Carrier 25HBC5 Single Stage Heat Pumps with Puron Refrigerant Instruction Manual
- June 4, 2024
- Carrier
Table of Contents
Turn to the experts
25HBC5, 25HCE4
Single Stage Heat Pumps
with Puron® Refrigerant
1-1/2 To 5 Nominal Tons
Installation Instructions
NOTE: Read the entire instruction manual before starting the installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use
can cause an explosion, fire, electrical shock, or other conditions which may
cause death, personal injury, or property damage. Consult a qualified
installer, service agency, or your distributor or branch for information or
assistance. The qualified installer or agency must use factory–authorized kits
or accessories when modifying this product. Refer to the individual
instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work
gloves. Use a quenching cloth for brazing operations. Have a fire extinguisher
available. Read these instructions thoroughly and follow all warnings or
cautions included in the literature and attached to the unit. Consult local
building codes and current editions of the National Electrical Code (NEC) NFPA
70. In Canada, refer to current editions of the Canadian electrical code CSA
22.1.
Recognize safety information. This is the safety–alert symbol. When you see
this symbol on the unit and in instructions or manuals, be alert to the
potential for personal injury. Understand these signal words; DANGER, WARNING,
and CAUTION. These words are used with the safety–alert symbol. DANGER
identifies the most serious hazards which will result in severe personal
injury or death. WARNING signifies hazards that could result in personal
injury or death. CAUTION is used to identify unsafe practices which may result
in minor personal injury or product and property damage. NOTE is used to
highlight suggestions that will result in enhanced installation, reliability,
or operation.
WARNING!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing the system, the main electrical
disconnect switch must be in the OFF position. There may be more than 1
disconnect switch. Lock out and tag the switch with a suitable warning label.
WARNING!
EXPLOSION HAZARD
Failure to follow this warning could result in death, serious personal injury,
and/or property damage. Never use air or gases containing oxygen for leak
testing or operating refrigerant compressors. Pressurized mixtures of air or
gases containing oxygen can lead to an explosion.
INSTALLATION RECOMMENDATIONS
In some cases, noise in the living area has been traced to gas pulsations from
improper installation of equipment.
- Locate the unit away from windows, patios, decks, etc. where unit operation sound may disturb customers.
- Ensure that vapor and liquid tube diameters are appropriate for unit capacity.
- Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
- Leave some slack between the structure and unit to absorb vibration.
- When passing refrigerant tubes through the wall, seal the opening with RTV or other pliable silicon-based caulk (see Fig. 1).
- Avoid direct tubing contact with water pipes, duct work, floor joists, wall studs, floors, and walls.
- Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing (see Fig. 1).
- Ensure that tubing insulation is pliable and completely surrounds the vapor tube.
- When necessary, use hanger straps that are 1 in. wide and conform to the shape of tubing insulation (see Fig. 1).
- Isolate hanger straps from insulation by using metal sleeves bent to conform to the shape of insulation.
Fig. 1 – Connecting Tubing
Installation
A07588
When the outdoor unit is connected to factory–approved indoor unit, the
outdoor unit contains a system refrigerant charge for operation with AHRI
rated indoor unit when connected by 15 ft. (4.57 m) of field–supplied or
factory accessory tubing. For proper unit operation, check refrigerant charge
using charging information located on the control box cover and/or in the
Check Charge section of this instruction.
IMPORTANT: Maximum liquid–line size is 3/8–in. OD for all residential
applications including long lines.
IMPORTANT: Always install the factory–supplied liquid–line filter drier.
Obtain replacement filter driers from your distributor or branch.
INSTALLATION
IMPORTANT: Effective January 1, 2015, all split system and packaged air
conditioners must be installed pursuant to applicable regional efficiency
standards issued by the Department of Energy.
CAUTION!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate
protective clothing and gloves when handling parts.
Check Equipment and Job Site Unpack Unit
Move to the final location. Remove the carton taking care not to damage the
unit.
Inspect Equipment
File a claim with the shipping company prior to installation if the shipment
is damaged or incomplete. Locate unit rating plate on unit corner panel. It
contains information needed to properly install the unit. Check the rating
plate to be sure the unit matches job specifications.
Install on a Solid, Level Mounting Pad
If conditions or local codes require the unit to be attached to the pad, tie-
down bolts should be used and fastened through knockouts provided in the unit
base pan. Refer to the unit mounting pattern in Fig. 2 to determine the base
pan size and knockout hole location.
For hurricane tie-downs, contact the distributor for details and PE
Certification (Professional Engineer), if required.
On rooftop applications, mount on a level platform or frame. Place unit above
a load–bearing wall and isolate unit and tubing set from the structure.
Arrange supporting members to adequately support the unit and minimize
transmission of vibration to the building. Consult local codes governing
rooftop applications.
Roof-mounted units exposed to winds above 5 mph may require wind baffles.
Consult the Service Manual – Residential Split System Air Conditioners and
Heat Pumps for wind baffle construction. The unit must be level to within ±2°
(±3/8 in/ft,±9.5 mm/m) per compressor manufacturer specifications.
Clearance Requirements
When installing, allow sufficient space for airflow clearance, wiring,
refrigerant piping, and service. Allow 24 in. (609.6 mm) clearance to the
service end of the unit and 48 in. (1219.2 mm) above the unit. For proper
airflow, a 6–in. (152.4 mm) clearance on 1 side of the unit and 12–in. (304.8
mm) on all remaining sides must be maintained. Maintain a distance of 24 in.
(609.6 mm) between units or 18 in. (457.2 mm) if no overhang within 12 ft.
(3.66 m). Position so water, snow, or ice from the roof or eaves cannot fall
directly on the unit. The 18” (457.2 mm) clearance option described above is
approved for outdoor units with wire grille coil guard only. Units with louver
panels require 24” (609.6 mm) between units. On rooftop applications, locate
units at least 6 in. above the roof surface.
Fig. 2 – Tiedown Knockout Locations
UNIT BASE PAN
Dimension in. (mm)| TIEDOWN KN| OCKOUT LOCAT| IONS in.
(mm)
---|---|---|---
A| B| C
23 X 23 (585 X 585)| 7–3/4 (196.8)| 4–13/32 (111.9)| 18–1/32 (457.9)
26 X 26 (660 X 660)| 9–1/8 (231.8)| 4–7/16 (112.7)| 21–1/4 (539.8)
31–1/2 X 31–1/2 (800 X 800)| 9–1/8 (231.8)| 6–9/16 (166.7)| 24–11/16 (627.1)
35 X 35 (889 X 889)| 9–1/8 (231.8)| 6–9/16 (166.7)| 28–7/16 (722.3)
Operating Ambient
The minimum outdoor operating ambient in a cooling mode without accessories is
55°F (12.78°C), and the maximum outdoor operating ambient in cooling mode is
125°F (51.67°C). The maximum outdoor operating ambient in heating mode is 66
°F (18.89°C).
Check Defrost Thermostat
Check defrost thermostat to ensure it is properly located and securely
attached. There is a liquid header with a distributor and feeder tube going
into the outdoor coil. At the end of one of the feeder tubes, there is a 3/8
in. O.D. stub tube approximately 2 in. (50.8 mm) long (see Fig. 3). The
defrost thermostat should be located on the stub tube. Note that there is only
one stub tube used with a liquid header, and on most units, it is the bottom
circuit.
A97517
Fig. 3 – Defrost Thermostat Location
Elevate Unit
CAUTION!
UNIT OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
Do not allow water and/or ice to build up in the base pan. Elevate the unit
per local climate and code requirements to provide clearance above the
estimated snowfall level and ensure adequate drainage of the unit.
Table 1 – Accessory Usage
Accessory| REQUIRED FOR LOW–AMBIENT COOLING APPLICATIONS (Below 55°F /
12.8°C)| **REQUIRED FOR LONG-LINE APPLICATIONS *| REQUIRED FOR
SEA COAST APPLICATIONS (Within² miles / 3.22 km)**
---|---|---|---
Accumulator| Standard| Standard| Standard
Ball Bearing Fan Motor| Yes†| No| No
Compressor Start Assist Capacitor and Relay| Yes| Yes| No
Crankcase Heater| Yes| Yes| No
Evaporator Freeze Thermostat| Yes| No| No
Hard Shutoff TXV| Yes| Yes| No
Isolation Relay| Yes| No| No
Liquid Line Solenoid Valve| No| See Long–Line Application Guideline| No
Motor Master® Control or Low Ambient Switch| Yes‡| No| No
Support Feet| Recommended| No| Recommended
*. For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Piping and Longline Guideline.
†. Additional requirement for Low–Ambient Controller (full modulation feature)
MotorMaster® Control.
‡. In units equipped with ECM OD motor, the motor needs to be replaced per
unit accessory guide to work properly. This motor kit comes with a new defrost
board that also needs to be installed. The unit will not meet AHRI-rated
efficiency once the motor and control board are replaced to use this
accessory.
Make Piping Connections
WARNING!
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final
unit disposal.
Use all service ports and open all flow–control devices, including solenoid
valves.
CAUTION!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
If ANY refrigerant tubing is buried, provide a 6–in (152.4 mm) vertical rise
at the service valve. Refrigerant tubing lengths up to 36–in (914.4 mm). may
be buried without further special consideration. Do not bury lines longer than
36 in (914.4 mm).
Outdoor units may be connected to the indoor section using an accessory tubing
package or field–supplied refrigerant grade tubing of the correct size and
condition. For tubing requirements beyond 80 ft, substantial capacity and
performance losses can occur. Following the recommendations in the Residential
Piping and Long Line Guideline will reduce these losses. Refer to Table 1 for
accessory requirements. Refer to Table 2 for field tubing diameters.
There are no buried–line applications greater than 36 in. (914.4 mm) If
refrigerant tubes or indoor coils are exposed to the atmosphere, they must be
evacuated to 500 microns to eliminate contamination and moisture in the
system.
Outdoor Unit Connected To Factory Approved Indoor Unit
The outdoor unit contains an approximate system refrigerant charge for
operation with an approved AHRI-rated indoor unit when connected by 15 ft
(4.57 m) of field-supplied or factory–accessory tubing, and a factory-supplied
filter drier. Some indoor units require additional subcooling to achieve
optimal heating performance. Using Table 5 or 6 – Additional Subcooling
Required, check refrigerant charge for maximum efficiency
Service Valves
Service valves are closed and plugged from the factory. Outdoor units are
shipped with a refrigerant charge sealed in the unit. Leave the service valves
closed until all other refrigerant system work is complete or the charge will
be lost. Leave the plugs in place until the line set tubing is ready to be
inserted.
Heat pumps require a piston metering device in the liquid service valve for
proper heating operation. The piston is shipped in the piston body of the
liquid service valve, temporarily held in place with a plastic cap. Do not
remove the plastic cap until the line set tubing is ready to be installed.
Refer to Fig. 4 and follow these steps for piston installation:
- Remove the plastic cap holding piston in the piston body of the liquid service valve.
- Check that the piston size (stamped on side of the piston) matches the number listed on the unit rating plate. Return piston to piston body of liquid service valve (either direction).
- Find a plastic bag taped to the unit containing a copper adapter tube, brass nut, and plastic washer.
- Install a plastic washer in the seat inside the piston body.
- Fit brass nut onto adapter tube and install tube onto liquid service valve. Tighten nut finger tight, then wrench additional ½ turn only [15-ft lbs (20.3 N-m)]. Over-tightening may damage the plastic washer and service valve’s piston body.
|
---|---
A14235
Fig. 4 – Liquid Service Valve with Heating Piston and Adapter Tube
|
A14236
Fig. 5 – Vapor Service Valve
Brazing Connections
Clean line set tube ends with emery cloth or steel brush. Remove any grit or
debris.
Connect vapor tube to fitting on outdoor unit vapor service valves (see Table
2). Connect liquid tubing to adapter tube on liquid service valve. Use
refrigerant-grade tubing.
CAUTION!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
Service valves must be wrapped in a heat–sinking material such as a wet cloth
while brazing.
Apply heat absorbing paste or heat sink product between service valve and
joint. Wrap service valves with a heat sinking material such as a wet cloth.
After wrapping the service valve with a wet cloth, the tubing set can be
brazed to the service valve using either silver bearing or non–silver bearing
brazing material. Do not use soft solder (materials that melt below
800°F/427°C). Braze joints using a Sil-Fos or Phos-copper alloy. Consult local
code requirements.
Some outdoor units contain a mechanical fitting at the liquid distributor.
This connection is not fielded serviceable and should not be disturbed. For
Liquid Service Valve – Braze line set to adapter tube BEFORE bolting adapter
to the valve. This helps prevent overheating and damage to plastic washers or
o-rings.
For Vapor Service Valve – remove the valve core from the Schrader port on
Service Valve BEFORE brazing. This helps prevent overheating and damage to
valve seals (refer to Fig. 5). Replace valve core when brazing is completed.
WARNING!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, and/or
property damage.
The refrigerant and oil mixture could ignite and burn as it escapes and
contacts the brazing torch. Make sure the refrigerant charge is properly
removed from both the high and low sides of the system before brazing any
component or lines.
Table 2 – Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (In.)
UNIT SIZE | LIQUID | **RATED VAPOR *** |
---|---|---|
Connection Diameter | Tube Diameter | Connection Diameter |
Tube Diameter
25HBC5, 25HCE4
18, 24| 3/8| 3/8| 5/8| 5/8
30, 36| 3/8| 3/8| 3/4| 3/4
42, 48| 3/8| 3/8| 7/8| 7/8
---|---|---|---|---
60| 3/8| 3/8| 7/8| 1–1/8
25HBC5 Only
37| 3/8| 3/8| 3/4| 3/4
61| 3/8| 3/8| 7/8| 1–1/8
*. Units are rated with 25 ft. (7.6 m) of lineset. See the Product Datasheet for performance data when using different size and length line sets.
Notes:
- Do not apply capillary tube indoor coils to these units.
- For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 20 ft. (6.09 m) vertical differential 250 ft. (76.2 m) Total Equivalent Length, refer to the Residential Piping and Longline Guideline – Air Conditioners and Heat Pumps using Puron refrigerant.
Mechanical Line Set Connections
If using mechanical or crimp-type line set connections, follow the crimp tool
manufacturer’s instructions.
NOTE: Should the use of mechanical fittings cause the failure of the
fittings or failure of the equipment, such would not be covered under the
standard warranty.
Installing with Indoor Piston
Heat pumps with piston indoor ratings are shipped with the correct indoor
piston size in the accessory bag. Check the piston size shipped with the
indoor unit to see if it matches the required indoor piston size. If it does
not match, replace the indoor piston with the correct piston size which is
listed on the rating plate.
NOTE: Heat pumps without piston indoor ratings may be installed as a
replacement component in a piston system. When installing a non-piston rated
heat pump with a piston indoor the correct indoor piston must be installed.
When not listed on the rating plate the correct piston size is listed in the
product data. Replacement pistons can be ordered from Replacement Components.
A10342
Fig. 6 – Indoor Piston Installation
Install Liquid Line Filter Drier Indoor
Refer to Fig. 7 and install the filter drier as follows:
- Braze 5 in. (127 mm) liquid tube to the indoor coil.
- Wrap the filter drier with a damp cloth.
- Braze filter drier to 5 in. (127 mm) long liquid tube from step 1.
- Connect and braze the liquid refrigerant tube to the filter drier.
IMPORTANT: Installation of the filter drier in the liquid line is required.
A05227
Fig. 7 – Liquid Line Filter Drier
CAUTION!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
Installation of filter drier in liquid line is required.
Evacuate Refrigerant Tubing and Indoor Coil
CAUTION!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using the recommended
deep vacuum method of 500 microns. The alternate triple evacuation method may
be used (see triple evacuation procedure in the service manual). Always break
a vacuum with dry nitrogen.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum of
500 microns and a vacuum gauge capable of accurately measuring this vacuum
depth. The deep vacuum method is the most positive way of assuring a system is
free of air and liquid water. A tight dry system will hold a vacuum of 1000
microns after approximately 7 minutes. (See Fig. 8.)
A95424
Fig. 8 – Deep Vacuum Graph
Final Tubing Check
IMPORTANT: Check to be certain factory tubing on both indoor and outdoor
units has not shifted during shipment. Ensure tubes are not rubbing against
each other or any sheet metal. Pay close attention to feeder tubes, makings
sure wire ties on feeder tubes are secure and tight.
Make Electrical Connections
WARNING!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Do not supply power to the unit with the compressor terminal box cover
removed.
Be sure field wiring complies with local and national fire, safety, and
electrical codes, and voltage to the system is within the limits shown on the
unit rating plate. Contact local power company for correction of improper
voltage. See unit rating plate for recommended circuit protection device.
NOTE: Operation of unit on improper line voltage constitutes abuse and
could affect unit reliability. See unit rating plate. Do not install the unit
in a system where voltage may fluctuate above or below permissible limits.
NOTE: Use copper wire only between the disconnect switch and unit.
NOTE: Install branch circuit disconnect of adequate size per NEC to
handle unit starting current. Locate disconnect within sight from and readily
accessible from the unit, per Section 440–14 of NEC.
Route Ground and Power Wires
Remove the access panel to gain access to unit wiring. Extend wires from
disconnect through the power wiring hole provided and into the unit control
box.
Connect Ground and Power Wires
WARNING!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
The unit cabinet must have uninterrupted or unbroken ground to minimize
personal injury if an electrical fault should occur. The ground may consist of
electrical wire or metal conduit when installed in accordance with existing
electrical codes.
Connect the ground wire to the ground connection in the control box for
safety.
Connect power wiring to the contactor as shown in Fig. 9.
DISCONNECT
PER N.E.C. AND/OR
LOCAL CODES
A94025
Fig. 9 – Line Connections Fig. 10
– 3–Phase Monitor Control
(Applies to 3–Phase Units Only)
Table 3 – 3-Phase Monitor LED Indicators
LED | STATUS |
---|---|
OFF | No call for compressor operation |
FLASHING | Reversed-phase |
ON | Normal |
Connect Control Wiring
Route 24v control wires through control wiring grommet and connect leads to
control wiring. See Thermostat Installation Instructions for wiring specific
unit combinations. (See Fig. 11.)
Use No. 18 AWG color-coded, insulated (35°C minimum) wire. If the thermostat
is located more than 100 ft (30.5 m) from the unit, as measured along the
control voltage wires, use No. 16 AWG color–coded wire to avoid excessive
voltage drop.
All wiring must be NEC Class 2 and must be separated from incoming power
leads.
Use furnace transformer, fan coil transformer, or accessory transformer for
control power, 24v/40va minimum.
Use of available 24v accessories may exceed the minimum 40va power
requirement. Determine total transformer loading and increase the transformer
capacity or split the load with an accessory transformer as required.
A02325 / a97413
Fig. 11 – Generic Wiring Diagrams
(See tstat Installation Instructions for specific unit combinations)
LEGEND
| 24-V FACTORY WIRING
| 24-V FIELD WIRING
| FIELD SPLICE CONNECTION
| OUTDOOR THERMOSTAT
| EMERGENCY HEAT RELAY
| SUPPLEMENTAL HEAT RELAY
Final Wiring Check
IMPORTANT: Check factory wiring and field wire connections to ensure
terminations are secured properly. Check wire routing to ensure wires are not
in contact with tubing, sheet metal, etc.
Compressor Crankcase Heater
When equipped with a crankcase heater, furnish power to the heater a minimum
of 24 hr before starting the unit. To furnish power to the heater only, set
the thermostat to OFF and close the electrical disconnect to the outdoor unit.
A crankcase heater is required if refrigerant tubing is longer than 80 ft
(24.38 m), or when the outdoor unit is 20 ft (6.10 m) below the indoor unit.
Refer to the Residential Piping and Long Line Guideline.
Install Electrical Accessories
Refer to the individual instructions packaged with kits or accessories when
installing.
Start-Up
CAUTION!
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
Wear safety glasses, protective clothing, and gloves when handling
refrigerant, and observe the following:
- Front seating service valves are equipped with Schrader valves.
CAUTION!
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental damage.
Federal regulations require that you do not vent refrigerant into the
atmosphere. Recover during system repair or final unit disposal.
CAUTION!
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this caution may result in personal injury, equipment
damage, or improper operation.
- Do not overcharge the system with refrigerant.
- Do not operate the unit in a vacuum or at negative pressure.
- Do not disable the low-pressure switches in scroll compressor applications.
- Compressor dome temperatures may be hot.
Follow these steps to properly start-up system:
- After the system is evacuated, fully open liquid and vapor service valves.
- Unit is shipped with valve stem(s) front seated (closed) and caps installed. Replace stem caps after the system is opened to refrigerant flow (back seated). Replace caps finger–tight and tighten with wrench an additional 1/12 turn.
- Close electrical disconnects to energize the system.
- Set the room thermostat at the desired temperature. Be sure the set point is below indoor ambient temperature for cooling mode operation.
- Set room thermostat to HEAT or COOL and fan control to ON or AUTO mode, as desired. Operate the unit for 15 minutes. Check system refrigerant charge.
Sequence of Operation
Turn on power to indoor and outdoor units. The transformer is energized.
Cooling
On a call for cooling, the thermostat makes circuits R–O and R–Y, and R–G.
Circuit R–O energizes reversing valve, switching it to the cooling position.
Circuit R–Y energizes the contactor, starting the outdoor fan motor and
compressor circuit. R–G energizes the indoor unit blower relay, starting the
indoor blower motor at high speed.
When the thermostat is satisfied, its contacts open, de-energizing the
contactor and blower relay. Compressors and motors should stop. If the indoor
unit is equipped with a time–delay relay circuit, the indoor blower will run
an additional 90 seconds to increase system efficiency.
Heating
On a call for heating, the thermostat makes circuits R–Y and R–G. Circuit R–Y
energizes the contactor, starting the outdoor fan motor and compressor.
Circuit R–G energizes the indoor blower relay, starting the blower motor at
high speed.
Should temperature continue to fall, R–W2 is made through the second– the
stage room thermostat. Circuit R–W2 energizes a relay, bringing on the first
bank of supplemental electric heat and providing the electrical potential to
the second heater relay (if used). If the outdoor temperature falls below the
setting of the outdoor thermostat (field installed option), contact close to
the complete circuit and bring on the second bank of supplemental electric
heat.
When the thermostat is satisfied, its contacts open, de-energizing the
contactor and relay. All heaters and motors should stop.
Quiet Shift-2
Quiet Shift-2, available on units with aluminum outdoor coils, is a field
selectable defrost mode (factory set to OFF), which will reduce the occasional
noise that could be heard at the start of defrost cycle and restarting of the
heating cycle. It is selected by placing DIP switch 3 on defrost board in the
ON position.
When the Quiet Shift-2 switch is placed in the ON position, and defrost is
initiated, the following sequence of operations will occur:
- The compressor will be de-energized for approximately 1 minute, then the reversing valve will be energized. A few seconds later, the compressor will be re-energized and the normal defrost cycle starts.
Once defrost termination conditions have been met, the following sequence will occur:
- The compressor will be de-energized for approximately 1 minute, then the reversing valve will be de-energized. A few seconds later, the compressor will be re-energized and the normal heating cycle starts.
Defrost
The defrost control is a time/temperature control that includes a field
selectable time period between defrost cycles (30, 60, 90, or 120. For non-
Quiet Shift 2 boards, the time period is selected using quick connects located
at the edge of the board. For Quiet Shift 2 boards, the time period is
selected using DIP switches located on the board. For Quiet Shift 2 boards
HK32EA011 and later used on Al coil product the setting is initial period only
then varies with defrost length).
For all defrost controls, the defrost thermostat senses coil temperature
throughout the heating cycle. When the coil temperature reaches the defrost
thermostat setting of approximately 32°F (0°C), it will close, which energizes
the DFT terminal and begins the defrost timing sequence. The timer runs only
when the defrost thermostat is closed and the contactor is energized.
Defrost mode is identical to cooling mode except that the outdoor fan motor
stops and second-stage heat are turned on to continue warming conditioned
spaces.
Defrost Speedup
Quiet Shift-2 Models
To initiate a forced defrost, speedup pins (J1) must be shorted with a flat
head screwdriver for 5 seconds and RELEASED. If the defrost thermostat is
open, a short defrost cycle will be observed (actual length depends on the
Quiet Shift-2 switch position). When Quiet Shift-2 is off, only a short
30-second defrost cycle is observed. With Quiet Shift-2 ON, the speedup
sequence is approximately 3 minutes; 1-minute compressor off period followed
by 30 seconds of defrost with compressor operation.
When returning to heating mode, the compressor will turn off for an additional
minute.
If the defrost thermostat is closed, a complete defrost cycle is initiated. If
the Quiet Shift-2 switch is turned on, the compressor will be turned off for
two 1-minute intervals as explained previously.
For HK32EA012 and later boards, if Quiet Shift 2 is enabled, the variable
defrosts intervals will be disabled to provide options where using a specific
setting is desired. In this case, the 30, 60, 90, or 120 settings will not
change unless the dipswitch is changed, and power is cycled.
NOTE: Forcing a defrost will reset the defrost interval to the DIP switch
setting before resuming variable length intervals based on defrost cycle
lengths.
All Other Models
To initiate defrost, the defrost thermostat must be closed. This can be
accomplished as follows:
-
Turn off power to the outdoor unit.
-
Disconnect outdoor fan motor lead from OF2 on the control board (see Fig. 12). Tape leads to prevent grounding.
-
Restart the unit in heating mode, allowing frost to accumulate on the outdoor coil.
-
After a few minutes in heating mode, the liquid line temperature should drop below the closing point of defrost thermostat (approximately 30°F/-1.11°C).
-
Short between speedup terminals with a flat-blade screwdriver.
This reduces the timing sequence to 1/25th of the original time. (See Table 4.) -
When you hear reversing valve change position, remove the screwdriver immediately; otherwise, the control will terminate the normal 10-minute defrost cycle in approximately 2 seconds.
NOTE: Length of defrost cycle is dependent upon the length of time it takes to remove the screwdriver from test pins after reversing valve has shifted. -
The unit will remain in defrost for the remainder of defrost cycle time or until defrost thermostat reopens at approximately 65°F (18.33°C) coil temperature of the liquid line.
-
Turn off power to the outdoor unit and reconnect the fan motor lead to OF2 on the control board.
Fig. 12 – Defrost
Control
Table 4 – Defrost Control Speedup–Timing Sequence
PARAMETER| MINIMUM (MINUTES)| MAXIMUM (MINUTES)| SPEEDUP
(NOMINAL)
---|---|---|---
30–minute cycle| 27| 33| 7 sec
50–minute cycle| 45| 55| 12 sec
90–minute cycle| 81| 99| 21 sec
10–minute cycle| 9| 11| 2 sec
5 minutes| 4.5| 5.5| 1 sec
Check Charge
Factory charge amount and desired subcooling are shown on the unit rating
plate. Additional subcooling may be required to achieve optimal heating
performance based on the installed indoor unit. (see Table 5 or 6).
The charging method is shown on the information plate inside the unit. For
TXV, use the subcooling method. For the piston, use superheat method. To
properly check or adjust the charge, conditions must be favorable for
subcooling or superheat charging. Favorable conditions exist when the outdoor
temperature is between 70°F and 100°F (21.11°C and 37.78°C), and the indoor
temperature is between 70°F and 80°F (21.11°C and 26.67°C).
Follow the procedure below:
Unit is factory charged for 15ft (4.57 m) of lineset. Adjust charge by adding
or removing 0.6 oz/ft (.018 kg/m) of 3/8 liquid line above or below 15ft (4.57
m) respectively.
For standard refrigerant line lengths (80 ft/24.38 m or less), allow the
system to operate in cooling mode for at least 15 minutes. If conditions are
favorable, check system charge by superheating method for fixed metering
device and subcooling method for TXV. If any adjustment is necessary, adjust
the charge slowly and allow the system to operate for 15 minutes to stabilize
before declaring a properly charged system. Refer to Table 5 or 6 for
additional subcooling required.
If the indoor temperature is above 80°F (26.67°C), and the outdoor temperature
is in the favorable range, adjust the system charge by weight based on line
length and allow the indoor temperature to drop to 80°F (26.67°C) before
attempting to check the system charge by subcooling method as described above.
If the indoor temperature is below 70°F (21.11°C), or the outdoor temperature
is not in the favorable range, adjust the charge for the line set length above
or below 15ft (4.57 m) only. The charge level should then be appropriate for
the system to achieve rated capacity. The charge level could then be checked
at another time when both indoor and outdoor temperatures are in a more
favorable range.
If the line length is beyond 80 ft (24.38 m) or greater than 20 ft (6.10 m)
vertical separation, See Residential Piping and Long Line Guideline for
special charging requirements.
Units with Cooling Mode TXV
Units installed with cooling mode TXV require charging by the subcooling
method.
- Operate the unit a minimum of 15 minutes before checking the charge.
- Measure liquid service valve pressure by attaching an accurate gauge to the service port.
- Measure liquid line temperature by attaching an accurate thermistor type or electronic thermometer to the liquid line near the outdoor coil.
- Refer to unit rating plate for required subcooling temperature.
- Refer to Table 7. Find the point where the required subcooling temperature intersects measured liquid service valve pressure.
- To obtain the required subcooling temperature at specific liquid line pressure, add refrigerant if the liquid line temperature is higher than indicated or reclaim refrigerant if the temperature is lower. Allow a tolerance of ?3°F.
Units with Indoor Pistons
Units installed with indoor pistons require charging by the superheat method.
The following procedure is valid when indoor airflow is within. 21 percent of
its rated CFM.
- Operate the unit a minimum of 15 minutes before checking the charge.
- Measure suction pressure by attaching an accurate gauge to the suction valve service port.
- Measure suction temperature by attaching an accurate thermistor type or electronic thermometer to the suction line at the service valve.
- Measure outdoor air dry–bulb temperature with a thermometer.
- Measure indoor air (entering indoor coil) wet–bulb temperature with a sling psychrometer.
- Refer to Table 8. Find outdoor temperature and evaporator entering air wet–bulb temperature. At this intersection, note superheat. Where a dash (––) appears on the table, do not attempt to charge the system under these conditions, or refrigerant slugging may occur. The charge must be weighted in, adding or removing 0.6 oz/ft of 3/8 liquid line above or below 15 ft (4.57 m) respectively.
- Refer to Table 9. Find superheat temperature located in item 6 and suction pressure. At this intersection, note the suction line temperature.
- If the unit has a higher suction line temperature than charted temperature, add refrigerant until the charted temperature is reached.
- If the unit has a lower suction line temperature than charted temperature, reclaim refrigerant until the charted temperature is reached.
- When adding refrigerant, charge in liquid form into the suction service port using a flow–restricting device.
- If outdoor air temperature or pressure at the suction valve changes, charge to the new suction line temperature indicated on the chart.
- Optimum performance will be achieved when the operating charge produces 5° to 6°F suction superheat at the suction service valve with 82°F outdoor ambient and 80°F (26.7°C) dry bulb 67°F (19.4°C) wet bulb indoor temperature (DOE “B” test conditions) at rated airflow.
Heating Check Chart Procedure
To check system operation during a heating cycle, refer to the Heating Check
Chart on the outdoor unit. This chart indicates whether a correct relationship
exists between system operating pressure and air temperature entering indoor
and outdoor units. If pressure and temperature do not match the chart, the
system refrigerant charge may not be correct. Do not use the chart to adjust
the refrigerant charge.
Table 5 – Additional Subcooling Required – Model 25H4**
Subcooling Delta from Rating Plate Value
Outdoor Unit Tonnage
Indoor Unit | Additional Subcooling Required
18| 24| 30| 36| 42| | 48| 60|
CAP1814AL*| –| CAP*2414AL| –| CAP3014AL*| –| CAP3614AL*| –|
CAP*4221AL| –| CAP4817AL*| +5| CAP6021AL*| –
CAP*2414AL| –| CAP2417AL*| –| CAP3017AL*| –| CAP*3617AL| –|
CAP4224AL*| –| CAP4821AL*| +3| CAP*6024AL| –
CAP2417AL*| –| CAP2517AL*| +5| CAP*3614AL| –| CAP3621AL*| –|
CAP4321AL*| +5| CAP*4824AL| +3| CAP6124AL| –
CNPV1814AL*| –| CAP3014AL*| –| CAP*3617AL| –| CAP4221AL*| +3|
CAP4817AL*| +5| CAP*6021AL| +5| CNPV6024AL| –
CNPV2414AL| +3| CAP3017AL*| –| CAP3621AL*| –| CAP*4224AL| +3|
CAP4821AL*| +3| CAP6024AL| +5| CSPH6012AL| –
CNPV2417AL| +3| CNPV2414AL*| –| CAP*3717AL| +5| CNPV3617AL| –|
CAP4824AL*| +3| CAP*6124AL| +5| FB4CNP060L| –
CSPH2412AL| +3| CNPV2417AL| –| CAP*3721AL| +5| CNPV3621AL| –|
CNPV4217AL| –| CNPV4821AL| –| FV4CNB006L| –
FB4CNF018L| –| CNPV3014AL| –| CNPV3014AL| –| CNPV4217AL| +3|
CNPV4221AL| –| CNPV4824AL| –| FX4DN(B, F)061L| –
FB4CNF024L| –| CNPV3017AL| –| CNPV3017AL| –| CNPV4221AL| +3|
CNPV4821AL| –| CNPV6024AL| +3| |
FB4CNP018L| –| CSPH2412AL| –| CNPV3617AL| –| CSPH3612AL| +3|
CNPV4824AL| –| CSPH4812AL| –| |
FB4CNP024L| –| CSPH3012AL| –| CNPV3621AL| –| CSPH4212AL| +5|
CSPH4212AL| –| CSPH6012AL| +3| |
FFMANP018| –| FB4CNF030L| –| CSPH3012AL| –| FB4CNF036L| –| CSPH4812AL| –|
FB4CNF048L| –| |
FFMANP019| –| FB4CNP030L| –| CSPH3612AL| +3| FB4CNF042L| +5| FB4CNF042L| –|
FB4CNP048L| –| |
FFMANP024| –| FFMANP024| –| FB4CNF030L| –| FB4CNP036L| –| FB4CNF048L| –|
FB4CNP060L| +3| |
FFMANP025| –| FFMANP025| –| FB4CNF036L| –| FB4CNP042L| +5| FB4CNP042L| –|
FV4CN(B, F)005L| +3| |
FPMAN018| –| FFMANP030| –| FB4CNP030L| –| FFMANP036| –| FB4CNP048L| –|
FV4CNB006L| +5| |
FPMAN024| –| FFMANP031| –| FB4CNP036L| –| FFMANP037| –| FV4CN(B, F)003L| –|
FX4DN(B, F)049L| +3| |
FPMBN018| –| FPMAN024| –| FFMANP030| –| FPMAN036| –| FV4CN(B,F)005L| +3|
FX4DN(B,F)061L| +5| |
FPMBN024| –| FPMAN030| –| FFMANP031| –| FV4CN(B, F)003L| –| FV4CNB006L| +5|
| | |
FV4CN(B,F)003L| +5| FPMBN024| –| FFMANP036| –| FV4CN(B,F)005L| +5|
FX4DN(B,F)043L| –| | | |
FV4CNF002L| +5| FPMBN030| –| FFMANP037| –| FV4CNB006L| +5| FX4DN(B, F)049L|
+3| | | |
FX4DNF019L| +3| FV4CN(B,F)003L| –| FPMAN030| –| FV4CNF002L| –| FX4DN(B,
F)061L| +5| | | |
FX4DNF025L| +3| FV4CNF002L| –| FPMAN036| –| FX4DN(B, F)037L| +5| | | | | |
| | FX4DN(B,F)031L| –| FPMBN030| –| FX4DN(B, F)043L| +5| | | | | |
| | FX4DN(B,F)037L| +5| FV4CN(B,F)003L| –| FX4DN(B, F)049L| +5| | | | | |
| | FX4DNF025L| –| FV4CN(B, F)005L| +5| | | | | | | |
| | | | FV4CNF002L| –| | | | | | | |
| | | | FX4DN(B,F)031L| –| | | | | | | |
| | | | FX4DN(B, F)037L| +5| | | | | | | |
| | | | FX4DN(B, F)043L| +5| | | | | | | |
Table 6 – Additional Subcooling Required – Model 25H5**
Subcooling Delta from Rating Plate Value
Outdoor Unit Tonnage
Indoor Unit | Additional Subcooling Required
18| 24| 30| 36| 42| 48| 60
CAP1814AL*| –| CAP*2414AL| –| CAP3014AL*| –| CAP3614AL*| –|
CAP*4221AL| –| CAP4817AL*| –| CAP6021AL*| –
CAP*2414AL| –| CAP2417AL*| –| CAP3017AL*| –| CAP*3617AL| –|
CAP4224AL*| –| CAP4821AL*| –| CAP*6024AL| –
CAP2417AL*| –| CAP2517AL*| +5| CAP*3614AL| –| CAP3621AL*| –|
CAP4321AL*| +5| CAP*4824AL| –| CAP6124AL| –
CNPV1814AL*| –| CAP3014AL*| –| CAP*3617AL| –| CAP4221AL*| –|
CAP4817AL*| +5| CAP*6021AL| –| CNPV6024AL| –
CNPV2414AL| –| CAP3017AL*| –| CAP3621AL*| –| CAP*4224AL| –|
CAP4821AL*| +3| CAP6024AL| –| CSPH6012AL| –
CNPV2417AL| –| CNPV2414AL*| –| CAP*3717AL| +5| CNPV3617AL| –|
CAP4824AL*| +3| CAP*6124AL| +3| FB4CNP060L| –
CSPH2412AL| –| CNPV2417AL| –| CAP*3721AL| +5| CNPV3621AL| –|
CNPV4217AL| –| CNPV4821AL| –| FV4CNB006L| –
FB4CNF018L| –| CNPV3014AL| –| CNPV3014AL| –| CNPV4217AL| –|
CNPV4221AL| –| CNPV4824AL| –| FX4DN(B, F)061L| –
FB4CNF024L| –| CNPV3017AL| –| CNPV3017AL| –| CNPV4221AL| –|
CNPV4821AL| –| CNPV6024AL| –| |
FB4CNP018L| –| CSPH2412AL| –| CNPV3617AL| –| CSPH3612AL| –|
CNPV4824AL| –| CSPH4812AL| –| |
FB4CNP024L| –| CSPH3012AL| –| CNPV3621AL| –| CSPH4212AL| –|
CSPH4212AL| –| CSPH6012AL| –| |
FFMANP018| –| FB4CNF030L| –| CSPH3012AL| –| FB4CNF036L| –| CSPH4812AL| –|
FB4CNF048L| –| |
FFMANP019| –| FB4CNP030L| –| CSPH3612AL| –| FB4CNF042L| –| FB4CNF042L| –|
FB4CNP048L| –| |
FFMANP024| –| FFMANP024| –| FB4CNF030L| –| FB4CNP036L| –| FB4CNF048L| –|
FB4CNP060L| –| |
FFMANP025| –| FFMANP025| –| FB4CNF036L| –| FB4CNP042L| –| FB4CNP042L| –|
FV4CN(B, F)005L| –| |
FPMAN018| –| FFMANP030| –| FB4CNP030L| –| FFMANP036| –| FB4CNP048L| –|
FV4CNB006L| +3| |
FPMAN024| –| FFMANP031| –| FB4CNP036L| –| FFMANP037| –| FV4CN(B, F)003L| –|
FX4DN(B, F)049L| –| |
FPMBN018| –| FPMAN024| –| FFMANP030| –| FPMAN036| –| FV4CN(B,F)005L| +3|
FX4DN(B,F)061L| +3| |
FPMBN024| –| FPMAN030| –| FFMANP031| –| FV4CN(B, F)003L| –| FV4CNB006L| +5|
| | |
FV4CN(B, F)003L| –| FPMBN024| –| FFMANP036| –| FV4CN(B,F)005L| +3|
FX4DN(B,F)043L| –| | | |
FV4CNF002L| –| FPMBN030| –| FFMANP037| –| FV4CNB006L| +5| FX4DN(B, F)049L|
+3| | | |
FX4DNF019L| –| FV4CN(B, F)003L| –| FPMAN030| –| FV4CNF002L| –| FX4DN(B,
F)061L| +5| | | |
FX4DNF025L| –| FV4CNF002L| –| FPMAN036| –| FX4DN(B, F)037L| –| | | | | |
| | FX4DN(B,F)031L| –| FPMBN030| –| FX4DN(B, F)043L| –| | | | | |
| | FX4DN(B,F)037L| +5| FV4CN(B,F)003L| –| FX4DN(B, F)049L| +3| | | | | |
| | FX4DNF025L| –| FV4CN(B, F)005L| +5| | | | | | | |
| | | | FV4CNF002L| –| | | | | | | |
| | | | FX4DN(B,F)031L| –| | | | | | | |
| | | | FX4DN(B, F)037L| +3| | | | | | | |
| | | | FX4DN(B, F)043L| +3| | | | | | | |
Table 7 – Required Liquid Line Temperatures °F
LIQUID PRESSURE AT SERVICE VALVE (PSIG)|
REQUIRED SUBCOOLING TEMPERATURE (°F)
---|---
8| 10| 12| 14| 16| 18
251| 76| 74| 72| 70| 68| 66
259| 78| 76| 74| 72| 70| 68
266| 80| 78| 76| 74| 72| 70
274| 82| 80| 78| 76| 74| 72
283| 84| 82| 80| 78| 76| 74
291| 86| 84| 82| 80| 78| 76
299| 88| 86| 84| 82| 80| 78
308| 90| 88| 86| 84| 82| 80
317| 92| 90| 88| 86| 84| 82
326| 94| 92| 90| 88| 86| 84
335| 96| 94| 92| 90| 88| 86
345| 98| 96| 94| 92| 90| 88
354| 100| 98| 96| 94| 92| 90
364| 102| 100| 98| 96| 94| 92
374| 104| 102| 100| 98| 96| 94
384| 106| 104| 102| 100| 98| 96
395| 108| 106| 104| 102| 100| 98
406| 110| 108| 106| 104| 102| 100
416| 112| 110| 108| 106| 104| 102
427| 114| 112| 110| 108| 106| 104
439| 116| 114| 112| 110| 108| 106
450| 118| 116| 114| 112| 110| 108
462| 120| 118| 116| 114| 112| 110
474| 122| 120| 118| 116| 114| 112
486| 124| 122| 120| 118| 116| 114
499| 126| 124| 122| 120| 118| 116
511| 128| 126| 124| 122| 120| 118
Table 8 – Superheat Charging (Heat Pump Only)
OUTDOOR TEMP (°F)| EVAPORATOR ENTERING AIR TEMPERATURE (°F
WB)
---|---
50| 52| 54| 56| 58| 60| 62| 64|
67| 68| 70| 72| 74| 76
55| 11| 11| 12| 12| 12| 13| 17| 20| 24| 24| 25| 25| 25| 25
60| 6| 6| 7| 7| 7| 7| 12| 16| 21| 22| 23| 23| 23| 23
65| –| –| –| –| –| 3| 7| 12| 18| 19| 21| 21| 22| 22
70| –| –| –| –| –| –| –| 7| 14| 16| 18| 20| 20| 20
75| –| –| –| –| –| –| –| 3| 11| 13| 16| 18| 18| 19
82| –| –| –| –| –| –| –| –| *6| 8| 12| 15| 16| 17
85| –| –| –| –| –| –| –| –| 4| 7| 11| 14| 15| 16
90| –| –| –| –| –| –| –| –| –| 4| 8| 12| 14| 15
95| –| –| –| –| –| –| –| –| –| –| 6| 10| 12| 14
100| –| –| –| –| –| –| –| –| –| –| 4| 8| 11| 12
105| –| –| –| –| –| –| –| –| –| –| 3| 6| 9| 11
110| –| –| –| –| –| –| –| –| –| –| –| 5| 7| 10
115| –| –| –| –| –| –| –| –| –| –| –| 3| 6| 8
*. Optimum performance point, 82°F outdoor ambient and (80°F dry bulb),( 67°F wet bulb) indoor conditions. (DOE B Test Conditions)
Where a dash (––) appears do not attempt to charge the system under these
conditions or refrigerant slugging may occur. The charge must be weighed in.
Note : Superheat °F is at low–the side service port, Allow a tolerance of
± 3°F
Note : Indoor dry bulb between 70°F and 80°F
Table 9 – Required Suction–Line Temperature
SUPERHEAT TEMP (°F)|
SUCTION PRESSURE AT SERVICE PORT (PSIG)
---|---
107.8| 112.2| 116.8| 121.2| 126| 130.8|
138.8| 140.8| 145.8
0| 35| 37| 39| 41| 43| 45| 47| 49| 51
2| 37| 39| 41| 43| 45| 47| 49| 51| 53
4| 39| 41| 43| 45| 47| 49| 51| 53| 55
6| 41| 43| 45| 47| 49| 51| 53| 55| 57
8| 43| 45| 47| 49| 51| 53| 55| 57| 59
10| 45| 47| 49| 51| 53| 55| 57| 59| 61
12| 47| 49| 51| 53| 55| 57| 59| 61| 63
14| 49| 51| 53| 55| 57| 59| 61| 63| 65
16| 51| 53| 55| 57| 59| 61| 63| 65| 67
18| 53| 55| 57| 59| 61| 63| 65| 67| 69
20| 55| 57| 59| 61| 63| 65| 67| 69| 71
22| 57| 59| 61| 63| 65| 67| 69| 71| 73
24| 59| 61| 63| 65| 67| 69| 71| 73| 75
26| 61| 63| 65| 67| 69| 71| 73| 75| 77
28| 63| 65| 67| 69| 71| 73| 75| 77| 79
30| 65| 67| 69| 71| 73| 75| 77| 79| 81
Final Checks
IMPORTANT: Before leaving your job, be sure to do the following:
- Ensure that all wiring is routed away from tubing and sheet metal edges to prevent rub–through or wire pinching.
- Ensure that all wiring and tubing are secure in the unit before adding panels and covers. Securely fasten all panels and covers.
- Tighten service valve stem caps to 1/12–turn past finger tight.
- Leave Owner’s Manual with the owner. Explain system operation and periodic maintenance requirements outlined in the manual.
- Fill out the Dealer Installation Checklist and place it in the customer file.
Care and maintenance
For continuing high performance and to minimize possible equipment failure,
periodic maintenance must be performed on this equipment.
The frequency of maintenance may vary depending upon geographic areas, such as
coastal applications. See Users Manual for information.
Training
My Learning Center is your central location for professional residential HVAC
training resources that help strengthen careers and businesses. We believe in
providing high-quality learning experiences both online and in the classroom.
Access My Learning Center with your HVACpartners credentials at
www.mlctraining.com. Please contact us a
mylearning@carrier.com with questions.
© 2021 Carrier. All rights reserved.
Edition Date: 06/21
Catalog No: 25HBC-HCE-04SI
Replaces:25HBC-HCE-03SI
The manufacturer reserves the right to change, at any time,
specifications and designs without notice and without obligations.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>