  • Model: BLF-48105H
  • Website:www.AntraPower.com
  • Voltage: High Voltage
  • Intended Users: Trained technicians only

Unpacking

Check the battery upon arrival to ensure there is no damage during transit. If you notice any dents or signs of damage, do not use the battery. Instead, report it to the carrier and contact customer service immediately.

Connecting Procedure

  1. Mount the battery securely on a rack or a safe location for installation.
  2. Ensure that the main DC power switch on the battery is in the OFF position.
  3. Connect the Positive Cable Connectors of the Inverter/Charger to the Positive terminal of the battery. Make sure the connection is tight and secure.
  4. Connect the Negative Cable Connectors of the Inverter/Charger to the Negative terminal of the battery. Ensure the connection is tight and secure.
  5. Verify all connections are correct and secure before switching on the main power switch.
  6. Note: For parallel connections, each battery terminal should have a properly sized dedicated cable. Never use a single cable to share multiple battery currents as it may cause overheating and fire.

Power ON / OFF, Reset

  • The battery enters power-saving mode when it has no load for a period of time.
  • To power the battery, press the reset button using a plastic needle. The State of Charge (SOC) LEDs will light up and the LCD screen will display the main screen. The RUN LED will flash.
  • To manually switch off the battery (put it into sleep mode), Press and hold the RST button.

Communication with Inverters

  1. Inverters & Protocol Supported: Ensure that the inverter supports one of the following protocols: CAN (Pylon, Growwatt, Victron, Goodwe, GinLong, Pengcheng, Sofar, etc.) or 485 (Pylon, Sol-Ark/SRNE, Growwatt, Deye, Voltronic, Paceic).
  2. Hardware-Ports/Wiring: The BMS Port is used for communication and can support both CAN and 485 protocols. Refer to the inverter’s user manual to locate the battery communication port on the inverter. Note that the right two RS485 ports are for inter-battery connections in multi-battery applications. Always use the RS485/CAN port for inverter or PC communications.
  3. Connect Procedures: If the inverter supports Pylon (CAN or 485), no additional steps are needed on the battery BMS.

If different protocols need to be used:

  1. Refer to the PC-Battery Communications Instructions and update the default protocol in the battery BMS to the one supported by the inverter.
  2. Single Battery:
    • Connect the INVERTER side RJ45 to the BMS port on the inverter.
    • Connect the BATTERY side RJ45 to the RS-485/CAN port.
    • Set DIP switches: ALL OFF (See Multiple Batteries Setup for Multiple Battery Applications).
    • Connect the battery and power on the inverter. Access the menu that enables BMS communication (specific to the inverter), and the inverter might beep for warning.
    • Choose Pylon (or other supported protocols) and confirm.
    • The inverter and battery should be connected, and the warning beep will stop.
  3. Multiple Batteries (SOC is the average of all batteries):
    • Set one of the batteries as the Master battery.
    • Connect the Master battery to the inverter using the RJ45 cable made in section 2.
    • Set DIP switches: DIP 1-4 of (Set as MASTER, address 0); DIP 5-8 as the total quantity of slaves connected to the Master. Refer to the provided table for specific configurations.

FAQ

Q: Can I use the battery if I notice any damage during transit?

  • A : No, if you notice any dent or signs of damage on the battery during transit, do not use it. Report the damage to the carrier and contact customer service immediately.

Q: What should I do if the battery does not power on?

  • A : If the battery does not power on, press and hold the reset button using a plastic needle. If the issue persists, contact customer service for further assistance.

Q: How do I connect multiple batteries to an inverter?

  • A : To connect multiple batteries, set one battery as the Master battery and connect it to the inverter using the provided RJ45 cable. Set the appropriate DIP switch configurations as instructed in the user manual.
  • To be operated by trained technicians only

Unpacking

  • Check the battery to make sure there is no damage during the transit, if any dent or other signs of damage are found, DO NOT use the battery. Report to the carrier and contact customer service immediately.

Connecting Procedure

  • Mount the battery securely on a rack or a place that is safe for battery installation.
  • Make sure the main DC power switch on the battery is in the OFF position.
  • Connect the Positive Cable Connectors of Inverter/Charger to the Positive terminal of the battery, and make sure it is tight and snug.
  • Connect the Negative Cable Connectors of the Inverter/Charger to the Negative terminal of the battery, and make sure it is tight and snug.
  • Verify all the connections are correct and secure before switching on the main power switch.
  • NOTE: Parallel connection, each battery terminal should have a proper-sized dedicated cable to the proper-sized bus terminal plate/bar where all battery cables, charger, and discharger cables are connected. NEVER use a single cable to share multiple battery currents in any circumstances. It will overheat the cable and may cause fire.

Power ON / OFF, Reset

  • The battery goes into power-saving mode when it has no load for a period.
  • Press the reset button using a plastic needle to power the battery. SOC LEDs will lid and the LCD screen will show the main screen. The RUN LED is flashing.
  • To switch off the battery (Manually put it into sleep mode), press and hold the RST button until the SOC LEDs flash 3 times, then release the button. All the lights will go off, as well as the LCD screen.
  • To reset the system, press and hold the RST button for about 10 seconds and release, the system is restarted.
  • Use the keys to navigate and monitor the BMS information such as cell voltages and temperatures.
  • NOTE: Loads below 50 watts might not be detected by the BMS, and it might trigger the sleep mode.
  • When Switching on the battery breaker after connecting to the inverter, overcurrent protection (OCP) might occur due to the large capacitor inside the inverter.
  • The red light will lid and the battery will come back to normal within 1-2 minutes. If it cannot be recovered, reset the battery.

Communication with Inverters

  1. Inverters & Protocol supported (Up to 16 Batteries to 1 inverter allowed)
    • Make sure the inverter supports one of the following protocols:
    • CAN: Pylon (Default), Growwatt, Victron, Goodwe, GinLong, Pengcheng, Sofar etc 485: Pylon (Default), Sol-Ark/SRNE, Growwatt, Deye, Voltronic, Paceic
  2. Hardware-Ports/Wiring-Port: BMS Port (CAN & 485 share the same port) as shown below. Refer to the inverter’s user manual and locate the battery communication port on the inverter.
    • Note: The right two RS485 ports are for inter-battery connections in multi-battery applications. Always use the RS485/CAN port for inverter or PC communications
    • DO NOT USE an internet cable for the communication between the inverter and the battery!
    • Make a cable according to your applications as follows:
    • For RS485 Protocol, use the following PINs:
    • PIN#1—————–485B
    • PIN#2—————–485A
    • For CAN Protocol, use the following PINs:
    • PIN#4—————–CAN_H
    • PIN#5—————–CAN_L
    • Check the Inverter’s manual find out the PIN out of RS485 or CAN, and crimp the connectors. Mark one side “INVERTER” and the other side “BATTERY”
    • ONLY 2 wires should be crimped into the RJ45 connectors.
    • Use a multimeter to check and confirm the conductivity of the cable.
  3. Connect Procedures
    • If the inverter supports Pylon (CAN or 485), nothing needs to be done on the battery BMS.
    • If different protocols need to be used, See the PC-Battery Communications
    • Instructions and update the default protocol in the battery BMS to the one supported by the inverter.
    • Single Battery
    • Connect the “INTERTER” side RJ45 to the port of BMS on the inverter
    • Connect the “BATTERY” side RJ45 to the port of RS-485/CAN
    • DIP: ALL OFF (See Multiple Batteries Setup for Multiple Battery Applications)
    • Connect the battery and Power ON the inverter, go to the menu that enables BMS communication (Inverter specific), the inverter might beep for a warning.
    • Choose Pylon (or other protocols) and confirm
    • The inverter and the battery should be connected, and the warning beep will stop.
    • Multiple batteries (SOC is the average of all batteries) DIP
    • Set one of the batteries as the Master battery, which is connected to the inverter using the
    • RJ45 cable made in section 2: DIP 1-4, of (Set as MASTER, address 0); DIP 5-8 as the total quantity of the slaves that are connected to the Master. The table is as follows:
Slave QTY DIP#1 DIP#2 DIP#3 DIP#4 DIP#5 DIP#6 DIP#7 DIP#8
1 OFF OFF OFF OFF ON OFF OFF OFF
2 OFF OFF OFF OFF OFF ON OFF OFF
3 OFF OFF OFF OFF ON ON OFF OFF
4 OFF OFF OFF OFF OFF OFF ON OFF
5 OFF OFF OFF OFF ON OFF ON OFF
6 OFF OFF OFF OFF OFF ON ON OFF
7 OFF OFF OFF OFF ON ON ON OFF
8 OFF OFF OFF OFF OFF OFF OFF ON
9 OFF OFF OFF OFF ON OFF OFF ON
10 OFF OFF OFF OFF OFF ON OFF ON
11 OFF OFF OFF OFF ON ON OFF ON
12 OFF OFF OFF OFF OFF OFF ON ON
13 OFF OFF OFF OFF ON OFF ON ON
14 OFF OFF OFF OFF OFF ON ON ON
15 OFF OFF OFF OFF ON ON ON ON
  • Set slave battery addresses as the following table
ADDRESS DIP#1 DIP#2 DIP#3 DIP#4 DIP#5 DIP#6 DIP#7 DIP#8 SLAVES
1 ON OFF OFF OFF OFF OFF OFF OFF BATTERY 1
2 OFF ON OFF OFF OFF OFF OFF OFF BATTERY 2
3 ON ON OFF OFF OFF OFF OFF OFF BATTERY 3
4 OFF OFF ON OFF OFF OFF OFF OFF BATTERY 4
5 ON OFF ON OFF OFF OFF OFF OFF BATTERY 5
6 OFF ON ON OFF OFF OFF OFF OFF BATTERY 6
7 ON ON ON OFF OFF OFF OFF OFF BATTERY 7
8 OFF OFF OFF ON OFF OFF OFF OFF BATTERY 8
9 ON OFF OFF ON OFF OFF OFF OFF BATTERY 9
--- --- --- --- --- --- --- --- --- ---

10

|

OFF

|

ON

|

OFF

|

ON

|

OFF

|

OFF

|

OFF

|

OFF

| BATTERY 10

11

|

ON

|

ON

|

OFF

|

ON

|

OFF

|

OFF

|

OFF

|

OFF

| BATTERY

11

12

|

OFF

|

OFF

|

ON

|

ON

|

OFF

|

OFF

|

OFF

|

OFF

| BATTERY

12

13

|

ON

|

OFF

|

ON

|

ON

|

OFF

|

OFF

|

OFF

|

OFF

| BATTERY 13

14

|

OFF

|

ON

|

ON

|

ON

|

OFF

|

OFF

|

OFF

|

OFF

| BATTERY

14

15

|

ON

|

ON

|

ON

|

ON

|

OFF

|

OFF

|

OFF

|

OFF

| BATTERY

15

  • Connect one of the master 485 ports (Not CAN/485) to an RS485 port on the slave, and connect those slaves using RS485 ports (Not CAN/485). Internet cables for routers can be used for Master-Slave and slave-slave communications.

See the diagram as follows:Antra-Power-BLF-48105H-Lithium-Ion-
Batteries-fig-2

Trouble Shooting

  • Check the cable conductivity
  • Check the correct port is used
  • Check the protocol match CAN to CAN, 485 to 485, etc.
  • Check the DIP pin settings are correct
  • Contact Customer Support for assistance.

PRECAUTIONS

  • ALWAYS KEEP ONE OR TWO FIRE DISTINGUISHERS ON-SITE
  • DO NOT short-circuit the positive and negative poles of the battery pack with metal conductors.
  • DO NOT throw the battery pack into the fire or heat it.
  • DO NOT discharge to 0V. Recharge the battery within 12 hours when it is completely empty, otherwise, the cells might be discharged to 0V and will have permeant damage to the battery.
  • Contact customer support if you accidentally flatten the battery and it goes into protection mode.
  • It is strictly forbidden to conduct artificial dissection of the battery pack. It is strictly forbidden to pierce the battery pack with nails or sharp objects.
  • It is strictly forbidden to hit the battery pack with a hammer or other external force. It is strictly forbidden to step on and drop the battery pack.
  • It is strictly forbidden to put the battery pack in a microwave oven or pressure vessel.
  • If any abnormal phenomenon occurs during charging or use, please stop charging and use immediately.
  • The best operating temperature of the product is 25 ± 5 ℃. If the product is not used within this temperature range, the capacity will be reduced.
  • If there is a malfunction or abnormality during use, please contact the customer service and
  • DO NOT disassemble the battery pack. It is very dangerous and will void the warranty.
  • DO NOT put the battery in water and avoid moisture environments.
  • DO NOT store, charge, and use this product near fire or heat sources.
  • When the battery pack emits a peculiar smell or leaks, STOP using it, charging, or discharging it. Disconnect any loads or chargers immediately, and move them to an open and ventilated place.
  • Keep it away from the fire source, and contact the customer service. When connecting to a load, NEVER connect the positive and negative poles reversely.

Customer Support Information