Q-TRAN Q-VAULT Direct Burial Transformer Installation Guide
- June 15, 2024
- Q-TRAN
Table of Contents
- Q-VAULT Direct Burial Transformer
- Product Information
- Specifications
- Product Usage Instructions
- Installation
- Outdoor Installation
- Indoor Installation
- Warnings
- Q: Can the Q-SET+QZ-DALI be used for outdoor landscape
- Q: What is the maximum lamp load for the Q-SET+QZ-60
- Q: Can I use a dimmer with the Q-SET+QZ-DALI?
- Q: Are there any special requirements for indoor
Q-VAULT Direct Burial Transformer
Product Information
Specifications
- Model Numbers:
- Q-SET+QZ-30
- Q-SET+QZ-60
- Q-SET+QZ-96
- Q-SET+QZ-DW-96
- Q-SET+QZ-DMX-96
- Q-SET+QZ-DALI-96
- Output Class: CLASS 2
- Max Lamp Load:
- Q-SET+QZ-30: 30W
- Q-SET+QZ-60: 60W
- Q-SET+QZ-96: 96W
- Q-SET+QZ-DW-96: 96W
- Q-SET+QZ-DMX-96: 96W
- Q-SET+QZ-DALI-96: 96W
- Primary Volts: 120V/277 (60Hz)
- Lamp Volts: 24VDC
- Dimmer Rating: 0-10/ELV/MLV
Product Usage Instructions
Installation
To install the Q-VAULT – Q-SET+QZ-DALI, follow these steps:
-
Ensure you are following all applicable local codes and
regulations. -
Choose the appropriate model number based on your
requirements. -
Connect the Q-SET LOW VOLTAGE LUMINAIRE POWER SUPPLY to your
power source. -
Make sure the output class matches your requirements.
-
Take note of the maximum lamp load for your model.
-
Connect the lamp to the Q-SET+QZ-DALI using the specified lamp
volts. -
If using a dimmer, ensure it is compatible with the dimmer
rating provided. -
Follow the specific installation instructions for outdoor or
indoor use, depending on your application.
Outdoor Installation
For outdoor installations, refer to the following
guidelines:
CSA Listing
Under 30 Volts = LV Wire Buried 0 to 6:
-
CSA Certified for both the U.S. and Canada to the UL-1838
Standard for Landscape Lighting with in-ground enclosure and
component power supply operating at less than 30VDC. -
The LV Q-WIRE can be installed underground up to 6 feet.
Pool & Spa – Under 30 Volts:
-
CSA Certified for the U.S. to the UL-379 Pool & Spa Power
Supply Standard. -
Intended for power supplies used to power fountain, swimming
pool, and spa luminaires operating at less than 30V.
15 to 30 Volts = LV Wire Buried 18:
-
CSA Certified for both the U.S. and Canada to UL-2108 Standard
with a listing of Low Voltage Luminaire Power Supply for lamps
operating at 12 or 24 volts where the secondary voltage is between
15 to 30 volts. -
The secondary wiring must be installed 18 inches below grade
per the N.E.C.
Indoor Installation
For indoor installations, follow these guidelines:
LV Lighting under 30 Volts:
-
CSA Certified for both the U.S. and Canada to UL-2108 Standard
as a Low Voltage Luminaire Power Supply for lamps operating at 12V
or 24V. -
Allows for live conductor lighting equipment mounted above 7
feet and other types of LV Lighting equipment, per N.E.C. Article
Note: It is important to refer to the last page of the user
manual for additional information.
Warnings
Pay attention to the following warnings during installation:
-
Conduit Connection Warning (for Q-VAULT
120/277V): Install the power unit at least 5 feet (1.5m)
away from the pool or spa and 10 feet (3.05m) away from a fountain.
If the power unit is installed within 10 feet (3.05m) of a pool or
spa, connect it to a GFCI protected branch circuit. -
Power Supply Cord Connection Warning: Install
the power unit at least 5 feet (1.5m) away from the pool, spa, or
fountain. If the power unit is installed indoors within 10 feet
(3.05m) of a pool, spa, or fountain, or outdoors, connect it to a
receptacle protected by a GFCI. -
Fire Risk Warning: If the installation
requires running wire through a building structure, special wiring
methods are needed. Contact a qualified electrician. -
Outdoor Cord-connected Unit Warning: The unit
should be connected to a GFCI protected hooded flush type cover
plate receptacle marked Wet Location.
FAQ
Q: Can the Q-SET+QZ-DALI be used for outdoor landscape
lighting?
A: Yes, the Q-SET+QZ-DALI is CSA Certified for outdoor landscape
lighting applications.
Q: What is the maximum lamp load for the Q-SET+QZ-60
model?
A: The Q-SET+QZ-60 has a maximum lamp load of 60W.
Q: Can I use a dimmer with the Q-SET+QZ-DALI?
A: Yes, the Q-SET+QZ-DALI is compatible with dimmers that have a
0-10/ELV/MLV rating.
Q: Are there any special requirements for indoor
installations?
A: For indoor installations, ensure that the LV Lighting
equipment is mounted above 7 feet and follow N.E.C. Article 411
guidelines.
INSTALLATION Q-VAULT – Q-SET+QZ-DALI
CANADA
· 3426-94 Luminaires – Landscape Lighting Systems – Certified to UL – 1838
Standard. · 3425-95 Luminaires – Low Voltage Lighting Systems – Certified to
UL – 2108 Standard. · 3425-96 Luminaires – Component Hydromassage – Certified
to UL – 379 Pool & Spa Standard.
· 3426-04 Luminaires – Landscape Lighting Systems – Component (including
Hydromassage). · 3425-15 Luminaires – Low Voltage Lighting Systems.
· For supply connections use wire rated for at least 90°C · Suitable for in-
ground installation. · Not for installation to conduit extending directly to
an underwater pool light forming shell. In line Pool and Spa rated junction
box required. · Suitable for use with submersible luminaries · Suitable for
direct burial use. · Warning: risk of fire – if installation involves running
wiring through a building structure, special wiring methods are needed.
Consult National
and Local Codes.
MODEL NUMBER
Q-SET+QZ-30 Q-SET+QZ-60 Q-SET+QZ-96 Q-SET+QZ-DW-96 Q-SET+QZ-DMX-96 Q-SET+QZ-
DALI-96
Q-SET LOW VOLTAGE LUMINAIRE POWER SUPPLY
OUTPUT CLASS
CLASS 2 CLASS 2 CLASS 2 CLASS 2 CLASS 2 CLASS 2
MAX LAMP LOAD
30W 60W 96W 96W 96W 96W
PRIMARY VOLTS
120V/277 (60Hz) 120V/277 (60Hz) 120V/277 (60Hz) 120V/277 (60Hz) 120V/277
(60Hz) 120V/277 (60Hz)
LAMP VOLTS
24VDC 24VDC 24VDC 24VDC 24VDC 24VDC
DIMMER RATING
0-10/ELV/MLV 0-10/ELV/MLV 0-10/ELV/MLV 0-10/ELV/MLV
NO NO
© 2023 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | sales@q-tran.com | www.q-tran.com
Specification subject to change. Rev-10-06-23
INSTALLATION Q-VAULT – Q-SET+QZ-DALI
Q-SET+QZ-30 Q-SET+QZ-60 Q-SET+QZ-96 Q-SET+QZ-DW-96 Q-SET+QZ-DMX-96 Q-SET+QZ-
DALI-96
Q-SET+QZ-30 Q-SET+QZ-60 Q-SET+QZ-96 Q-SET+QZ-DW-96 Q-SET+QZ-DMX-96 Q-SET+QZ-
DALI-96
Q-SET+QZ-30 Q-SET+QZ-60 Q-SET+QZ-96 Q-SET+QZ-DW-96 Q-SET+QZ-DMX-96 Q-SET+QZ-
DALI-96
OUTDOOR
CSA LISTING
Under 30 Volts = LV Wire Burried 0″ to 6″
Outdoor Landscape Lighting – Under 30 Volts CSA Certified for both the U.S.
and Canada to the UL-1838 Standard for Landscape Lighting with in-ground
enclosure and component power supply operating at less than 30VDC. This
listing allows for the LV Q-WIRE to be installed 0″ to 6″ underground.
Pool & Spa – Under 30 Volts CSA Certified for the U.S. to the UL-379 Pool &
Spa Power Supply Standard. This listing is intended for power supplies used to
power fountain, swimming pool and spa luminaires operating at less than 30V.
OUTDOOR 15 to 30 Volts = LV Wire burried 18″
Outdoor Landscape Lighting – 15 to 30 Volts CSA Certified for both the U.S. and Canada to UL-2108 Standard with a listing of “Low Voltage Luminaire Power Supply” for lamps operating at 12 or 24 volts where the secondary voltage is between 15 to 30 volts. Please note that the secondary wiring must be installed 18″ below grade per the N.E.C.
INDOOR
LV Lighting under 30 Volts
Indoor Open Conductor Systems – Under 30V
CSA Certified for both the U.S. and Canada to UL-2108 Standard as a “Low
Voltage Luminaire Power Supply” for lamps operating at 12V or 24V allows for
live conductor lighting equipment mounted above 7 feet and other types of LV
Lighting equipment, per N.E.C. Article 411. When tested in conjunction with
open conductor lighting system.
NOTE:
Refer to the last page.
Q-VAULT 120/277V (50/60HZ) – 24V
FOR CONDUIT CONNECTION WARNING – RISK OF SHOCK. Install power unit 5 feet (1.5
m) or more from the pool or spa and 10 feet (3.05 m) or more from a fountain.
Where the power unit is installed within 10 feet (3.05 m) of a pool or spa,
connect unit to GFCI protected branch circuit.
FOR POWER SUPPLY CORD CONNECTION WARNING – RISK OF SHOCK. Installed power unit
5 feet (1.5M) or more from the pool, spa, or fountain. Where the power unit is
installed (a) indoors within 10 feet (3.05) of a pool, spa, or fountain or (B)
outdoors, connect power unit to a receptacle protected by a GFCI.
WARNING – RISK OF FIRE. If installation requires running wire through a
building structure, special wiring methods are needed. Contact a qualified
electrician.
WARNING – Outdoor Cord-connected unit shall be connected to a GFCI protected
hooded flush type cover plate receptacle marked “Wet Location”.
WARNING – Do not use extension cords.
The main Secondary Wiring is intended for shallow burial – less than 6 inches
(152 mm)
For Supply connections use wire rated for at least 90C. · SUITABLE FOR INDOOR
/ OUTDOOR USE · SUITABLE FOR USE WITH SUBMERSIBLE LUMINAIRES OR SUBMERSIBLE
PUMPS · SUITABLE FOR USE WITH LOW VOLTAGE LANDSCAPE LUMINAIRES / FITTINGS
CONTACT YOUR LOCAL DISTRIBUTOR OR Q-TRAN FOR Q-WIRE, Q-CLIK OR PROPER ACCESSORY KITS.
© 2023 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | sales@q-tran.com | www.q-tran.com
Specification subject to change. Rev-10-06-23
INSTALLATION Q-VAULT – Q-SET+QZ-DALI
ROUGH IN WIRING
1
Excavate a 14″ x 30″ x 16″ deep hole for the Q-VAULT direct burial housing.
2
Dig trenches for primary & secondary wiring to Q-VAULT housing location.
3
Place drain pipe at a 30 degree angle at the lowest slope of land for proper drainage. Fill bottom of pit
with a minimum of 4″ of gravel.
SEE DIAGRAM A
Note: Increase width to 30″ x 30″ when stabilizing bars are used.
1-3
DIAGRAM A
14″ Land
30″
Excavated Hole
Soil
16″
Drain Pipe
Gravel 4″
4
Bring all primary and secondary wiring into housing.
A: Entry location is provided at both the bottom and
side of the Junction Box located on the Q-VAULT
housing.
B: On the bottom of Junction Box there are: (4) 3/4″ NPT and (2) 1/2″ NPT KO’s. SEE DIAGRAM B
C: Using the Field Drill Guide Labels provided in the installation kit you are able to drill for various fitting sizes. Only knock out openings for conduits being utilized in installation. SEE DIAGRAM C
5
After all field wiring has been installed with proper lead lengths, tighten all fittings properly to assure
they are water proof. All drilled entries require Q Click wire
connectors to insure water tight connection. Use
of other connectors voids warranty.
6
Coil and store field wiring in Junction Box area.
Note: Label all wiring for future reference.
4-6
DIAGRAM B
Knock Outs (in)
1/2 3/4
NPT KO’s
2 4
BBoottttoomm VViieeww
DIAGRAM C
Side Label
Front Label
1/2″ Fittings · Front: 8 max · Side: 2 per side max
3/4″ Fittings · Front: 6 max · Side: 1 per side max
1″ Fittings · Front: 3 max · Side: 1 per side max
1-1/2″ Fittings · Front: 2 max
1/2″ Fittings · Front: 1 max
FOR COMPLETE WATER TIGHT GUARANTEE
PRIMARY WIRING IN (120-277V)
Conduit Use Installation Kit · Step 1: Putty · Step 2: Epoxy · Step 3:
Syringe Non-conduit – use Q-CLIK NPT.75, Q.750-1E, Q-WIRE 12/2+GND
WARRANTY IS VOID IF THE CORRECT METHOD IS NOT USED.
SECONDARY WIRING OUT (12-24V)
Low voltage wire (non-conduit) · Q-CLIK
· NPT-or knock outs in bottom of Q-VAULT, .5-.75 · MST to drill into the side
of the housing, .5-1.25
· Q-WIRE low voltage marine grade UFB wire (recommended) 10-14AWG · Standard
Q-CLIK insert
Conduit low voltage, requires Seal Kit (sold separately) · Step 1: Putty ·
Step 2: Epoxy · Step 3: Syringe
© 2023 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | sales@q-tran.com | www.q-tran.com
Specification subject to change. Rev-10-06-23
INSTALLATION Q-VAULT – Q-SET+QZ-DALI
7
Clean debris from the top perimeter and install gasket. SEE DIAGRAM D
8
Install door and tighten the 6 door bolts in the number sequence shown. SEE DIAGRAM E
Note: Nut driver can be used to get bolts seated before final tightening. Proper door bolt tightening must be done with a ratchet wrench using a 3/8″ socket at a maximum torque of 50 in-lbs.
9
Attach the provided Support Bars to the Q-VAULT housing using the 6-32 X 5/8 screws. SEE DIAGRAM F
*OPTIONAL: Concrete Pour Ring Nut & Bolt Installation. SEE DIAGRAM G
Level housing and fill hole with gravel to 4″ of below grade. Add soil to
10 surface. SEE DIAGRAM H
All wire entry/exits other than conduit entries MUST use Q-CLIK connectors.
Failure to use them will void warranty.
*Gasket
1 6
3 5
Clean Surface
4
2
7
DIAGRAM D
8
DIAGRAM E
Top View of Q-VAULT housing door. Maximum torque 50 in-lbs.
*Gasket only fits one way. Gasket easily slides over Q-VAULT posts. If you are having to force the gasket, it is backwards (Gasket must sit on top of Q-VAULT. No portion should be overhanging).
9
DIAGRAM F
Support bar 6-32×5/8 screws (QTY:4)
DIAGRAM G
5/16 Nut (QT Y:10)
5/16 Nylock Nut (QT Y:10)
5/16×3″ Bolt (QT Y:10)
Shown with lawn Guard Ring Shown without lawn Guard Ring
30″
Land
10
DIAGRAM H
Drain Pipe
Soil
16″
Gravel 4″
11
Remove cover if installed, be sure to store cover and cover gasket in a clean and dry location.
12 Move field wiring out of the way.
NFC tag
Stick your phone through the slot, holding it over the driver’s NFC tag. Read
the factory default settings of the driver. Write the desired address and
output voltage. Only applicable
to Q-SET+QZ-DMX and
Q-SET-QZ-DALI
10.70″ 2.34″
9.78″
13 Place Q-SET+QZ low voltage luminaire power supply cassette into the
Q-VAULT housing.
14
Landscape Lighting: Landscape Lighting: Bring primary field wiring directly into the Cassette’s primary terminal block through open hole.
Primary Connections:
– Ground to ground labeled on terminal block – Neutral to neutral labeled on
terminal block – Hot to hot labeled on terminal block
SEE DIAGRAM I
11-14
DIAGRAM I
Q-SET+QZ Q-VAULT-5
(Must be purchased with Q-VAULT-5) *Install only one Q-SET+QZ per Q-VAULT-5
INPUT
OUTPUT
HOT NEU GND
30W, 60W, 96W
© 2023 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | sales@q-tran.com | www.q-tran.com
Specification subject to change. Rev-10-06-23
INSTALLATION Q-VAULT – Q-SET+QZ-DALI
HOUSING DOOR: Underside View
CSA Label Desiccant Pouch Spare Parts
HOUSING
HOUSING: Outside View Hole Drill Guide Label: Refer to sticker instructions
NPT
National Pipe Taper
(Conduit Entries)
MST
Machine Screw Thread
(Housing Entries)
For Field Drilled KO’s
Fits
1
Q-ZET
·
Knock Outs (in)
1/2 3/4
NPT KO’s
2 4
Bottom View
Q-CLIK inserts
0.5″ 1.0″ 1.25″
0.75″
INSTALLING Q-SET+QZ
Determine proper lengths and trim to correct length. Low Voltage Connections:
1CH: Q-SET+QZ Connect red wire to +24V on low voltage terminal block. Connect
black wire to – on low voltage terminal block .
2CH: Q-SET+QZ-DW Connect black wire to +24V on low voltage terminal block.
Connect red wire to Warm on low voltage terminal block. Connect blue wire to
Cool on low voltage terminal block.
Non-Dim
HOT NEU GND
Phase Dimmer
HOT NEU GND
0-10V Dimming
HOT NEU GND
DIM +
DIM
+
OUTPUT
INPUT
Cool Warm
1CH
2CH +
LED
30/60/96W
+ _
96W
LED
© 2023 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | sales@q-tran.com | www.q-tran.com
Specification subject to change. Rev-10-06-23
INSTALLATION Q-VAULT – Q-SET+QZ-DALI
INSTALLING Q-SET+QZ
Low Voltage Connections:
1CH: Q-SET+QZ-DMX / Q-SET+QZ-DALI Connect red wire to +24V on low voltage
terminal block. Connect black wire to – on low voltage terminal block.
2CH: Q-SET+QZ-DMX / Q-SET+QZ-DALI Connect black wire to +24V on low voltage
terminal block. Connect red wire to Warm on low voltage terminal block.
Connect blue wire to Cool on low voltage terminal block.
3CH: Q-SET+QZ-DMX / Q-SET+QZ-DALI Connect black wire to +24V on low voltage
terminal block. Connect red wire to R on low voltage terminal block. Connect
green wire to G on low voltage terminal block. Connect blue wire to B on low
voltage terminal block.
4CH: Q-SET+QZ-DMX / Q-SET+QZ-DALI Connect black wire to +24V on low voltage
terminal block. Connect red wire to R on low voltage terminal block. Connect
green wire to G on low voltage terminal block. Connect blue wire to B on low
voltage terminal block. Connect white wire to W on low voltage terminal block.
DMX
HOT NEU GND
DALI
HOT NEU GND
D+ D_ GND
DMX Controller
DALI
DALI Bus
Controller Power Supply
By others. By others.
OUTPUT
INPUT
1CH
2CH +
LED
30/60/96W
+ _
96W
Cool Warm
LED
R G B_
LED
3CH
96W
+ 4CH
96W
R G B W
LED
SIMPLE AS 1, 2, 3
Use putty provided to seal wires in potting well. It is important that the well is liquid tight so that when the re-enterable epoxy is poured, it
does not escape out the bottom. Be sure the putty is put into the very
bottom of the well to allow ample room for the epoxy. SEE DIAGRAM O
A: The 3M-8882 re-enterable epoxy takes several hours to set. When
2 set it will form a into a water tight “jello” consistency.
B: Mix the two part epoxy together per 3M instructions located on the epoxy
packaging.
C: Push all the mixed epoxy together to one end of the bag. Cut the corner of
the bag.
3 A: Using the syringe pull the mixed epoxy into the syringe by pulling
the plunger out slowly.
B: Slowly dispense the mixed epoxy from the syringe into the utilized potting
wells. SEE DIAGRAM P
Note: Potting is now complete
LAST STEP
Final Door Installation
Gasket and door installed only in one direction · Clean housing area where
door gasket will rest · Reinstall clean door gasket.
Before Door is Installed Put velcro desiccant bag in place. Attach the two
velcro loop coins on the desiccant bag to the two velcro hook coins on the
underside of the housing door. SEE DIAGRAM Q
1
DIAGRAM O
2-3
DIAGRAM P
DIAGRAM Q
Press Putty into Bottom of Well.
4 5
1
2 6
3
Hand ratchet screws in sequence before fully tightineing bolts to max 50 IN- LBS
Note: Install door and tighten the 6 door bolts NOT TO EXCEED 50 IN-LBS. Door bolt tightening must be done with a ratchet wrench using a 3/8″ socket.
© 2023 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | sales@q-tran.com | www.q-tran.com
Specification subject to change. Rev-10-06-23
INSTALLATION Q-VAULT – Q-SET+QZ-DALI
NEC CODE & UL STANDARDS FOR LIGHTING
Systems Operating at 30 Volts or Less
READ ACROSS & DOWN
SECONDARY WIRE & BURIAL DEPTH
MAX VOLTS
15V AC 30V DC 15V AC
Only 30V AC 30V DC 30V AC 30V DC
UL- NEC
UL 1838 NEC Annex A
UL Pool & Spa NEC 680 UL 2108 NEC 411
NEC Annex A UL 1598 NEC 410
LUMINAIRE LISTING
Low Voltage Landscape Lighting Luminaires
Low Voltage Pool & Spa Luminaires Low Voltage
Lighting Luminaires
Luminaires
POWER SUPPLY TRANSFORMER
Wire Type
& Burial Depth Grade
6″
Below Grade
6″+
Conduit
UF-B (Q-Wire)
Wire to Class 1 NEC – Chapter 3
0-6″
UF-B (Q-Wire)
L.V.Cable
UF-B Underground Feeder – Burial
Max Secondary Volt at Power
Supply with no load (Open Circuit).
NEC = National Electric Code NFPA-70
UL = Underwriters Laboratories Inc.
Article 411.3 (B-2) Listed NEC – 2008
Grounded Isolation for LV Wet Location
Secondary Circuit Protector 25A Max
Open / Bare Conductor (When Tested)
120V
Only
Wet
UL 1838 – LV Landscape Lighting System: 15V AC / 30V DC Max Output at Power
Supply – No Load Luminaires + Power Supplies must be UL 1838 Listed as
complimentary components for lighting garden, walkway, patio areas, trees and
similar outdoor locations with in ground and above ground fixtures; and for
certain indoor locations such as atriums and shopping malls. This listing also
covers luminaires submersed in or floating on ponds, rivers, water features
and lakes or a portable self contained fountains per NEC Article 682 where
immersed persons would not be present as defined by luminaire installation
instructions.
UL 1838 allows LV Underground Lighting Cable – no other listing permits this
wire type. 120V Primary only. Not for indoor use. Note: NEC Annex A = UL 1838
Submersed
Dry or Damp
UL 1838 Low Voltage Landscape NEC Annex A Lighting Power Supply
UL Pool & Spa Low Voltage Pool & Spa
UL 506
NEC
NEC 680
UL 2108 NEC 411 Annex A
Low Voltage Luminaire Primarily for Wet Locations
120V
Only UL Pool & Spa Listing: 15V AC only Max Output at Power Supply – No Load *
Indoor & Outdoor
Luminaires 4 Power Supplies must be UL Pool & Spa Listed as complimentary components for lighting a Pool, Spa, permanent fountain
or other bodies of water intended to contain immersed persons. All wiring must be Class 1 per NEC Chapter 3. 120V Primary only.
Install per NEC Article 680
Low Voltage Luminaire for Submersed Locations with immersed persons
UL 2108 – LV Lighting System: 30V AC / 30V DC Max Output at Power Supply – No load Luminaires + Power Supplies must be UL 2108 Listed as complimentary components. This Standard covers: 4113 (A) Listed Systems for exposed bare conductor systems comprised of cable, linear track or the like where the support structure is exposed and current carrying; here the Power Supply must be listed as part of the same identified lighting systems. Note: Use Power Supply as defined in Luminaire installation instructions.
4113 (B) Assembly of Listed Parts covers mono, dual or multi point L.V Luminaires which are an assembly of listed parts if a UL 2108
Low Voltage Luminaire Power Supply is utilized. For wet Location luminaires UL 2108 covers luminaires with up to 30 volt input provided they are Class
I wired per NEC Chapter 3. For wet Location luminaires with inputs not exceeding 15 volts, UL 1838 applies.
Note: NEC Article 411 + Annex A = UL 2108.
Low Voltage Luminaire Primarily for Dry and Damp Locations
UL 1598 – Luminaires: 30V AC / 30V DC Max Output at Power Supply – No load This UL Standard applies to line voltage luminaires for use in non- hazardous locations and allows up to 600 volts input and all wiring must be Class 1 per NEC Chapter 3. Low Voltage luminaires powered by remote transformer are NOT covered by this standard.
Low
Power Supply
Voltage Luminaires Power Supply
General Purpose or Specialty Transformer
Obsolete for LV Remote Dry, Damp & Wet
15V AC/30DC MAX
Output at power supply with no load
15 AC only MAX
Output at power supply with no load
30V AC/30DC MAX
Output at power supply with no load
600 MAX Transformer
300 MAX low Voltage
This Listing does not cover:
· LV Landscape Lighting products and Submersible Luminaires installed in the United States at 15V or less. (UL 1838 is the Standard per NEC-Annex A)
· Swimming Pool & Spa Luminaires (UL Pool & Spa is the Standard per NEC Article 680)
· Low Voltage Lighting Systems powered by remote transformers (UL 2108 is the Standard per NEC 411 & Annex A)
Note: NEC Article 410
Intended for Line Voltage Luminaires for Dry, Damp and Wet Locations
UL 506-General Purpose or Specialty Transformers: 600V Max
This UL Standard is a transformer standard only and is not a complimentary component to any luminaire standard. UL 1838, Pool & Spa and 2108
does not permit the use of UL 506 transformers unless the transformer is additionally tested and subsequently listed to UL 1838, Pool & Spa or 2108. A
UL-506 transformer may be tested as an internal components to a UL-1598 luminaire, to be an integral transformer.
The Scope of UL-506 (Section 1.2) specifically excludes use in Landscape Lighting Systems and for use in Pool & Spa Lighting Systems.
Additionally, a Cord and Plug connection is not permitted. In no instance can a UL-506 transformer be used in Landscape or Pool & Spa
Lighting. A UL 1838, UL Pool Spa and UL 2108 Power Supply may power a UL-1598 luminaire that was listed prior to the UL-2108 effective
date since these Luminaires are required to be Class 1 wired per NEC Chapter 3.
General Purpose Transformer
Conduit (Q-CLIK)
Yes
UF-B (Q-WIRE)
No
L.V. Cable Optional
Exceeds Standard
Complimentary Component
Transformer Power Supply
T
PS
The UL limit of 15 volts AC at the Power Supply under no load (Open Circuit) was established for life safety due to shock potential in wet conditions. The Standard also requires a grounded isolation barrier between the primary and secondary windings. In the Pool & Spa Standard the primary must be 120V & the connection must be in a separate junction box or compartment.
Q-SET = 3 UL Listings
Q-HEX = 2 UL Listings
UL 1838 UL 2108 UL Pool
& Spa
UL 1838 UL 2108
QOM = 1 UL Listings
UL 1838
Key
© COPYRIGHT Q-TRAN, INC. 2023
Power Supply
© 2023 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | sales@q-tran.com | www.q-tran.com
Specification subject to change. Rev-10-06-23
INSTALLATION Q-VAULT – Q-SET+QZ-DALI
© 2023 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | sales@q-tran.com | www.q-tran.com