Arenal KWR-7QA03-921-20220321 Slurry Density Analyser Instruction Manual
- June 13, 2024
- Arenal
Table of Contents
Arenal KWR-7QA03-921-20220321 Slurry Density Analyser
Symbols and conventions
Mounting locations
inside canopy
Temperature | Operating: 0-50 degC; Storage: -10ºC to +60ºC |
---|---|
Relative humidity | 10-90% (non condensing) |
Mounting angle
Mounting to the wall
Remove the aluminum plates to mount the analyzer to the wall
Electrical cables installation
To connect the UDT to the analyser
Name in Analyser| Name in UDT| Explanation| Wire numbers| Wire
Colour
---|---|---|---|---
24VDC GND B- A+| 24VDC 0VDC B- A+| 24Vdc + 0 Vdc Modbus RTU Modbus RTU| 1
2
3
4
| Brown White Yellow
The power supply of the QA03-SDA
90-263 Vac
50-60 Hz
L N
mA wiring output
On LT4301TADAC display | Parameter | Terminal on HMI | Color |
---|
E1 – mA-1 common ground- E2 – mA-1 +
E3 – mA-2 common ground E4 – mA-2 +
| SG Temperature| D14 C15 D14 D15| Yellow Green White Brown
On QM132-IOM Module| Parameter| Terminal on QM132
---|---|---
mA-1 common ground- mA-1 +
mA-2 common ground mA-2 +
| SG
Temperature
| 25) Aout1 GND
26) Aout 1+
23) Aout2 GND
24) Aout 2+
mA wiring input
On LT4301TADAC display | Terminal on HMI |
---|---|
4-20 mA input + | D13 AND C12 (connect them together) |
4-20 mA input – | D12 |
On QM132-IOM Module | Terminal on QM132 |
--- | --- |
4-20 mA input 1+ | 1) Ain1+ |
4-20 mA input 1- | 2) Ain1 GND |
4-20 mA input 2+ | 3) Ain2+ |
4-20 mA input 2- | 4) Ain2 GND |
Open collector outputs
- The 6 open collector outputs can be programmed to suit your application in process control.
- Currently, three collector outputs have been used. As a standard, these are set to be sourced outputs (positive logic).
- Pre-wiring all these outputs will give the following schedule:
Wire | Terminal on HMI |
---|---|
24Vdc+ | A3 (“V1+”) |
24Vdc GND | B3 (“V1-“) |
Output (24V) | B4 (“Q2”) SG value is lower than the low alarm value |
Output (24V) | A4 (“Q3”) SG value is higher than the high alarm level |
Pulse (24V) | B5 (“Q4”) Solids Production pulse per ton |
Output (24V) | A5 (“Q5”) Analyzer fault |
Free | B6 (“Q6”) |
Free | A6 (“Q7”) |
Below is a description of each open collector:
- SG value is lower than the low alarm value
- This open collector output will give a positive constant voltage when the SG is lower than the low alarm level. This voltage can be used to switch a relay contact that switches a valve or pump.
- The output can be powered by the internal power on the main board. Add a second fuse after the power converter to the 24Vdc connector on the left bottom and wire this to the below-mentioned terminals on top of the HMI.
Wire | Terminal on HMI | Terminal on QM132 |
---|---|---|
24Vdc+ | A3 (“V1+”) | Not yet available |
24Vdc GND | B3 (“V1-“) | |
Output (24V) | B4 (“Q2”) |
SG value is higher than the high alarm level
- The open collector output #3 will give a positive constant voltage when the SG is higher than the high alarm level. This voltage can be used to switch a relay contact that switches a valve or pump.
- The output can be powered by the internal power on the main board. Add a second fuse after the power converter to the 24Vdc connector on the left bottom and wire this to the below-mentioned terminals on top of the HMI.
Wire | Terminal on HMI | Terminal on QM132 |
---|---|---|
24Vdc+ | A3 (“V1+”) | Not yet available |
24Vdc GND | B3 (“V1-“) | |
Output (24V) | A4 (“Q3”) |
Solids Production pulse
- This open collector output will give a positive pulse when 1-ton solids are produced.
- This is only the case when the production shift is started.
- When the production shift is started and the analyzer is restarted, the shift is started again, but the totals are reset to 0.
- The output can be powered by the internal power on the main board. Add a second fuse after the power converter to the 24Vdc connector on the left bottom and wire this to the below-mentioned terminals on top of the HMI.
- Set the pulse duration in steps of 10 ms in the IO Module settings, Digital IN/OUT.
Wire | Terminal on HMI | Terminal on QM132 |
---|---|---|
24Vdc+ | A3 (“V1+”) | D1-2out COM |
24Vdc GND | B3 (“V1-“) | D1-2out GND |
Pulse (24V) | B5 (“Q4”) | Dout1 |
Analyzer fault
- This open collector output will give a positive constant voltage when the analyzer is in fault mode. A fault mode is triggered when a measurement is not possible anymore. In general, this is the case when the analyzer cannot communicate with the transmitters.
- This voltage can be used to switch a relay contact that switches a valve or pump.
- The output can be powered by the internal power on the main board. Add a second fuse after the power converter to the 24Vdc connector on the left bottom and wire this to the below-mentioned terminals on top of the HMI.
Wire | Terminal on HMI | Terminal on QM132 |
---|---|---|
24Vdc+ | A3 (“V1+”) | D1-2out COM |
24Vdc GND | B3 (“V1-“) | D1-2out GND |
Output (24V) | A5 (“Q5”) | Dout2 |
Open collector inputs
- The 6 open collector inputs can be programmed to suit your application in process control. Currently, one collector input is used. As a standard, these are set to be sourced inputs (positive logic). Pre-wiring all these outputs will give the following schedule:
Wire | Terminal on HMI |
---|---|
24Vdc+ | Connect + to the positive side of your switch. Protect by fuse. |
24Vdc GND | D3 (IC1) |
Free | D2 (i2) |
Input switch | C3 (I3) Negative side of your switch. Take a sample of the |
process by pressing this button for 0,5-9 secs. After 10 seconds, you can
press again to indicate that sampling stopped. The logging file contains of ID
of the sample.
Free| D4 (i4)
Free| C4 (i5)
Free| D5 (i6)
Free| C5 (i7)
Spool piece/wafer Installation
Mounting position
- In the vertical pipe, mounting position is not relevant
- In the horizontal pipe, a mounting position must be as in the picture:
mounting location
- a. Mounting 7x diameter after last obstruction and 5x diameter before next obstruction (pump, bend, narrowing, valve)
Startup
- Start-up and commissioning by unauthorized personnel is at their own risk.
- During start-up, when the mA outputs are not connected, an error code is shown. Simply press the X to remove the error and it won’t show up anymore.
Correcting mA outputs
- a) The mA output of the SG and the Density is not the same. To get these the same, follow the below instructions.
- b) Press the SG box in the above picture, and the following menu will open with a prompt for a level 2 User ID and Password code in order to gain access.
- c ) A tap on the User ID block will open the keypad. Type EL as the user ID and press enter.
- d) The keypad will open again for the password. Type 07AF as the password and press enter, which will then take you back to the level 2 menu as above, but now indicating both the user ID (EL) and the password as.
- e) Press OK, which will then open the Field Calibration menu below. Press > to go to the DO and AO settings:
- f) Note that the range of 4-20 mA for the SG is here: 1..2 SG. And that the current mA output is 14,60. Now, go back to the main screen:
- g) Press DENSITY
- h) Make sure all settings are as above. Then Press > to go to the following screen.
- i) The 4-20 mA value is 17,24 because the range is here 1000..1800 (while SG was 1..2). Change as follows:
- j) Press save. The next screen will be shown:
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>