NTI TFTN Series 3-Zone Boiler Installation Guide
- June 15, 2024
- NTI
Table of Contents
NTI TFTN Series 3-Zone Boiler
Overview
- The N-Link (3-Zone Control Module) is designed to connect to TFTN series boilers, enabling the control of up to (3) additional heating zones.
- Together with the boiler’s integrated zone controls, this allows for a combined total of up to (6) distinct heating zones.
- The N-Link’s unique communication with NTI boilers allows it to take full advantage of the connected boiler’s HMI, including full control of each heating zone’s individual parameters.
- Unlike other, more rudimentary zone controllers, the N-Link maintains awareness of each heating zone’s specific requirements during heating demands and can therefore serve multiple, different heating zones within a household or commercial application more effectively.
Specifications
High-Voltage I/O
Table 2-1: High-Voltage Barrier Connections
Connection | Description |
---|---|
MAIN POWER INPUT (120VAC) | LINE |
NEUTRAL | Neutral (L2) input for 120VAC power supply and 120VAC zone loads |
(e.g. 120VAC zone pumps)
ZONE OUPUTS (120VAC or 24VAC)
| ZONE 1/4| – Activate on CH demand from respective THERMOSTAT INPUT (or NTI Room Sensor configured to respective zone); output voltage sourced from ZONE INPUT
– Deactivate (following overrun time) on DHW demand
– Each circuit protected by dedicated 5A fuse (slow-blow)
ZONE 2/5
ZONE 3/6
120VAC or 24VAC
| 120V| Jumper to ZONE INPUT for 120VAC zone outputs (e.g. zone pumps)
ZONE
INPUT
| Jumper to required voltage supply for zone outputs (e.g. to 120V for
120VAC zone pumps or R (24V) for 24VAC zone valves)
R (24V)| Jumper to ZONE INPUT for 24VAC zone outputs (e.g. zone valves)
24VAC RETURN
|
COMMON
| – Return/Neutral leg of 24VAC power supply
– Connection point for Return/Neutral leg of optional 24VAC loads (e.g. zone valves)
– Complete circuit protected by single 2A blade fuse (fast-blow)
Low-Voltage I/O
Table 2-2: Low-Voltage PCB Connections
Connection | Description |
---|
THERMOSTAT INPUTS
|
ZONE 1/4
| R| – Circuit closure between R and W initiates CH demand and activates output for respective zone (see Table 2-1 )
– R = 24VAC output; W = 24VAC input; C = common
– Protected by single 2A blade fuse (fast-blow)
– For 2-wire devices, connect only to R and W (do NOT connect to C )
W
C
ZONE 2/5
| R
W
C
ZONE 3/6
| R
W
C
ALRM (Alarm)
| – Dry contacts (NO); close during lockout or other alarm condition; may be connected to BMS
– Maximum capacity = 2A (MAX) at 24VAC
EBUS
| B| – Connection point for external BUS devices (e.g. NTI Room Sensors, NTI boilers, NTI SENSYS, other N-Links, etc.)
– B = (+) input; T = (-) or GND input
T
B
T
Installation
Wall-Mounting
- Select a suitable location near the boiler to secure the N-Link to the wall.
- Position the N-Link against the wall and mark the position of the (2) keyholes at the top corners of the mounting flanges [A].
- Install (2) fasteners of the appropriate type into these marked positions and mount the NLink via the (2) keyholes [A]:
- For 16” stud spacing or plywood installation, use appropriately sized wood screws
- For drywall or masonry installation, use appropriately sized drywall or masonry screws and anchors
- Secure the N-Link by installing (2) additional fasteners through the bottom screw holes [B].
Field-Wiring
- To remove the N-Link’s protective cover panel, loosen the (4) screws in the slotted cut-outs along its top and bottom edges, then gently slide it towards you (away from the wall).
- For the low-voltage wiring, there are (4) cut-outs at the top of the N-Link with (3) provided grommets, which—-if needed—-must be removed and replaced with strain-reliefs suitable for 18-22AWG wiring.
- For the high-voltage wiring, there are (4) cut-outs at the bottom of the N-Link, with (3) provided grommets, which—-if needed—-must be removed and replaced with strain-reliefs suitable for 14-18AWG wiring.
Zone Pumps (120VAC)
- Wire the “hot” connection for up to (3) zone pumps to barrier position(s): ZONE 1/4, ZONE 2/5, and ZONE 3/6, respectively
- Wire the “return” connection for up to (3) zone pumps to barrier position(s): NEUTRAL
- Jumper between barrier position(s): ZONE INPUT and 120V
- Connect to the boiler via its BUS connector, respecting the polarity: B-B, T-T
Zone Valves (24VAC)
- Wire the “hot” connection for up to (3) zone valves to barrier position(s): ZONE 1/4, ZONE 2/5, and ZONE 3/6, respectively
- Wire the “return” connection for up to (3) zone valves to barrier position(s): COMMON
- Jumper between barrier position(s): ZONE INPUT and R
- Connect to the boiler via the BUS
NTI Room Sensors
- If preferred, you can use up to (3) NTI Room Sensors with the N-Link instead of thermostats by connecting them via the EBUS connector—-again, respecting the polarity: B-B, T-T
- Refer to the NTI Room Sensor instructions to assign the desired zone address for each zone (i.e. zone 1/4, 2/5, 3/6)
Dip Switches
- When connecting to TFTN boilers, ensure both dip switches on the N-Link’s zone control PCB (C3Z) are toggled to the “OFF” position to assign it to control zones 4, 5, and 6, while the boiler controls zones 1, 2, and 3 (or vice versa, if desired)
Troubleshooting
Bus Collision
Table 4-1: EBUS traffic collisions
EBUS wiring| Ensure EBUS connections are wired with correct polarity: B-B
and T-T
---|---
Dip switch settings| Ensure only (1) device with a Zone Control PCB (C3Z) has
its dip switches in the “ON” position either the N-Link or the TFTN
boiler; not both
Cascade settings
| If using boilers which are cascaded together…
· Disconnect the N-Link and ensure the boiler addresses are set correctly with respect to each other
· Remove the Wi-Fi harness from each “ follower ” boiler
Room Sensor address
| If using NTI Room Sensors in lieu of thermostats…
· Ensure each NTI Room Sensor is set to a unique zone address (i.e. 1-3 or 4-6). See the NTI Room Sensor installation instructions
Incorrect Zone Output Activation
- Zone Outputs
- Ensure Zone Output wires are connected to the correct Zone Pump or Valve
- Zone Inputs
- If using thermostats, ensure each is connected to the correct Zone Input
- If using NTI Room Sensors, ensure each is set to the correct Zone Address
Before calling NTI Technical Support
If you are still experiencing unexpected behaviour from your N-Link, please
refer to the following guidelines before calling NTI Technical Support:
- Check the LED indicator lights on the Zone Controller PCB (C3Z) for error warnings:
- If any LEDs are ‘RED’, refer to the boiler’s HMI for details on the error
- Refer to the boiler’s Installation & Operation Manual (IOM) for advice on how to clear the error from the system
- Turn “OFF” the power to the N-Link and/or the boiler, wait 15 seconds, then turn it back “ON” to reinitialize the system:
- Make sure to only do this while the boiler is in standby mode; do NOT do this during a heating demand.
Parts List
Table 5-1: Spare Parts List
# | Spare Part Code | Spare Part Description |
---|---|---|
1 | 64980499 | PCB, Zone Controller (C3Z) |
2 | Contact Tech Support | PCB, Field Connection Board (FCB) |
3 | 64980471 | 24Vac transformer (40VA) |
4 | Contact Tech Support | High-voltage, wiring barrier (11-pos) |
5 | 64980476 | Blade fuse, 2A (24VAC circuit) |
6 | 64980480 | Cartridge fuse, 2A (slow-blow, 5 x 20mm) |
7 | 64980478 | Cartridge fuse, 5A (slow-blow, 1/4″ x 1-1/4”) |
8 | 64980477 | Fuse holder, panel-mount (1/4″ x 1-1/4”) |
9 | 65111933 | Low-voltage, screw terminal connector (2-pos) |
10 | 65111934-01 | Low-voltage, screw terminal connector (3-pos) |
12 | 6000084095 | Wiring grommet (7/8”) |
13 | Contact Tech Support | Sheet metal base (with decal) |
--- | --- | --- |
14 | Contact Tech Support | High-voltage, barrier cover (with decal) |
15 | Contact Tech Support | Sheet metal cover (with NTI logo) |
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>