FRIGIDAIRE Q5RD Series 2 2 Single Package Heat Pump Owner’s Manual

June 15, 2024
Frigidaire

FRIGIDAIRE Q5RD Series 2 2 Single Package Heat Pump

FRIGIDAIRE-Q5RD-eries-2-2-Single-Package-Heat-Pump-PRO

Product Information

Specifications

  • Product Name : Q5 Series Single Packaged Heat Pump
  • Efficiency : High efficiency
  • Installation : Slab installation
  • Certifications: ETL and ETLc listed
  • Compressor: State of the art scroll compressor
  • Refrigerant : Earth-friendly non-ozone depleting refrigerant
  • Coil Design : Indoor and outdoor coils designed for optimized heat transfer, minimized size and cost, increased durability and reliability
  • Finish : Polyester urethane coat finish with 950 hour salt spray finish, resists corrosion 50% better than comparable units
  • Installation Features: Easy to install and transport, allows installations in tight areas, guard protects coil from damage, drainage system
  • Serviceability: Access panels for easy servicing, easy access to evaporator coil and fan motor
  • Control : Reliable industry standard control with various time settings
  • Delay Feature : Five minute delay after shutdown to prevent compressor failure
  • Refrigeration System : Factory installed for easier servicing and protection from liquid flood back
  • Motor: Heavy duty PSC motor for long lasting reliability and quiet operation, protected from rain and snow
  • Low Voltage Circuit Protection: Includes 3 Amp fuse
  • Drainage : Optimized drainage capabilities

Product Usage Instructions

Installation

  1. Choose a suitable location on a slab for installation.
  2. Ensure that the unit is placed in a well-ventilated area with adequate clearance for airflow.
  3. Connect the necessary electrical supply to the unit.
  4. Ensure that the unit is level and secure.

Serviceability

  1. To access controls and the compressor, open the side access panels.
  2. For cleaning and general maintenance, access the evaporator coil through the designated panel.
  3. For servicing the fan motor, follow the instructions provided by the manufacturer.

Control Settings
Refer to the user manual or control documentation for detailed instructions on setting up the control according to your specific climate requirements.

FAQ

  • Q: What certifications does the Q5 Series Single Packaged Heat Pump have?
    A: The Q5 Series is ETL and ETLc listed.

  • Q: What type of compressor does it have?
    A: The Q5 Series features a state of the art scroll compressor as standard equipment.

  • Q: Is the refrigerant used in this heat pump ozone-depleting?
    A: No, the refrigerant used is earth-friendly and non-ozone depleting.

  • Q: How does the polyester urethane coat finish resist corrosion?
    A: The 950 hour salt spray finish, with a thickness of 1.5 mil, resists corrosion 50% better than comparable units.

  • Q: Can this heat pump be installed in tight areas?
    A: Yes, the Q5 Series allows for installations in tight areas due to its clearance requirements on the duct side of the unit.

Q5RD Series

Single Packaged Heat Pump, Single Phase

  • 13 SEER, R-410A
  • 2 thru 5 Ton Units
  • Cooling: 24,000 to 56,000 Btuh
  • Heating: 24,000 to 54,500 Btuh

The Q5 Series single packaged heat pumps are high efficiency self contained cooling and heating units that can be installed on a slab. Units are ETL and ETLe listed.

WARRANTY

  • This product offers a 10-year All-Parts Warranty.
  • This product offers a 10 year Quality Pledge to replace the entire unit, if the unit’s major component (compressor) fails within the first 10 years of operation, to the original owner.
  • Consumer product registration required for both 10 year All Parts Warranty and Quality Pledge within a limited period of time after the installation. See current warranty document or visit our consumer web site listed on the back of this document for warranty details.

FEATURES and BENEFITS

  • Quality Compressor: State of the art scroll compressor is standard equipment.
  • R-410A Refrigerant: Earth friendly non-ozone depleting refrigerant.
  • Hi/Low Pressure Switches: Ensure long compressor life.
  • Copper Tube / Aluminum Fin Coils: Both indoor and outdoor coils are designed to optimize heat transfer, minimize size and cost, and increase durability and reliability.
  • Designed using Galvanized Steel: with a polyester urethane coat finish. The 950 hour salt spray finish is 1.5 mil thick and resists corrosion 50% better than comparable units.
  • Compact Footprint and Profile: make the Q5 Series easy to install and transport.
  • 0″ Clearance: to combustibles on duct side of the unit allows for installations in tight areas.
  • Wire guard coated with Earth Friendly Epoxy and plastic mesh hail guard: A guard that will never rust and protects the units coil from being damaged.
  • Raised Base Pan: allows water to drain away from away from the unit.
  • Easy Compressor and Control Access: Designed to make servicing easier for the contractor, access panels are provided to all controls and the compressor from the side of the unit.
  • Easy access: to the evaporator coil for cleaning and General maintenance.
  • Removable Top Grille Assembly: Allows ease of service to the fan motor.
  • Time/Temperature Defrost: a reliable, industry standard control offers various time settings to meet any type climate.
  • Five Minute Restart Time Delay: when the units shuts down, a five minute delay keeps the unit from restarting, eliminating the highest cause of compressor failure.
  • Liquid Line Filter Driers: Factory installed at a convenient location for service.
  • Accessible Service Valves: simplify servicing of the refrigeration system.
  • Suction Accumulator: provides protection from liquid flood back and future compressor failures.
  • Permanently Lubricated Condenser Motor: A heavy duty PSC motor for long lasting reliability and quiet operation. Requires no maintenance and is completely protected from rain and snow.
  • Low voltage Transformer: Includes 3 Amp fuse to protect low voltage circuit.
  • Drain Trap Included: design optimizes drainage capabilities.
  • Duct Collars: reduce installation costs.
  • Outdoor thermostat: is standard equipment.
  • Optional Electric Heat: Field installed 5 – 20 KW.

MODEL IDENTIFICATION CODE

DIMENSIONS

MODEL N.UMBER

152$-

| L

LENGTH

| W

WIDTH

| H

HEIGHT

| ****

A

| ****

B

---|---|---|---|---|---
024K| 49| 35| 22.2| 40.15| 7.61
030K| 49| 35| 30.2| 40.15| 7.61
036KA| 49| 35| 30.2| 35.02| 2.48
042K| 49| 35| 30.2| 35.02| 2.48
048KA| 49| 35| 34.2| 35.02| 2.48
060K| 49| 35| 38.2| 35.02| 2.48

PHYSICAL SPECIFICATIONS

Q5RD Models

  • Amperage and wire size based on refrigeration system only with 60° C wire, 50 ft. length. See Electrical Data tables for supplemental electric heaters. Refer to National Electric Code for additional derating factors for field installed conductors.
  • Use time delay fuse or “HACR” type circuit breaker.

SYSTEM HEATING AND COOLING CAPACITIES

MODEL NUMBER 152$| COOLING BTUH| 3%%2| %%2| HEATING BTUH| HSPF
---|---|---|---|---|---
024K| 24,000| 13| 11.5| 24,000| 7.7
030K| 28,600| 13| 11.0| 26,600| 7.7
036KA| 35,000| 13| 11.2| 34,000| 7.7
042K| 40,500| 13| 11.2| 40,000| 7.7
048KA| 47,000| 13| 11.0| 45,000| 7.7
060K| 56,000| 13| 11.0| 54,500| 7.7

Q5RD SERIES SMALL PACK

UNIT| BLOWER SETTING|  External Static Pressure Drop – inches water column
0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7| 0.8
CFM| HEAT RISE| CFM| BLOWER SETTING| CFM| BLOWER SETTING| CFM| BLOWER SETTING| CFM| BLOWER SETTING| CFM-| BLOWER SETTING| CFM-| BLOWER SETTING| CFM-| BLOWER SETTING

024K

| Low| 607| 52| 555| 57| 490| 64| 437| 72| 368| 86| 291| 109| 255| 124| |
Med†| 899| 35| 854| 37| 802| 39| 743| 43| 670| 47| 601| 53| 533| 59| |
High| 1220| 26| 1178| 27| 1133| 28| 1091| 29| 1024| 31| 946| 33| 844| 37| 743| 43

030K

| Low| 847| 37| 808| 39| 770| 41| 726| 44| 664| 48| 562| 56| 460| 69| |
High†| 1104| 29| 1114| 28| 1064| 30| 1010| 31| 935| 34| 846| 37| 710| 44| 536| 59

036KA

| Low†| 1318| 24| 1284| 25| 1248| 25| 1207| 26| 1160| 27| 1110| 28| 1043| 30| 957| 33
High| 1551| 20| 1521| 21| 1477| 21| 1434| 22| 1388| 23| 1342| 24| 1263| 25| 1180| 27

036K

| Tap T1| 1100| 29| 900| 35| 750| 42| 650| 49| 580| 54| 520| 61| 480| 66| 455| 69
Tap T2*| 1208| 26| 1080| 29| 1025| 31| 972| 33| 926| 34| 874| 36| 813| 39| 752| 42
Tap T3
| 1262| 25| 1199| 26| 1153| 27| 1110| 28| 1070| 30| 1027| 31| 965| 33| 906| 35
Tap T4| 1370| 23| 1333| 24| 1300| 24| 1260| 25| 1230| 26| 1180| 27| 1070| 30| 1010| 31
Tap T5| 1410| 22| 1340| 24| 1450| 22| 1320| 24| 1280| 25| 1240| 25| 1195| 26| 1150| 27

042K

| Tap T1| 1480| 21| 1455| 22| 1415| 22| 1390| 23| 1355| 23| 1320| 24| 1290| 24| 1255| 25
Tap T2*| 1575| 20| 1545| 20| 1515| 21| 1475| 21| 1440| 22| 1420| 22| 1385| 23| 1345| 23
Tap T3**| 1635| 19| 1505| 21| 1575| 20| 1545| 20| 1515| 21| 1485| 21| 1455| 22| 1425| 22
Tap T4| 1775| 18| 1740| 18| 1715| 18| 1695| 19| 1665| 19| 1635| 19| 1610| 20| 1580| 20
Tap T5| 2065| 15| 2040| 15| 2020| 16| 1985| 16| 1960| 16| 1940| 16| 1905| 17| 1850| 17

048KA

| Low| 1460| 22| 1440| 22| 1420| 22| 1390| 23| 1360| 23| 1325| 24| 1285| 25| 1235| 26
Med†| 1840| 17| 1815| 17| 1790| 18| 1760| 18| 1715| 18| 1660| 19| 1605| 20| 1535| 21
High| 2155| 15| 2115| 15| 2065| 15| 2020| 16| 1955| 16| 1895| 17| 1830| 17| 1740| 18

048K

| Tap T1| 1480| 21| 1455| 22| 1415| 22| 1390| 23| 1355| 23| 1320| 24| 1290| 24| 1255| 25
Tap T2*| 1575| 20| 1545| 20| 1515| 21| 1475| 21| 1440| 22| 1420| 22| 1385| 23| 1345| 23
Tap T3
| 1635| 19| 1505| 21| 1575| 20| 1545| 20| 1515| 21| 1485| 21| 1455| 22| 1425| 22
Tap T4| 1775| 18| 1740| 18| 1715| 18| 1695| 19| 1665| 19| 1635| 19| 1610| 20| 1580| 20
Tap T5| 2065| 15| 2040| 15| 2020| 16| 1985| 16| 1960| 16| 1940| 16| 1905| 17| 1850| 17

060K

| Tap T1| 1370| 23| 1340| 24| 1310| 24| 1280| 25| 1260| 25| 1230| 26| 1195| 26| 1160| 27
Tap T2| 1470| 21| 1440| 22| 1410| 22| 1380| 23| 1360| 23| 1320| 24| 1290| 24| 1250| 25
Tap T3*| 1550| 20| 1520| 21| 1480| 21| 1450| 22| 1430| 22| 1400| 23| 1380| 23| 1350| 23
Tap T4
| 1810| 17| 1770| 18| 1740| 18| 1720| 18| 1690| 19| 1660| 19| 1610| 20| 1575| 20
Tap T5| 1890| 17| 1870| 17| 1840| 17| 1820| 17| 1800| 18| 1770| 18| 1710| 18| 1670| 19

NOTES : Temperature rises shaded gray are for reference only. These conditions are not recommended. Heat rise valves calculated with 10KW Heater Kit.

  • Denotes factory set cooling speed
  • Denotes factory set electric heating speed
  • Denotes Factory cooling and electric heating speed

ACCESSORIES

MODEL IDENTIFICATION CODE

HEAT PUMP COOLING EXPANDED RATINGS

Q5RD-024K

Q5RD-030K

Q5RD-036KA

@5RD-042K Q5RD-048KA Q5RD-060K

HEAT PUMP HEATING EXPANDED RATINGS

Q5RD-024K

Q5RD-030K

Q5RD-036KA

Q5RD-042K

Q5RD-048KA

Q5RD-060K

GENERAL TERMS OF LIMITED WARRANTY

NORDYNE will furnish a replacement for any part of this product which fails in normal use and service within the first ten years of installation, in accordance with the terms of the warranty. For complete details of the Limited Warranty, including applicable terms and conditions, see your local installer or contact the NORDYNE warranty department for a copy.

  • 8000 Phoenix Parkway | O’Fallon, MO 63368-3827
  • Specifications and illustrations subject to change without notice and without incurring obligations. Printed in U.S.A (09/2010)
  • 205D-0910 (Replaces 205D-0809)
  • www.frigidairehvac.com
  • FRIGIDAIRE is a registered trademark of Electrolux Home Products Inc. and used under a license from Electrolux Home Products, Inc. © Nortek Global HVAC, LLC. All Rights Reserved.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Frigidaire User Manuals

Related Manuals