neptronic SKS4 Steam to Steam Humidifier User Guide

June 4, 2024
neptronic

SKS4 Steam to Steam Humidifier
Modbus Communication Module User Guide neptronic SKS4 Steam to Steam
HumidifierSKS4-Modbus Guide-211019

Introduction

The SKS4 Modbus Communication Module User Guide provides information for using Neptronic ® communication feature. The controller uses Modbus communication protocol over the serial line in the RTU mode and provides a Modbus network interface between client devices and Neptronic SKS4 devices.
The SKS4 Modbus Guide assumes that you are familiar with Modbus terminology.
The following are the requirements for Modbus:

  • Data Model. The SKS4 Steam to Steam Humidifier Modbus server data model uses only the Modbus Registers table.
  • Register Address:
    o As per protocol base (base 0); for PLC add 1 to the protocol base.
    o As per holding register (base 400001).

Note: Ensure that the Modbus communication software used does not have a limit on the range of the register addresses that can be viewed and supports 6-digit holding registers.

  • Function Codes. The SKS4 Steam to Steam Humidifier Modbus server supports a limited function codes subset comprising:
    o Read Holding Registers (0x03)
    o Write Single Register (0x06)
    o Write Multiple Registers (0x10)

  • Exception Responses. The SKS4 Steam to Steam Humidifier Modbus server supports the following exception codes:
    o Illegal data address
    o Illegal data value
    o Slave device busy

  • Serial Line. The SKS4 Steam to Steam Humidifier Modbus over serial line uses RTU transmission mode over a two-wire configuration RS485 (EIA/TIA-485 standard) physical layer.
    o The physical layer can use fixed baud rate selection or automatic baud rate detection (default) as per the Modbus Auto Baud Rate device menu item or holding register index 1.
    o The supported baud rates are 9600, 19200, 38400, and 57600.
    o The physical layer also supports variable parity control and stop bit configuration as per the Modbus
    Comport Config device menu item or holding register index 2.
    o In auto baud rate configuration, if the device detects only consecutive bad frames (2 or more) for one second with any given baud rate, it will reinitialize itself to the next baud rate.

  • Addressing. The SKS4 Steam to Steam Humidifier device only answers at the following address:
    o The device’s unique address (1 to 246) can be set through the device menu or through holding register index 0.

Modbus Registers

Table Glossary

Name Description Name Description
W Writable Register ASCII For registers containing ASCII (8-bit) characters
RO Read Only Register MSB Most Significant Byte
Unsigned For range of values from 0 to 65,535, unless otherwise specified
LSB Least Significant Byte
Signed For range of values from -32,768 to 32,767, unless otherwise
specified MSW Most Significant Word
Bit String For registers with multiple values using bit mask (example,
flags) LSW Least Significant Word

Modbus Registers Table

Protocol Base| Holding Register| Description| Data Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---


0

| ****

40000 1

| ****

Modbus Address and Product Type

| ****

Unsigned

| MSB = Product type, not writable

LSB = Modbus Address (1 to 247), writable

| **** W|


1

| ****

40000 2

| ****

Device Baud Rate

| Unsigned

Scale 100

| 0, 9600, 19200, 38400, and 57600, 0 = Auto Baud Rate Detection Value/100 (e.g. 38400 baud = 384)| W|

19200


2

| ****

40000 3

| ****

Modbus Slave Communication Port Configuration

| ****

Unsigned

| 0 = No parity, 2 Stop bits 1 = Even parity, 1 Stop bit 2 = Odd parity, 1 Stop bit| ****

W

| ****

No parity, 2 Stops bits

3| 40000 4| Product Name (characters 8 & 7)| ASCII| MSB = char 6, LSB = char 7| W|
4| 40000 5| Product Name (characters 6 & 5)| ASCII| MSB = char 4, LSB = char 5| W|
5| 40000 6| Product Name (characters 4 & 3)| ASCII| MSB = char 2, LSB = char 3| W|
6| 40000 7| Product Name (characters 2 & 1)| ASCII| MSB = char 0, LSB = char 1| W|
7| 40000 8| Product Actual Firmware Version (in Integer x100)| Unsigned

Scale 100

| 1 to 65535 (e.g. 100)| RO|
Protocol Base| Holding Register| Description| Data Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---
8| 40000 9| Product Actual EEPROM Version (in Integer x100)| Unsigned Scale 100| 1 to 65535 (e.g. 100)| RO|
2000| 40 2001| Control Signal| Unsigned  Scale 1000| Units: Volt (V), Range: 0V to 15V Value x 1000 (e.g. 1V = 1000)| RO| 0V
2001| 40 2002| Room RH Signal| Unsigned  Scale 1000| Units: Volt (V), Range: 0V to 15V Value x 1000 (e.g. 1V = 1000)| RO| 0V
2002| 40 2003| Supply RH Signal| Unsigned  Scale 1000| Units: Volt (V), Range: 0V to 15V  Value x 1000 (e.g. 1V = 1000)| RO| 0V
2003| 40 2004| Water Level Signal| Unsigned  Scale 1| Units: Hz, Range: 0 to 30000Hz  Value x 1 (e.g. 10Hz = 10)| RO| 0Hz
2004| 40 2005| Water Level Low Signal| Unsigned  Scale 1000| Unit: Volt (V), Range: 0V to 10V  Value x 1000 (e.g. 1V = 1000)| RO| ** 0V
2005| 40
2006| Water Level High Signal| Unsigned  Scale 1000| Unit: Volt (V), Range: 0V to 10V  Value x 1000 (e.g. 1V = 1000)| RO| 0V
2006| 40
2007| Water Temperature Signal| Unsigned  Scale 1000| Unit: Volt (V), Range: 0V to 10V  Value x 1000 (e.g. 1V = 1000)| RO| 0V
2007| 40
2008| Foam Signal| Unsigned  Scale 1000| Unit: Volt (V), Range: 0V to 10V  Value x 1000 (e.g. 1V = 1000)| RO| 0V
2008| 40
2009| Cabinet Temperature Signal| Unsigned  Scale 1000| Unit: Volt (V), Range: 0V to 10V  Value x 1000 (e.g. 1V = 1000)| RO| 0V
2009| 40
2010| Board Temperature Signal| Unsigned Scale 1000| Unit: Volt (V), Range: 0V to 10V  Value x 1000 (e.g. 1V = 1000)| RO| 0V
2010| 40
2011| Main Power Supply| Unsigned  Scale 10| Unit: Volt (V), Range: 0V to 40V  Value x 10 (e.g. 1V = 10)| RO| 0V
2011| 40
2012| Steam Valve Feedback Signal| Unsigned  Scale 1000| Units: Volt (V), Range: 0V to 10.5V
Value x 1000 (e.g. 1V = 1000)| RO| 0V
Protocol Base| Holding Register| Description| Data Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---
**
4000| ** 40 4001| Steam Output Feedback Signal| Unsigned Scale 1000| Unit: Volt (V), Range: 0V to 10V Value x 1000 (e.g. 1V = 1000)| RO| ** 0V


4001

| ****

40 4002

| ****

Steam Valve Signal

| Unsigned

Scale 1000

| Unit: Volt (V), Range: 0V to 10V

Value x 1000 (e.g. 1V = 1000)

| **** RO| 0V


6000

| ****

40 6001

| ****

Control Input

| Unsigned

Scale 100

| Unit: %, Range: 0% to 100%

Value x 100 (e.g. 10% = 1000)

| W| 0%


6001

| ****

40 6002

| ****

Control Min

| Unsigned

Scale 100

| Unit: %, Range: 0% to 100%

Value x 100 (e.g. 10% = 1000)

| W| 0%
6002| 40 6003| Control Max| Unsigned Scale 100| Unit: %, Range: 0% to 100% Value x 100 (e.g. 10% = 1000)| W| 0%
** 6003| 40 6004| Control Bias| Signed Scale 100| Unit: %, Range: -10% to 10% Value x 100 (e.g. 10% = 1000)| W| 0%
6004| 40
6005| Room RH| Unsigned Scale 100| Unit: % RH, Range: 0% RH to 100% RH Value x 100 (e.g. 10% RH = 1000)| RO| 0% RH
6005| 40
6006| Room RH Min| Unsigned Scale 100| Unit: % RH, Range: 0% RH to 100% RH Value x 100 (e.g. 10% RH = 1000)| RO| ** 0% RH
** 6006| 40 6007| Room RH Max| Unsigned Scale 100| Unit: % RH, Range: 0% RH to 100% RH Value x 100 (e.g. 10% RH = 1000)| RO| 0% RH
6007| 40
6008| Room RH Bias| Unsigned Scale 100| Unit: % RH, Range: 0% RH to 100% RH Value x 100 (e.g. 10% RH = 1000)| RO| 0% RH
6008| 40
6009| Supply High Limit RH| Unsigned Scale 100| Unit: % RH, Range: 0% RH to 100% RH Value x 100 (e.g. 10% RH = 1000)| RO| 0% RH
**
6009| 40 6010| Supply High Limit RH Min| Unsigned Scale 100| Unit: %, Range: 0% to 100% Value x 100 (e.g. 10% = 1000)| W| 0%
6010|
40 6011| Supply High Limit RH Max| Unsigned Scale 100| Unit: %, Range: 0% to 100% Value x 100 (e.g. 10% = 1000)| W| 0%
Protocol Base| Holding Register| ****

Description

| ****

Data Type

| ****

Units, Limits, State Texts

| ****

Writable

| Default Value
---|---|---|---|---|---|---


6011

| ****

40 6012

| ****

Supply High Limit RH Bias

| Signed

Scale 100

| Unit: %, Range: -10% to 10%

Value x 100 (e.g. 10% = 1000)

| ****

W

| ****

0%

6012| 40 6013| Water Temperature Signal Min| Unsigned

Scale 1000

| Unit: Volt (V), Range: 0V to 10V

Value x 1000 (e.g. 1V = 1000)

| RO| 0V
6013| 40 6014| Water Temperature Signal Max| Unsigned

Scale 1000

| Unit: Volt (V), Range: 0V to 10V

Value x 1000 (e.g. 1V = 1000)

| RO| 0V


6014

| ****

40 6015

| ****

Water Temperature

| Unsigned

Scale 100

| Unit: ºC/ºF, Range: 0°C to 125°C or 32°F to 257°F

Value x 100 (e.g. 5°C = 500 or 40ºF = 4000)

| ****

RO

| 50°C or 122°F
6015| 40 6016| Water Temperature Min| Unsigned

Scale 100

| Unit: ºC/ºF, Range: 0°C to 250°C or 32°F to 482°F

Value x 100 (e.g. 5°C = 500 or 40ºF = 4000)

| RO| 0°C or 32°F
6016| 40 6017| Water Temperature Max| Unsigned

Scale 100

| Unit: ºC/ºF, Range: 0°C to 250°C or 32°F to 482°F  Value x 100 (e.g. 5°C = 500 or 40ºF = 4000)| RO| 125°C or

257°F


6017

| ****

40 6018

| ****

Water Temperature Bias

| Unsigned

Scale 100

| Unit: ºC/ºF, Range: -10°C to 10°C or -18°F to 18°F  Value x 100 (e.g. 5°C = 500 or 14ºF = 1400)| ****

RO

| ****

0°C or 32°F


6018

| ****

40 6019

| ****

Cabinet Temperature

| Unsigned

Scale 100

| Unit: ºC/ºF, Range: -20°C to 100°C or -4°F to 212°F  Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)| ****

RO

| ****

0°C or 32°F


6019

| ****

40 6020

| ****

Modbus TCP IP Keep Alive Time Out (0)

| Unsigned

Scale 1

| Unit: Minutes (min), Range: 1 to 1440 mins  Value x 1 (e.g. 5 mins = 5)|


W

| ****

5 min

6020| 40 6021| Modbus TCP IP Keep Alive Time Out (1)| | Unit: Minutes (min), Range: 1 to 1440 mins| |
6021| 40 6022| HRL Temperature| Signed

Scale 100

| Unit: ºC/ºF, Range: -40°C to 260°C or -40°F to 500°F  Value x 100 (e.g. 5°C = 500 or 40ºF = 4000)| RO| 0°C or 32°F
6022| 40 6023| HRL Humidity| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 1% RH = 100)

| RO| 0% RH
6023| ** 40 6024| Board Temperature| Unsigned Scale 100| Unit: ºC/ºF, Range: 0°C to 100°C or 32°F to 212°F  Value x 100 (e.g. 5°C = 500 or 32ºF = 3200)| RO| 0°C or 32°F
**
6024| 40 6025| Power Output Feedback Bias| Unsigned Scale 1000| Unit: Volt (V), Range: 0V to 10V  Value x 1000 (e.g. 1V = 1000)| W| ** 0V
Protocol Base| Holding Register| Description| Data Type| Units, Limits, State Texts| Writable| Default Value**
---|---|---|---|---|---|---


6025

| ****

40 6026

| ****

Power Output Feedback Min

| Unsigned

Scale 1000

| Unit: Volt (V), Range: 0V to 10V

Value x 1000 (e.g. 1V = 1000)

| ****

W

| ****

0V


6026

| ****

40 6027

| ****

Power Output Feedback Max

| Unsigned

Scale 1000

| Unit: Volt (V), Range: 0V to 10V

Value x 1000 (e.g. 1V = 1000)

| ****

W

| ****

0V


6027

| ****

40 6028

| ****

Power Output Feedback

| Unsigned

Scale 100

| Unit: %, Range: 0% to 100%

Value x 100 (e.g. 10% = 1000)

| ****

RO

| ****

0%


6028

| ****

40 6029

| ****

Steam Valve Control

| Unsigned

Scale 100

| Unit: %, Range: 0% to 100%

Value x 100 (e.g. 10% = 1000)

| ****

RO

| ****

0%

6029| 40 6030| Water Level| Unsigned

Scale 10

| Unit: %, Range: 0% to 120%

Value x 10 (e.g. 10% = 100)

| RO| 78%
6030| 40 6031| Water Probe Low Pos Reading| Unsigned

Scale 1

| Unit: Hz, Range: 0 to 30000 Hz

Value x 1 (e.g. 1 Hz = 1)

| RO| 30000Hz
6031| 40 6032| Water Probe High Pos Reading| Unsigned

Scale 1

| Unit: Hz, Range: 0 to 30000 Hz

Value x 1 (e.g. 1 Hz = 1)

| RO| 30000Hz
6032| 40 6033| Water Probe Abs Low Pos Reading| Unsigned

Scale 1

| Unit: Hz, Range: 0 to 30000 Hz

Value x 1 (e.g. 1 Hz = 1)

| RO| 30000Hz
6033| 40 6034| Water Probe Abs High Pos Reading| Unsigned

Scale 1

| Unit: Hz, Range: 0 to 30000 Hz

Value x 1 (e.g. 1 Hz = 1)

| RO| 30000Hz
6034| 40 6035| Room RH Network Reading| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| W| 0% RH
6035| 40 6036| Room RH Setpoint| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| W| 40% RH
6036| 40 6037| Room RH Unoccupied Setpoint| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| W| 30% RH
6037| 40 6038| Room RH Vacant Setpoint| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| W| 20% RH


6038

| ****

40 6039

| ****

Room Demand Proportional Gain

| Unsigned

Scale 10

| No Unit, Range: 1 to 200

Value x 10 (e.g. 10 = 100)

| ****

W

| ****

20

Protocol Base| Holding Register| Description| Data Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---


6039

| ****

40 6040

| ****

Room Demand Integral Time

| Unsigned

Scale 10

| Unit: sec, Range: 0 to 900 sec

Value x 10 (e.g. 10sec = 100)

| ****

W

| ****

0 sec


6040

| ****

40 6041

| ****

Room Demand Derivative Time

| Unsigned

Scale 10

| Unit: sec, Range: 0 to 60 sec

Value x 10 (e.g. 10sec = 100)

| ****

W

| ****

0 sec

6041| 40 6042| Room Demand| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| RO| 0% RH


6042

| ****

40 6043

| ****

Room Demand Proportional Band (0)

| Unsigned

Scale 10

| Unit: %, Range: 1% to 100%

Value x 10 (e.g. 10% RH = 100)

| ****

W

| ****

5%

6043| 40 6044| Room Demand Proportional Band (1)| | Unit: %, Range: 1% to 100%| |
6044| 40 6045| Supply High Limit Network Reading| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| W| 0% RH
6045| 40 6046| Supply High Limit Setpoint| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| W| 80% RH


6046

| ****

40 6047

| ****

Supply High Limit Proportional Gain

| Unsigned

Scale 10

| No Unit, Range: 1 to 200

Value x 10 (e.g. 10 = 100)

| ****

W

| ****

10


6047

| ****

40 6048

| ****

Supply High Limit Integral Time

| Unsigned

Scale 10

| Unit: sec, Range: 0 to 900 sec

Value x 10 (e.g. 10sec = 100)

| ****

W

| ****

0 sec


6048

| ****

40 6049

| ****

Supply High Limit Derivative Time

| Unsigned

Scale 10

| Unit: sec, Range: 0 to 60 sec

Value x 10 (e.g. 10sec = 100)

| ****

W

| ****

0 sec

6049| 40 6050| Supply High Limit Demand| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| RO| 0% RH


6050

| ****

40 6051

| ****

Supply High Limit Proportional Band (0)

| Unsigned

Scale 10

| Unit: %, Range: 1% to 100%

Value x 10 (e.g. 10% RH = 100)

| ****

W

| ****

10%

6051| 40 6052| Supply High Limit Proportional Band (1)| | Unit: %, Range: 1% to 100%| |
6052| 40 6053| Humidity Control Network Demand| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| W| 0% RH
Protocol Base| Holding Register| Description| Data Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---
6053| 40 6054| Humidity Control Network High Limit| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH  Value x 100 (e.g. 10% RH = 1000)| W| 100% RH
6054| 40 6055| Humidity Demand| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH  Value x 100 (e.g. 10% RH = 1000)| RO| 0% RH
6055| 40 6056| Humidity Demand Low Dead Band (0)| Unsigned

Scale 100

| Unit: %, Range: 0% to 100%  Value x 100 (e.g. 10% = 1000)| W| 1%
6056| 40 6057| Humidity Demand Low Dead Band (1)| | Unit: %, Range: 0% to 100%| |
6057| 40 6058| Network Timeout (0)| Unsigned

Scale 1

| Unit: Seconds (sec), Range: 1 to 900 sec  Value x 1 (e.g. 10sec = 10)| W| 900 sec
6058| 40 6059| Network Timeout (1)| | Unit: Seconds (sec), Range: 1 to 900 sec| |
6059| 40 6060| System Power Output| Unsigned

Scale 100

| Unit: %, Range: 0% to 100%  Value x 100 (e.g. 10% = 1000)| RO| 0%


6060

| ****

40 6061

| ****

System Steam Capacity

| Unsigned

Scale 10

| Unit: kg/hr or lb/hr, Range: 0 to 300 kg/hr or 0 to 66 1lb/hr

Value x 10 (e.g. 10 kg/hr = 100 or 10 lb/hr = 100)

| ****

RO

| 0 kg/hr or

0 lb/hr


6061

| ****

40 6062

| ****

Water Level Replace Interval (0)

| Unsigned

Scale 1

| Unit: Days, Range: 0 day to 7 days  Value x 1 (e.g. 1 day = 1)| ****

W

| ****

7day

6062| 40 6063| Water Level Replace Interval (1)| | Unit: Days, Range: 0 day to 7 days  Value x 1 (e.g. 1 day = 1)| |
6063| 40 6064| Boiler Anti-freeze Keep Warm Setpoint (0)| Signed

Scale 100

| Unit: ºC/ºF, Range: -40ºC to 100ºC or -40ºF to 212ºF  Value x 100 (e.g. 10 º C = 1000 or 40ºF = 4000)| RO| 30°C or 86°F
6064| 40 6065| Boiler Anti-freeze Keep Warm Setpoint (1)| | Unit: ºC/ºF, Range: -40ºC to 100ºC or -40ºF to 212ºF| |
6065| 40 6066| Boiler Anti-freeze Keep Warm (0)| Signed

Scale 100

| Unit: ºC/ºF, Range: -40ºC to 100ºC or -40ºF to 212ºF  Value x 100 (e.g. 10 º C = 1000 or 40ºF = 4000)| RO| 10°C or 50°F
6066| 40 6067| Boiler Anti-freeze Keep Warm (1)| | Unit: ºC/ºF, Range: -40ºC to 100ºC or -40ºF to 212ºF| |
6067| 40 6068| Boiler Anti-freeze Drain (0)| Signed

Scale 100

| Unit: ºC/ºF, Range: -40ºC to 100ºC or -40ºF to 212ºF  Value x 100 (e.g. 10 º C = 1000 or 40ºF = 4000)| RO| 1°C or 34°F
Protocol Base| Holding Register| **Description| Data Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---
6068| 40
6069| Boiler Anti-freeze Drain (1)| | Unit: ºC/ºF, Range: -40ºC to 100ºC or -40ºF to 212ºF| |
6069| 40
6070**| Boiler Demand| Unsigned

Scale 100

| Unit: %, Range: 0% to 100%  Value x 100 (e.g. 10% = 1000)| W| 0%


6070

| ****

40 6071

| ****

Boiler Capacity

| ****

Unsigned

Scale 10

| Unit: kg/hr or lb/hr, Range: 0 to 3000kg/hr or 0 to 6613.8lb/hr  Value x 10 (e.g. 10 kg/hr = 100 or 10 lb/hr = 100)| ****

RO

| ****

15 kg/hr or

33.06 lb/hr


6071

| ****

40 6072

| ****

Boiler Power Output

| Unsigned

Scale 100

| Unit: %, Range: 0% to 100%  Value x 100 (e.g. 10% = 1000)| ****

RO

| ****

0%


6072

| ****

40 6073

| ****

Boiler Run Time (0)

| Unsigned

Scale 100

| Units: Hours (h), Range: 0 to 21474836.47 h  Value x 100 (e.g. 10h = 1000)| ****

RO

| ****

0h

6073| 40 6074| Boiler Run Time (1)| | Units: Hours (h), Range: 0 to 21474836.47 h| |
6074| 40 6075| Boiler Run Time (2)| | Units: Hours (h), Range: 0 to 21474836.47 h| |
6075| 40 6076| Boiler Run Time (3)| | Units: Hours (h), Range: 0 to 21474836.47 h| |


6076

| ****

40 6077

| ****

Boiler On Time (0)

| Unsigned

Scale 100

| Units: Hours (h), Range: 0 to 21474836.47 h  Value x 100 (e.g. 10h = 1000)| ****

RO

| ****

0h

6077| 40 6078| Boiler On Time (1)| | Units: Hours (h), Range: 0 to 21474836.47 h| |
6078| 40 6079| Boiler On Time (2)| | Units: Hours (h), Range: 0 to 21474836.47 h| |
6079| 40 6080| Boiler On Time (3)| | Units: Hours (h), Range: 0 to 21474836.47 h| |


6080

| ****

40 6081

| ****

Boiler Service Run Time (0)

| Unsigned

Scale 100

| Units: Hours (h), Range: 0 to 21474836.47 h  Value x 100 (e.g. 10h = 1000)| ****

RO

| ****

0h

6081| 40 6082| Boiler Service Run Time (1)| | Units: Hours (h), Range: 0 to 21474836.47 h| |
6082| 40 6083| Boiler Service Run Time (2)| | Units: Hours (h), Range: 0 to 21474836.47 h| |
6083| 40 6084| Boiler Service Run Time (3)| | Units: Hours (h), Range: 0 to 21474836.47 h| |
6084| 40 6085| Boiler Service On Time (0)| Unsigned Scale 100| Units: Hours (h), Range: 0 to 21474836.47 h  Value x 100 (e.g. 10h = 1000)| RO| ** 0h
Protocol Base| Holding Register| ****Description| Data Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---
6085| 40
6086| Boiler Service On Time (1)| | Units: Hours (h), Range: 0 to 21474836.47 h| |
6086| 40
6087| Boiler Service On Time (2)| | Units: Hours (h), Range: 0 to 21474836.47 h| |
6087| 40
6088**| Boiler Service On Time (3)| | Units: Hours (h), Range: 0 to 21474836.47 h| |


6088

| ****

40 6089

| ****

Boiler Minimum Steam Output

| Unsigned

Scale 1

| Unit: %, Range: 1% to 25%  Value x 1 (e.g. 1% = 1)| ****

W

| ****

5%


6089

| ****

40 6090

| ****

Boiler Drain Interval

| Unsigned

Scale 1

| Units: Hours (h), Range: 0 to 24 h  Value x 1 (e.g. 1 h = 1)| ****

W

| ****

6h


6090

| ****

40 6091

| ****

Boiler Drain Volume

| Unsigned

Scale 1

| Unit: %, Range: 25% to 100%  Value x 1 (e.g. 30% = 300)| ****

W

| ****

100%


6091

| ****

40 6092

| ****

Boiler Max Steam Output

| Unsigned

Scale 1

| Unit: %, Range: 0% to 100%  Value x 1 (e.g. 30% = 300)| ****

W

| ****

100%


6092

| ****

40 6093

| ****

Boiler Idle Time Drain

| Unsigned

Scale 1

| Unit: Hours (h), Range: 0 to 72 h  Value x 1 (e.g. 1 h = 1)| ****

W

| ****

24h


6093

| ****

40 6094

| ****

Boiler Idle Temperature Setpoint

| Unsigned

Scale 1

| Unit: ºC/ºF, Range: 0°C to 60°C or 32°F or 140°F  Value x 1 (e.g. 5°C = 500 or 32ºF = 3200)| ****

W

| ****

0°C or 32°F


6094

| ****

40 6095

| ****

Boiler Blowdown Rate

| Unsigned

Scale 1

| Unit: %, Range: 0% to 100%  Value x 1 (e.g.1% = 1)| ****

W

| ****

0%


6095

| ****

40 6096

| ****

Boiler Service Interval

| Unsigned

Scale 1

| Unit: Hours (h), Range: 1000 to 3000 h  Value x 1 (e.g. 1500 h = 1500)|


W

| ****

1000h


6096

| ****

40 6097

| ****

Boiler Idle Tank Rinse Interval

| Unsigned

Scale 1

| Unit: Days, Range: 1 to 7 days  Value x 1 (e.g. 1 day = 1)| ****

W

| ****

3 day

6097| 40 6098| Actuator Deadband| Unsigned

Scale 1

| Unit: %, Range: 0% to 25%  Value x 1 (e.g. 5% = 5)| W| 5%


6098

| ****

40 6099

| ****

Boiler Manual Calibration Time (0)

| Unsigned

Scale 100

| Units: Hours (h), Range: 0 to 21474836.47 h  Value x 100 (e.g. 10h = 1000)| ****

RO

| ****

0h

6099| 40 6100| Boiler Manual Calibration Time (1)| | Units: Hours (h), Range: 0 to 21474836.47 h| |
Protocol Base| Holding Register| Description| Data Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---
6100| 40 6101| Boiler Manual Calibration Time (2)| | Units: Hours (h), Range: 0 to 21474836.47 h| |
6101| 40 6102| Boiler Manual Calibration Time (4)| | Units: Hours (h), Range: 0 to 21474836.47 h| |
6102| 40 6103| Steam Valve Feedback| Unsigned

Scale 100

| Unit: %, Range: 0% to 100%

Value x 100 (e.g. 1% = 100)

| RO| 0%


10000

| ****

4 10001

| ****

Air Flow

| Unsigned

Scale 1

| 0 = Closed

1 = Open

| ****

RO

| ****

Closed


10001

| ****

4 10002

| ****

Supply High Limit

| Unsigned

Scale 1

| 0 = Closed

1 = Open

| ****

RO

| ****

Closed


10002

| ****

4 10003

| ****

Interlock

| Unsigned

Scale 1

| 0 = Closed

1 = Open

| ****

RO

| ****

Closed


10003

| ****

4 10004

| ****

Binary External Demand

| Unsigned

Scale 1

| 0 = 0%

1 = 100%

| ****

RO

| ****

0%


10004

| ****

4 10005

| ****

Water Leak Detection

| Unsigned

Scale 1

| 0 = Ok

1 = Leak

| ****

RO

| ****

Ok


10005

| ****

4 10006

| ****

Thermal Cutout

| Unsigned

Scale 1

| 0 = Closed

1 = Open

| ****

RO

| ****

Closed


10006

| ****

4 10007

| ****

RS485 Interface

| Unsigned

Scale 1

| 0 = No

1 = Yes

| ****

RO

| ****

No


10007

| ****

4 10008

| ****

Ethernet Interface

| Unsigned

Scale 1

| 0 = No

1 = Yes

| ****

RO

| ****

No


10008

| ****

4 10009

| ****

Contactors PCB Fuse

| Unsigned

Scale 1

| 0 = Normal

1 = Blown Fuse

| ****

RO

| ****

Normal


10009

| ****

4 10010

| ****

Control PCB Fuse

| Unsigned

Scale 1

| 0 = Normal

1 = Open Fuse

| ****

RO

| ****

Normal

11000| 4 11001| Drain Valve| Unsigned

Scale 1

| 0 = Off

1 = On

| RO| Off
Protocol Base| Holding Register| ****

Description

| ****

Data Type

| ****

Units, Limits, State Texts

| ****

Writable

| Default Value
---|---|---|---|---|---|---
11001| 4 11002| Alarm Warning Relay| Unsigned

Scale 1

| 0 = Off

1 = On

| RO| Off
11002| 4 11003| Service Warning Relay| Unsigned

Scale 1

| 0 = Off

1 = On

| RO| Off
11003| 4 11004| Water Level Valve| Unsigned

Scale 1

| 0 = Off

1 = On

| RO| Off


11004

| ****

4 11005

| ****

Tank Water Valve

| Unsigned

Scale 1

| 0 = Off

1 = On

| ****

RO

| ****

Off


11005

| ****

4 11006

| ****

Drain Cooler Valve

| Unsigned

Scale 1

| 0 = Off

1 = On

| ****

RO

| ****

Off


11006

| ****

4 11007

| ****

Drain Pump

| Unsigned

Scale 1

| 0 = Off

1 = On

| ****

RO

| ****

Off


11007

| ****

4 11008

| ****

Drain Pump 2

| Unsigned

Scale 1

| 0 = Off

1 = On

| ****

RO

| ****

Off


11008

| ****

4 11009

| ****

Drain Pump 3

| Unsigned

Scale 1

| 0 = Off

1 = On

| ****

RO

| ****

Off


11009

| ****

4 11010

| ****

Alarm LED

| Unsigned

Scale 1

| 0 = Off

1 = On

| ****

RO

| ****

Off


11010

| ****

4 11011

| ****

Power LED

| Unsigned

Scale 1

| 0 = Off

1 = On

| ****

RO

| ****

Off


11011

| ****

4 11012

| ****

Buzzer

| Unsigned

Scale 1

| 0 = Off

1 = On

| ****

RO

| ****

Off


12000

| ****

4 12001

| ****

Network Control State

| Unsigned

Scale 1

| 0 = Normal

1 = Fault

| ****

W

| ****

Normal


12001

| ****

4 12002

| ****

Water Level Low

| Unsigned

Scale 1

| 0 = Inactive

1 = Active

| ****

RO

| ****

Inactive

Protocol Base| Holding Register| Description| Data Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---


12002

| ****

4 12003

| ****

Water Level High

| Unsigned

Scale 1

| 0 = Inactive

1 = Active

| ****

RO

| ****

Inactive


12003

| ****

4 12004

| ****

Foam Sensor

| Unsigned

Scale 1

| 0 = NoFoam

1 = Foam

| ****

RO

| ****

NoFoam

12004| 4 12005| HRL Lock Setpoint| Unsigned

Scale 1

| 0 = Unlock

1 = Lock

| W| Unlock


12005

| ****

4 12006

| ****

Notify Alarm

| Unsigned

Scale 1

| 0 = Off

1 = On

| ****

W

| ****

Off


12006

| ****

4 12007

| ****

Notify Warning

| Unsigned

Scale 1

| 0 = Off

1 = On

| ****

W

| ****

Off


12007

| ****

4 12008

| ****

Notify App Msg

| Unsigned

Scale 1

| 0 = Off

1 = On

| ****

W

| ****

Off


12008

| ****

4 12009

| ****

Inhibit Resistive Probe

| Unsigned

Scale 1

| 0 = No

1 = Yes

| ****

W

| ****

No

12009| 4 12010| Boiler Service Operation| Unsigned

Scale 1

| 0 = Not Allowed 1 = Allowed| W| Allowed
12010| 4 12011| Boiler Service Due| Unsigned

Scale 1

| 0 = Off

1 = On

| RO| Off
12011| 4 12012| Foam| Unsigned

Scale 1

| 0 = Ok

1 = Detected

| RO| Ok


12012

| ****

4 12013

| ****

Boiler Line Rinse

| Unsigned

Scale 1

| 0 = Off

1 = On

| ****

W

| ****

On

12013| 4 12014| Power Up Drain| Unsigned Scale 1| 0 = Off

1 = On

| W| Off
12014| 4 12015| Manual Water Calibration State| Unsigned Scale 1| 0 = Ok

1 = Required

| RO| Ok
Protocol Base| Holding Register| Description| Data Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---
15000| 4 15001| System Power State| Unsigned

Scale 1

| 0 = Off

1 = On

| W| Off



15001

| ****


4 15002

| ****


System Log Verbose Level

| ****

Unsigned

Scale 1

| 0 = None

1 = Emergency

2 = Alert

3 = Critical

4 = Error

| 5 = Warning

6 = Notice

7 = Info

8 = Debug

| ****


W

| ****


Debug


15002

| ****

4 15003

| ****

Modbus Server Units

| Unsigned

Scale 1

| 0 = Metric

1 = Imperial

| ****

W

| ****

Metric

15003| 4 15004| Control Signal Type| Unsigned

Scale 1

| 0 = 0-10Vdc

1 = 2-10Vdc

| 2 = 4-20mA

3 = 0-20mA

| W| 0-10Vdc


15004

| ****

4 15005

| ****

Room RH Signal Type

| Unsigned

Scale 1

| 0 = 0-10Vdc

1 = 2-10Vdc

| 2 = 4-20mA

3 = 0-20mA

| ****

W

| ****

0-10Vdc


15005

| ****

4 15006

| ****

Supply RH Signal Type

| Unsigned

Scale 1

| 0 = 0-10Vdc

1 = 2-10Vdc

| 2 = 4-20mA

3 = 0-20mA

| ****

W

| ****

0-10Vdc


15006

| ****

4 15007

| ****

Control Profile

| Unsigned

Scale 1

| 0 = ExternAnalog

1 = ExternNetwork

2 = InternAnalog

| 3 = InternNetwork

4 = HRL

5 = Custom

| ****

W

| ****

ExternAnalog


15007

| ****

4 15008

| ****

Modulating High Limit Profile

| Unsigned

Scale 1

| 0 = Disabled

1 = ExternAnalog

2 = ExternNetwork

| 3 = InternAnalog

4 = InternNetwork

5 = Custom

| ****

W

| ****

Disabled

15008| 4 15009| Occupancy State| Unsigned

Scale 1

| 0 = Occupied

1 = Unoccupied

| 2 = Vacant

3 = Off

| RO| Occupied
15009| 4 15010| Room RH Source| Unsigned

Scale 1

| 0 = None

1 = RoomRH

| 2 = Network| W| None
15010| 4 15011| Room RH Setpoint Source| Unsigned Scale 1| 0 = None

1 = Internal

| 2 = ControlInput| W| None
15011| 4 15012| Supply High Limit Reading Source| Unsigned Scale 1| 0 = None

1 = SuppyHLRH

| 2 = Network| W| None
Protocol Base| Holding Register| Description| Data Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---


15012

| ****

4 15013

| ****

Supply High Limit Setpoint Source

| Unsigned

Scale 1

| 0 = None

1 = Internal

| ****

2 = ControlInput

| ****

W

| ****

None

15013| 4 15014| Humidity Control Demand Source| Unsigned

Scale 1

| 0 = None

1 = ControlInput

| 2 = RoomDemand

3 = Network

| W| ControlInput
15014| 4 15015| Humidity Control High Limit Source| Unsigned

Scale 1

| 0 = None

1 = ControlInput

| 2 = SupplyHLDemand

3 = Network

| W| None


15015

| ****

4 15016

| ****

Humidity Control Cutout State

| Unsigned

Scale 1

| 0 = Off

1 = Normal

2 = LowLimit

| 3 = HighLimit

4 = NoAirFlow

5 = Interlock

| ****

RO

| ****

Off


15016

| ****

4 15017

| ****

Boiler Request

| Unsigned

Scale 1

| 0 = None

1 = Reset Alarms 2 = Drain

| 3 = Reset Counters 4 = Filling

5 = WaterCalib

| ****

W

| ****

None



15017

| ****


4 15018

| ****


Boiler State

| ****

Unsigned

Scale 1

| 0 = Off

1 = Idle

2 = LineRinse

3 = TankRinse

4 = Filling

| 5 = Draining

6 = Heating

7 = Boiling

8 = Alarm

| ****


RO

| ****


Off

15018| 4 15019| Boiler Fill Mode| Unsigned

Scale 1

| 0 = OneShot

1 = Pulsed

| W| Pulsed



15019

| ****


4 15020

| ****


Boiler Alarm

| ****


Unsigned

Scale 1

| 0 = Normal

1 = FailedPump

2 = FillTimeout

3 = BlockedPiping

4 = HeatTimeout

5 = Overheat

| 6 = WaterLeak

7 = Service

8 is Reserved

9 = TankBlocked

10 = RefillDelay

| ****


RO

| ****


Normal

15020| 4 15021| Boiler Idle Tank Rinse On| Unsigned

Scale 1

| 0 = Off

1 = On

| W| Off
15021| 4 15022| Boiler Idle Tank Rinse Off| Unsigned

Scale 1

| 0 = Off

1 = On

| W| Off
15022| 4 15023| Water Probe Auto Calib| Unsigned

Scale 1

| 0 = None

1 = Once

| 2 = Always| W| Always
Protocol Base| Holding Register| Description| **Data Type| Units, Limits, State Texts| Writable| Default Value**
---|---|---|---|---|---|---


15023

| ****

4 15024

| ****

Boiler Startup Tank Rinse

| Unsigned

Scale 1

| 0 = Off

1 = On

| **** W| Off


15024

| ****

4 15025

| ****

Water Level Probe Warning

| Unsigned

Scale 1

| 0 = Ok

1 = Replace

| RO| ** OK
15025| 4
15026**| Water Level Probe Failure| Unsigned

Scale 1

| 0 = None

1 = Capacitive

| 2 = Resistive

3 = Both

| RO| None
15026| 4 15027| Water Level Probe Alarm| Unsigned

Scale 1

| 0 = OK

1 = Defect

| 2 = NoCalib| RO| Ok

Notes………………..

400 Lebeau blvd, Montreal, Qc, H4N 1R6, Canada
www.neptronic.com
Toll free in North America: 1-800-361-2308
Tel.: 514-333-1433
Fax: 514-333-3163
Customer service fax: 514-333-1091
Monday to Friday: 8:00am to 5:00pm (Eastern time)