Danfoss EKE 3470P Pump and Level Controller Installation Guide

June 1, 2024
Danfoss

Danfoss EKE 3470P Pump and Level Controller

Product Specifications

  • Model: EKE 3470P
  • Application: Pump and Level controller
  • Display: LCD
  • Dimensions:
    • Width: 110 mm (4.33 in.)
    • Height: 280 mm (11 in.)
    • Depth: 63 mm (2.48 in.)
    • Weight: 60 mm (2.36 in.)

Product Usage Instructions

Installation

  1. Place the Pump and Level controller in a suitable location near the vessel.
  2. Connect the necessary cables and wires according to the I/O descriptions provided.

Setup and Calibration

  1. Power on the controller and navigate the settings using the keypad and LCD.
  2. Set the desired liquid level control parameters including pump start and stop conditions.

Operation

  1. Monitor the LCD for real-time information on liquid levels, pump status, and alarms.
  2. Use the keypad to adjust settings or acknowledge alarms as needed.

FAQ

  • Q: How do I reset the system remotely?
  • A: Use the Remote Reset function described in the Digital Input section of the manual.
  • Q: What are the analog inputs used for?
  • A: The analog inputs are used for monitoring parameters like liquid levels, pump motor amperage, pressure values, and temperature.

Introduction

  • The EKE 3470P Pump and Level controller is a complete solution for controlling the liquid level in vessels including control and protection of pumps.
  • It is easy to set up and use. The LCD and simple keypad combine to provide an easy-to-navigate, operator-friendly interface for set point and calibration entry.
  • Reference: For details please see EKE 3470P Data Sheet.

Applications

Danfoss-EKE-3470P-Pump-and-Level-Controller-FIG-2

Dimensions

Dimensions EKE 3470P

Danfoss-EKE-3470P-Pump-and-Level-Controller-FIG-3

I/O Descriptions

Digital Input and Output| Description| Type
DO 1| High-Level Shutdown Alarm| OUTPUT
DO 2| Liquid Feed Solenoid Valve #1| OUTPUT
DO 3| Liquid Feed Solenoid Valve #2| OUTPUT
DO 4| Pump #1 Start| OUTPUT
DO 5| Pump #2 Start| OUTPUT
DO 6| Pump #3 Start| OUTPUT
DO 7| Transfer Pump Solenoid Valve| OUTPUT
DO 8| Pump Bypass Solenoid Valve| OUTPUT
DO 9| Superheat Oil Rectifier – Solenoid Valve| OUTPUT
DO 10| General Alarm| OUTPUT
DO 11| Shutdown Alarm| OUTPUT
DO 12| High-Level Alarm| OUTPUT
DO 13| Low-Level Shutdown Alarm| OUTPUT
DO 14| Pump Mode – Evaporator Injection Signal| OUTPUT
DO 15| General Alarm 1,2, 3 or Low-Level Alarm (select)| OUTPUT
DI 1| System Remote Enable/Disable| INPUT
DI 2| Remote Reset| INPUT
DI 3| Float Switch – High-Level Shutdown Alarm (HLSD)| INPUT
DI 4| Pump #1 Aux Run Contacts| INPUT
DI 5| Pump #2 Aux Run Contacts| INPUT
DI 6| Pump #3 Aux Run Contacts| INPUT
DI 7| Float Switch – High-Level Alarm| INPUT
DI 8| Float Switch – Transfer Solenoid| INPUT
DI 9| Float Switch – Liquid Feed Solenoid Valve #1| INPUT
DI 10| Float Switch – Liquid Feed Solenoid Valve #2| INPUT
DI 11| Float Switch – Low-Level Alarm| INPUT
DI 12| Float Switch – Low-Level Shutdown Alarm (LLSD)| INPUT
DI 13| Pumps Enable/Disable| INPUT
DI 14| Liquid Motorized Valve #1 Alarm| INPUT
DI 15| Liquid Motorized Valve #2 Alarm| INPUT
DI 16| Superheat Oil Rectifier Activation| INPUT
DI 17| Stepper Valve Driver Alarm| INPUT
DI 18| General Alarm 1| INPUT
DI 19| General Alarm 2| INPUT
DI 20| General Alarm 3| INPUT

Analog

Analog Input and Output| Description| Signal| Type
AO 1| Liquid Feed Motorized Valve #1 or Pump Speed 3| 0–10 V| OUTPUT
AO 2| Liquid Feed Motorized Valve #2 or Pump Speed 2| 0–10 V| OUTPUT
AO 3| Pump Speed 1 or All Pumps Speed(2)| 0–10 V| OUTPUT
AO 4| Liquid Level Output| 0–10 V| OUTPUT
AO 5| Oil Rectifier Stepper Valve Driver EKF or ICM| 0–10 V| OUTPUT
AI 1| Vessel Liquid Level Probe| 4–20 mA| INPUT
AI 2| Pump Motor #1 Amps| 4–20 mA| INPUT
AI 3| Pump Motor #2 Amps| 4–20 mA| INPUT
AI 4| Pump Motor #3 Amps| 4–20 mA| INPUT
AI 5| Vessel Pressure| 4–20 mA| INPUT
AI 6| Pump Discharge Pressure| 4–20 mA| INPUT
AI 7| Pump Motor #1 Discharge or Delta Pressure| 4–20 mA (1)| INPUT
AI 8| Pump Motor #2 Discharge or Delta Pressure| 4–20 mA (1)| INPUT
AI 9| Pump Motor #3 Discharge or Delta Pressure| 4–20 mA (1)| INPUT
AI 10| Oil Rectifier SH S2 Temp C| PT1000| INPUT
(1) is set for 0–10 V input but conditioned externally to accept a 4–20 mA input. Pressure sensor output must be 4–20 mA

(2) Based on parameter selection

Top board

Danfoss-EKE-3470P-Pump-and-Level-Controller-FIG-4

Top board – Digital Input details

Danfoss-EKE-3470P-Pump-and-Level-Controller-FIG-5

Bottom board

Danfoss-EKE-3470P-Pump-and-Level-Controller-FIG-6

CONTACT

  • Danfoss A/S
  • Climate Solutions
  • danfoss.com
  • +45 7488 2222

Any information, including, but not limited to information on the selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to the form, fit or function of the product.
All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals