jumper wire (included) which can
be used to connect the neutral terminal to the chassis.
When a neutral-ground bond is required with a SureSine model that has an AC
receptacle, the internal neutral-ground jumper must be connected and the
chassis must be bonded to ground.
2.8.4.2 Internal Neutral-Ground Bond vs. External Neutral-Ground Bond
When a neutral-ground bond is required with a SureSine model that has AC
terminals, the neutral-ground bond can be connected internally or externally.
Having the internal neutral-chassis bond with the chassis bonded to ground
provides a neutral-ground bond at the inverter AC power source and may be
required by local code. However, an external neutral ground bond may be
preferred or in some cases required.
An example of when an external neutral-ground bond may be required is for a
system that has an external single pole AC transfer switch with another AC
power source such as a generator or utility AC power so they share the same
neutral-ground bond at all times.
If there is a double pole transfer switch which isolates both the line and
neutral from another AC power source, the internal neutral-ground bond can be
used with a separate neutral-ground bond for the other AC power source. This
would be required with mobile applications (RV,marine etc.)
where the inverter neutral is bonded to the vehicle or ship metal frame and
grid (shore) power is bonded to the “shore” earth ground.
For 120 V / 60 Hz “-HW” (hardwired) models the neutral-ground jumper can be
removed to allow for an external AC neutral bond to ground.
Removing the internal Neutral Ground with a 120 V, 60 Hz model that have AC
terminals without an external Neutral Ground bond will void the safety certifi
cation. Consult with local jurisdiction before removing any existing bonding
jumper to ensure that it meets local code requirements.
Neutral-ground bond installation requirements are as follows.
- One and only one AC neutral-ground bond can be present in the system.
- There must be no internal ground bond if there is an external AC ground bond.
- Connecting or disconnecting the internal ground bond can only be performed by qualifi ed personnel and requires tool access to the interior of the inverter.
- Removal of the internal neutral ground bond with 120 V / 60 Hz should only be done with models which include AC terminals.
2.8.4.3 Internal Neutral-Ground Bond Jumper Wiring Instructions SureSine Inverter Cover Removal:
- The cover of the SureSine inverter needs to be removed in order to access the Neutral-Ground Bond Jumper wire terminals.
- Lay the SureSine inverter on a fl at surface with no wires connected to the inverter. Ensure that no DC power wires are connected to the DC terminals before removing the cover.
- Remove the fi ve (5) screws of the AC faceplate to detach it from the inverter.
- Then remove the top three (3) screws of the DC faceplate and pull the top plate off from the inverter if required.
- The jumper wire is connected to the AC neutral and chassis screws as indicated in Figure 19 and Figure 20. Use a torque of 22 in-lbs / 2.5 Nm when replacing screws.
Replacing the SureSine Inverter Cover:
- Place the top cover of the inverter with the slotted edges fully inserted into the groves of the chassis. The cover may need to be pushed into place with a good deal of pressure to fully seat it to the chassis.
- Insert and tighten the fi ve (5) screws at the top of the DC faceplate attaching it to the top chassis cover. Do not tighten any of the screws to torque before they are all inserted correctly to avoid stripping the screws.
- Place the AC faceplate back onto the end of the chassis and insert and tighten the (5) 5 screws securing it to the chassis. Do not tighten any of the screws to torque before they are all inserted correctly to avoid stripping the screws.
2.8.5 Grounding Connections
U.S. installed grounding systems must conform to all U.S. National Electrical
Code (NEC) requirements, and/or to any local regulations. Non-U.S. grounding
systems must meet all national and local requirements of the country of
installation.
NOTE: Resistive-earthed systems are acceptable.
Use only one grounding electrode unless multiple grounding electrodes are
reliably bonded together.
All grounding conductors must conform to local codes and regulations.
NOTE: Conductors identifi ed by the color green (or green and yellow)
shall only be used for grounding purposes.
Interrupt all power input to the SureSine before working on the grounding
system.
2.8.5.1 Chassis Ground
The SureSine chassis grounding terminal is located on the outside of the case
as shown in the DC wiring diagrams in Section 2.8.6. Use copper wire to
connect the chassis grounding terminal, and other dead metal, to earth ground.
A ring wire terminal is required for stranded copper wiring.
A terminal is not required for solid copper wiring.
Use Table 8 to size the equipment grounding wire for the chassis based on the
DC over-current protection rating per NEC requirements.
Table 8: Minimum Wire Sizes for Copper Ground Cable
Over Current Protection Device Rating (Amps)| Minimum Copper Wire Size
(AWG / mm 2 )
---|---
15| #14 / 2.08
20| #12 / 3.31
30-60| #10 / 5.26
100| #8 / 8.36
200| #6 / 13.3
If the equipment ground wiring is combined with other equipment grounding wiring to a common bus bar, the equipment grounding wire sizing requirement from the bus bar to ground is sized to the highest overcurrent protection rating of the DC System.
2.8.5.2 DC System Ground
Ensure that the DC system ground is properly bonded to ground.
NEC Section 250.166(B) states that the DC Grounding Electrode Conductor (GEC)
must be sized not smaller than the largest DC conductor in the system, and not
smaller than the 8 AWG. However, NEC Section 250.166(C) indicates that for DC
GEC connections to rod, pipe, or plate grounding electrodes, #6 AWG is
adequate.
If the system grounding and equipment grounding is combined to a common bus
bar, the earth ground wiring must be sized to the larger of the two.
The internal AC neutral-ground bond is grounded with the chassis equipment
grounding.
If the AC Neutral internal bond jumper is removed, an external AC neutralearth
bond is required. For details, refer to Figure 17 in Section 2.8.4.2.
2.8.6 DC Connections
DC Connections will vary by site application. The SureSine Inverter can
support 12-volt, 24-volt, and 48-volt battery systems.
| WARNING: HAZARDOUS CURRENT, RISK OF FIRE OR EXPLOSION
---|---
• Do NOT allow the positive (+) DC cable to touch the Negative (–) DC cable.
Allowing these cables to touch can create dangerous current or a possible fi
re/explosion hazard.
• Locate battery breakers or fused disconnects for easy access and free from
hydrogen gas/sulfuric acid fumes. The battery DC circuit breaker or fuse
should be within 6 inches from the battery bank or as close as possible.
| IMPORTANT:
---|---
• Since battery banks can vary widely, the DC wiring illustrations do not show
individual batteries or their connections. Consult the system designer and
installer for proper cabling of the specifi c site confi guration.
• Be certain that the battery connection is made with correct polarity. The
SureSine has battery reverse polarity protection implemented with an internal
fuse which will have to be replaced if connected with reverse polarity.
• Secure the cable to the battery bank following industry Best Practices.
Hardware may vary depending on site application and local regulatory code.
• Measure the voltage on the open battery wires BEFORE connecting to the
SureSine. Ensure the correct voltage of the battery is used with the selected
model to be installed.
• A circuit breaker or fuse is required in the ungrounded battery cable. See
Section 2.8.2 Over-current Protection Requirements for more information.
• Refer to Section 2.8.2 Over-current Protection Requirements for recommended
DC battery circuit breaker/fuse ratings and Section 2.8.3 DC
and AC Power Wire Sizing Requirements for DC battery wire sizing.
• Use a proper crimping Tool to crimp the terminals to the bare ends of the
wires where required. Connections should be tight so they can’t slide out.
2.8.6.1 Negative Grounding
For wiring diagrams showing NEGATIVELY grounded DC Wiring:
- For 150 W & 300 W Models: See Figure 21 on page 27
- For 700 W, 1,000 W, 1,250 W & 2,500 W Models: See Figure 23 on page 28
2.8.6.2 Positive Grounding
For wiring diagrams showing POSITIVELY grounded DC Wiring:
- For 150 W & 300 W Models: See Figure 22 on page 27
- For 700 W, 1,000 W, 1,250 W & 2,500 W Models: Figure 24 on page 28
2.8.6.3 DC Wiring Procedure
STEP 1. Before wiring, verify that all breakers are in the
open/disconnected position, and that all fuses are removed from the holders.
STEP 2. Connect a battery cable between the grounded battery bank post
(–) for a negative grounded system or (+) for a positive grounded system) and
inverter battery terminal of the same polarity.
STEP 3. Connect a battery cable to the ungrounded DC input terminal (+)
for a negative grounded system or (–) for a positive grounded system).
STEP 4. Wire a breaker or in-line fused disconnect switch in the
ungrounded battery cable no further than 12” (305 mm) from the ungrounded
battery post. When wiring a fused disconnect switch, make sure the fuse is
between the battery and the switch. Make sure the breaker or disconnect switch
is in the OPEN position. Do not connect the ungrounded battery cable to the
battery at this time.
| WARNING: SHOCK HAZARD
---|---
Do not close the battery breaker or disconnect switch until all system wiring
is completed.
|
---|---
2.8.7 AC Connections
| WARNING: SHOCK HAZARD
---|---
This unit is not provided with a GFDI device. This inverter must be used with
an external GFDI device as required by the Article 690 of the National
Electrical Code for the installation location.
| CAUTION: EQUIPMENT DAMAGE
---|---
• AC loads should not exceed the continuous and surge power ratings.
Exceeding these ratings could cause a fault and shut off the inverter. Loads
that have inrush currents that can exceed the highest power surge current
rating could damage the inverter.
• There are many types of loads that have high starting surges including
pumps, fans, refrigerator or air conditioner, air compressors, electric
motors,
switched mode power supplies, and power tools. These loads can have a power
surge of 2 to 5 times the running power of the load or even higher. If
the manufacturer does not provide a surge rating for the load, check with the
manufacturer or multiply the maximum power by an appropriate sizing factor
for the type of load being used. If there are other loads in the system, the
surge power requirement must be added to the total running power of the other
loads in the AC system.
• Observe AC output voltage and frequency markings on the SureSine. Be sure AC
loads are compatible for proper load operation and to avoid damage to
loads and/or inverter.
Models which include AC terminals require permanent, hardwired AC connections.
This may require additional hardware such as sub-panels, circuit breakers,
fuses, disconnect switches or ground-fault circuit interrupter (GFCI) breakers
or outlets. AC wiring must comply with local regulatory code for the specifi c
site.
No additional AC wiring is required with models that come factory wired with
an AC outlet. A Ground Fault Interrupter power strip or plug-in outlet is
recommended.
2.8.8 AC Wiring
The 150 W, 300 W, and 700 W Models comes either factory-wired or have the
option of being hardwired. The 1,000 W , 1,250 W, and 2,500 W Models require
permanent, hardwired connections. Wiring must comply with local regulatory
code for the specific site.
| WARNING: RISK OF FIRE
---|---
Ensure wire sizes comply with local regulatory code.
| IMPORTANT:
---|---
• A circuit breaker or fuse is required on the hot AC line wire near the
inverter.
• Refer to Section 2.8.2 for recommended AC circuit breaker/fuse ratings
• Refer to Section 2.8.3 DC and AC Power Wire Sizing Requirements for AC wire
sizing.
• Use a proper crimping tool to crimp the terminals to the bare ends of the
wires where required. Connections should be tight so they can’t slide out.
• There must be one and only one AC neutral ground bond. Do not install The
SureSine inverter with an external neutral-ground bond unless the internal
neutral-ground bond has been removed. Refer to Section 2.8.4.1 for details.
A three-conductor copper cable with at least a 75°C insulation rating can be used for wiring the AC circuits.
2.8.8.1 AC Wiring Procedure
STEP 1. Before wiring, verify that the AC Output Mode Switch is in the Center/
OFF position, all breakers in the system are in the open/ disconnected
position, and all fuses are removed from the holders.
STEP 2. Connect the earth/ ground wire between the Earth terminal of the
SureSine inverter and the earth ground connection of the AC device, AC
receptacle, or AC distribution panel.
STEP 3. Connect the AC Neutral wire between the AC neutral terminal of the
SureSine inverter and the neutral connection of the AC receptacle or AC
distribution panel. Ensure that the distribution panel does not have a neutral
ground connection.
STEP 4.
a. Connect the AC line wire between the AC Line terminal of the SureSine
inverter and the fuse or AC circuit breaker.
b. Then connect another wire between the fuse or AC circuit breaker and
the line connection of the AC receptacle or AC distribution panel.
2.9 Check Wiring and Power Up
- Review wiring steps and double-check all wiring and connections.
- Verify that the battery is wired with correct polarity to the SureSine.
- Connect the ungrounded battery cable to the ungrounded battery post.
| WARNING: RISK OF EXPLOSION
---|---
Connecting the battery to the SureSine with the breaker or disconnect closed will cause a spark at the point of connection. There is a RISK OF EXPLOSION in hazardous areas or locations where explosive gases have accumulated. - Close the battery breaker or disconnect switch to power up the inverter.
- One of the SureSine LEDs will fl ash red during startup and then the Status LED should illuminate solid Green indicating successful startup and no faults.
- Use the SureSine AC Output Mode Switch to turn on and off the AC output of the inverter. See Table 9 on page 32 for the AC output power status LED.
OPERATION
3.1 LED Indications
Two Light Emitting Diodes (LEDs) are on the front of the unit to provide
Status and AC Output Status. Table 9 defi nes what the LEDs represent.
Table 9: LED Indications
STATUS LED 1 | AC Output LED | Operation or State |
---|---|---|
OFF | OFF | No power or Battery below 9.5 V |
GREEN | OFF | AC Output OFF |
GREEN | GREEN | AC Output ON |
GREEN | GREEN (BLINK)2 | AC Standby Mode |
GREEN | RED (BLINK)2 | Low Voltage Disconnect (LVD) Warning |
GREEN | RED | Low Voltage Disconnect (LVD) |
RED | RED (BLINK)2 | Inverter or System Fault 3 (Recoverable) |
RED | RED | Inverter or System Fault 3 (Critical Fault. Requires a reboot.) |
1 The Status LED flickers ON very briefly when the LED is OFF. The Status LED
flickers OFF very briefly when the LED is GREEN or RED solid. The “heartbeat”
occurs every 5 seconds.
2 0.5 Hz. Rate
3 See Section 3.4 on page 34 for more information concerning faults.
3.2 Ethernet Jack LEDs
In addition to the STATUS and AC Output LEDs, two (2) small LEDs can be found
on the Ethernet RJ-45 jack. These LEDs indicate the LAN/WAN network link and
activity status as follows:
Table 10: Ethernet Jack LED Indications
Condition | Green LED | Yellow LED |
---|---|---|
Network Connection OK | ON | OFF |
Network Activity | ON | Blinking |
Error | OFF | ON |
3.3 AC Output Mode Switch Operation
The AC Output Mode Switch will always turn the inverter on directly in the ON
(up) position. To enable ON/OFF control with a wired remote switch or a
communication command (digital command), the switch must be in the REMOTE
position. Select remote switch or digital command using DIP Switch # 1.
3.4 Protections
3.4.1 Low Voltage Disconnect (LVD)
The SureSine will disconnect AC Output when the battery discharges below the
Low Voltage Disconnect (LVD) set point (after a 4-minute delay).
AC Output will resume when the battery has recharged to Low Voltage Reconnect
(LVR) set point. The LVD/LVR thresholds are adjustable using DIP Switch 4. See
“Adjusting Settings” on page 11 for details.
Audible LVD Warnings:
- The SureSine will beep four (4) times when the battery discharges to the LVD Warning threshold voltage.
- The SureSine will beep twice when Low Voltage Disconnect occurs.
- The LVD Warning occurs 0.3 V above the selected LVD threshold.
3.4.2 High Voltage Disconnect (HVD)
The SureSine will shut down and disconnect AC Output if battery voltage
exceeds 15.5 V. It will automatically reconnect when the battery voltage
decreases to 14.5 V.
3.4.3 High Temperature Disconnect (HTD)
If the SureSine heat sink temperature rises above 95°C, an HTD fault will
occur and the SureSine will disconnect the AC Output. Normal operation will
automatically resume when the heat sink cools to 80°C.
3.4.4 Over Current and Short Circuit Protection (Critical Fault)
The SureSine inverter has full electronic protection against AC overloads and
short circuits on AC Output. Three (3) automatic retries will be attempted
every 10 seconds.
If a short circuit still persists after three (3) retries, the fault must be
manually cleared in one of the following ways:
a. Disconnect, then reconnect battery power.
b. Use the SureSine Utility Mobile app to send a Reset command.
COMMUNICATION OPTIONS
The SureSine Inverter line provides communication options to monitor system data and control operations using a computer or mobile device. The SureSine Inverter comes with the following communication options:
-
All Models:
– Bluetooth for wireless communication to a computer or mobile device
– EIA-485 for connection to a ModBus™ EIA-485 serial network with other devices in the system which may include other SureSine inverters, Morningstar products, and 3rd-party equipment
– (Future Feature Improvement) MS-CAN (Morningstar Communication Area Network) for a wired communication connection to other Morningstar products
– Figure 29 shows the location of the communication ports for the 150 W and 300 W models.
– Figure 30 shows the locations of the communication ports for the 700 W to 2,500 W models. -
700 W to 2,500 W Models Only:
– Ethernet (for ModBus TCP/IP™ connection over WAN/LAN)
– USB Data Port for ModBus™ serial communications to a PC
Figure 29 shows the location of the communication ports for the 150 W and 300
W models.
Figure 30 shows the locations of the communication ports for the 700 W to
2,500 W models.
|
---|---
ModBus™ and ModBus TCP/IP™ are non-proprietary open standard protocols for
serial and Ethernet networks. The ModBus™ specifi cation document is available
from the SureSine Product page at
https://www.morningstarcorp.com/products/suresine/.
The ModBus™ specifi cation document provides details on register locations,
scaling, and variable defi nitions. ModBus™ software can be used to monitor,
control and program the SureSine inverter.
The factory default Modbus ID = 1
Using communication options may require changing DIP Switch 7 for Ethernet
Security and/or DIP Switch 8 to enable the Bluetooth feature.
- See Table 1 on page 12 for details on DIP Switch Settings.
- See Section 4.1 for details about Ethernet Security.
- See Section 4.2 for information about the Bluetooth feature.
4.1 Ethernet Security
When DIP switch 7 is set to disabled, write commands over Ethernet to the
SureSine are not allowed. This includes the control commands (on/off, reset
control, etc) and adjustments to custom set points and network settings. It
does not affect remote monitoring over Ethernet.
Write commands are always enabled with the EIA-485 or USB local serial ports.
DIP Switch 7 also does not affect the ability to change custom settings or
send commands using the Bluetooth app.
This is a safety feature to prevent unintended changes to custom settings, but
it is not a replacement for proper network security.
4.2 Bluetooth
Bluetooth is for connecting a mobile device to the SureSine Inverter. DIP
Switch #8 must be enabled (ON) for this feature to function. See Section 2.4
on page 11 for details on enabling this feature.
4.2.1 To Connect the SureSine using Bluetooth
- Set the AC Output Mode Switch to REMOTE.
- Make sure the Bluetooth feature on your digital device is turned ON.
- See Section 4.2.2 on page 38 for instructions on downloading and installing the SureSine Utility Mobile App to your digital device.
- Use the SureSine Utility mobile app to control and monitor the activities of the SureSine Inverter.
4.2.2 SureSine Mobile Utility App
The SureSine inverter has a Mobile Utility App available for monitoring and
settings adjustments, and fi rmware updates. This app is designed for Android
and Apple (coming soon) devices and connects using Bluetooth.
See Section 5.0 for fi rmware update information.
The SureSine Mobile Utility App will be available at Google Play and Apple App
stores.
4.3 Ethernet (for ModBus TCP/IP™)
The Ethernet port provides an interface between the SureSine inverter and a
LAN/ WAN network or the Internet. The SureSine supports Ethernet
communications using ModBus TCP/IP™ protocol..
The RJ-45 Ethernet jack features two (2) indicator LEDs for connection status
and network traffi c.
The Factory Default Network Settings are as follows.
- IP 192.168.1.253
- Subnet Mask 255.255.255.0
- Gateway 192.168.1.1
- Primary DNS Server 192.168.1.1
- Secondary DNS Server 192.168.1.1
- ModBus™ TCP/IP Port 502
The controller’s MAC Address is located on the serial label on the side of the
controller.
The factory default ModBus ID = 1.
The Network Settings can be changed using ModBus™.
4.3.1 To Connect to a Local Area Network or to the Internet
- Insert one end of a CAT5, CAT6, or CAT7 cable into the Ethernet port on the SureSine Inverter.
- Insert the other end of that cable into a router or Ethernet Switch.
- Connect using the ModBus™ software of choice.
The factory default ModBus™ ID = 1.
A network diagram is shown in Figure 33. The SureSine can also be connected
directly to a PC using an Ethernet cross-over cable. 4.4 EIA-485 Device
Communication
EIA-485 is a networking standard for serial communication between multiple
devices on a bus. The EIA-485 port on the SureSine inverter is for connecting
to one or more devices on an EIA-485 network through the open standard ModBus™
protocol.
Morningstar EIA-485 devices include the GenStar, TriStar-MPPT-60/M (150 and
600 V) models, or with other Morningstar products with the RSC-1 Serial-to-
EIA-485 Adapter.
The TriStar-MPPT Charge Controller and RSC Serial adapters require an external
12 V power source to enable the EIA-485 communications. The 12 Vdc Auxiliary
Power feature of 700 W to 2,500 W models can be used, therefore, to power
Morningstar EIA-485 devices in an EIA-485 Network.
For more information on EIA-485 networking, refer to the Morningstar Product Connectivity Manual, Networking & Communications, at https://www.morningstarcorp.com/wp-content/uploads/2014/02/MS-Comm- Document-2010.pdf.
4.4.1 To Connect the SureSine Inverter to an EIA-485 Device
- Connect the A and B wires from the EIA-485 device to the A and B terminals on the DC Side of the SureSine Inverter.
- Connect the other ends of the A and B wires to the EIA-485 device.
- If using the Auxiliary Power feature of a SureSine 700 W to 2,500 W model to power Morningstar EIA-485 devices in an EIA-485 Network:
• connect the Ground (GND) terminal wire from the EIA-485 device(s) to the –12 V terminal of the SureSine inverter
• connect the Power terminal wire from the EIA-485 device(s) to the (+12 V) terminal of the SureSine inverter.
Note: The 12 V Auxiliary Power rating is 1 Watt which will limit the number of EIA-485 devices that can be powered.
4.5 USB Port
A USB port is available on the 700 W, 1,000 W, 1,250 W, and 2,500 W models.
The USB port can be used for ModBus™ communications. This port requires a
USB-A plug. If connecting a computer, a USB-to-USB cable is required.
Note: USB-B and USB-C are backwards compatible with USB-A.
The factory default ModBus ID = 1.
4.6 MS-CAN (Future Feature)
MS-CAN is for communicating with other Morningstar components within the
network.
This feature is not available at this time. Check the Morningstar website
(www.morningstarcorp.com) for updates. Note:
The Morningstar component must be MS-CAN enabled.
4.6.1 To Connect the SureSine to another Morningstar Device
- Insert one end of an RJ-45 cable (CAT5, CAT6, or CAT6e) into the MS-CAN IN port on the SureSine Inverter.
- Insert a terminator resister into the MS-CAN OUT port, if no other Morningstar devices are to be connected.
- Connect the other end of the RJ-45 cable to the other Morningstar device.
4.6.2 To Connect the SureSine to a Morningstar Network
- Insert one end of an RJ-45 cable (CAT5, CAT6, or CAT6e) into the MS-CAN OUT port on the fi rst device in the daisy chain.
- Insert the other end of that RJ-45 cable into the MS-CAN IN port on the SureSine Inverter.
- Insert another RJ-45 cable into the MS-CAN OUT port on the SureSine Inverter.
- Insert the other end of the RJ-45 cable into the MS-CAN IN port on the next Morningstar device in the network.
- Insert a 120 Ohm CANBUS terminator resister into the MS-CAN OUT port on the fi nal device, if no other Morningstar devices are to be connected.
FIRMWARE UPDATE PROCEDURE
To update the SureSine fi rmware, use the SureSine Utility Mobile App to
activate the fi rmware update. The SureSine Mobile Utility App includes the
latest version of the SureSine fi rmware when installing or updating the app.
Select the fi rmware update icon on the bottom right of the mobile app and
follow the directions on the screen to update the firmware.
SPECIFICATIONS
6.1 SureSine Model Numbers
Figure 41 defi nes the SureSine Model numbers and how they relate to the
product specifi cations.
Use Figure 41 to choose the SureSine model number from the list in Table 11.
- B = North American Type B
- HW = Hardwired
- UNI = Universal
Table 11: SureSine Model Numbers
Battery Voltage | Continuous Power in Watts |
---|---|
150 W | 300 W |
12 Vdc | SI-150-12-120- 60-B |
SI-150-12-120- 60-HW | SI-300-12-120- 60-HW |
SI-150-12-127- 60-HW | SI-300-12-127- 60-HW |
SI-150-12-127- 60-UNI | SI-300-12-127- 60-UNI |
SI-150-12-220- 60-HW | SI-300-12-220- 60-HW |
SI-150-12-220- 60-UNI | SI-300-12-220- 60-UNI |
SI-150-12-230- 50-HW | SI-300-12-230- 50-HW |
SI-150-12-230- 50-UNI | SI-300-12-230- 50-UNI |
24 Vdc | SI-150-24-120- 60-B |
--- | --- |
SI-150-24-120- 60-HW | SI-300-24-120- 60-HW |
SI-1000-24-120- 60-HW | SI-1250-24-120- 60-HW |
SI-150-24-127- 60-HW | SI-300-24-127- 60-HW |
SI-150-24-127- 60-UNI | SI-300-24-127- 60-UNI |
SI-150-24-220- 60-HW | SI-300-24-220- 60-HW |
SI-150-24-220- 60-UNI | SI-300-24-220- 60-UNI |
SI-150-24-230- 50-HW | SI-300-24-230- 50-HW |
SI-1000-24-230- 50-HW | SI-1250-24-230- 50-HW |
SI-150-24-230- 50-UNI | SI-300-24-230- 50-UNI |
48 Vdc | SI-150-48-120- 60-B |
SI-150-48-120- 60-HW | SI-300-48-120- 60-HW |
SI-1000-48-120- 60-HW | SI-1250-48-120- 60-HW |
SI-150-48-127- 60-HW | SI-300-48-127- 60-HW |
SI-1000-48-127- 60-HW | SI-1250-48-127- 60-HW |
SI-150-48-127- 60-UNI | SI-300-48-127- 60-UNI |
SI-150-48-220- 60-HW | SI-300-48-220- 60-HW |
SI-1000-48-220- 60-HW | SI-1250-48-220- 60-HW |
SI-150-48-220- 60-UNI | SI-300-48-220- 60-UNI |
SI-150-48-230- 50-HW | SI-300-48-230- 50-HW |
SI-1000-48-230- 50-HW | SI-1250-48-230- 50-HW |
SI-150-48-230- 50-UNI | SI-300-48-230- 50-UNI |
6.2 Technical Specifi cations
The following tables provides the specifi cations for the SureSine Inverter
Industrial Line.
Table 12: Specifi cations for the SureSine 150 and SureSine 300
Specification | Model |
---|---|
SureSine 150 | SureSine 300 |
Rated Battery Voltage | 12 V |
Battery Operational Voltage Range | 10.0 to 16.5 V |
66.0 V | 10.0 to 16.5 V |
Maximum Continuous DC Input Current | 18 A |
AC Output Voltage (Frequency) Options | 120 V (60 Hz) / 230 V (50 Hz) / 127 V |
(60 Hz) / 220 V (60 Hz.)
Maximum Continuous AC Output Current| 120 V| 1.25 A| 2.5 A
230 V| 0.65 A| 1.3 A
127 V| 1.7 A| 2.4 A
220 V| 0.7 A| 1.4 A
Continuous AC Output Power @ 40°C| 150 W| 300 W
Power Surge @40°C (< 5 sec)| 300 Watts| 600 W
1 minute Surge Power @ 40°C| 225 Watts| 450 W
3 minute Surge Power @ 40°C| 180 Watts| 360 W
Peak Efficiency| 89%| 89%| 90%| 91%| 91%| 92%
Total Harmonic Distortion (THD )| < 2%
Self-Consumption| AC ON| 2.6 W| 3.9 W
AC OFF or Standby| 0.65 W| 0.65 W
Transient Surge Protection| Battery and AC Loads
Auxiliary Power| Not Available
Remote Switch| Yes
Product Weight (lbs. / kg)| 9.6 lbs. / 4.4 kg| 12.5 lbs. / 5.7 kg
Shipping Weight| 11 lbs. / 5.0 kg| 13.5 lbs. / 6.2 kg
Dimensions (L × W × H) (Factory-wired Models)| 12.3″ x 7.5″ x 3.78″
(312 mm × 190 mm × 96 mm)| 13.0″ x 7.5″ x 3.78″
(337 mm × 190 mm × 96 mm)
Dimensions (L × W × H) (Hardwired Models)| 12.6″ x 7.5″ x 3.78″
(321 mm × 190 mm × 96 mm)| 13.0″ x 7.5″ x 3.78″
(346 mm × 190 mm × 96 mm)
Mechanical:
Battery Power Stud Bolt Size / Torque| M8 (~5/16″); 20 in-lbs. / 2.3 Nm; hand
tighten
AC Power Stud Size / Torque| M6 (~1/4″); 20 in-lbs. / 2.3 Nm
Grounding Terminal wire size / Torque| 14 – 2 AWG (2.5 – 10 mm2); 35 in-lbs. /
4 Nm
EIA-485/ Remote / Auxiliary plug-screw Block Terminals| 16 to 28 AWG (1.0 to
0.1 mm2); 5 in-lbs. / 0.57 nm
**** AC Receptacle Options| 120 V Models| N. A. NEMA 5, B-Type| N. A. NEMA 5,
B-Type
230 V Models| Universal A-L Type| Universal A-L Type
Table 13: Specifi cations for the SureSine 700 and SureSine 1000
Specification | Model |
---|---|
SureSine 700 | SureSine 1000 |
Rated Battery Voltage | 12 V |
Battery Operational Voltage Range | 10.0 to 16.5 V |
66.0 V | 20.0 to |
33.0 V
| 40.0 to
66.0 V
Maximum Continuous DC Input Current| 84 A| 38 A| 18.5 A| 54 A| 26.5 A
AC Output Voltage (Frequency) Options| 120 V (60 Hz) / 230 V (50 Hz) / 127 V
(60 Hz) / 220 V (60 Hz.)
Maximum Continuous AC Output Current
| 120 V| 5.8 A| 8.3 A
230 V| 3.0 A| 4.3 A
127 V| 5.5 A| 8.0 A
220 V| 3.2 A| 4.5 A
Continuous AC Output Power @ 40°C| 700 W| 1,000 W
Power Surge @40°C (< 5 sec)| 1,400 W| 2,000 W
1 minute Surge Power @40°C| 1,050 W| 1,500 W
3 minute Surge Power @40°C| 840 W| 1,200 W
Peak Efficiency| 91%| 92%| 92%| 93%| 93%
Total Harmonic Distortion (THD )| 2%
Self-Consumption
| AC ON| 9.4 W| 10.0 W
AC OFF or Standby| < 2.8 W| < 2.3 W
Transient Surge Protection| Battery and AC Loads
Auxiliary Power| 12 V, 1 W
Remote Switch| Yes
Product Weight (lbs. / kg)| 32.0 lbs. / 14.5 kg| 30.0 lbs. / 13.5 kg| 36.0
lbs. / 16.5 kg
Shipping Weight| 35.5 lbs. / 16.5 kg| 33.5 lbs. / 15.5 kg| 39.0 lbs. / 18.0 kg
** Dimensions (L × W × H) (Factory-wired Models)| 12 V ONLY:
20.63″ x 9.72″ x 6.14″ (524 mm × 247 mm × 156 mm)| 24 V & 48 V:
18.23″ x 9.72″ x 6.14″ (463 mm x 247 mm x 156 mm)| N/A
** Dimensions (L × W × H) (Hardwired Models)| 12 V ONLY:
21.2″ x 9.72″ x 6.14″ (538 mm × 247 mm × 156 mm)| 24 V & 48 V:
18.83″ x 9.72″ x 6.14″ (477 mm x 247 mm x 156 mm)| 24 V & 48 V:
21.2″ x 9.72″ x 6.14″ (538 mm x 247 mm x 156 mm)
Mechanical:
Battery Power Stud Bolt Size / Torque| M6 (~1/4″); 35 in-lbs. / 4 Nm
AC Power Stud Size / Torque| M6 (~1/4″); 20 in-lbs. / 2.3 Nm
Grounding Terminal wire size / Torque| 14 – 2 AWG (2.5 – 10 mm2); 35 in-lbs. /
4 Nm
EIA-485/ Remote / Auxiliary plug-screw block Terminals| 16 to 28 AWG (1.0 to
0.1 mm2); 5 in-lbs. / 0.57 Nm
AC Receptacle Options| 120 V Models| N. A. NEMA 5, B-Type| Not Available
230 V Models| Universal A-L Type| Not Available
See Table 15 for Common Specifi cations for all Models.
Table 14: Specifi cations for the SureSine 1250 and SureSine 2500
Specification | Model |
---|---|
SureSine 1250 | SureSine 2500 |
Rated Battery Voltage | 24 V |
Battery Operational Voltage Range | 20.0 to 33.0 V |
66.0 V
Maximum Continuous DC Input Current| 68 A| 33 A| 66 A
AC Output Voltage (Frequency) Options| 120 V (60 Hz) / 230 V (50 Hz) / 127 V
(60 Hz) / 220 V (60 Hz.)
Maximum Continuous AC Output Current| 120 V| 10.4 A| 21.0 A
230 V| 5.4 A| 11.0 A
127 V| 10.0 A| 20.0 A
220 V| 5.7 A| 11.5 A
Continuous AC Output Power @ 40°C| 1,200 W| 2.500 W
Power Surge @40°C (< 5 sec)| 2,500 W| 5,000 W
1 minute Surge Power @40°C| 1,875 W| 3,750 W
3 minute Surge Power @40°C| 1,500 W| 3,000 W
Peak Efficiency| 93%| 94%| 95%
Total Harmonic Distortion (THD )| 2%
Self-Consumption| AC ON| 9.4 W| 10.0 W
AC OFF or Standby| < 2.8 W| < 2.3 W
Transient Surge Protection| Battery and AC Loads
Auxiliary Power| 12 V, 1 W
Remote Switch| Yes
Product Weight (lbs. / kg)| 39.0 lbs. / 17.5 kg| 59.0 lbs. / 27.0 kg
Shipping Weight| 42.5 lbs. / 19.5 kg| 63.0 lbs. / 28.5 kg
Dimensions (L × W × H) (Factory-wired Models)| N/A| N/A
Dimensions (L × W × H) (Hardwired Models)| 21.2″ x 9.72″ x 6.14″ (538 mm x 247
mm x 156 mm)| 23.04″ x 9.72″ x 7.48″ (584 mm x 247 mm x 190 mm)
Mechanical:
Battery Power Stud Bolt Size / Torque| M6 (~1/4″); 35 in-lbs. / 4 Nm
AC Power Stud Size / Torque| M6 (~1/4″); 20 in-lbs. / 2.3 Nm
Grounding Terminal wire size / Torque| 14 – 2 AWG (2.5 – 10 mm2); 35 in-lbs. /
4 Nm
EIA-485/ Remote / Auxiliary plug-screw block Terminals| 16 to 28 AWG (1.0 to
0.1 mm2); 5 in-lbs. / 0.57 Nm
**** AC Receptacle Options| 120 V Models| Not Available| Not Available
230 V Models| Not Available| Not Available
See Table 15 for Common Specifi cations for all Models.
Table 15: Common Specifi cations for all Models
|
---|---
Features| Waveform – Pure Sine Wave
Galvanically Isolated
Cooling – Fanless natural convection
Electronic Protections| AC Output Short Circuit
AC Output Overload
High Heat Sink Temperature – Load Disconnect
Battery Reverse Polarity – Replaceable internal fuse
Heat Sink Temperature: Warning 90°C; Fault > 95°C; Recovery 80°C
Environmental| Storage Temperature Range: -40°C to +60°C
Operating Temperature Range – 40°C to +60°C
Humidity – 100% non-condensing
Enclosure IP Rating: IP 20
Altitude – 2,000 meters
Communications| MODBUS RS-485
MS-CAN
MODBUS over Ethernet (700 Watts and above only)
USB (700 Watts and above only)
Wireless Communications Bluetooth (Android and Apple)
Data Storage 4 MB / 5 years internal 4 MB / 5 years internal
Warranty| 5 Years
Table 16: Low Voltage Disconnect Settings
Low Voltage Disconnect Factory Default & Presets (All Models)| 12-volt
Models| 24-volt Models| 48-volt Models
---|---|---|---
LVD| LVR| Alarm| LVD| LVR| Alarm| LVD|
LVR| Alarm
Factory Default Settings (DIP 4 OFF)| 11.8| 12.8| 12.1| 23.6| 25.6| 24.2|
47.2| 51.2| 48.4
Preset Low (DIP 4 ON, DIP 5 OFF)| 10.5| 11.6| 10.8| 21.0| 23.2| 21.6| 42.0|
46.4| 43.2
Preset High (DIP 4 ON, DIP 5 ON) | 11.5| 12.6| 11.8| 23.0| 25.2| 23.6| 46.0|
50.4| 47.2
*Note : DIP 4 in the OFF position allows the factory-default values to be
changed using the RS485 communication port or Bluetooth App, if needed. When
DIP 4 is in the OFF position, it disables DIP 5. So when DIP 4 is in the OFF
position, the position of DIP 5 is irrelevant.
APPENDIX A: DC BATTERY WIRE SIZING
Wire sizing requirements are based on the ampacity (or current carrying
capacity) of conductors. The NEC includes Ampacity Tables which are used to
determine the ampacity for a given wire size as indicated in Section 310.15.
The battery wire ampacity must be greater than or equal to 125% of maximum
continuous battery current of the SureSine inverter. If the inverter is not
intended to be used to full capacity smaller wires can be used but only with
an undersized breaker to ensure that the current will not exceed the current
carrying capacity of the wire.
Correction and adjustment factors may be required to account for the
following:
- maximum ambient temperature
- temperatures at different parts of the circuit (rooftops or engine rooms for example)
- wire terminal temperature ratings
- multi conductor cables
- conduit fi ll and other factors
The following tables provide the 1-way, maximum length for cables and wires
based on the system voltage and ampacity with a 2% voltage drop.
Table 17: Minimum Battery Wire Sizes – 75°C Rated Stranded Copper
Model| Max Battery Continuous Current| Wire Size in a raceway,
cable, or earth (NOTE: 1)| Wire Size in Free Air (NOTE 2)| Metric
Wire Size mm 2 (NOTE 3)
---|---|---|---|---
Watts| Volts| @30°C| 30° – 60°C| @30°C| 30°-45°C
150 W| 12 Vdc| 18 Amps| 10 AWG| 8 AWG > 55°C| 10 AWG| 10 AWG| > 4 mm2
150 W| 24 Vdc| 8 Amps| 14 AWG| 14 AWG| 14 AWG| 14 AWG| > 1.5 mm2
150 W| 48 Vdc| 4 Amps| 14 AWG| 14 AWG| 14 AWG| 14 AWG| > 1.5 mm2
300 W| 12 Vdc| 36 Amps| 8 AWG| 6 AWG > 35°C| 8 AWG| 6 AWG > 55°C| > 6 mm2
300 W| 24 Vdc| 16 Amps| 12 AWG| 10 AWG| 12 AWG| 10 AWG| > 4 mm2
300 W| 48 Vdc| 8 Amps| 14 AWG| 14 AWG| 14 AWG| 14 AWG| > 1.5 mm2
700 W| 12 Vdc| 84 Amps| 2 AWG| 1 AWG > 30°C
1/0 AWG > 55°C| 4 AWG| 3 AWG > 40°C
2 AWG > 50°C| > 25 mm2
700 W| 24 Vdc| 38 Amps| 6 AWG| 4 AWG > 50°C| 8 AWG| 6 AWG > 55°C| > 6 mm2
700 W| 48 Vdc| 18.5 Amps| 10 AWG| 8 AWG > 55°C| 10 AWG| 10 AWG| > 4 mm2
1,000 W| 24 Vdc| 54 Amps| 4 AWG| 3 AWG > 45°C| 6 AWG| 4 AWG > 50°C| > 16 mm2
1,000 W| 48 Vdc| 26.5 Amps| 8 AWG| 6 AWG > 55°C| 8 AWG| 8 AWG| > 6 mm2
1,250 W| 24 Vdc| 68 Amps| 3 AWG| 2 AWG > 40°C
1 AWG > 50°C| 6 AWG| 4 AWG > 40°C
3 AWG > 55°C| > 16 mm2
1,250 W| 48 Vdc| 33 Amps| 8 AWG| 6 AWG > 40°C
4 AWG > 55°C| 8 AWG| 6 AWG > 55°C| > 10 mm2
2,500 W| 48 Vdc| 66 Amps| 3 AWG| 2 AWG > 40°C
1 AWG > 50°C| 6 AWG| 4 AWG > 55°C| > 16 mm2
Note 1 : Per NEC 2023 [see NEC Table 310.16, formerly 310.15(b)(16)],
ampacity for not more than three current- carrying conductors in a raceway,
cable, or earth (buried)
Note 2: Per NEC 2023 [see NEC Table 310.17, formerly 310.15(b)(17)],
ampacity for conductors in free air
Note 3 : Estimated. See local code requirements for metric cable sizing
(70°C or 90°C)
Table 18: Minimum Battery Wire Sizes – 90°C Rated Stranded Copper
Model| Max Battery Continuous Current| Wire Size in a raceway,
cable, or earth (NOTE: 1)| Wire Size in Free Air (NOTE 2)
---|---|---|---
Watts| Volts| @30°C| 30° – 60°C| @30°C| 30°-45°C
150 W| 12 Vdc| 18 Amps| 10 AWG| 10 AWG| 10 AWG| 10 AWG
150 W| 24 Vdc| 8 Amps| 16 AWG| 16 AWG| 14 AWG| 16 AWG
150 W| 48 Vdc| 4 Amps| 16 AWG| 16 AWG| 14 AWG| 16 AWG
300 W| 12 Vdc| 36 Amps| 8 AWG| 6 AWG > 45°C| 8 AWG| 8 AWG
300 W| 24 Vdc| 16 Amps| 12 AWG| 10 AWG > 55°C| 12 AWG| 12 AWG
300 W| 48 Vdc| 8 Amps| 16 AWG| 16 AWG| 14 AWG| 16 AWG
700 W| 12 Vdc| 84 Amps| 3 AWG| 2 AWG > 35°C
1 AWG > 45°C| 4 AWG| 3 AWG > 50°C
700 W| 24 Vdc| 38 Amps| 8 AWG| 6 AWG > 40°C
4 AWG > 55°C| 8 AWG| 8 AWG
700 W| 48 Vdc| 18.5 Amps| 10 AWG| 10 AWG| 10 AWG| 10 AWG
1,000 W| 24 Vdc| 54 Amps| 6 AWG| 4 AWG > 35°C
3 AWG > 45°C| 6 AWG| 4 AWG > 50°C
1,000 W| 48 Vdc| 26.5 Amps| 8 AWG| 6 AWG > 55°C| 8 AWG| 8 AWG
1,250 W| 24 Vdc| 68 Amps| 4 AWG| 3 AWG > 40°C
2 AWG > 50°C| 6 AWG| 4 AWG > 40°C
3 AWG > 55°C
1,250 W| 48 Vdc| 33 Amps| 8 AWG| 6 AWG > 50°C| 8 AWG| 6 AWG > 55°C
2,500 W| 48 Vdc| 66 Amps| 4 AWG| 3 AWG > 40°C
2 AWG > 50°C| 6 AWG| 4 AWG > 55°C
Note 1 : Per NEC 2023 [see NEC Table 310.16, formerly 310.15(b)(16)],
ampacity for not more than three current-carrying conductors in a raceway,
cable, or earth (buried)
Note 2: Per NEC 2023 [see NEC Table 310.17, formerly 310.15(b)(17)],
ampacity for conductors in free air
Table 19: Celsius-to-Fahrenheit Conversions
°Celsius | °Fahrenheit |
---|---|
30 | 86 |
35 | 95 |
40 | 104 |
45 | 113 |
50 | 122 |
55 | 131 |
60 | 140 |
APPENDIX B: DC VOLTAGE DROP TABLES
Good system design generally requires large conductor wires that limit voltage drop losses to 2% or less. Table 20 and Table 21 provide wire sizing for a maximum of 2% voltage drop. Longer distance wire runs may require signifi cantly larger wire sizes to reduce the voltage drop to an acceptable level.
B.1 Voltage Drop Chart for 75°C or 90ºC Stranded Copper Wire (Feet), 12
Volt System
For 24- or 48-volt systems, multiply the values in Table 20 by:
- 2 for 24-volt systems
- 4 for 48-volt systems
Table 20: Maximum 1-way Distance (Feet), 2% Voltage Drop Chart for 75°C or 90ºC Stranded Copper Wire, 12-Volt System
Wire Size (AWG) | Amps |
---|---|
70 | 60 |
25 | 20 |
4/0 | 31.3 |
3/0 | 24.8 |
2/0 | 19.6 |
1/0 | 15.6 |
1 | 12.3 |
86.4 | |
2 | 9.8 |
68.6 | 85.7 |
3 | 7.8 |
67.9 | |
4 | 6.2 |
54.0 | 86.4 |
6 |
54.2
8| | | | 3.4| 3.8| 4.3| 4.9| 5.7| 6.8| 8.5| 11.4| 14.2| 17.1| 21.4| 34.2
10| | | | | | | 3.1| 3.6| 4.3| 5.4| 7.2| 8.9| 10.7| 13.4| 21.5
12| | | | | | | | | 2.7| 3.4| 4.5| 5.6| 6.7| 8.4| 13.4
14| | | | | | | | | | 2.1| 2.8| 3.5| 4.2| 5.3| 8.5
16| | | | | | | | | | | | 2.2| 2.7| 3.3| 5.3
| | | | | | | | | | | | | | |
B.2 Voltage Drop Chart for 75°C or 90ºC Stranded Copper Wire (Meters), 12
Volt System
For 24- or 48-volt systems, multiply the values in Table 21 by:
- 2 for 24-volt systems
- 4 for 48-volt systems
Table 21: Maximum 1-way Distance (Meters), 2% Voltage Drop Chart for 75°C or 90ºC Stranded Copper Wire, 12-Volt System
Wire Size (mm 2 ) | Amps |
---|---|
70 | 60 |
25 | 20 |
95 | 8.0 |
70 | 5.8 |
50 | 4.0 |
35 | 3.0 |
25 | 2.1 |
30.0
16| 1.4| 1.6| 1.7| 1.9| 2.1| 2.4| 2.7| 3.2| 3.8| 4.8| 6.3| 7.9| 9.5| 11.9|
19.0
10| | 1.0| 1.1| 1.2| 1.3| 1.5| 1.7| 2.0| 2.4| 3.0| 4.0| 5.0| 6.0| 7.5| 11.9
6| | | | 0.7| 0.8| 0.9| 1.0| 1.2| 1.4| 1.8| 2.4| 3.0| 3.6| 4.4| 7.1
4| | | | | | 0.6| 0.7| 0.8| 0.9| 1.2| 1.6| 2.0| 2.4| 3.0| 4.7
2.5| | | | | | | | 0.5| 0.6| 0.7| 1.0| 1.2| 1.5| 1.8| 2.9
1.5| | | | | | | | | | | | 0.6| 0.7| 0.9| 1.6
APPENDIX C: WARRANTY
The SureSine™ inverters are warrantied to be free from defects in materials
and workmanship for a period of FIVE (5) years from the date of shipment to
the original end user. Warranty on replaced units or fi eld-replaced
components, will be limited only to the duration of the original product
coverage.
Morningstar will, at its option, repair or replace any such defective unit.
C.1 Claim Procedure
Before requesting warranty service, check the operator’s manual, including
any troubleshooting section, to verify product failure.
To begin the warranty replacement process, contact your authorized Morningstar
distributor or dealer for assistance with troubleshooting and, if necessary,
obtaining an Return Material Authorization (RMA) number.
An RMA number must be issued by Morningstar prior to return of any unit(s)
under this warranty. Required RMA information:
(A) purchase location – business or company name – and date
(B) full model and serial numbers (SN is 8-digits on unit bar label)
(C) failure behavior, including LED indications
(D) array confi guration, panel Pmax, Voc, Vmp, Isc, and nominal battery
voltage; these specifi cations are needed to receive assistance.
(E) multi-meter available (for fi eld troubleshooting)
If the dealer is contacted, and is not able to assist with warranty claim,
contact Morningstar Tech support at
support@morningstarcorp.com. Provide
proof of date and place of purchase, and all details listed in preceding
paragraph.
C.2 Warranty Exclusions And Limitations
This warranty does not apply under the following conditions:
- Damage by accident, negligence, abuse or improper use
- PV or load currents exceeding the ratings of the product
- Unauthorized product modifi cation or attempted repair
- Damage occurring during shipment
- Damage resulting from acts of nature such as lightning, weather extremes, or infestation
WARRANTY
THE WARRANTY AND REMEDIES SET FORTH ABOVE ARE EXCLUSIVE AND IN LIEU OF ALL
OTHERS, EXPRESS OR IMPLIED. MORNINGSTAR SPECIFICALLY DISCLAIMS ANY AND ALL
IMPLIED WARRANTIES, INCLUDING, WITHOUT LIMITATION, WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
No Morningstar distributor, agent or employee is authorized to make any modifi
cation or extension to this warranty.
MORNINGSTAR IS NOT RESPONSIBLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY
KIND, INCLUDING BUT NOT LIMITED TO LOST PROFITS, DOWN-TIME, GOODWILL OR DAMAGE
TO EQUIPMENT OR PROPERTY.
APPENDIX D: REVISION HISTORY
Date | Reason for Revision | Revision |
---|---|---|
October 2022 | Original Publication | 0 |
December 2022 | Modified a Wire and Cable Safety WARNING: SHOCK HAZARD involving |
the Neutral-ground Bond. Added 3rd bullet.
Replaced Section 2.8.4, Grounding and Bonding Requirements, with revised text.
Revised Table 9 to modify the System Fault indications.| 1
April 2023| MOUNTING, CLEARANCE AND LOCATION SAFETY:
Revised CAUTION to remove “…by anyone or anything.” CERTIFICATIONS: Updated
listings.
Global Change: Changed “SureSine Utility App” to “Sure Sign Utility Mobile
App”.
Section 2.2, Additional Hardware Requirements. Revised bullet for AC Wiring to
remove model specificity.
Section 2.3.1:
• CAUTION: Equipment Damage. Modified first bullet regarding zero-clearance.
•CAUTION: HOT SURFACE/BURN HAZARD. Revised to remove “by anyone”.
Section 1.5, Figure 5. Updated the dimension values. Section 1.6, Figure 6.
Updated the dimension values.
Section 2.4.1, Figure 11. Revised illustration to modify DIP #1. Section
2.4.2, Table 1. Updated DIP #1 Function definition and Note. Section 2.8.2,
WARNING: Rick of Fire. Revised first sentence.
Figure 17. Modified the Illustration to remove the connection between the DC
Earth Ground and the AC Neutral-Ground Bond.
Section 2.9, Check Wiring and Power Up. Modified Step 5.
Global Change: Changed Modbus and Modbus TCP/IP to ModBus™ and ModBus TCP/IP™
Section 4. Communication Options. Revised the list of communication options.
Section 4.2.2, SureSine Utility App. Revised the section.
Section 4.3, Ethernet (for ModBus TCP/IP™. Revised the section.
Section 4.3.1. Revised the heading title, steps to connect the inverter to the
Internet, and Figure 33.
Section 4.4. EIA-485 Device Communications. Revised the section. Section
4.5.USB Port. Revised the section.
Section 5.0 Firmware Update Procedure. Revised the section. Added new Figure.
Section 6. Specifications.
• Added Product Key Illustration and table.
• Revised specifications for weight, shipping weight, and dimensions. Added
dimensions for the hardwired models.| 2
MS-003650 Rev 2
© 2023 Morningstar Corporation.
All rights reserved.