neptronic SKS4 Steam to Steam Humidifier User Guide
- June 4, 2024
- neptronic
Table of Contents
SKS4 Steam to Steam Humidifier
Modbus Communication Module User Guide SKS4-Modbus Guide-211019
Introduction
The SKS4 Modbus Communication Module User Guide provides information for using
Neptronic ® communication feature. The controller uses Modbus communication
protocol over the serial line in the RTU mode and provides a Modbus network
interface between client devices and Neptronic SKS4 devices.
The SKS4 Modbus Guide assumes that you are familiar with Modbus terminology.
The following are the requirements for Modbus:
- Data Model. The SKS4 Steam to Steam Humidifier Modbus server data model uses only the Modbus Registers table.
- Register Address:
o As per protocol base (base 0); for PLC add 1 to the protocol base.
o As per holding register (base 400001).
Note: Ensure that the Modbus communication software used does not have a limit on the range of the register addresses that can be viewed and supports 6-digit holding registers.
-
Function Codes. The SKS4 Steam to Steam Humidifier Modbus server supports a limited function codes subset comprising:
o Read Holding Registers (0x03)
o Write Single Register (0x06)
o Write Multiple Registers (0x10) -
Exception Responses. The SKS4 Steam to Steam Humidifier Modbus server supports the following exception codes:
o Illegal data address
o Illegal data value
o Slave device busy -
Serial Line. The SKS4 Steam to Steam Humidifier Modbus over serial line uses RTU transmission mode over a two-wire configuration RS485 (EIA/TIA-485 standard) physical layer.
o The physical layer can use fixed baud rate selection or automatic baud rate detection (default) as per the Modbus Auto Baud Rate device menu item or holding register index 1.
o The supported baud rates are 9600, 19200, 38400, and 57600.
o The physical layer also supports variable parity control and stop bit configuration as per the Modbus
Comport Config device menu item or holding register index 2.
o In auto baud rate configuration, if the device detects only consecutive bad frames (2 or more) for one second with any given baud rate, it will reinitialize itself to the next baud rate. -
Addressing. The SKS4 Steam to Steam Humidifier device only answers at the following address:
o The device’s unique address (1 to 246) can be set through the device menu or through holding register index 0.
Modbus Registers
Table Glossary
Name | Description | Name | Description |
---|---|---|---|
W | Writable Register | ASCII | For registers containing ASCII (8-bit) characters |
RO | Read Only Register | MSB | Most Significant Byte |
Unsigned | For range of values from 0 to 65,535, unless otherwise specified | ||
LSB | Least Significant Byte | ||
Signed | For range of values from -32,768 to 32,767, unless otherwise | ||
specified | MSW | Most Significant Word | |
Bit String | For registers with multiple values using bit mask (example, | ||
flags) | LSW | Least Significant Word |
Modbus Registers Table
Protocol Base| Holding Register| Description| Data
Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---
0
| ****
40000 1
| ****
Modbus Address and Product Type
| ****
Unsigned
| MSB = Product type, not writable
LSB = Modbus Address (1 to 247), writable
| **** W|
1
| ****
40000 2
| ****
Device Baud Rate
| Unsigned
Scale 100
| 0, 9600, 19200, 38400, and 57600, 0 = Auto Baud Rate Detection Value/100 (e.g. 38400 baud = 384)| W|
19200
2
| ****
40000 3
| ****
Modbus Slave Communication Port Configuration
| ****
Unsigned
| 0 = No parity, 2 Stop bits 1 = Even parity, 1 Stop bit 2 = Odd parity, 1 Stop bit| ****
W
| ****
No parity, 2 Stops bits
3| 40000 4| Product Name (characters 8 & 7)| ASCII| MSB = char 6, LSB =
char 7| W|
4| 40000 5| Product Name (characters 6 & 5)| ASCII| MSB = char 4, LSB =
char 5| W|
5| 40000 6| Product Name (characters 4 & 3)| ASCII| MSB = char 2, LSB =
char 3| W|
6| 40000 7| Product Name (characters 2 & 1)| ASCII| MSB = char 0, LSB =
char 1| W|
7| 40000 8| Product Actual Firmware Version (in Integer x100)| Unsigned
Scale 100
| 1 to 65535 (e.g. 100)| RO|
Protocol Base| Holding Register| Description| Data
Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---
8| 40000 9| Product Actual EEPROM Version (in Integer x100)| Unsigned
Scale 100| 1 to 65535 (e.g. 100)| RO|
2000| 40 2001| Control Signal| Unsigned Scale 1000| Units: Volt (V),
Range: 0V to 15V Value x 1000 (e.g. 1V = 1000)| RO| 0V
2001| 40 2002| Room RH Signal| Unsigned Scale 1000| Units: Volt (V),
Range: 0V to 15V Value x 1000 (e.g. 1V = 1000)| RO| 0V
2002| 40 2003| Supply RH Signal| Unsigned Scale 1000| Units: Volt
(V), Range: 0V to 15V Value x 1000 (e.g. 1V = 1000)| RO| 0V
2003| 40 2004| Water Level Signal| Unsigned Scale 1| Units: Hz,
Range: 0 to 30000Hz Value x 1 (e.g. 10Hz = 10)| RO| 0Hz
2004| 40 2005| Water Level Low Signal| Unsigned Scale 1000| Unit:
Volt (V), Range: 0V to 10V Value x 1000 (e.g. 1V = 1000)| RO| ** 0V
2005| 40 2006| Water Level High Signal| Unsigned Scale 1000| Unit:
Volt (V), Range: 0V to 10V Value x 1000 (e.g. 1V = 1000)| RO| 0V
2006| 40 2007| Water Temperature Signal| Unsigned Scale 1000| Unit:
Volt (V), Range: 0V to 10V Value x 1000 (e.g. 1V = 1000)| RO| 0V
2007| 40 2008| Foam Signal| Unsigned Scale 1000| Unit: Volt (V),
Range: 0V to 10V Value x 1000 (e.g. 1V = 1000)| RO| 0V
2008| 40 2009| Cabinet Temperature Signal| Unsigned Scale 1000| Unit:
Volt (V), Range: 0V to 10V Value x 1000 (e.g. 1V = 1000)| RO| 0V
2009| 40 2010| Board Temperature Signal| Unsigned Scale 1000| Unit:
Volt (V), Range: 0V to 10V Value x 1000 (e.g. 1V = 1000)| RO| 0V
2010| 40 2011| Main Power Supply| Unsigned Scale 10| Unit: Volt (V),
Range: 0V to 40V Value x 10 (e.g. 1V = 10)| RO| 0V
2011| 40 2012| Steam Valve Feedback Signal| Unsigned Scale 1000|
Units: Volt (V), Range: 0V to 10.5V
Value x 1000 (e.g. 1V = 1000)| RO| 0V
Protocol Base| Holding Register| Description| Data
Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---
** 4000| ** 40 4001| Steam Output Feedback Signal| Unsigned Scale
1000| Unit: Volt (V), Range: 0V to 10V Value x 1000 (e.g. 1V = 1000)| RO|
** 0V
4001
| ****
40 4002
| ****
Steam Valve Signal
| Unsigned
Scale 1000
| Unit: Volt (V), Range: 0V to 10V
Value x 1000 (e.g. 1V = 1000)
| **** RO| 0V
6000
| ****
40 6001
| ****
Control Input
| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| W| 0%
6001
| ****
40 6002
| ****
Control Min
| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| W| 0%
6002| 40 6003| Control Max| Unsigned Scale 100| Unit: %, Range:
0% to 100% Value x 100 (e.g. 10% = 1000)| W| 0%
** 6003| 40 6004| Control Bias| Signed Scale 100| Unit: %, Range:
-10% to 10% Value x 100 (e.g. 10% = 1000)| W| 0%
6004| 40 6005| Room RH| Unsigned Scale 100| Unit: % RH, Range: 0% RH
to 100% RH Value x 100 (e.g. 10% RH = 1000)| RO| 0% RH
6005| 40 6006| Room RH Min| Unsigned Scale 100| Unit: % RH, Range: 0%
RH to 100% RH Value x 100 (e.g. 10% RH = 1000)| RO| ** 0% RH
** 6006| 40 6007| Room RH Max| Unsigned Scale 100| Unit: % RH,
Range: 0% RH to 100% RH Value x 100 (e.g. 10% RH = 1000)| RO| 0% RH
6007| 40 6008| Room RH Bias| Unsigned Scale 100| Unit: % RH, Range: 0%
RH to 100% RH Value x 100 (e.g. 10% RH = 1000)| RO| 0% RH
6008| 40 6009| Supply High Limit RH| Unsigned Scale 100| Unit: % RH,
Range: 0% RH to 100% RH Value x 100 (e.g. 10% RH = 1000)| RO| 0% RH
** 6009| 40 6010| Supply High Limit RH Min| Unsigned Scale 100|
Unit: %, Range: 0% to 100% Value x 100 (e.g. 10% = 1000)| W| 0%
6010| 40 6011| Supply High Limit RH Max| Unsigned Scale 100|
Unit: %, Range: 0% to 100% Value x 100 (e.g. 10% = 1000)| W| 0%
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| Default Value
---|---|---|---|---|---|---
6011
| ****
40 6012
| ****
Supply High Limit RH Bias
| Signed
Scale 100
| Unit: %, Range: -10% to 10%
Value x 100 (e.g. 10% = 1000)
| ****
W
| ****
0%
6012| 40 6013| Water Temperature Signal Min| Unsigned
Scale 1000
| Unit: Volt (V), Range: 0V to 10V
Value x 1000 (e.g. 1V = 1000)
| RO| 0V
6013| 40 6014| Water Temperature Signal Max| Unsigned
Scale 1000
| Unit: Volt (V), Range: 0V to 10V
Value x 1000 (e.g. 1V = 1000)
| RO| 0V
6014
| ****
40 6015
| ****
Water Temperature
| Unsigned
Scale 100
| Unit: ºC/ºF, Range: 0°C to 125°C or 32°F to 257°F
Value x 100 (e.g. 5°C = 500 or 40ºF = 4000)
| ****
RO
| 50°C or 122°F
6015| 40 6016| Water Temperature Min| Unsigned
Scale 100
| Unit: ºC/ºF, Range: 0°C to 250°C or 32°F to 482°F
Value x 100 (e.g. 5°C = 500 or 40ºF = 4000)
| RO| 0°C or 32°F
6016| 40 6017| Water Temperature Max| Unsigned
Scale 100
| Unit: ºC/ºF, Range: 0°C to 250°C or 32°F to 482°F Value x 100 (e.g. 5°C = 500 or 40ºF = 4000)| RO| 125°C or
257°F
6017
| ****
40 6018
| ****
Water Temperature Bias
| Unsigned
Scale 100
| Unit: ºC/ºF, Range: -10°C to 10°C or -18°F to 18°F Value x 100 (e.g. 5°C = 500 or 14ºF = 1400)| ****
RO
| ****
0°C or 32°F
6018
| ****
40 6019
| ****
Cabinet Temperature
| Unsigned
Scale 100
| Unit: ºC/ºF, Range: -20°C to 100°C or -4°F to 212°F Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)| ****
RO
| ****
0°C or 32°F
6019
| ****
40 6020
| ****
Modbus TCP IP Keep Alive Time Out (0)
| Unsigned
Scale 1
| Unit: Minutes (min), Range: 1 to 1440 mins Value x 1 (e.g. 5 mins = 5)|
W
| ****
5 min
6020| 40 6021| Modbus TCP IP Keep Alive Time Out (1)| | Unit: Minutes
(min), Range: 1 to 1440 mins| |
6021| 40 6022| HRL Temperature| Signed
Scale 100
| Unit: ºC/ºF, Range: -40°C to 260°C or -40°F to 500°F Value x 100 (e.g.
5°C = 500 or 40ºF = 4000)| RO| 0°C or 32°F
6022| 40 6023| HRL Humidity| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 1% RH = 100)
| RO| 0% RH
6023| ** 40 6024| Board Temperature| Unsigned Scale 100| Unit:
ºC/ºF, Range: 0°C to 100°C or 32°F to 212°F Value x 100 (e.g. 5°C = 500 or
32ºF = 3200)| RO| 0°C or 32°F
** 6024| 40 6025| Power Output Feedback Bias| Unsigned Scale 1000|
Unit: Volt (V), Range: 0V to 10V Value x 1000 (e.g. 1V = 1000)| W| **
0V
Protocol Base| Holding Register| Description| Data
Type| Units, Limits, State Texts| Writable| Default Value**
---|---|---|---|---|---|---
6025
| ****
40 6026
| ****
Power Output Feedback Min
| Unsigned
Scale 1000
| Unit: Volt (V), Range: 0V to 10V
Value x 1000 (e.g. 1V = 1000)
| ****
W
| ****
0V
6026
| ****
40 6027
| ****
Power Output Feedback Max
| Unsigned
Scale 1000
| Unit: Volt (V), Range: 0V to 10V
Value x 1000 (e.g. 1V = 1000)
| ****
W
| ****
0V
6027
| ****
40 6028
| ****
Power Output Feedback
| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| ****
RO
| ****
0%
6028
| ****
40 6029
| ****
Steam Valve Control
| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| ****
RO
| ****
0%
6029| 40 6030| Water Level| Unsigned
Scale 10
| Unit: %, Range: 0% to 120%
Value x 10 (e.g. 10% = 100)
| RO| 78%
6030| 40 6031| Water Probe Low Pos Reading| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 30000Hz
6031| 40 6032| Water Probe High Pos Reading| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 30000Hz
6032| 40 6033| Water Probe Abs Low Pos Reading| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 30000Hz
6033| 40 6034| Water Probe Abs High Pos Reading| Unsigned
Scale 1
| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
| RO| 30000Hz
6034| 40 6035| Room RH Network Reading| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| W| 0% RH
6035| 40 6036| Room RH Setpoint| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| W| 40% RH
6036| 40 6037| Room RH Unoccupied Setpoint| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| W| 30% RH
6037| 40 6038| Room RH Vacant Setpoint| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| W| 20% RH
6038
| ****
40 6039
| ****
Room Demand Proportional Gain
| Unsigned
Scale 10
| No Unit, Range: 1 to 200
Value x 10 (e.g. 10 = 100)
| ****
W
| ****
20
Protocol Base| Holding Register| Description| Data
Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---
6039
| ****
40 6040
| ****
Room Demand Integral Time
| Unsigned
Scale 10
| Unit: sec, Range: 0 to 900 sec
Value x 10 (e.g. 10sec = 100)
| ****
W
| ****
0 sec
6040
| ****
40 6041
| ****
Room Demand Derivative Time
| Unsigned
Scale 10
| Unit: sec, Range: 0 to 60 sec
Value x 10 (e.g. 10sec = 100)
| ****
W
| ****
0 sec
6041| 40 6042| Room Demand| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| RO| 0% RH
6042
| ****
40 6043
| ****
Room Demand Proportional Band (0)
| Unsigned
Scale 10
| Unit: %, Range: 1% to 100%
Value x 10 (e.g. 10% RH = 100)
| ****
W
| ****
5%
6043| 40 6044| Room Demand Proportional Band (1)| | Unit: %, Range: 1% to
100%| |
6044| 40 6045| Supply High Limit Network Reading| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| W| 0% RH
6045| 40 6046| Supply High Limit Setpoint| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| W| 80% RH
6046
| ****
40 6047
| ****
Supply High Limit Proportional Gain
| Unsigned
Scale 10
| No Unit, Range: 1 to 200
Value x 10 (e.g. 10 = 100)
| ****
W
| ****
10
6047
| ****
40 6048
| ****
Supply High Limit Integral Time
| Unsigned
Scale 10
| Unit: sec, Range: 0 to 900 sec
Value x 10 (e.g. 10sec = 100)
| ****
W
| ****
0 sec
6048
| ****
40 6049
| ****
Supply High Limit Derivative Time
| Unsigned
Scale 10
| Unit: sec, Range: 0 to 60 sec
Value x 10 (e.g. 10sec = 100)
| ****
W
| ****
0 sec
6049| 40 6050| Supply High Limit Demand| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| RO| 0% RH
6050
| ****
40 6051
| ****
Supply High Limit Proportional Band (0)
| Unsigned
Scale 10
| Unit: %, Range: 1% to 100%
Value x 10 (e.g. 10% RH = 100)
| ****
W
| ****
10%
6051| 40 6052| Supply High Limit Proportional Band (1)| | Unit: %, Range:
1% to 100%| |
6052| 40 6053| Humidity Control Network Demand| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| W| 0% RH
Protocol Base| Holding Register| Description| Data
Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---
6053| 40 6054| Humidity Control Network High Limit| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH Value x 100 (e.g. 10% RH = 1000)|
W| 100% RH
6054| 40 6055| Humidity Demand| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH Value x 100 (e.g. 10% RH = 1000)|
RO| 0% RH
6055| 40 6056| Humidity Demand Low Dead Band (0)| Unsigned
Scale 100
| Unit: %, Range: 0% to 100% Value x 100 (e.g. 10% = 1000)| W| 1%
6056| 40 6057| Humidity Demand Low Dead Band (1)| | Unit: %, Range: 0% to
100%| |
6057| 40 6058| Network Timeout (0)| Unsigned
Scale 1
| Unit: Seconds (sec), Range: 1 to 900 sec Value x 1 (e.g. 10sec = 10)|
W| 900 sec
6058| 40 6059| Network Timeout (1)| | Unit: Seconds (sec), Range: 1 to
900 sec| |
6059| 40 6060| System Power Output| Unsigned
Scale 100
| Unit: %, Range: 0% to 100% Value x 100 (e.g. 10% = 1000)| RO| 0%
6060
| ****
40 6061
| ****
System Steam Capacity
| Unsigned
Scale 10
| Unit: kg/hr or lb/hr, Range: 0 to 300 kg/hr or 0 to 66 1lb/hr
Value x 10 (e.g. 10 kg/hr = 100 or 10 lb/hr = 100)
| ****
RO
| 0 kg/hr or
0 lb/hr
6061
| ****
40 6062
| ****
Water Level Replace Interval (0)
| Unsigned
Scale 1
| Unit: Days, Range: 0 day to 7 days Value x 1 (e.g. 1 day = 1)| ****
W
| ****
7day
6062| 40 6063| Water Level Replace Interval (1)| | Unit: Days, Range: 0
day to 7 days Value x 1 (e.g. 1 day = 1)| |
6063| 40 6064| Boiler Anti-freeze Keep Warm Setpoint (0)| Signed
Scale 100
| Unit: ºC/ºF, Range: -40ºC to 100ºC or -40ºF to 212ºF Value x 100 (e.g.
10 º C = 1000 or 40ºF = 4000)| RO| 30°C or 86°F
6064| 40 6065| Boiler Anti-freeze Keep Warm Setpoint (1)| | Unit: ºC/ºF,
Range: -40ºC to 100ºC or -40ºF to 212ºF| |
6065| 40 6066| Boiler Anti-freeze Keep Warm (0)| Signed
Scale 100
| Unit: ºC/ºF, Range: -40ºC to 100ºC or -40ºF to 212ºF Value x 100 (e.g.
10 º C = 1000 or 40ºF = 4000)| RO| 10°C or 50°F
6066| 40 6067| Boiler Anti-freeze Keep Warm (1)| | Unit: ºC/ºF, Range:
-40ºC to 100ºC or -40ºF to 212ºF| |
6067| 40 6068| Boiler Anti-freeze Drain (0)| Signed
Scale 100
| Unit: ºC/ºF, Range: -40ºC to 100ºC or -40ºF to 212ºF Value x 100 (e.g.
10 º C = 1000 or 40ºF = 4000)| RO| 1°C or 34°F
Protocol Base| Holding Register| **Description| Data
Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---
6068| 40 6069| Boiler Anti-freeze Drain (1)| | Unit: ºC/ºF, Range: -40ºC
to 100ºC or -40ºF to 212ºF| |
6069| 40 6070**| Boiler Demand| Unsigned
Scale 100
| Unit: %, Range: 0% to 100% Value x 100 (e.g. 10% = 1000)| W| 0%
6070
| ****
40 6071
| ****
Boiler Capacity
| ****
Unsigned
Scale 10
| Unit: kg/hr or lb/hr, Range: 0 to 3000kg/hr or 0 to 6613.8lb/hr Value x 10 (e.g. 10 kg/hr = 100 or 10 lb/hr = 100)| ****
RO
| ****
15 kg/hr or
33.06 lb/hr
6071
| ****
40 6072
| ****
Boiler Power Output
| Unsigned
Scale 100
| Unit: %, Range: 0% to 100% Value x 100 (e.g. 10% = 1000)| ****
RO
| ****
0%
6072
| ****
40 6073
| ****
Boiler Run Time (0)
| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 21474836.47 h Value x 100 (e.g. 10h = 1000)| ****
RO
| ****
0h
6073| 40 6074| Boiler Run Time (1)| | Units: Hours (h), Range: 0 to
21474836.47 h| |
6074| 40 6075| Boiler Run Time (2)| | Units: Hours (h), Range: 0 to
21474836.47 h| |
6075| 40 6076| Boiler Run Time (3)| | Units: Hours (h), Range: 0 to
21474836.47 h| |
6076
| ****
40 6077
| ****
Boiler On Time (0)
| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 21474836.47 h Value x 100 (e.g. 10h = 1000)| ****
RO
| ****
0h
6077| 40 6078| Boiler On Time (1)| | Units: Hours (h), Range: 0 to
21474836.47 h| |
6078| 40 6079| Boiler On Time (2)| | Units: Hours (h), Range: 0 to
21474836.47 h| |
6079| 40 6080| Boiler On Time (3)| | Units: Hours (h), Range: 0 to
21474836.47 h| |
6080
| ****
40 6081
| ****
Boiler Service Run Time (0)
| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 21474836.47 h Value x 100 (e.g. 10h = 1000)| ****
RO
| ****
0h
6081| 40 6082| Boiler Service Run Time (1)| | Units: Hours (h), Range: 0
to 21474836.47 h| |
6082| 40 6083| Boiler Service Run Time (2)| | Units: Hours (h), Range: 0
to 21474836.47 h| |
6083| 40 6084| Boiler Service Run Time (3)| | Units: Hours (h), Range: 0
to 21474836.47 h| |
6084| 40 6085| Boiler Service On Time (0)| Unsigned Scale 100| Units:
Hours (h), Range: 0 to 21474836.47 h Value x 100 (e.g. 10h = 1000)| RO|
** 0h
Protocol Base| Holding Register| ****Description| Data
Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---
6085| 40 6086| Boiler Service On Time (1)| | Units: Hours (h), Range: 0
to 21474836.47 h| |
6086| 40 6087| Boiler Service On Time (2)| | Units: Hours (h), Range: 0
to 21474836.47 h| |
6087| 40 6088**| Boiler Service On Time (3)| | Units: Hours (h), Range: 0
to 21474836.47 h| |
6088
| ****
40 6089
| ****
Boiler Minimum Steam Output
| Unsigned
Scale 1
| Unit: %, Range: 1% to 25% Value x 1 (e.g. 1% = 1)| ****
W
| ****
5%
6089
| ****
40 6090
| ****
Boiler Drain Interval
| Unsigned
Scale 1
| Units: Hours (h), Range: 0 to 24 h Value x 1 (e.g. 1 h = 1)| ****
W
| ****
6h
6090
| ****
40 6091
| ****
Boiler Drain Volume
| Unsigned
Scale 1
| Unit: %, Range: 25% to 100% Value x 1 (e.g. 30% = 300)| ****
W
| ****
100%
6091
| ****
40 6092
| ****
Boiler Max Steam Output
| Unsigned
Scale 1
| Unit: %, Range: 0% to 100% Value x 1 (e.g. 30% = 300)| ****
W
| ****
100%
6092
| ****
40 6093
| ****
Boiler Idle Time Drain
| Unsigned
Scale 1
| Unit: Hours (h), Range: 0 to 72 h Value x 1 (e.g. 1 h = 1)| ****
W
| ****
24h
6093
| ****
40 6094
| ****
Boiler Idle Temperature Setpoint
| Unsigned
Scale 1
| Unit: ºC/ºF, Range: 0°C to 60°C or 32°F or 140°F Value x 1 (e.g. 5°C = 500 or 32ºF = 3200)| ****
W
| ****
0°C or 32°F
6094
| ****
40 6095
| ****
Boiler Blowdown Rate
| Unsigned
Scale 1
| Unit: %, Range: 0% to 100% Value x 1 (e.g.1% = 1)| ****
W
| ****
0%
6095
| ****
40 6096
| ****
Boiler Service Interval
| Unsigned
Scale 1
| Unit: Hours (h), Range: 1000 to 3000 h Value x 1 (e.g. 1500 h = 1500)|
W
| ****
1000h
6096
| ****
40 6097
| ****
Boiler Idle Tank Rinse Interval
| Unsigned
Scale 1
| Unit: Days, Range: 1 to 7 days Value x 1 (e.g. 1 day = 1)| ****
W
| ****
3 day
6097| 40 6098| Actuator Deadband| Unsigned
Scale 1
| Unit: %, Range: 0% to 25% Value x 1 (e.g. 5% = 5)| W| 5%
6098
| ****
40 6099
| ****
Boiler Manual Calibration Time (0)
| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 21474836.47 h Value x 100 (e.g. 10h = 1000)| ****
RO
| ****
0h
6099| 40 6100| Boiler Manual Calibration Time (1)| | Units: Hours (h),
Range: 0 to 21474836.47 h| |
Protocol Base| Holding Register| Description| Data
Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---
6100| 40 6101| Boiler Manual Calibration Time (2)| | Units: Hours (h),
Range: 0 to 21474836.47 h| |
6101| 40 6102| Boiler Manual Calibration Time (4)| | Units: Hours (h),
Range: 0 to 21474836.47 h| |
6102| 40 6103| Steam Valve Feedback| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 1% = 100)
| RO| 0%
10000
| ****
4 10001
| ****
Air Flow
| Unsigned
Scale 1
| 0 = Closed
1 = Open
| ****
RO
| ****
Closed
10001
| ****
4 10002
| ****
Supply High Limit
| Unsigned
Scale 1
| 0 = Closed
1 = Open
| ****
RO
| ****
Closed
10002
| ****
4 10003
| ****
Interlock
| Unsigned
Scale 1
| 0 = Closed
1 = Open
| ****
RO
| ****
Closed
10003
| ****
4 10004
| ****
Binary External Demand
| Unsigned
Scale 1
| 0 = 0%
1 = 100%
| ****
RO
| ****
0%
10004
| ****
4 10005
| ****
Water Leak Detection
| Unsigned
Scale 1
| 0 = Ok
1 = Leak
| ****
RO
| ****
Ok
10005
| ****
4 10006
| ****
Thermal Cutout
| Unsigned
Scale 1
| 0 = Closed
1 = Open
| ****
RO
| ****
Closed
10006
| ****
4 10007
| ****
RS485 Interface
| Unsigned
Scale 1
| 0 = No
1 = Yes
| ****
RO
| ****
No
10007
| ****
4 10008
| ****
Ethernet Interface
| Unsigned
Scale 1
| 0 = No
1 = Yes
| ****
RO
| ****
No
10008
| ****
4 10009
| ****
Contactors PCB Fuse
| Unsigned
Scale 1
| 0 = Normal
1 = Blown Fuse
| ****
RO
| ****
Normal
10009
| ****
4 10010
| ****
Control PCB Fuse
| Unsigned
Scale 1
| 0 = Normal
1 = Open Fuse
| ****
RO
| ****
Normal
11000| 4 11001| Drain Valve| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| ****
Writable
| Default Value
---|---|---|---|---|---|---
11001| 4 11002| Alarm Warning Relay| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
11002| 4 11003| Service Warning Relay| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
11003| 4 11004| Water Level Valve| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
11004
| ****
4 11005
| ****
Tank Water Valve
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
RO
| ****
Off
11005
| ****
4 11006
| ****
Drain Cooler Valve
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
RO
| ****
Off
11006
| ****
4 11007
| ****
Drain Pump
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
RO
| ****
Off
11007
| ****
4 11008
| ****
Drain Pump 2
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
RO
| ****
Off
11008
| ****
4 11009
| ****
Drain Pump 3
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
RO
| ****
Off
11009
| ****
4 11010
| ****
Alarm LED
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
RO
| ****
Off
11010
| ****
4 11011
| ****
Power LED
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
RO
| ****
Off
11011
| ****
4 11012
| ****
Buzzer
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
RO
| ****
Off
12000
| ****
4 12001
| ****
Network Control State
| Unsigned
Scale 1
| 0 = Normal
1 = Fault
| ****
W
| ****
Normal
12001
| ****
4 12002
| ****
Water Level Low
| Unsigned
Scale 1
| 0 = Inactive
1 = Active
| ****
RO
| ****
Inactive
Protocol Base| Holding Register| Description| Data
Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---
12002
| ****
4 12003
| ****
Water Level High
| Unsigned
Scale 1
| 0 = Inactive
1 = Active
| ****
RO
| ****
Inactive
12003
| ****
4 12004
| ****
Foam Sensor
| Unsigned
Scale 1
| 0 = NoFoam
1 = Foam
| ****
RO
| ****
NoFoam
12004| 4 12005| HRL Lock Setpoint| Unsigned
Scale 1
| 0 = Unlock
1 = Lock
| W| Unlock
12005
| ****
4 12006
| ****
Notify Alarm
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
W
| ****
Off
12006
| ****
4 12007
| ****
Notify Warning
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
W
| ****
Off
12007
| ****
4 12008
| ****
Notify App Msg
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
W
| ****
Off
12008
| ****
4 12009
| ****
Inhibit Resistive Probe
| Unsigned
Scale 1
| 0 = No
1 = Yes
| ****
W
| ****
No
12009| 4 12010| Boiler Service Operation| Unsigned
Scale 1
| 0 = Not Allowed 1 = Allowed| W| Allowed
12010| 4 12011| Boiler Service Due| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
12011| 4 12012| Foam| Unsigned
Scale 1
| 0 = Ok
1 = Detected
| RO| Ok
12012
| ****
4 12013
| ****
Boiler Line Rinse
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
W
| ****
On
12013| 4 12014| Power Up Drain| Unsigned Scale 1| 0 = Off
1 = On
| W| Off
12014| 4 12015| Manual Water Calibration State| Unsigned Scale 1| 0
= Ok
1 = Required
| RO| Ok
Protocol Base| Holding Register| Description| Data
Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---
15000| 4 15001| System Power State| Unsigned
Scale 1
| 0 = Off
1 = On
| W| Off
15001
| ****
4 15002
| ****
System Log Verbose Level
| ****
Unsigned
Scale 1
| 0 = None
1 = Emergency
2 = Alert
3 = Critical
4 = Error
| 5 = Warning
6 = Notice
7 = Info
8 = Debug
| ****
W
| ****
Debug
15002
| ****
4 15003
| ****
Modbus Server Units
| Unsigned
Scale 1
| 0 = Metric
1 = Imperial
| ****
W
| ****
Metric
15003| 4 15004| Control Signal Type| Unsigned
Scale 1
| 0 = 0-10Vdc
1 = 2-10Vdc
| 2 = 4-20mA
3 = 0-20mA
| W| 0-10Vdc
15004
| ****
4 15005
| ****
Room RH Signal Type
| Unsigned
Scale 1
| 0 = 0-10Vdc
1 = 2-10Vdc
| 2 = 4-20mA
3 = 0-20mA
| ****
W
| ****
0-10Vdc
15005
| ****
4 15006
| ****
Supply RH Signal Type
| Unsigned
Scale 1
| 0 = 0-10Vdc
1 = 2-10Vdc
| 2 = 4-20mA
3 = 0-20mA
| ****
W
| ****
0-10Vdc
15006
| ****
4 15007
| ****
Control Profile
| Unsigned
Scale 1
| 0 = ExternAnalog
1 = ExternNetwork
2 = InternAnalog
| 3 = InternNetwork
4 = HRL
5 = Custom
| ****
W
| ****
ExternAnalog
15007
| ****
4 15008
| ****
Modulating High Limit Profile
| Unsigned
Scale 1
| 0 = Disabled
1 = ExternAnalog
2 = ExternNetwork
| 3 = InternAnalog
4 = InternNetwork
5 = Custom
| ****
W
| ****
Disabled
15008| 4 15009| Occupancy State| Unsigned
Scale 1
| 0 = Occupied
1 = Unoccupied
| 2 = Vacant
3 = Off
| RO| Occupied
15009| 4 15010| Room RH Source| Unsigned
Scale 1
| 0 = None
1 = RoomRH
| 2 = Network| W| None
15010| 4 15011| Room RH Setpoint Source| Unsigned Scale 1| 0 = None
1 = Internal
| 2 = ControlInput| W| None
15011| 4 15012| Supply High Limit Reading Source| Unsigned Scale 1| 0 =
None
1 = SuppyHLRH
| 2 = Network| W| None
Protocol Base| Holding Register| Description| Data
Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---
15012
| ****
4 15013
| ****
Supply High Limit Setpoint Source
| Unsigned
Scale 1
| 0 = None
1 = Internal
| ****
2 = ControlInput
| ****
W
| ****
None
15013| 4 15014| Humidity Control Demand Source| Unsigned
Scale 1
| 0 = None
1 = ControlInput
| 2 = RoomDemand
3 = Network
| W| ControlInput
15014| 4 15015| Humidity Control High Limit Source| Unsigned
Scale 1
| 0 = None
1 = ControlInput
| 2 = SupplyHLDemand
3 = Network
| W| None
15015
| ****
4 15016
| ****
Humidity Control Cutout State
| Unsigned
Scale 1
| 0 = Off
1 = Normal
2 = LowLimit
| 3 = HighLimit
4 = NoAirFlow
5 = Interlock
| ****
RO
| ****
Off
15016
| ****
4 15017
| ****
Boiler Request
| Unsigned
Scale 1
| 0 = None
1 = Reset Alarms 2 = Drain
| 3 = Reset Counters 4 = Filling
5 = WaterCalib
| ****
W
| ****
None
15017
| ****
4 15018
| ****
Boiler State
| ****
Unsigned
Scale 1
| 0 = Off
1 = Idle
2 = LineRinse
3 = TankRinse
4 = Filling
| 5 = Draining
6 = Heating
7 = Boiling
8 = Alarm
| ****
RO
| ****
Off
15018| 4 15019| Boiler Fill Mode| Unsigned
Scale 1
| 0 = OneShot
1 = Pulsed
| W| Pulsed
15019
| ****
4 15020
| ****
Boiler Alarm
| ****
Unsigned
Scale 1
| 0 = Normal
1 = FailedPump
2 = FillTimeout
3 = BlockedPiping
4 = HeatTimeout
5 = Overheat
| 6 = WaterLeak
7 = Service
8 is Reserved
9 = TankBlocked
10 = RefillDelay
| ****
RO
| ****
Normal
15020| 4 15021| Boiler Idle Tank Rinse On| Unsigned
Scale 1
| 0 = Off
1 = On
| W| Off
15021| 4 15022| Boiler Idle Tank Rinse Off| Unsigned
Scale 1
| 0 = Off
1 = On
| W| Off
15022| 4 15023| Water Probe Auto Calib| Unsigned
Scale 1
| 0 = None
1 = Once
| 2 = Always| W| Always
Protocol Base| Holding Register| Description| **Data
Type| Units, Limits, State Texts| Writable| Default Value**
---|---|---|---|---|---|---
15023
| ****
4 15024
| ****
Boiler Startup Tank Rinse
| Unsigned
Scale 1
| 0 = Off
1 = On
| **** W| Off
15024
| ****
4 15025
| ****
Water Level Probe Warning
| Unsigned
Scale 1
| 0 = Ok
1 = Replace
| RO| ** OK
15025| 4 15026**| Water Level Probe Failure| Unsigned
Scale 1
| 0 = None
1 = Capacitive
| 2 = Resistive
3 = Both
| RO| None
15026| 4 15027| Water Level Probe Alarm| Unsigned
Scale 1
| 0 = OK
1 = Defect
| 2 = NoCalib| RO| Ok
Notes………………..
400 Lebeau blvd, Montreal, Qc, H4N 1R6, Canada
www.neptronic.com
Toll free in North America:
1-800-361-2308
Tel.: 514-333-1433
Fax: 514-333-3163
Customer service fax: 514-333-1091
Monday to Friday: 8:00am to 5:00pm (Eastern time)
References
- Neptronic | Home - Humidifier Distributor & HVAC Products
- Neptronic | Home - Humidifier Distributor & HVAC Products
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>