Panasonic U-8MF3R7 3WAY Type MF3 Air Conditioner Instruction Manual

June 15, 2024
Panasonic

Panasonic U-8MF3R7 3WAY Type MF3 Air Conditioner Instruction Manual
Panasonic U-8MF3R7 3WAY Type MF3 Air Conditioner

Connectable indoor unit lineup

This booklet is the operating instructions for outdoor unit. Regarding the indoor unit, see the operating instructions supplied with the indoor unit.

Thank you for purchasing this Panasonic product. This product is a commercial air conditioner outdoor unit. Installation Instructions attached.

Product Information

If you have problems or questions concerning your Air Conditioner, you will need the following information. Model and serial numbers are on the nameplate.

Model No.
Serial No.
Date of purchase
Dealer’s address
Phone number

Safety Precautions

The following symbols used in this manual, alert you to potentially dangerous conditions to users, service personnel or the appliance:

WARNING This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.

CAUTION This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.

Warning Icon Prohibited matters

Warning Icon Matters to be observed

WARNING

Confirm to authorized dealer or specialist on usage of specified refrigerant type. Using of refrigerant other than the specified type may cause product damage, burst and injury etc.

This air conditioner has no ventilator for intaking fresh air from outdoors. You must open doors or windows frequently when you use gas or oil heating appliances in the same room, which consume a lot of oxygen from the air.

Otherwise there is a risk of suffocation in an extreme case.

Warning Icon Never use or store gasoline or other flammable vapor or liquid near the air conditioner — it is very dangerous.

Do not use this appliance in a potentially explosive atmosphere.

Never touch the unit with wet hands.

Do not insert your fingers or other objects into the air conditioner indoor or outdoor unit, rotating parts may cause injury.

Warning Icon Provide a power outlet to be used exclusively for each unit, and a power supply disconnect, Earth

Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD) for overcurrent protection should be provided in the exclusive line.

Provide a power outlet exclusively for each unit, and full disconnection means having a contact separation in all poles must be incorporated in the fixed wiring in accordance with the wiring rules.

To prevent possible hazards from insulation failure, the unit must be grounded.

Warning Icon Do not use modified cord, joint cord, extension cord or unspecified cord to prevent overheating and fire.

Warning Icon If the refrigerant comes in contact with a flame, it produces a toxic gas.

For safety, be sure to turn the air conditioner off and also to disconnect the power before cleaning or servicing.
Warning Icon

Pull off the power plug from  a receptacle, or switch off the breaker, or switch off the power disconnecting mean to isolate the air conditioner from the main power supply in case of emergency.

Dispose of according to national and/or local legislation.

Warning Icon This product must not be modified or disassembled under any circumstances.

Modified or disassembled unit may cause fire, electric shock or injury.

Do not clean inside the indoor and outdoor units by users. Engage authorized dealer or specialist for cleaning.

In case of malfunction of this appliance, do not repair by yourself. Contact to the sales dealer or service dealer for a repair and disposal.

  • Fan speed cannot be controlled.
  • The unit stops running immediately even if it is switched on for operation.
  • The fan does not stop even if the operation is stopped. Contact immediately your local dealer for maintenance/repair.

CAUTION

This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons.

This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that do not play with the appliance.

Keep the fire alarm and the air outlet at least 1.5m away from the unit.

Do not cool or heat the room too much if babies or invalids are present.

Do not turn the air conditioner on and off from the power mains switch. Use the ON/OFF operation button.

Warning Icon Do not stick anything into the air outlet of the outdoor unit. This is dangerous because the fan is rotating at high speed.

Do not touch the air inlet or the sharp aluminum fins of the outdoor unit. You may get injured.

Do not sit or step on the unit. You may fall down accidentally.
Warning Icon

Do not stick any object into the FAN CASE. You may be injured and the unit may be damaged.
Warning Icon

NOTICE

  • The compressor may occasionally stop during thunderstorms. This is not a mechanical failure. The unit automatically recovers after a few minutes.

Installation

  • This air conditioner must be installed properly by qualified installation technicians in accordance with the Installation Instructions provided with the unit.
  • Before installation, check that the voltage of the electric supply in your home or office is the same as the voltage shown on the nameplate.

WARNING

Avoid the following locations for installation.

  • Locations where smoke or combustible gas exists. Also locations of extremely high temperature such as a greenhouse.
  • Locations where excessively high heat-generating objects are placed.

Attention:

  • Avoid installing the outdoor unit where salty sea water can splash directly onto it or in sulphurous air near a spa. (To protect the air conditioner from heavy corrosion)

Wiring

  • All wiring must conform to the local electrical codes. (Consult your dealer or a qualified electrician for details.)
  • Each unit must be properly grounded with a ground (or earth) wire or through the supply wiring.
  • Wiring must be done by a qualified electrician.

Operation Preparation

Turn the power mains on 5 hours before the start of operation. (For warm- up)

  • Leave the power mains ON for continuous use.

NOTE

Pull off the power plug from a receptacle, or switch off the breaker, or switch off the power disconnecting mean to isolate the air conditioner from the main power supply when not in use for a long time.

Operation Condition

Outdoor Unit| Indoor temperature range| Outdoor temperature range
---|---|---
3WAY (Type MF3)
| Cooling| 14°C   25°C (WBT)| -10°C| 52°C (DBT)
-10°C   43°C (DBT)1
Heating| 16°C| 30°C (DBT)| -20°C| 18°C (WBT)
Cooling & Heating| ―| -10°C| 24°C (*DBT)

Use this air conditioner under the following temperature range.

DBT: Dry bulb temperature
WBT: Wet bulb temperature
*1: The maximum allowable temperature of this air conditioning
system is reduced to 43°C when using the existing R22 pipe.

Important Information Regarding The Refrigerant Used

This product contains fluorinated greenhouse gases. Do
not vent gases into the atmosphere.
Refrigerant type: R410A
GWP(1) value: 2088
(1)GWP = global warming potential

Periodical inspections for refrigerant leaks may be required depending on European or local legislation. Please contact your local dealer for more information.

Names of Parts

OUTDOOR UNIT
Product Overview

Optional

Wireless Remote Controller

For all indoor units

Timer Remote Controller
Timer Remote Controller

Model No. CZ-RTC4

For all indoor units

High-spec Wired Remote Controller

Read the operating instructions included with the Remote Controller.

  • Operation
    Refer to the Operating Instructions attached to the optional Remote Controller.

  • Adjusting Airfl ow Direction
    Refer to the Operating Instructions attached to the indoor unit and optional Remote Controller.

  • Maintenance
    Refer to the Operating Instructions attached to the indoor unit.

  • Troubleshooting
    Refer to the Operating Instructions attached to the indoor unit.

Specifications

Outdoor unit

3WAY (Type MF3)

Model Name U-8MF3R7 U-10MF3R7 U-12MF3R7 U-14MF3R7 U-16MF3R7
Power source 380 – 400 – 415 V 3N ~ 50 Hz, 380 – 400 V 3N ~ 60 Hz
Cooling capacity kW 22.4 28.0 33.5 40.0
Heating capacity kW 25.0 31.5 37.5 45.0
Sound pressure level dB(A) 54.0 57.0 60.0 61.0
Sound power level dB(A) 76.0 78.0 81.0 82.0
Unit dimensions (H×W×D) mm 1842×1180×1000 1842×1180×1000
1842×1180×1000 1842×1180×1000 1842×1180×1000
Net weight kg 264 265 289 337

Performance test condition: AS / NZS 3823.2
Rated conditions
Cooling : Indoor intake air temp. 27°C DB / 19°C WB. Outdoor intake air temp. 35°C DB.
Heating : Indoor intake air temp. 20°C DB. Outdoor intake air temp. 7°C DB / 6°C WB.

© Panasonic Corporation 2018 – 2022
Printed in Malaysia

Panasonic Corporation
http://www.panasonic.com

ACXF55-19201
DC0418-10922

Panasonic Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals