itsensor TXMINI-DIN43650 Transmitter User Manual
- June 4, 2024
- itsensor
Table of Contents
itsensor TXMINI-DIN43650 Transmitter
INTRODUCTION
The TxMini-DIN43650 Transmitter is a 4-20 mA 2-wires temperature transmitter
for head mount, powered by the current loop. Its configuration is accomplished
by connecting the TxConfig-DIN43650 interface configuration. The configuration
does not require that the transmitter be powered.
The output current is linearized according to the selected input sensor and
adjusted to the configured range.
SPECIFICATIONS
Sensor Input: User defined. The supported sensors are listed in
Table 1, along with their maximum ranges.
Pt100: Type 3-wire, Excitation 0.8 mA, α= 0.00385, according IEC 60751
(ITS-90).
Pt1000: Type 3-wire, Excitation 0.8 mA, α= 0.00385, according NBR 13773.
IEC 60751 (ITS-90).
For 2-wire sensors, tie terminals 3 and 4 together.
Switch-on delay: < 2.5 s. The accuracy is only guaranteed after 15
minutes.
Calibration error: < 0.12 % (RTD).
Terms of reference: ambient: 25 ° C; voltage: 24 Vdc, load: 250 Ω;
settling time: 15 minutes.
Temperature Effect: < ± 0.2 % / 25 °C
Response time: typical 1.6 s
Maximum voltage allowed at input terminals no sensor: 3 V. RTD current:
800 µA.
RTD cable resistance effect: 0.005 °C / Ω.
Maximum allowable cable resistance for RTD: 25 Ω.
Sensor Type | Typical Accuracy | Minimum Accuracy |
---|---|---|
Pt100 / Pt1000 | 0.1 % | 0.2 % |
Table 1 – Calibration error, percentage of the full measurement range
Power supply influence: 0.006 % / V typical (percentage of the full
measure range).
Output: 4-20 mA or 20-4 mA current, 2-wired; linear in relation to the
temperature measurement by the selected sensor.
Output Resolution: 2 µA.
Power supply: 8 to 35 Vdc, across the transmitter;
Maximum load (RL): RL (max.) = (Vdc – 8) / 0.02 [Ω] Where: Vdc= Power
supply voltage (8-35 Vdc) Operating Temperature: -40 to 85 °C
Humidity: 0 to 90 % RH
Electromagnetic Compatibility: EN 61326-1:2006
No electrical isolation between input and output.
Internal protection against polarity inversion.
Cold junction compensation for thermocouples.
Thread Type: M24x2
Connection Wire Cross Section: 0.14 a 1.5 mm² (*)
When soldering the Pt100 wires, each wire should be inserted no more than 1 mm
into the hole.
Table 2 – Sensors accepted by the transmitter
Sensor Type| Maximum Measurement Range| Minimum
Measurement Range
---|---|---
Pt100| -200 to 650 °C| 40 °C
| (-328 to 1202 °F)| (104 °F)
Pt1000| -200 to 650 °C| 40 °C
| (-328 to 1202 °F)| (104 °F)
Order Codes:
- P/N: 8806050406: TxMini-DIN43650 transmitter;
- P/N: 8816021069: TxConfig-DIN43650 Interface.
CONFIGURATION
The sensor offset can be adjusted through the TxConfig II software. The USB
cable may be connected to the transmitter without causing any measurement
errors.
The user must select the sensor and most suitable range to the process. The
chosen range must not exceed the maximum range specified for that sensor and
should not be narrower than the minimum range for that same sensor.
The communication interface TxConfig-DIN43650 is not electrically isolated from the transmitter’s input.
SOFTWARE CONFIGURATION
The fields in the screen mean:
-
General Information: This field shows information that identifying the transmitter. This information should be sent to the manufacturer in an eventual request for technical assistance.
-
Sensor: Select the type of sensor to be used. See Table 1.
-
Measuring Range: Sets de measurement range of the transmitter.
Lower Range Limit: equivalent temperature for a current of 4 mA. Upper
Range Limit: equivalent temperature for a current of 20 mA. Sensor Range
The values chosen cannot exceed the range of sensor shown in this field. See Table 1 of this manual.
Minimum Range
Do not set a lower band (span) that the Minimum Range indicated below in this same field. See Table 1 of this manual. -
Sensor Failure: It establishes the output behavior, when the transmitter indicates a failure:
Minimum: output current goes to < 3.8 mA (down-scale), typically used for refrigeration.
Maximum: output current goes to > 20.5 mA (up-scale), typically used for heating. -
Zero Correction: It corrects small deviations presented in the transmitter output, for example, when the sensor is replaced.
-
Send Configuration: It applies the new setup. Once sent, the setup will be immediately adopted by the transmitter.
-
Read Configuration: Reads the current setup in the transmitter connected. The screen now presents the current setup that may be changed by the user.
FACTORY SETTING:
- Sensor: Pt100 3-wire, range 0 to 100 °C
- Sensor failure: upscale (maximum).
- 0 °C zero correction.
- Unit: °C;
- Output: 4 to 20 mA.
Upon purchase order, the user can define a specific setup.
MECHANICAL INSTALLATION
Transmitter TxMini-DIN43650 was designed to be installed in tubes and other small places. Vibrations, moisture and extreme temperatures, electro-magnetic interference, high voltage and other interferences can permanently damage the unit, and could cause error in the measured value.
ELECTRICAL INSTALLATION
- Polyamide enclosure.
- Section of the cable used: 0.14 to 1.5 mm ²
RECOMMENDATIONS FOR INSTALLATION
- Sensor signals conductors must go through the plant system separate from power leads (loop), if possible in grounded conduits.
- The instruments must be powered from the instrumentation power supply circuit.
- In control and monitoring applications is essential to consider what can happen when any part of the system fails.
- It is recommended the use of suppressors in contact coils, solenoids and any inductive load.
POWER AND COMMUNICATION CONNECTION
Terminal 3 is used to communicate with the transmitter (TxConfig-DIN43650
interface must be used).
Terminal 4 can be connected to cable shield, if needed.
| 1| LOOP +
---|---|---
2| LOOP –
3| COMM
4| SHIELD
SENSOR CONNECTION
Terminals 1, 2 and 3 are dedicated to sensor connection. Terminals 1 and 2
must be shorted, as shown in the figure below.
For appropriate cable resistance compensation, the same cable type should be used for all terminals. Maximum wire resistance is 25 Ω. Usage of a 3 or 4 wire with conductors of equal length and gauge is recommended.
OPERATION
The sensor offset can be adjusted through the TxConfig II software. The USB
cable may be connected to the transmitter without causing any measurement
errors.
The user must select the sensor and most suitable range to the process. The
chosen range must not exceed the maximum range specified for that sensor and
should not be narrower than the minimum range for that same sensor.
It is important to note that the transmitter accuracy is based on the maximum
range of the sensor used, even when a narrower range is programmed. Example:
- The Pt100 input has a max. range of –200 to +650 °C. Its accuracy is 0.2 % of the full range, resulting in a maximum allowed error of 1.7 °C (0.2 % of 850 °C).
- This error may be present even when a narrower range is configured for the sensor (for example: 0 to 100 °C.).
Note: When Pt100 simulators are used with the transmitter, make sure the excitation current of the simulator is compatible with the Pt100 excitation current of the transmitter, which is 0.8 mA.