Greengate 120277V OSW-U Wall Switch Ultrasonic Occupancy Instructions

June 15, 2024
Greengate

Greengate 120277V OSW-U Wall Switch Ultrasonic Occupancy

Product Information

The OSW-U Wall Switch Ultrasonic Occupancy Sensor (120/277V) is an energy- saving, motion sensing lighting control that replaces a conventional wall switch. It utilizes ultrasonic technology to detect room motion and is designed to provide maximum convenience with its Automatic On Mode. The sensor is also equipped with a Manual Off pushbutton that can be used in either mode. The OSW-U-0721-MV is compliant with California Title 20 regulations and is suitable for various room orientations, furniture placements, and switch locations.

The sensor features a self-contained design and does not require a wallplate, which is not included in the package. It has a dimensional height of 1.8 inches (45.7mm) and a mounting height of 4.15 inches (105.4mm).

The OSW-U-0721-MV has a maximum load/relay rating of 0-800W for incandescent bulbs at 120V, and 0-800W for fluorescent bulbs at 120V or 0-1200W for fluorescent bulbs at 277V. It operates at a voltage of 120/277 VAC and a frequency of 60 Hz. The available color options for the sensor are White (W), Ivory (V), and Almond (A). Please note that not all colors may be available in stock and some color options may have extended lead times.

The sensor is backed by a five-year warranty.

Product Usage Instructions

Installation

  1. Turn off the power to the circuit where the wall switch will be installed.
  2. Remove the existing wall switch.
  3. Connect the wires from the circuit to the corresponding terminals on the OSW-U-0721-MV sensor, following the provided wiring diagrams for single-pole or 3-way installations.
  4. Securely mount the sensor onto the wall using the provided mounting plate, ensuring it is positioned at the desired height.
  5. Turn on the power to the circuit.

Operating Modes The OSW-U-0721-MV sensor has two operating modes: Automatic On Mode and Manual Off Mode.

  • Automatic On Mode: In this mode, the sensor will automatically turn on the lights when it detects motion in the room. To activate Automatic On Mode, ensure the override jumper is set to “A”.
  • Manual Off Mode: In this mode, the sensor will not automatically turn on the lights. To activate Manual Off Mode, ensure the override jumper is set to “M”.

Override Jumper The override jumper is used to switch between Automatic On Mode and Manual Off Mode. Set the jumper to “A” for Automatic On Mode and “M” for Manual Off Mode.

Field of View The OSW-U-0721-MV sensor has a wide field of view, allowing it to detect motion in a large area of the room.

Contact Information If you have any questions or need further assistance, you can contact Cooper Lighting Solutions at:

Cooper Lighting Solutions 1121 Highway 74 South Peachtree City, GA 30269 Phone: 770-486-4800 Website: www.cooperlighting.com

PRODUCT OVERVIEW

Top Product Features

  • 120 and 277V in the same unit
  • No minimum load requirement
  • Air-gap switch ensures no leakage current to load
  • Complete no gap coverage
  • NEMA WD7 Guide robotic method utilized to verify coverage patterns
  • Wall switches are ideal for smaller spaces where you will not have obstructions of line-of-sight due to switch location, room orientation or furniture placement

OSW-U Wall Switch Ultrasonic Occupancy Sensor (120/277V)

The self-contained OSW-U-0721-MV is an energy-saving, motion sensing ighting control that replaces a conventional wall switch and utilizes ultrasonic technology to detect room motion.

Typical Applications
Offices • Conference rooms • Board rooms • Utility rooms

Product Certification

Product Features

Dimensional Details

Mounting Height

Order Information

Wallplate not included

Catalog Number

Catalog Number Ratings Coverage Voltage Color


OSW-U-0721-MV- (-W, V, A)

| Incandescent: 0-800W @ 120V Fluorescent: 0-800W @ 120V Fluorescent: 0-1200W @ 277V Max Load/Relay| ****


180°; 500 sq. ft.

| ****


120/277 VAC 60 Hz

| ****


W=White, V=Ivory, A=Almond

| | | | Notes

Not all colors are available in stock and some color options may have extended lead times.

Product Specifications

  • Technology
    Ultrasonic (US)

  • Mechanical
    Mounting Plate Dimensions: 4.15”H x 1.94”W (10.54cm x 4.92cm)
    Product Housing Dimensions: 2.73”H x 1.8”W x 1.8”D (6.93cm x 4.57cm x 4.57cm)
    Environment:

    • Operating temperature: 60° F – 80°F (15°C – 26°C)
    • Relative humidity operating: Less than 95%, non-condensing
    • For indoor use only
    • Housing: Durable, injection molded housing. ABS resin complies with UL 94V-0
    • Mounting: Fits in a standard 3.5” deep back box
  • Electrical
    Electrical ratings:

    • 120 VAC:

    • Incandescent/Tungsten

    • Max. load: 6.7 amps, 800W, 60 Hz

    • Motor Load: 1/4HP @ 125 VAC

    • 277 VAC:

    • Fluorescent/Magnetic Ballast –

    • Max. load: 4.3 amps, 1200W, 60 Hz

    • Motor Load: 1/4HP @ 125 VAC
      Ballast Compatibility:

    • Compatible with magnetic ballasts

  • Hardware Specifications
    Status Indicators: Red LED for Ultrasonic detection

  • Controls and Performance
    Time delays:

    • 15 seconds to 15 minutes
      Operating modes:

    • Automatic On/Automatic Off

    • Manual On/Automatic Off
      Shut off delay:

    • Adjustable 30 sec. – 15 min.

  • Standards/Ratings
    cULus Listed

  • Warranty
    Five year warranty standard

Overview

The sensor produces a low-intensity, inaudible sound to detect occupancy in a room. Changes in the sensor’s acoustic wave caused by motion, such as walking into a room, reaching for a telephone or swiveling in a chair, will cause the lights to turn ON. The sensor does not respond to audible sound. In the Automatic On Mode, lights will turn ON automatically when a person enters the room. In Manual On Mode, lights are turned ON by pressing the touchplate at the top of the switch. When the room is vacated, lights turn OFF automatically after the programmed time delay. An air-gap switch ensures no leakage current to load for maximum product reliability

Wiring Diagrams

Single-Pole Wiring Diagram FLR, LED

Single level switching

3-Way Wiring Diagram FLR, LED

For 3-way applications Do Not exceed the load ratings of a single switch.
Load rating can not be doubled!

Controls

Field of View
The OSW-U-0721 series has a coverage range of 180°, a minor motion coverage area of approximately 300 sq. ft., and a maximum coverage area of approximately 500 sq. ft. Maximum coverage area may vary somewhat according to room shape and the presence of obstructions.

Control Systems

Greengate

121 gigatin slutions Peachtree City, GA 30269
www.cooperlighting.com

© 2022 Cooper Lighting Solutions All Rights Reserved. Specifications and dimensions subject to change without notice.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Greengate User Manuals

Related Manuals