Arenal KWR-7QA03-921-20220321 Slurry Density Analyser Instruction Manual

June 13, 2024
Arenal

Arenal-LOGO

Arenal KWR-7QA03-921-20220321 Slurry Density Analyser

Arenal-KWR-7QA03-921-20220321-Slurry-Density-Analyser-
PRODUCT

Symbols and conventions

Arenal-KWR-7QA03-921-20220321-Slurry-Density-
Analyser-FIG-1

Mounting locations

inside canopy

Temperature Operating: 0-50 degC; Storage: -10ºC to +60ºC
Relative humidity 10-90% (non condensing)

Mounting angle

Mounting to the wall

Remove the aluminum plates to mount the analyzer to the wall

Electrical cables installation

Arenal-KWR-7QA03-921-20220321-Slurry-
Density-Analyser-FIG-3

To connect the UDT to the analyser

Name in Analyser| Name in UDT| Explanation| Wire numbers| Wire Colour
---|---|---|---|---
24VDC GND B- A+| 24VDC 0VDC B- A+| 24Vdc + 0 Vdc Modbus RTU Modbus RTU| 1

2

3

4

| Brown White Yellow

Arenal-KWR-7QA03-921-20220321-Slurry-Density-Analyser-
FIG-4

The power supply of the QA03-SDA

90-263 Vac

50-60 Hz


L N

mA wiring output

On LT4301TADAC display Parameter Terminal on HMI Color

E1 – mA-1 common ground- E2 – mA-1 +

E3 – mA-2 common ground E4 – mA-2 +

| SG Temperature| D14 C15 D14 D15| Yellow Green White Brown
On QM132-IOM Module| Parameter| Terminal on QM132
---|---|---
mA-1 common ground- mA-1 +

mA-2 common ground mA-2 +

| SG

Temperature

| 25)  Aout1 GND

26)  Aout 1+

23)  Aout2 GND

24)  Aout 2+

mA wiring input

On LT4301TADAC display Terminal on HMI
4-20 mA input + D13 AND C12 (connect them together)
4-20 mA input – D12
On QM132-IOM Module Terminal on QM132
--- ---
4-20 mA input 1+ 1)  Ain1+
4-20 mA input 1- 2)  Ain1 GND
4-20 mA input 2+ 3)  Ain2+
4-20 mA input 2- 4)  Ain2 GND

Open collector outputs

  • The 6 open collector outputs can be programmed to suit your application in process control.
  • Currently, three collector outputs have been used. As a standard, these are set to be sourced outputs (positive logic).
  • Pre-wiring all these outputs will give the following schedule:
Wire Terminal on HMI
24Vdc+ A3 (“V1+”)
24Vdc GND B3 (“V1-“)
Output (24V) B4 (“Q2”) SG value is lower than the low alarm value
Output (24V) A4 (“Q3”) SG value is higher than the high alarm level
Pulse (24V) B5 (“Q4”) Solids Production pulse per ton
Output (24V) A5 (“Q5”) Analyzer fault
Free B6 (“Q6”)
Free A6 (“Q7”)

Below is a description of each open collector:

  • SG value is lower than the low alarm value
  • This open collector output will give a positive constant voltage when the SG is lower than the low alarm level. This voltage can be used to switch a relay contact that switches a valve or pump.
  • The output can be powered by the internal power on the main board. Add a second fuse after the power converter to the 24Vdc connector on the left bottom and wire this to the below-mentioned terminals on top of the HMI.
Wire Terminal on HMI Terminal on QM132
24Vdc+ A3 (“V1+”) Not yet available
24Vdc GND B3 (“V1-“)
Output (24V) B4 (“Q2”)

SG value is higher than the high alarm level

  • The open collector output #3 will give a positive constant voltage when the SG is higher than the high alarm level. This voltage can be used to switch a relay contact that switches a valve or pump.
  • The output can be powered by the internal power on the main board. Add a second fuse after the power converter to the 24Vdc connector on the left bottom and wire this to the below-mentioned terminals on top of the HMI.
Wire Terminal on HMI Terminal on QM132
24Vdc+ A3 (“V1+”) Not yet available
24Vdc GND B3 (“V1-“)
Output (24V) A4 (“Q3”)

Solids Production pulse

  • This open collector output will give a positive pulse when 1-ton solids are produced.
  • This is only the case when the production shift is started.
  • When the production shift is started and the analyzer is restarted, the shift is started again, but the totals are reset to 0.
  • The output can be powered by the internal power on the main board. Add a second fuse after the power converter to the 24Vdc connector on the left bottom and wire this to the below-mentioned terminals on top of the HMI.
  • Set the pulse duration in steps of 10 ms in the IO Module settings, Digital IN/OUT.
Wire Terminal on HMI Terminal on QM132
24Vdc+ A3 (“V1+”) D1-2out COM
24Vdc GND B3 (“V1-“) D1-2out GND
Pulse (24V) B5 (“Q4”) Dout1

Analyzer fault

  • This open collector output will give a positive constant voltage when the analyzer is in fault mode. A fault mode is triggered when a measurement is not possible anymore. In general, this is the case when the analyzer cannot communicate with the transmitters.
  • This voltage can be used to switch a relay contact that switches a valve or pump.
  • The output can be powered by the internal power on the main board. Add a second fuse after the power converter to the 24Vdc connector on the left bottom and wire this to the below-mentioned terminals on top of the HMI.
Wire Terminal on HMI Terminal on QM132
24Vdc+ A3 (“V1+”) D1-2out COM
24Vdc GND B3 (“V1-“) D1-2out GND
Output (24V) A5 (“Q5”) Dout2

Open collector inputs

  • The 6 open collector inputs can be programmed to suit your application in process control. Currently, one collector input is used. As a standard, these are set to be sourced inputs (positive logic). Pre-wiring all these outputs will give the following schedule:
Wire Terminal on HMI
24Vdc+ Connect + to the positive side of your switch. Protect by fuse.
24Vdc GND D3 (IC1)
Free D2 (i2)
Input switch C3 (I3) Negative side of your switch. Take a sample of the

process by pressing this button for 0,5-9 secs. After 10 seconds, you can press again to indicate that sampling stopped. The logging file contains of ID of the sample.
Free| D4 (i4)
Free| C4 (i5)
Free| D5 (i6)
Free| C5 (i7)

Spool piece/wafer Installation

Mounting position

  • In the vertical pipe, mounting position is not relevant
  • In the horizontal pipe, a mounting position must be as in the picture:

mounting location

  • a. Mounting 7x diameter after last obstruction and 5x diameter before next obstruction (pump, bend, narrowing, valve)

Startup

  • Start-up and commissioning by unauthorized personnel is at their own risk.
  • During start-up, when the mA outputs are not connected, an error code is shown. Simply press the X to remove the error and it won’t show up anymore.

Correcting mA outputs

  • a) The mA output of the SG and the Density is not the same. To get these the same, follow the below instructions.
  • b) Press the SG box in the above picture, and the following menu will open with a prompt for a level 2 User ID and Password code in order to gain access.
  • c ) A tap on the User ID block will open the keypad. Type EL as the user ID and press enter.
  • d) The keypad will open again for the password. Type 07AF as the password and press enter, which will then take you back to the level 2 menu as above, but now indicating both the user ID (EL) and the password as.
  • e) Press OK, which will then open the Field Calibration menu below. Press > to go to the DO and AO settings:
  • f) Note that the range of 4-20 mA for the SG is here: 1..2 SG. And that the current mA output is 14,60. Now, go back to the main screen:
  • g) Press DENSITY
  • h) Make sure all settings are as above. Then Press > to go to the following screen.
  • i) The 4-20 mA value is 17,24 because the range is here 1000..1800 (while SG was 1..2). Change as follows:
  • j) Press save. The next screen will be shown:

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals