S P CAD HE 450 Counter Flow High Efficiency Heat Recovery Unit Instruction Manual
- June 14, 2024
- S P
Table of Contents
- GENERAL INFORMATION
- TECHNICAL INFORMATION
- INSTALLATION
- CHARACTERISTICS AND ELECTRICAL CONNECTIONS
- REMOTE CONTROL ADJUSTMENTS —- INSTALLER
- FROST PROTECTION MODE
- SWITCHING ON THE CAD HE 325/450/575
- ALARM INDEX
- SPARE PARTS
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
CAD HE 325/450/575 EC V BASIC
GENERAL INFORMATION
1.1 Introduction
This product was manufactured according to rigorous technical safety rules in
compliance with DC standards. The DC declaration and the manual can be
downloaded from the Internet.
Before installing and using this product, carefully read these instructions,
which contain important indications to ensure your safety and that of the
users during the installation, commissioning and servicing of this product.
Once the installation is terminated, store the manual on a place where it is
accessible.
The installation of this product (implementation, connections, commissioning,
and maintenance) and all other interventions must be performed by a
professional, applying the recognized rules of good practice, standards and
safety regulations in force.
It must conform to the prescriptions related to Electromagnetic Compatibility
(EMC) and the Low Voltage Directive (LVD).
S&P shall not be held responsible for possible injuries and/or damages caused
by the noncompliance with safety instructions or following a modification of
the product.
The CAD HE 325/450/575 Units are designed for dual flow air ventilation and
air treatment applications in public and private buildings:
- Indoor installation
- Minimum recommended ambient temperature where the unit is installed >10ºC
- Working temperature: -25°C / +40°C.
- Relative humidity: max 95% non-condensing.
- Atmosphere not potentially explosive.
- Atmosphere with low salt content, without corrosive chemical agents.
1.2 Acceptance – Storage
In case of missing, non-conforming, or totally or partially damaged delivered
products, the Purchaser must make written reservation on the transporter’s
receipt and confirm them within seventy-two (72) hours by sending a
recommended letter to the transporter, as well as a copy to S&P. Acceptance of
the unit without any reservation will deprive the purchaser of any subsequent
recourse against us.
The product must be stored in an area protected from bad weather, shocks and
stains due to splashing or splattering of any kind during its transport from
the supplier to the end customer and onto the worksite before installation.
1.3 Warranty and Liability
Warranty
The unit supplied by S&P is warranted 2 years. Parts only starting from the
invoicing date.
S&P agrees to replace the parts or the unit whose operation is recognized
defective by our departments except for all damages and interests or penalties
such as operating losses, commercial prejudice, or other immaterial or
indirect damages.
The following are not covered by our warranty: defects resulting from an
abnormal usage or a usage not conforming to the recommendations of our
manuals; faults observed as a consequence to normal wear; incidents caused by
negligence, lack of monitoring, or servicing; faults due to the incorrect
installation of the devices or to bad storage conditions before mounting.
In any case, S&P will not be responsible for transformed unit, repaired even
partially.
TECHNICAL INFORMATION
2.1 General information
Extraction of stale air and supply of fresh air in public/private premises
with heat recovery by a counter flow aluminium heat exchanger.
Condensation forms during the heat exchange process is recovered in the
condensate tray, which must be connected to a waste water drain.
The CAD HE 325/450/575 has a 100% heat exchanger bypass system which allows
free cooling by night. The principle of free-cooling uses free energy from the
outdoor air to ventilate and cool buildings when outdoor air temperature is
lower than the exhaust air temperature, during the night in summer for
example. The system operates automatically or can be used manually.
2.2 Description
Outdoor air (ODA):
Install the fresh air intake (wall or roof) at a sufficient distance from any
are high pollution (trees, exhaust fumes, road, etc).
** This duct must be sealed and insulated to prevent condensation.
Supply air (SUP):
To avoid thermal losses and optimize the performance of the installation, it
is recommended to use insulated ducts.
Extract air (ETA):
To avoid thermal losses and optimize the performance of the installation, it
is recommended to use insulated ducts.
Exhaust air (EHA):
This duct must be sealed and insulated to prevent condensation.
By-pass:**
The CAD HE 325/450/575 has a 100% heat exchanger bypass system which allows
free cooling by night. The principle of free-cooling uses free energy from the
outdoor air to ventilate and cool buildings when outdoor air temperature is
lower than the exhaust air temperature.
2.3 Dimensions (in mm)
Remote control via cable (1,5m included)
Optional:
Max. cable length: 50m (control wire type min. H05VV F 4G 0,25)
INSTALLATION
The CAD HE 325/450/575 heat recovery unit is designed for indoor
installation.
We recommend a min. temperature of >10ºC in the room where the unit is
installed to guarantee a good efficiency of the unit.
In areas where temperatures can be below -10º C in the winter time, it is
necessary to install a pre-heating device.
CHARACTERISTICS AND ELECTRICAL CONNECTIONS
| Power (V/Hz)| Power (W)| Absorbed current (A)| Working temperature (°C)
---|---|---|---|---
CAD 325| 230/50| 230| 1,3| from -25 to 40
CAD 325 PH| 230/50| 1730| 8,1| from -25 to 40
CAD 450| 230/50| 345| 2,08| from -25 to 40
CAD 450 PH| 230/50| 1845| 9.| from -25 to 40
CAD 575| 230/50| 362| 3.| from -25 to 40
CAD 575 PH| 230/50| 1862| 9,3| from -25 to 40
Yellow/ amarillo/ jaune/ giallo/ Geel
4.1. Sensor connection
The CAD HE can work in proportional mode controlled by a sensor 0-10V (see
electrical scheme).
The output control voltage for the sensor is adjusted between 2V and 8V. The
2V output signal correspond with the output signal to the fans of 4V and the
8V output signal correspond with the 10V output signal to the fans.
The chart below show the working range of the recommended S&P sensors.
CO2 sensors: SCO2-AD 0/10V; SCO2-G 0/10V
Relative humidity sensors (r.H.): SHT-A 0-10V; SHT-G 0/10V
REMOTE CONTROL ADJUSTMENTS —- INSTALLER
The remote control allows:
Adjust the airflows (1° speed, 2 speed, 37 speed)
Timer for adjusting the filter maintenance period (6, 9, 12 or 15 months)
(factory setting 9 months)
Adjust the balance of supply/extraction airflows
Adjustment of the airflows
To adjust the airflow turn the potentiometer carefully clock wise with a small
screw driver. The potentiometer has 16 positions (from 0 to F). To each of
these positions are assigned an output voltage to the fans. As higher the
output voltage as higher the airflow and vice versa.
To adjust the airflow turn the potentiometer carefully clock wise with a small
screw driver. The
Position Potentiometer | 0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | A | B | C | D | E | F |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Assigned Voltage | 2.5 | 3 | 3.5 | 4 | 4.5 | 5 | 5.5 | 6 | 6.5 | 7 | 7.5 | 8 | 8.5 | 9 | 9.5 |
10
Factory setting: 1st speed = 3; 2nd speed = 7 and 3rd speed = F.
Adjustment of the filter maintenance period
It is possible to set the period to 6, 9, 12 or 15 months (9 months factory
setting). The filter clogging depends on the pollution of the area where the
unit is installed. We recommend checking the time in which the filter clogs
and adjusting this period. It is advisable to do this after the second filter
change. Of course, after the installation, the extract air is dusty and not
representative. During the second filter check, if you notice that the filters
are clean you can increase the time (12 or 15, months), if you notice that the
filters are very dirty you should decrease the time (6 months).
Open the box and adjust the timing as shown. To do this, set the micro
contacts 1 and 2 as shown in the drawings below to adjust the month.
Supply/extraction airflow adjustment
In the case that in the building is a chimney, gas oven or any apparatus which
needs combustion air and there is no additional supply air opening for this,
it is necessary to adjust the unit in the way that the combustion is not
affected. It is necessary to adda supplementary air supply equal to the
extract airflow due to the natural draught of the chimney.
This feature can be used also to balance once the installation is finished the
two airflows.
Example:
- Minimum calculated airflow = 90m/h
- Supply airflow necessary = 99 m3/h
→ Potentiometer position 5 = +10% 3
The adjustment is made on the supply airflow compared with extraction airflow.
REMOTE CONTROL ADJUSTMENTS- USER
Speed adjustment:
Pressing the “airflow adjustment” buttons you can change the speed. The LED
will be green illuminated (see pictures below).
Automatic bypass:
The CAD HE 325/450/575 works with a pre-programmed automatic bypass.
The following conditions have to be fulfilled to open/close the bypass.
Tint = indoor temperature
Text = outdoor temperature
Manual bypass:
Pressing the button “manual bypass” the bypass will open for 8 hours. During
the bypass activated the button is green illuminated. To deactivate (close)
within the 8 the bypass you have to push the button again (illumination is
off).
Standby function:
Push and hold the button for 3 seconds, the unit will switch into the standby
mode. (see drawing below). To switch the unit on push the button again.
Maintenance and replacement of the filter:
When the button is red illuminated, please check the filter as a maintenance
is necessary. After the filter change press the button during 3 seconds in
order to reset the filter alarm.
For opening the unit press the buttons to release the door.
For security reasons the unit has an integrated electro magnetic door switch
which disconnects the power supply when the door is opened.
For maintenance purposes an additional safety isolator switch should be
installed.
****Once the door is opened you can access the filters to change them.
FROST PROTECTION MODE
CAD HE 325/450/575 EC V BASIC:
All standard units have an automatic frost protection system installed. In the
case that the exhaust air (EHA) temperature fall below 5°C and the outdoor air
temperature is less than 0°C the defrost mode will start. The supply fan
decreases the velocity whilst the exhaust fan works on the nominal airflow.
This unbalance avoids the building of ice into the exchanger.
In case that this unbalance will not be enough the unit stops during 2 hours.
Every 2 hours the CAD will start-up for a short time to check if the
temperature conditions are favourable to return to work normal.
We recommend not to use this unit in combination with devices which are using
combustion air unless there is a security device installed which would switch
of the unit in case of pressure difference in the house.
CAD HE 325/450/575 EC V BASIC PH:
In the “PH” units there is installed an electric heater element as a pre-
heater. This pre-heater avoids the ice building in the exchanger without
unbalancing the airflows and works fully autonomous without any need for
adjustments from user side.
Function:
In the case that the exhaust air (EHA) fall below 5°C the frost protection
starts activating the pre-heater. The pre-heater is working proportional in
dependency of the temperatures measured by the unit. If the power of the pre-
heater is not enough to keep the exhaust temperature (EHA) above 3°C the
velocity of both fans will be reduced proportionally in order to increase the
temperature for the supply air. If this is still not enough, to the avoid
freezing of the exchanger, the unit stops during 2 hours. Every 2 hours the
CAD will start-up for a short time to check if the temperature conditions are
favourable to return to work normal.
Technical datas:
Electrical supply: ~230 Vac 50 Hz
Power: 1500 W
Absorbed current: 6,8 A
Thermal difference at nominal airflow:
P: Electric power
P: Electric power
Q: Airflow
Cp: Specific heat of air
Cp(0°C)=1006 lj/kj. K
P: air density
SWITCHING ON THE CAD HE 325/450/575
To start your CAD HE 325/450/575 unit use the following process:
-
Verify that all system components are correctly installed and connected: Fresh air intake duct insulated and connected correctly (Do not use a fresh air intake equipped with insect screen)
Fresh air and exhaust ducts insulated and connected correctly Fresh air and exhaust vents connected
Flow regulators mounted in the right direction (if installed)
Air outlet using insulated duct and connected to the outside (Using a roof cowl or outlet without an insect screen)
Insulated flexible ducts taut and large radius bends (if installed)
Check that the unused spigots on plenums are sealed (if installed) Condensation drain well connected (siphon)
Check that all connections are sealed (on the CAD HE 325/450/575, on plenums and vents) Check the setting of the power circuit breaker -
Turn on the CAD HE 325/450/575.
-
Check the airflows.
ALARM INDEX
Through the LED located in the user control it is possible to supervise the status of the unit. This Led will show the alarm (check see table) in case of produce the failure of some critical components of the unit or simply by notification (replacement filters, by-pass manual mode, supply temperature <11ºC). Depending on risk level of the alarm generated, the control will manage the response required. If it is necessary, the unit will be stopped for safety reasons.
Priority | Alarm/State | LED | ACTION |
---|---|---|---|
1 | Extract fan Failure | Red LED, 1 blink | Unit stops |
2 | Supply fan failure | Red LED, 2 blinks | Unit stops |
3 | Supply air temperature <11°C | Red LED, 4 blinks | Unit stops. Every 2 hours |
the unit starts for 5
minutes to check if
conditions allow normal
operation.
4| ODA Sensor failure (fresh air)| Red LED, 5 blinks| Normal operation
5| SUP sensor failure (supply)| Red LED, 6 blinks| Normal operation
6| ETA sensor failure (extract)| Red LED, 7 blinks| Normal operation
7| EHA sensor failure (exhaust)| Red LED, 8 blinks| Normal operation
8| Dirty filter failure| Red LED continuous| Normal operation
9| ON Bypass manual mode| Green LED continuous| Normal operation
10| Active defrost| Green LED blinking| Defrost management
SPARE PARTS
| CAD 325| CAD 450| CAD 575|
---|---|---|---|---
1| R153708007| R153667001| R153815001| Supply air fan
2| R153708001| R153667007| R153815007| Extract air fan
3| | R153667016| R153667016| Main control circuit
4| | R153667009| R153667009| Servomotor
S&P SISTEMAS DE VENTILACIÓN, S.L.U.
C. Llevant, 4
Polígono Industrial Llevant
08150 Parets del Vallès
Barcelona – España
Tel. +34 93 571 93 00
www.solerpalau.com