Autonics M4W Series Indicator-Thumbwheel Switch Panel Meters Instruction Manual

June 10, 2024
Autonics

Indicator / Thumbwheel Switch Panel Meters
Ordering Information
M4W Series
INSTRUCTION MANUAL

M4W Series Indicator-Thumbwheel Switch Panel Meters

Thank you for choosing our Autonics product.
Read and understand the instruction manual and manual thoroughly before using the product.
For your safety, read and follow the below safety considerations before using.
For your safety, read and follow the considerations written in the instruction manual, other manuals and Autonics website.
Keep this instruction manual in a place where you can find easily.
The specifications, dimensions, etc. are subject to change without notice for product improvement. Some models may be discontinued without notice.
Follow Autonics website for the latest information.

Safety Considerations

  • Observe all ‘Safety Considerations’ for safe and proper operation to avoid hazards.
  • symbol indicates caution due to special circumstances in which hazards may occur.

Warning Failure to follow instructions may result in serious injury or death.

  1. Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime / disaster prevention devices, etc.) Failure to follow this instruction may result in personal injury, economic loss or fire.

  2. Do not use the unit in the place where flammable / explosive / corrosive gas, high humidity, direct sunlight, radiant heat, vibration, impact or salinity may be present.
    Failure to follow this instruction may result in explosion or fire.

  3. Install on a device panel to use.
    Failure to follow this instruction may result in fire or electric shock.

  4. Do not connect, repair, or inspect the unit while connected to a power source.
    Failure to follow this instruction may result in fire or electric shock.

  5. Check ‘Connections’ before wiring.
    Failure to follow this instruction may result in fire.

  6. Do not disassemble or modify the unit.
    Failure to follow Caution Failure to follow instructions may result in injury or product damage.
    01. When connecting the power / measurement input and relay output, use
    AWG 24 (0.20 mm2) to AWG 15 (1.65 mm2) cable or over and tighten the
    terminal screw with a tightening torque of 0.98 to 1.18 N m.
    Use the wiring suitable for the load current capacity.
    Failure to follow this instruction may result in fire or malfunction due to contact
    failure.
    02. Use the unit within the rated specifications.
    Failure to follow this instruction may result in fire or product damage.
    03. Use a dry cloth to clean the unit, and do not use water or organic solvent.
    Failure to follow this instruction may result in fire or electric shock.
    04. Keep the product away from metal chip, dust, and wire residue which flow
    into the unit.
    Failure to follow this instruction may result in fire or product damage.w this instruction may result in fire or electric shock.

Caution Failure to follow instructions may result in injury or product damage.

  1. When connecting the power / measurement input and relay output, use AWG 24 (0.20 mm2) to AWG 15 (1.65 mm2) cable or over and tighten the terminal screw with a tightening torque of 0.98 to 1.18 N m. Use the wiring suitable for the load current capacity.
    Failure to follow this instruction may result in fire or malfunction due to contact failure.

  2. Use the unit within the rated specifications.
    Failure to follow this instruction may result in fire or product damage.

  3. Use a dry cloth to clean the unit, and do not use water or organic solvent.
    Failure to follow this instruction may result in fire or electric shock.

  4. Keep the product away from metal chip, dust, and wire residue which flow into the unit.
    Failure to follow this instruction may result in fire or product damage.

Cautions during Use

  • Follow instructions in ‘Cautions during Use’.
    Otherwise, It may cause unexpected accidents.

  • Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the power.

  • Keep away from high voltage lines or power lines to prevent inductive noise.
    In case installing power line and input signal line closely, use line filter or varistor at power line and shielded wire at input signal line.
    Do not use near the equipment which generates strong magnetic force or high frequency noise.Connection with the line filter| Connection with the varistor
    ---|---
    Autonics M4W Series Indicator Thumbwheel Switch Panel Meters -
Filter|

  • This unit may be used in the following environments.
    – Indoors (in the environment condition rated in ‘Specifications’)
    – Altitude max. 2,000 m
    – Pollution degree 2
    – Installation category II

Ordering Information

This is only for reference, the actual product does not support all combinations.
For selecting the specified model, follow the Autonics webstie.

Autonics M4W Series Indicator Thumbwheel Switch Panel Meters -
parts

  1. Output
    No mark: Indicator
    1P: Single setting
    2P: Dual setting

  2. Input type
    DV: DC voltage
    AV: AC voltage
    DA: DC current
    AA: AC current
    W: Power
    T: Rotation
    S: Speed
    DI: Scaling (DC 4 – 20 mA)

  3. AC measurement method
    No mark: AVG
    R: RMS

  4. Measurement input
    Refer to measurement input specifications.

Measurement Input Specifications

Measurement input Input type
DV AV
No mark
1 199.9 mVDC ****
m / min
0-10  VDC= 0-10 VDC=
2 1.999 VDC ****
/ min
0 -10 VAC– 0 -10 VAC–
3 19.99 VDC ****
4 199.9 VDC ****
5 300 VDC ****
6
7
8
DX
AX
XX Option
  1. This specification is based on the transducer with 0 – 10 VDC output.
    When the output of transducer is DC 4 – 20 mA or 1 – 5 VDC
    , use the scaling meter.

  2. This specification is based on the tacho generator with 0 – 10 VDC ****or 0 – 10 VAC∼ output.

Product Components

  • Product (+ bracket)
  • Instruction manual

Dimensions

  • Unit: mm, For the detailed drawings, follow the Autonics website.
  • Following items are based on single setting model.

Autonics M4W Series Indicator Thumbwheel Switch Panel Meters -
Dimensions

Cautions during Wiring

  • Unit: mm, Use terminals of size specified below.

Autonics M4W Series Indicator Thumbwheel Switch Panel Meters -
Wiring

Connections

■ Indicator![Autonics M4W Series Indicator Thumbwheel Switch Panel Meters

Specifications

Input type| DC voltage| AC voltage| DC current| AC current| Power| on,| Scaling
---|---|---|---|---|---|---|---
Max. allowable input| ≤ 300 VDC | ≤ 400 VAC∼| ≤ DC2 A| ≤ AC 5A| ≤ 10 VDC | ≤ 10 VDC: ****
≤ 10 VAC∼| DC 4 – 20 mA
≈ 150 % F.S. for each measured input range 01)
Display method| 7-segment (red) LED (character height: 14 mm)
Display accuracy| Dependent on the input type
DC input| ± 0.2 % F.S. rdg ± 1-digit| ± 0.3 % FS. rdg
± 1-digit
AC input| ± 0.5% F.S. rdg ± 1-digit
Display scale| 1999
Sampling time| 2.5 times / sec
Response speed| ≈ 2 sec (0 to 1999)
Sampling cycle| 300 ms
Operation method| Dual integral method
Unit weight| Dependent on the output type
Indicator| ≈ 168g
Single setting| ≈ 253 g
Dual setting| ≈ 278g
Approval|

  1. At 400 VAC∼ input: ≈ 120 % F.S. for each measured input range
Output type Indicator Single setting Dual setting
Power supply01) 110 / 220 VAC∼ ± 100/0 50 / 60 Hz
Power consumption Dependent on the input type
DC input 2W 3W 3W
AC input 4 VA 5VA 5VA
Contact capacity 250 VAC∼ 3 A,
150VDC ****3 A 250 VAC∼ 3 A,

150 VDC 3 A
Contact composition| –| lc x 1| lc x 2
Insulation resistance| 100 MΩ (500VDC
megger)
Dielectric strength| 2,000 VAC∼ 50 / 60 Hz for 1 min
Noise immunity| ± 1 kV square wave noise (pulse width: 1 μs) by the noise simulator
Vibration| 0.75 mm double amplitude at frequency of 10 to 55 Hz (for 1 minute) in each X,Y, Z direction for 1 hours
Vibration (malfunction)| 0.5 mm double amplitude at frequency of 10 to 55 Hz (for 1 minute) in each X, Y,Z direction for 10 min
Shock| 300 m/s² (≈ 30 G) in each X, Y, Z direction for3 times
Shock (malfunction)| 100 m/s² (≈ 10 G) in each X, Y, Z direction for3 times
Relay life cycle| Mechanical: ≥ 10,000,000 operations
Electrical: ≥ 100,000 operations (250 VAC∼ 3A resistive load)
Ambient temperature| -10 to 50 °C, storage: -25 to 65 °C (no freezing or condensation)
Ambient humidity| 35 to 85 %RH, storage: 35 to 85 %RH (no freezing or condensation)

  1. Power supply 24 – 70 VDC ****, 100 – 240 VAC∼ 50 / 60 Hz options are also available to order.

Error

  • When 1999 or -1999 flashes with a certain measurement input, disconnect power supply and then check the cables.

18, Bansong-ro 513Beon-gil, Haeundae-gu, Busan,
Republic of Korea, 48002
www.autonics.com
+82-51-519-3232
sales@autonics.com
TCD210077AA

Documents / Resources

| Autonics M4W Series Indicator-Thumbwheel Switch Panel Meters [pdf] Instruction Manual
M4W Series Indicator-Thumbwheel Switch Panel Meters, M4W Series, Indicator- Thumbwheel Switch Panel Meters, Thumbwheel Switch Panel Meters, Switch Panel Meters, Panel Meters, Meters
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Autonics User Manuals

Related Manuals