inVENTer iV-Twin+ Ventilation Device Instruction Manual

June 4, 2024
inVENTer

iV-Twin+ Ventilation Device

Installation instructions
iV-Twin+

Ventilation device
with heat recovery

www.inventer.eu

Trademarks, copyrights and industrial property rights
inVENTer®, Xenion®, inVENTron®, Inventin und Clust-Air® is a protected trademark of inVENTer GmbH.
The copyright to this document remains with the manufacturer. Rights to all content and images: © inVENTer GmbH 2022.
All trademarks used in this document are the property of their respective manufacturers and are hereby acknowledged.

Disclaimer
This documentation represents a translation of the original German installation instructions. It must be passed on to the user (tenant, owner, property management, etc.) after completion of the installation. The contents of this documentation have been checked for conformity with the hardware and software described. Nevertheless, deviations cannot be excluded, so that no guarantee can be given for complete conformity.
This documentation describes the functionality of the standard range. For reasons of clarity, the documentation does not contain all detailed information on all types of the product and cannot take into account every conceivable case of operation, installation and assembly.
The illustrations in this documentation may differ slightly from the design of the product you have purchased. The function remains the same despite the difference in detail.
This documentation is updated regularly. Necessary corrections and appropriate supplements are always included in subsequent editions. You can also find the latest version at www.inventer.eu/ downloads.

Company Information

Publisher:

inVENTer GmbH Ortsstraße 4a D-07751 Löberschütz Germany

Telefon: Fax: E-Mail: Web:

+49 (0) 36427 211-0 +49 (0) 36427 211-113 info@inventer.de www.inventer.eu

CEO: Annett Wettig VAT ID number: DE 815494982 Jena District Court HRB 510380

2

Ventilation device iV-Twin+ | Installation instructions

TaBLE OF CONTENTS
Table of contents
1 User and Safety instructions…………………………………………………………………………………….. 4 1.1 User information………………………………………………………………………………………………. 4 1.2 Safety instructions……………………………………………………………………………………………. 5
2 System overview iV-Compact ventilation device ……………………………………………………….. 8 2.1 Construction ……………………………………………………………………………………………………. 9 2.2 Functions………………………………………………………………………………………………………… 10 2.3 Control elements ……………………………………………………………………………………………… 12
3 Preparing for installation ………………………………………………………………………………………….. 14 3.1 Installation Position ………………………………………………………………………………………….. 14 3.2 Position of the wall opening ………………………………………………………………………………. 15 3.3 Dimensions …………………………………………………………………………………………………….. 15 3.4 Sectional drawings ventilation device …………………………………………………………………. 16 3.5 Dimensional drawings of the components …………………………………………………………… 17
4 Installation and assembly…………………………………………………………………………………………. 18 4.1 Check the scope of supply ………………………………………………………………………………… 18 4.2 Create wall opening …………………………………………………………………………………………. 19 4.3 Laying cables to the wall opening of the ventilation device ……………………………………. 20 4.4 Installing the wall sleeve …………………………………………………………………………………… 22 4.5 External termination Ventilation device Variante Standard montieren ……………………… 25 4.6 Inserting separating element……………………………………………………………………………… 27 4.7 Slide-in thermal accumulator(thermal accumulator and inVENTron Slim) ………………… 28 4.8 Insert Xenion reversible fan, connect and check functions…………………………………….. 30 4.9 Fitting the inner panel……………………………………………………………………………………….. 34
5 Technical Data …………………………………………………………………………………………………………. 35 5.1 General specifications………………………………………………………………………………………. 35 5.2 Specifications according to ErP Directive, Regulation 1254/2014 …………………………… 36 5.3 Specifications according to ErP Directive, Regulation 1254/2014 …………………………… 37
6 Scope of supply……………………………………………………………………………………………………….. 39
7 Troubleshooting ………………………………………………………………………………………………………. 40
8 Warranty and guarantee……………………………………………………………………………………………. 41
9 Service…………………………………………………………………………………………………………………….. 41

Ventilation device iV-Twin+ | Installation instructions

3

USER AND SAFETY INSTRUCTIONS

1 User and Safety instructions

Thank you for purchasing this high quality product from inVENTer!
This section provides an overview of the basic safety precautions for safe and proper operation of your ventilation system.

1.1 User information

Safety and warning instructions

The safety and warning instructions in these installation instructions have a uniform structure and are marked with a symbol on the left side of the instruction. A signal word in front of the text also indicates the hazard level. If several hazard levels occur, the safety note for the highest level is always used.

The safety instructions and warnings contain the following information:

SIGNAL WORD: Type and origin of the hazard. Possible consequences of the danger! · Measures to avoid hazard.

The signal word indicates the severity of the potential hazard unless the preventive measures are taken:

DANGER means: Imminent danger of serious injury or death.

WARNING means: Possible danger of serious injury or death.

CAUTION means: Direct danger or minor/significant injury.

NOTICE Means: Direct or possible risk of property damage due to an adverse event/state.

If you see these signs, follow the measures described to avoid possible danger and damage.

Other symbols used in this documentation

In addition to the safety and warning instructions, the following symbols are used:

i

A TIPsymbol indicates practical and useful tips for handing your ventilation device.

Additional tools and aids are required.

!

Red bar over a graphic: Illustration shows the outer wall.
Blue bar over a graphic: Illustration shows the outer wall.
Action required: This prompts the user to perform a specific action. Check results: Requires user to check results ofthe action performed. Action focus: To be taken into account in the corresponding assembly step.

4

Ventilation device iV-Twin+ | Installation instructions

USER AND SAFETY INSTRUCTIONS

1.2 Safety instructions
The operating instructions are part of your iV-Compact ventilation device and must be available at all times (see www.inventer.eu/downloads). Before carrying out any work on the system, read this documentation carefully and observe all the instructions for installation, commissioning and maintenance given in this chapter. In addition, observe the safety instructions that precede the instructions described. Failure to observe the safety instructions may result in personal injury and/or damage to property.
These installation instructions only cover the standard variant (referred to as the “Standard variant” in the following text) of the iV-Twin+ ventilation device. Information on the variants can be found in the separate installation instructions for the respective components.
Intented use
The ventilation device is used to ventilate living rooms, rooms similar to living rooms and other areas where people spend their time, e.g. living rooms and bedrooms, offices, basements and attics. It is controlled via a controller of the inVENTer system (also referred to as “controller” in the following text).
General information
· Observe the applicable standards, regulations and directives when carrying out work. In particular, also applicable building regulations, the fire protection ordinance and accident prevention regulations of the employers’ liability insurance association.
· Only use the device/system in accordance with the applications described in this documentation and only in conjunction with the components recommended and approved byinVENTer GmbH and specified in this documentation. Modifications or conversions to the unit/system are not permitted.
· Your ventilation device/system is exclusively designed for use in ambient temperatures between -20 and 50°C.
· Faultless and safe operation of the unit/system requires proper transport, storage and assembly as well as careful maintenance.
Installation and assembly
· CAUTION: The device may only be installed by qualified personel. · Before starting the work, you should have a project that shows the number of
ventilation units, the location of the ventilation units, the ventilation principle (cross ventilation, individual room ventilation, exhaust ventilation) and the associated controllers. The exact positioning of the individual units and control units must be checked on site and, if necessary, adapted to the conditions on site with the involvement of the responsible planner or the user. For optimal functioning, it is recommended that the unit be installed at an appropriate location in the upper wall area. · WARNING: For the joint operation of a ventilation unit with fireplaces, securing measures must be taken to prevent the occurrence of negative pressure in the building. The decision as to which measures should be carried out is made by the responsible chimney sweep and/or building planner. · NOTICE: The ventilation unit is not suitable for drying out buildings. Do not operate the device until all construction work has been completed.

Ventilation device iV-Twin+ | Installation instructions

5

USER AND SAFETY INSTRUCTIONS

· NOTICE: Contamination of components by e.g. plaster residues will damage the components! Seal the ventilation unit/air outlets of the ventilation unit dust-tight during the entire construction work. Do not remove any thread locks until final assembly.
· NOTICE: Do not install the unit near room air thermostats or in the immediate vicinity/above sensitive pictures or furniture.
· NOTICE: The construction of the ventilation unit has a separation of air volume flows in the wall sleeve. During and after installation, make sure that vertical air volume separation is installed at all times!
· NOTICE: Observe the specified minimum distances on both sides of the wall and frontally to avoid unintentional mixing of different air volume flows and to ensure access to the device and its components. A minimum distance of 1.2 m must be maintained between adjacent air openings. (, page 14 f.).
· NOTICE: The wall sleeve must be integrated into the building envelope (airtightness level) in accordance with the current state of the art, taking into account constructional and physical specifications (“RAL installation”). The material for this is to be provided by the customer.
· NOTICE: When bringing the wall construction up to the wall sleeve, observe the necessary blocking levels to avoid interrupting the composite thermal insulation system. If uncertain, consult your planner before installation!
· NOTICE: Install the wall sleeve with aslope of 1 – 2° to the outer wall to ensure that any condensation that may occur is drained off.
· NOTICE: The divce must not be used in locations where direct contact with splashing water is possible over a long period of time and/or the device is exposed to direct jets of water. Observe the specifications of VDE 0100 when selecting the installation location.
· NOTICE: Store components standing upright outside the wall sleeve and do not throw them to avoid damage and breakage of the components, especially the thermal accumulator.
· NOTICE: To prevent algae from settling around the outer closures, the installation instructions must be followed exactly (apply all sealing tapes!). We recommend a biocide pre-setting/water-repellent pre-treatment of the façade surface around the exterior finishes. Ask your planner about this!
· NOTICE: When mounting components in (exterior) walls with insulation, use insulation anchors to ensure secure fastening of the components. Insulation anchors are not included in the scope of delivery, they are optionally available!
· NOTICE: Use only permanently elastic sealing compound suitable for outdoor use to seal the joints at all outdoor terminations!
· NOTICE: The device has plastic surfaces that are sensitive to scratches. Do not touch components with oily and/or dirty hands. Avoid contact with sharp or pointed objects.
Electrical connection of the reversible fan
· DANGER: The device may only be installed by qualified personel.
· CAUTION: When using the ventilation device in protection area 1 according to VDE 0100, all plug connections must be positioned in the wall sleeve at the rear of the fan device.
· NOTICE: The ventilationdevice operates with protective extra-low voltage. It muss not be connected directly to the 230 Vpower supply system.
· NOTICE: Laying cables whose sheathing under plaster is not plaster-resistant leads to short circuits and cable fires! Lay cables without a plaster- resistant cable sheath in the empty conduit.
· NOTICE: The use of a too small cable cross-section leads to a too high voltage drop and/or the contacting is not guaranteed! Use a cable cross- section of at least 0,75 mm² (stranded wire) for the fan BUS. Use wire end ferrules with collars to connect the stranded wires.

6

Ventilation device iV-Twin+ | Installation instructions

USER AND SAFETY INSTRUCTIONS
· NOTICE:When using several ventilation units, controlled via several controllers, you must ensure that the ventilation units are synchronised with each other (see controller installation instructions). All controllers should be connected via a mains fuse in the house distribution board.
If your device has a defect, contact the factory representative responsible for you or our technical service.
Use contrary to the intended purpose leads to the exclusion of any liability claims.
Improper use
Any use that is not mentioned in the chapter Intended use is considered improper use.
Do not install/operate the equipment in areas where the following may enter or occur:
· Environment with high oil or grease content. · Flammable gases, liquids or vapours. · Extreme dust exposure. · Enviroment temperatures outside -20 ­ 50 °C · Obstacles preventing access to or removal of components of the ventilation device.
The ventilation device is not to be used as an opening to the outside and/or for the purpose of smoke discharge/smoke extraction in basements without windows.
Qualified personnel
The device/system may only be set up, operated and cleaned in conjunction with this documentation and the documentation for the controllers.
Assembly, electrical connection and initial commissioning of the device/system may only be carried out by qualified personnel. Qualified personnel in the sense of the safety instructions in this documentation are persons who are authorized to install, commission and label devices, systems and circuits in accordance with safety engineering standards.
Comformity
The ventilation device complies with the technical safety requirements and standards of electrical appliances for domestic use. It is compliant with applicable European Union and United Kingdom directives: The full text of the EU Declaration of Conformity is available at the following Internet address: https://www.inventer.eu/downloads/

Ventilation device iV-Twin+ | Installation instructions

7

SYSTEM OVERVIEW VENTILATION DEVICE IV-TWIN+

2 System overview Ventilation device iV-Twin+

The iV-Twin+ ventilation system was developed as a single room unit with heat recovery for separate ventilation of separate rooms or as a supplementary unit to existing ventilation devices. It is designed for the ventilation of living rooms and bedrooms in detached houses and apartment buildings, hotels and guesthouses, rooms in public facilities and workrooms in office buildings.

As a single room device, the iV-Twin+ does not require paired operation. The creation of a spatial connection through overflow measures is not necessary. The iV-Twin+ can therefore also be used in classic extract air rooms such as kitchens, utility rooms, bathrooms and bathrooms. It is
suitable for installation in new buildings as well as for retrofitting in old buildings. The installation is generally carried out in the outer wall.

A lockable inner panel discreetly covers the iV-Twin+ visually from the interior. In the outdoor area, a freely selectable cover conceals the components of the ventilation unit. The air volume
flow separators integrated into the inner panel and the outer cover ensure that there is no mixing of different air flows outside the wall sleeve.

The standard lenght of the separating element is 765mm.The standard length of the wall sleeve is 495 mm. For larger wall thicknesses, a wall sleeve with a length of 745 mm or 495 can be ordered. Both versions can be shortened on site.

The ventilation unit is controlled via one of the following controllers1) of the inVENTer system:

· Pure

· MZ-Home

· sMove

Components · Separating element for the wall sleeve · Wall sleeve · External termination · Pollen and activated carbon filter (optional) · Inner panel

· Half cylinder heat accumulator (2x) · Fan unit with dust filter class
ISO Coarse 45% (G3) and reversing fan Mini-Xenion (2x),
connecting cable

Models

The ventilation devices of the iV-Twin+ product series differ in their external terminations. This documentation only contains information on the standard version of the ventilation device. Information on the variants can be found in the separate installation instructions for the respective components.
· Standard variant: Ventilation device iV-Twin+ with driving rain-proof weather protection hood Flex Twin+, incl. air volume separation (white/grey/anthracite/special colour/nord).
· Corner variant: Ventilation device iV-Twin+ Corner (hereinafter referred to as the “Corner variant”) for integration of the external closure in the window reveal (white/grey/anthracite/special colour/ nord)
· Nordic variant: Ventilation device iV-Twin+ Nordic (in the further text “Variant Nordic”) for integration of the external closure in clinker brick walls (white/grey/anthracite/special colour/ north).

  1. The installation instructions for the controllers are not part of this documentation.

8

Ventilation device iV-Twin+ | Installation instructions

2.1 Construction C

SYSTEM OVERVIEW VENTILATION DEVICE IV-TWIN+
B A

D

14

98

18

10

12

11

17

15

13

16 Figure 1: iV-Twin+ ventilation device overview

5 6
7

4

180°

Standard variant:
1

3

2

Flex Twin+

Components

A External termination1):
Weather protection hood Flex
1 Weather protection hood base plate 2 Air volume flow separation
(pre-assembled) 3 Weather protection hood cover
B Wall sleeve
4 Wall sleeve R-D200 5 Interior wall mounting material 6 Recess fan BUS cable

C Thermal accumulator insert
(Thermal accumulator, fan unit)
7 Separator R-D200x765 8 Half cylinder heat accumulator (2x) 9 Thermal accumulator handle 10 Dust filter G3 (ISO Coarse 45%) (2x) 11 Half-cylinder fan unit with
Reversing fan Mini-Xenion (2x) 12 Knob fan unit (2x) 13 Plug fan Mini-Xenion (2x) 14 Connecting cable iV-Twin+
D Flair Twin+ inner panel

15 Inner panel base plate 16 Spacer (4 x) 17 Inner panel cover 18 Air volume separation

  1. The description of the components of all other possible external finishes can be found in the separate installation instructions of the respective external finish.

Ventilation device iV-Twin+ | Installation instructions

9

SYSTEM OVERVIEW VENTILATION DEVICE IV-TWIN+
2.2 Functions
Ventilation device iV-Twin+
The iV-Twin+ ventilation device is used to ensure the ventilation of living spaces. In addition, installation in classic extract air rooms is possible. The integrated heat accumulator ensures optimum heat recovery at maximum air volume flow.
As a single room device, the iV-Twin+ combines a supply air and extract air device in one. To ensure that the ventilation system functions correctly and that the pressure stability in the room is guaranteed, the supply air volume must correspond to the exhaust air volume at all times. A separating element vertically divides the wall sleeve into two airtight chambers. Each chamber contains a fan unit and a heat accumulator in half-cylinder geometry.
Due to a high pressure build-up and the active speed control of the motor (integrated wind pressure stabiliser) in the Mini-Xenion reversing fan, the air volume flow in the system is kept almost constant even in the event of pressure fluctuations caused by the weather.
In order to ensure the full functionality of the ventilation unit throughout the year, a temperature monitor is integrated in the Mini-Xenion reversing fan. This measures the temperature of the air flow at the fan. If the temperature at the fan falls below + 5 °C, the reversible fan is automatically switched to extract air mode for 4 cycles. This allows the thermal accumulator to heat up again and prevents cooling of the interior due to cold supply air. During this phase, the operating mode that has been set on the controller is ineffective. Subsequently, the controller switches the ventilation device back to the originally selected mode.
The most important components of the iV system are the ceramic thermal accumulator, the reversing fan, air guiding vanes for straightening the air volume flow, filters for different requirements, a closable inner panel and an outer cover. A control device (controller) completes the system.
The operation of the iV ventilation systems is intuitive with the matching inVENTer controllers. Different operating modes or air volume flows can be set individually. The iV-Twin+ must be equipped with its own sMove or Pure controller. It is also recommended to consider the MZ-Home Controller as a separate zone.
The iV-Twin+ ventilation unit can be installed in area 1 according to VDE 0100. It meets the requirements of protection class IPX4. Please note the different installation situations (chapter 4.8). If installed incorrectly, the requirement will not be met.
In rooms with humidity entry, it is suggested to install a separate hygrostat (sMove, Pure) or the humidity sensor (MZ-Home) in the room.

SYSTEM OVERVIEW VENTILATION DEVICE IV-TWIN+
Function of the iV-Twin+ in reverse mode In
70 s
Figure 2: Function of the iV-Twin+ in reverse mode The ventilation system works according to the principle of regenerative heat recovery. The integrated thermal accumulator is charged with the thermal energy of the room air as it flows externally (extract air). After 70 seconds, the reversing fan changes the direction of rotation each time. After the direction of rotation has changed, the heat accumulator releases the stored heat energy to the incoming fresh air (supply air). The two fans are each operated as a pair in push-pull mode: One reversing fan conveys supply air into the interior, while the other reversing fan conveys stale exhaust air out of the interior at the same time. Function of the iV-Twin+ in exhaust air mode
If the ventilation mode is selected on the controller, the iV-Twin+ ventilation unit operates in extract air mode. Both reversing fans are switched to extract air mode at the same time, i.e. both fans simultaneously convey used extract air from the interior to the outside. In this operating mode, there is no heat recovery. It is particularly recommended for the rapid removal of moisture and odour load peaks.
Figure 3: Function of the ventilation unit iV-Twin+ in extract air mode

10

Ventilation device iV-Twin+ | Installation instructions

Ventilation device iV-Twin+ | Installation instructions

11

SYSTEM OVERVIEW VENTILATION DEVICE IV-TWIN+

2.3 Control elements

The ventilation device is operated via a controller of the inVENTer system. Depending on the controller different operating modes and functions can be set.
Basic controls

Designation

Pure

sMove

Number of controllable ventilation devices
Multi-zone control

Max. 2 No

Operating concept

· Switch

s4: Max. 2 s8: Max. 4 No
· Touch

Operating modes Functions

· Heat recovery · Through-ventilation · OFF (standard version only)
· Pause-Function (1 h)

· Heat recovery · Through-ventilation · OFF (standard version only)
· Pause-Function (1……8 h) · Boost-Funktion (15 min)

Fan speed Unit communication External interface

3 Output levels, predefined
Cable
1 potential-free switching contact per control module: · Pressure switch (NC) · Other sensors (NO)

infinitely adjustable, 4 Output levels, predefined
Cable
1 potential-free switching contact per control controller: · Pressure switch (NC) · Other sensors (NO)

12

Ventilation device iV-Twin+ | Installation instructions

SYSTEM OVERVIEW VENTILATION DEVICE IV-TWIN+

Multi-zone control Designation

MZ-Home

ON 12

Number of controllable ventilation devices Multi-zone control Operating concept
Operating modes
Functions

Operating Unit & Clust-Air module
Max. 8 (excl. sensors)
max. 4 zones with ax. 2 devices [plus sensors] per zone
· Touch · Weekly timer
· Heat recovery · Through-ventilation · OFF
· Pause-Function (1…..8 h) (zonal) · Dehumidification with variable air volume flow

Fan speed Unit communication External interface

4 Output levels, freely selectable
Cable
1 potential-free switching contact per Clust-Air module (max. 4) · Pressure switch (NC/NO) · Other sensors (NO)

For detailed information, see the controller’s installation and operating instructions.

Ventilation device iV-Twin+ | Installation instructions

13

PREPARING FOR INSTALLATION
3 Preparing for installation
3.1 Installation Position
· The installation location can be derived from the positioning proposal of the ventilation planning. The exact positioning of the individual devices and control units must be checked by the customer and adjusted on site if necessary. Consult the responsible planner about this! For optimum function, it is recommended that the ventilation device is installed at an appropriate point in the upper wall area (e.g. 1.80 m UEFF [upper edge of finished floor]).
· Do not place the ventilation unit above radiators, room thermostats, sensitive furniture and/or pictures.
· The divce must not be used in locations where direct contact with splashing water is possible over a long period of time and/or the device is exposed to direct jets of water.
Minimum distances of the wall opening for the ventilation device:
· Minimum distances to components / building elements on the internal and external wall:
NOTICE: Malfunction due to incorrect positioning of the ventilation device. · Note insulation thickness and possible shutters! · Do not install near radiators! · Observe minimum distance of 1.2 m to adjecent air openings!

A

1,2 m
B

1,0 m 1,4 m

1,0 m

C
1,2 m ­ 0,75 y
y

1 between two ventilation units in a room to avoid mixing different air volume flows: 2 to adjacent components on the outer wall (observe insulation thickness/roller shutter):
upwards: 450 mm from centre axis wall opening/wall installation system Simplex downwards/sideways: 250 mm from centre axis wall opening/wall installation system Simplex

3 to adjacent building components on the inner wall: 250 mm from opening center.

4 to frontally adjacent building components:

300 mm for cleaning work.

5 between a weather protection hood and another ventilation system: 1.2 m

14

Ventilation device iV-Twin+ | Installation instructions

PREPARING FOR INSTALLATION
3.2 Position of the wall opening External termination Ventilation device Variante Standard montieren

Ø225

250

5

1

250

5

148

148

1

249

4

4

2

165

165

3 279 Position wall opening

3

260

2

279

Position wall installation system Simplex

Figure 4: Dimensioned drawing wall opening iV-Twin+ (interior view)

1 Wall opening (Fig. 4, left) Wall installation system Simplex (Fig. 4, right)
2 Contour Weather Protection Hood3) 3 Soffit

4 Door-/Window frame 5 Bottom edge of lintel4)

  1. Minimum distance to adjacent components on the inner wall (from centre axis) 3)Fit weather protection hood at lintel level 2) Minimum distance to adjacent building components on the outer wall 4) Consider insulation thickness and possible shutters

3.3 Dimensions
Designation Wall thickness1) Wall opening for wall sleeve Wall sleeve R-D200x495 (745 / 745) Weather protection hood Flex Twin+ Flair Twin+ V-233×233 inner panel

Depth/ Lenght [mm] > 270

Wide [mm] High [mm] ­

Wall thickness1)

Ø225

495 ­ 745

Ø200

23 ­ 88

279

313

233

233

  1. Standard variant: with exterior rendering, insulation, brickwork and interior rendering 2) open

Ventilation device iV-Twin+ | Installation instructions

15

PREPARING FOR INSTALLATION

3.4 Sectional drawings ventilation device

For sectional drawings of other variants of your ventilation unit, see the installation instructions for your specific external termination.

Schnittzeichnung Ventilation device iV-Twin+, Standard variant

10

9

10

11

1

Ø200 233

8

2

279

6 7

250 89

5

4

3

270

61

D

C

B

A

Figure 5: Sectional drawings ventilation device iV-Twin+ (Top view)

A Interior plaster/ interior structure B Masonry

C Insulation D Exterior plaster

1 Inner panel base plate 2 Separating element Flair Twin+ inner
panel (pre-assembled) 3 Inner panel panel 4 Separating element Flair Twin+ inner
panel (pre-assembled) 5 Wall sleeve R-D200 6 Separating element for the wall sleeve

7 Weather protection hood Flex Twin+ 8 Separating element weather protection
hood Flex Twin+(pre-assembled) 9 Half cylinder heat accumulator 10 Dust filter ISO Coarse 45% (G3)
(Part of the fan unit)
11 Fan unit half cylinder

16

Ventilation device iV-Twin+ | Installation instructions

3.5 Dimensional drawings of the components Flair Twin+ inner panel
A 7
6

PREPARING FOR INSTALLATION

A – A

3

1

5 UP

2

215 313
148

5

A

215

233

4 3 4xØ4,8

Figure 6: Dimensional drawing Flair Twin+ V-233×233 inner panel

4 61

1 Inner panel panel 2 Separating element (pre-assembled) 3 Spacer (4 x) 4 Inner panel base plate

5 Marking arrow
6 Interior wall fixing borehole 7 optional: Fixing hole outer wallØ 6 mm,
min 40 mm deep (4x)

Weather protection hood Flex Twin+

23

4 x Ø4,8

1

21

7

313

252

194,5

2 6
8 Weather prote27c9tion hood cover

Ø200

2

6

5

7

4

3

89

194,5

Weather protection hoo2d21base plate

Figure 7: Dimensional drawing weather protection hood Flex Twin+

1 Weather protection hood base plate 2 Separating element (pre-assembled) 3 Fixing hole outer wall (4 x)
Ø 8 mm, min. 50 mm deep (4 x) 4 Simplex mounting hole (4 x)

5 Sealing strip guide 6 Weather protection hood cover 7 Protective grid 8 Drip edge top

Ventilation device iV-Twin+ | Installation instructions

17

INSTALLATION AND ASSEMBLY

4 Installation and assembly

i

Read this chapter carefully before installation to avoid installation errors. The installtion and connection of the ventilation device must be carried out by qualfied personnel.

4.1 Check the scope of supply
Check the delivery for completeness and transport damage upon receipt, using the delivery note. Report missing items immediately.
These assembly instructions describe the standard version of the product. The scope of delivery of the wall sleeves for integrating the Connect controller platform, as well as the interior termination variants, can be found in the separately available installation instructions for the respective system component.

1a 2

1b 1c

4x

11 External termination

1 a: Cover WSH1) Flex-Twin+

4x

1e

1 b: Baseplate WSH1) Flex-Twin+

1 c: Separating element Flex

4x

Twin+(pre-assembled)

1d: Sealing strip guide

1d

1 e: Interior wall mounting material

The Flex-Twin+ weather protection hood

is available in different colours and ma-

terials (stainless steel / aluminium [with

increased salt resistance]), must be

2a

ordered according to the desired colour

and texture.

3a 4 18

2d 4a

2b 2c 3b
3c 3d
4b
4x

22 Wall sleeve R-D200 2 a: Styrofoam discs 2 b: Mounting wedges set 2 c: Recess for fan cable 2 d: Interior wall mounting material
33 Thermal accumulator iV-Twin+ 3 a: Separating element 3 b: Half cylinder heat accumulator 3 c: Half cylinder fan unit 3 d: Connecting cable iV-Twin+
44 Inner panel Flair iV-Twin+ 4 a: Inner panel base plate
4c 4 b: Cover inner panel with divider (pre-assembled) 4 c: Interior wall mounting material

  1. WSH: Weather protection hood
    Ventilation device iV-Twin+ | Installation instructions

INSTALLATION AND ASSEMBLY
4.2 Create wall opening
CAUTION: Falling masonry when creating the wall opening can lead to physical injuries and /or damage to property! · Install protection against falling masonry on building exterior. · Remove objects from the inmediate vicinity of the building´s exterior.
In new buildings/constructions we recommend the use of the optional Simplex D200 wall mounting system, D230 wall block, or Woodplex for timber post and beam construction.
Observe the minimum distances and the installation position of the ventilation device. If uncertain, consult your planner before installation!
Create the wall opening through core drilling Drill with core drill attachment or milling drill Ø 225 mm,

Ø 225

Requirements: · The masonry must be dry and in a load-bearing
condition. · No load-bearing elements in the position of the drill
hole.
Insert wall sleeve with a slope of 1 – 2° to the outer
! wall. The wall sleeve must have a slope of 1 ­ 2° to the exterior wall side. Alternatively the drilling can be carried through with a slope.
The wall opening for the ventilation device has been created.

Ventilation device iV-Twin+ | Installation instructions

19

INSTALLATION AND ASSEMBLY
4.3 Laying cables to the wall opening of the ventilation device
CAUTION: Exposed electrical components. Electric shock and injury due to live components (16 V DC)! · Installation and connection must only be carried out by qualified and trained personnel.
Once the wall opening has been created, the cables necessary for operating the ventilation system are laid to the wall opening for the ventilation device. They connect the valve gate of the ventilation device with the control components and thus establish the signal transmission and/or voltage transmission between controller and Mini-Xenion reversing fan.

NOTICE: Cables to the wall opening of the ventilation device

not laid. No connection of the reversible fan possible!

Routing of the cables to the wall opeing of the ventilationdevice

must be done in this installtion step. Laying the connection cables

between the sMove/ Pure/ MZ-Home controllers and the Mini-Xe-

45°

nion reversing fan is not part of this documentation. For more

information, see the installation instructions of each contoller.

Cable to the ventilation device wall opening
The following cables, depending on the control device, are laid to the wall opening for the ventialation device:

Pure sMove MZ-Home

Use

Cable type

Operating volatge fan Stranded cable

and

6 ­ 16 V DC,

device communication e.g.: LiYY 3×0.75 mm²

Cable origin
Pure control module
sMove operating device
Clust-Air module CAM17 in the ventilation zone

INSTALLATION AND ASSEMBLY

Principle diagrams for cable laying
The corresponding connection diagrams and assembly steps for installing the controller are not part of this documentation! They can be found in the installation instructions of the respective control unit (Pure, sMove, MZ- Home).

Regler Pure, sMove and MZ-Home

6 ­ 16 V DC, 230 V AC

One after the other:

Cable Type LiYY, 3-wire, wire cross-section 0.75 mm² length see controller

Switch power supply unit
Star shaped:

Control device:
Pure: Control module sMove: Operating device MZ-Home: Clust-Air module

Ventilation devices 1)

Cable Type LiYY, 3-wire, wire cross-section 0.75 mm² length 33 mm max.

Ventilation devices 1)

Switch power supply unit

Control device:
Pure: Control module sMove: Operating device MZ-Home: Clust-Air module

Terminal blocks

  1. 4 ventilation devices only possible with sMove s8

20

Ventilation device iV-Twin+ | Installation instructions

Ventilation device iV-Twin+ | Installation instructions

21

INSTALLATION AND ASSEMBLY

4.4 Installing the wall sleeve

Measuring tape, angle grinder, spirit level, non-pressing 2K polyurethane foam, cutter, mounting wedge set and styrofoam discs.

Requirements: · The wall opening Ø 225 mm is finished. · The fan BUS is laid.

DC B

Y

X = ?

A

Determine the exact thickness X:

D = Exterior rendering, incl. other superstructures if

applicable.

C = Insulation, if necessary inl. air gap (optional)

B = Masonry, incl. relining if necessary.

A = Interior plaster.

Y = Protrusion of the

wall sleeve in the outer area (depending on the

installation situation exterior rendering or masonry)

External termination
Standard variant: Corner

Inner panel

X in [mm] =
Flex Twin+
A + B + C + D A + B

A + B

Nordic

double-skin Masonry (clinker)
single-skin Masonry (ETICS)

A + B A + B

Y in [mm] =
10 10
(for installation directly on the masonry)
UBP + 10
(for installation with substructure panel UBP)
C + D – 200
(min. 30 mm)
C + D – 95
(min. 30 mm)

X + Y

Cut the wall sleeve to the determined dimension X + a protrusion of Y on the exterior wall. Be careful not to cut away the cut-out for
! the fan connecting cable.
File the edges.

12 h 9 h
3 h 6 h
1 ­ 2°

INSTALLATION AND ASSEMBLY
Remove the styrofoam discs from the wall sleeve.
Insert the wall sleeve into the wall opening so it is flush with the interior wall. Note the thickness of the plaster.
The recess for the connection cables is
! located on the interior wall side and near the cables laid to the wall opening.
Guide all connecting cables through the cut-out in the wall sleeve.
NOTICE: Anaccumulation of condensation-water in the wallsleeve. Damage to the exterior wall and masonry and the building structure! · Insert wall sleeve with a slope of
1 – 2° to the outer wall.
Attach the wall sleeve inside and outside with the mounting wedges so that there is a slope of 1 ­ 2° to the exterior wall.
Check the angle of the wall sleeve using a spirit level.
NOTICE: Contamination of components by e.g. plaster residues will damage the components of the wall sleeve! · Before foaming the free space between
the wall sleeve and the masonry, insert the Styrofoam discs. · Do not remove the thread locks of the fastening elements until the inner panel is fitted.
Align the two lateral fastening elements of the wall sleeve horizontally.

22

Ventilation device iV-Twin+ | Installation instructions

Ventilation device iV-Twin+ | Installation instructions

23

INSTALLATION AND ASSEMBLY
24 h
24

Insert the styrofoam discs into the wall sleeve from the inside and outside. NOTICE: Interruption of the thermal insulation composite system. Damage to the building structure! · During installation, replace the wall structure as far as the wall sleeve and if necessary guide the housing (flush-mounted inner covers) towards it. · Observe the necessary barrier levels.
Foam-seal the gap between teh wall sleeve and masonry all the way around with non-pressing 2K polyurethane foam.
Cut off the excess, hardened assembly foam and protruding assembly wedges as follows: · Flush with the inner wall · Flush with the outer wall
! Make sure not to damage the connecting cable on the interior wall.
The wall sleeve set is installed.
Ventilation device iV-Twin+ | Installation instructions

INSTALLATION AND ASSEMBLY

4.5 Installing the external termination Standard variant

The assembly of any exterior termination variants is not part of this documentation! It can be found in the installation instructions of the respective external closure.

NOTICE Installing on an unfinished exterior wall leads to damage to the exterior wall! · Only install the external termination once the exterior wall is finished and fully dried .

NOTICE Penetration of condensation water and/or algae accumulation around the weather protection hood leads to damage to the masonry/exterior wall and/or discolouration of the façade! · Secure all sealing tapes on the weather protection hood circumferentially before installing the
external termination. · Before installation, carry out a biocidal pre- treatment/ water-repellent pre-treatment of the
surface around the external termiantion (consult your planner regarding this!)

Installing the external weather protection hood

Spirit level, pencil, power drill with Ø 8mm drill bit, cordless screwdriver, wall anchors (wallplugs for insulation for insulated exterior walls), permanently elastic external sealant, sealing tape, screws
Requirements: · The exterior wall is completed and even. · The wall sleeve set is installed.

Remove the styrofoam disc on the outside wall side from the wall sleeve.

Simplex

Slide the base plate onto the projecting wall sleeve.
! The protective grille is directed towards the floor.

Level the base plate inner panel with a spirit level.

ø 8 mm

Mark the four drill holes: Outer holes (blue arrow) Masonry. Inner holes (green arrow) Simplex.

Drill the four holes Ø 8 mm, min 50 mm deep

Ventilation device iV-Twin+ | Installation instructions

25

INSTALLATION AND ASSEMBLY 4 x
26

i

TIP: Do not apply the sealing tape until inmediately before installing the base plate. This

prevents the sealing tape from swelling too

much and makes installation easier.

Attach the sealing tape, 9 mm, outside wall side and circumferentially along the guide on the base plate.
! Do not seal the fixing holes!

Insert the wall anchors into the boreholes.

Screw the base plate weather protection hood into the wall anchors with 4 screws.

i

TIP: Use insulation dowels for fastening when attaching the base plate to external walls with

insulation or when using the wall installation

block/wall installation system Simplex. These

are not included in the scope of supply, they

are available as an option.

NOTICE: By wrong sealing of the joint between the base plate and the outer wall the cover cannot be put on. · Seal only the upper joint between the base
plate and the outer wall.

Seal only the upper joint between the base plate and the outer wall.
Place the panel on the four spacers. Engage the panel downwards
! The guides on the cover hook behind the base plate.

The weather protection hood Flex Twin+ is installed.

Ventilation device iV-Twin+ | Installation instructions

INSTALLATION AND ASSEMBLY

4.6 Inserting separating element

NOTICE: IF the separating element is not positioned in the wall sleeve or is positioned incorrectly, there is a possibility of mixing different air volume flows! · A separating element vertically divides the wall sleeve into two airtight chambers. · Push the separating element into the separating bar of the weather protection hood!

Measuring tape, blade knife

Requirements: · The weather protection hood is installed.
Remove the styrofoam discs from the wall sleeve.

L = ?

L + 20

Shorten the partition element to the length of the wall sleeve + 20 mm.
NOTICE: Wrong/ No positioning of the separator element leads to mixing of different air volume flows in the system! · Position the wider sealing lip (red arrow)
on the separating element at the bottom of the wall sleeve. · Push the separating element completely into the wall sleeve and the separating insert of the weather protection hood!

Ventilation device iV-Twin+ | Installation instructions

Slide the power supply unit in the mounting socket.
! Push the separating element into the weather protection hood.
! The partition element has an inner wall projection of about 10 mm. The separator is pushed in.
27

INSTALLATION AND ASSEMBLY
4.7 Insert the heat accumulator, shorten the fan BUS, strip the insulation and connect it to the iV-Twin+ connection cable.
NOTICE Do not store/stack the thermal accumulator insert outside the wall sleeve as doing so will damage the thermal accumulator’s ceramic. · Insert the thermal accumulator immediately after removing it from the packaging.
Side cutters, stripping tool, connection cable (scope of delivery)
Requirements: · The weather protection hood is installed. · The separator is pushed in.
Slide the thermal accumulator half cylinders each to the right and left of the separating element from the interior as far as they will go in the direction of the weather protection hood.
! · The handles face the interior. · The connecting cables protrude into the interior. The thermal accumulator insert has been installed.

1

2

1 Shorten the fan BUS, 3-wire, to your determined wall thickness minus 260mm, but at least to 150mm.
2 Strip approx. 7 mm of insulation from the cables on the fan BUS.
Connect the fan BUS with the iV-Twin+ connection cable.

INSTALLATION AND ASSEMBLY
NOTICE: · Ensure the correct sequence of the wire colours so that the fans start.
(IV) (III) (V)

DIR2 (V) VOUT+ (IV) DIR1 (III)

Attach the three fan BUS cables in the free pole of the corresponding connection terminal according to the following table (do not use wire end ferrules):

Fan BUS (cable coming from the controller)

Connecting cable

Terminal block

Definition

Colour

Terminal block

Definition

Colour

DIR1 (III) Signal direction 1 White DIR1 (III) Signal direction 1 Yellow / Pink

VOUT+ (IV) Operating voltage Green VOUT+ (IV) Operating voltage Green / Rot

DIR2 (V) Signal direction 2 Brown DIR2 (V) Signal direction 2 Brown / Blue

The iV-Twin+ connection cable is connected to the fan BUS.

28

Ventilation device iV-Twin+ | Installation instructions

Ventilation device iV-Twin+ | Installation instructions

29

INSTALLATION AND ASSEMBLY
4.8 Insert Xenion reversible fan, connect and check functions
The mounting of the conversier fans varies depending on the place of use: · Use in protection zone 2 and higher (standard) · Use in protection zone 1 (IPX4)
Use in protection zone 2 and higher (standard)
Requirements: · Die Thermal accumulator sind in die Wall sleeve
eingeschoben. · The iV-Twin+ connection cable is connected to the
fan BUS. Slide the heat storage half cylinders each to the
right and left of the separating element from the interior as far as they will go in the direction of the
! weather protection hood. ! · The filters are directed towards the heat
accumulator.
! · The finger guards face towards the interior. · The plug-in connections can be reached.
Push both fan units up to the heat accumulators respectively.
Both fan units are mounted.
Pass one of the cables on the fan under the sealing lip so that all cables are on the side with the fan BUS.

i
CHECK:

INSTALLATION AND ASSEMBLY
NOTICE: Incorrect electrical connection will damage the fan motor! · Always connect the ventilation device to
the mains supply via a controller.
Insert the plugs of the cables on the fan into the sockets of the iV-Twin+ connection cable.
i TIP:The plugs are not assigned to the sockets and can be plugged together as desired.
Place the cable in the wall sleeve.
The fan units are connected to the controller
Check that the fans start up and move. In heat recovery mode, the fans move in opposite directions.

30

Ventilation device iV-Twin+ | Installation instructions

Ventilation device iV-Twin+ | Installation instructions

31

INSTALLATION AND ASSEMBLY
Use in protection zone 1 (IPX4) CAUTION: INcorrect positioning of the cables and plug connections leads to personal injury and/or short-circuiting of the fans! · Position all plug connections behind the fan unit to ensure IPX4 protection requirements.

Requirements: · The thermal accumulator are positioned in the wall
sleeve. · The iV-Twin+ connection cable is connected to the
fan BUS.
Insert a fan unit into the side of the wall sleeve where the fan BUS is not located.
! · The filter is directed towards the heat accumulator.
! · The finger guard faces the interior. · The fan unit is only pushed in so far that it is flush with the inner wall.
! · The plug-in connections can be reached.
Guide the cable with the plug connection over the upper sealing lip to the side with the fan BUS. To do this, press the separating element slightly downwards.
NOTICE: Incorrect electrical connection will damage the fan motor! · Always connect the ventilation device to
the mains supply via a controller.

Insert the plug of the cable on the fan into a socket of the iV-Twin+ connection cable.

Insert the plug of the cable on the fan of the second fan unit into the second socket of the iV-Twin+ connection cable.

i

TIP: The plugs are not assigned to the sockets

and can be plugged together as desired.

INSTALLATION AND ASSEMBLY

The cables and plug connections are pushed into the wall sleeve and thus placed between the heat storage unit and the fan unit.

Slide the second fan unit into the still free side of the wall sleeve (the side where the fan BUS is located).

! · The filter is directed towards the heat accumulator.

! · The finger guard faces the interior. · The fan unit is only pushed in so far

!

that it is flush with the inner wall (no cable visible).

CHECK:

The fan is connected to the controller.
Check that the fans start up and move. In heat recovery mode, the fans move in opposite directions.

32

Ventilation device iV-Twin+ | Installation instructions

Ventilation device iV-Twin+ | Installation instructions

33

INSTALLATION AND ASSEMBLY

4.9 Fitting the inner panel
The installation of the inner panel is illustrated using the example of the fan units used in protection zone 2 and higher. If the fan units are installed for use in protection zone 1 (close flush with the wall sleeve), the inner cover is installed in the same way.

Spirit level, pencil, screwdriver

Requirements: · The thermal accumulator insert has been installed. · The reversing fans are connected.

Remove the thread locks from the fastening elements of the wall sleeve.
Place the base plate inner panel centric to the wall sleeve on the inner wall.
! · The position arrow on the base plate points upwards.

Screw the base plate weather protection hood into the wall anchors with 4 screws.
Place the panel on the four spacers.
! · The position arrows on the back of the inner panel cover point upwards.
! · Check: The inVENTer logo is located at the bottom right.
! · The separating element is inserted into the receptacle of the inner panel.
4x CLICK
The inner panel is fitted.

TECHNICAL DATA

5 Technical Data
5.1 General specifications
Feature Operating range [°C] Extract air/outdoor air Flow rate in reversed mode [m³/h] Extract airflow [m³/h] (EN 13141-8) Sound pressure level, distance 2 m [dB (A)] Standard sound level difference [dB] Thermal efficiency of heat recovery (‘w) Input voltage [V DC] Power consumption [W] Volume flow-related electr. Specific fan power input [W/(m³/h)] Protection class (EN 61140) Protection class (EN 60529) Standard filter class
ISO 16890 EN 779: 2012 Frost protection
Comformity
Energy efficiency class (SEC class)

Value -20 ­ 50 Without aggresive gases, dust and oils 5 ­ 23 10 ­ 45 14 ­ 38 Standard variant: 45 ­ 56 0.94 6 ­ 16 0.5 ­ 3 0.18 III IPX4
ISO Coarse 45% G3 Automatic by reversing operation (down to -20 °C)
A+ / A

34

Ventilation device iV-Twin+ | Installation instructions

Ventilation device iV-Twin+ | Installation instructions

35

TECHNICAL DATA
5.2 Specifications according to ErP Directive, Regulation 1254/2014
On the energy label you will find the following information from the product data sheet: · Energy efficiency class (SEC class) · Sound power level Lwa · Maximum air flow (supply air)

iV-Twin+ iV-Twin+ Corner iV-Twin+ Nordic

Demand controlled
Pure with sensor sMove with sensor
MZ-Home

Manually controlled
Pure without sensor sMove without sensor

A+

A+

A

A

B

C

D

E

F

G

46

23 m3/h

dB (A)

ENERGIA · · · ENERGIJA · ENERGY · ENERGIE · ENERGI

2016

1254/2014

36

Ventilation device iV-Twin+ | Installation instructions

TECHNICAL DATA

5.3 Specifications according to ErP Directive, Regulation 1254/2014

iV-Twin+ ventilation device, demand controlled

iV-Twin+ product data sheet according to VO 1254/2014 EU dated 11 July 2014

Pt. Description a Supplier

b Model identifier

cold

c

EC class / Specific Energy Consumption (SEC) [kWh/(m²a)]

average

warm

d Ventilation type

e Type of drive

f

Type of heat recovery system

g Degree of temperature change t [%]

h Maximum air flow rate [m³/h]

i

Electrical input power (incl. control) [W]

j

Sound power level Lwa [dB (A)]

k

Reference air flow [m³/h]

l

Reference pressure difference [Pa]

m SEL [W/m³/h]

n Control factor

o Internal and external transfer [%]

p Mixing quota [%]

q

Position and description of the indicator for filter change

Instructions regarding controllable supply and extract

r

air grilles on the façade

(uni-directional ventilation devices only)

s Internet address

t

Sensitivity to pressure changes [%]

u Airtightness between interior and exterior [m³/h]

v

Annual power consumption [kWh/(m²a)]

cold

w

Annual savings Heating energy [kWh/(m²a)]

average

warm

Values

inVENTer GmbH

iV-Twin+ iV-Twin+ Corner iV-Twin+ Nordic

-90.439

A+

-44.95

-18.89

BVU

2

regenerative

94

23

3

46

16.1

0

0.18

0.65

1.8

0.6

Control device

none
www.inventer.eu 44.5 3.2 1.05 93.06 47.57 21.51

Ventilation device iV-Twin+ | Installation instructions

37

TECHNICAL DATA

Manually controlled

iV-Twin+ product data sheet according to VO 1254/2014 EU dated 11 July 2014

Pt. Description a Supplier

b Model identifier

cold

c

EC class / Specific Energy Consumption (SEC) [kWh/(m²a)]

average

warm

d Ventilation type

e Type of drive

f

Type of heat recovery system

g Degree of temperature change t [%]

h Maximum air flow rate [m³/h]

i

Electrical input power (incl. control) [W]

j

Sound power level Lwa [dB (A)]

k Reference air flow [m³/h]

l

Reference pressure difference [Pa]

m SEL [W/m³/h]

n Control factor

o Internal and external transfer [%]

p Mixing quota [%]

q

Position and description of the indicator for filter change

Instructions regarding controllable supply and extract

r

air grilles on the façade

(uni-directional ventilation devices only)

s Internet address

t

Sensitivity to pressure changes [%]

u Airtightness between interior and exterior [m³/h]

v Annual power consumption [kWh/(m²a)]

cold

w

Annual savings Heating energy [kWh/(m²a)]

average

warm

Values

inVENTer GmbH

iV-Twin+ iV-Twin+ Corner iV-Twin+ Nordic

-85.346

A

-40.596

-14.96

BVU

2

regenerative

94

23

3

46

16.1

0

0.18

1

1.8

0.6

Control device

none
www.inventer.eu 44.5 3.2 2.48 91.55 46.80 21.16

38

Ventilation device iV-Twin+ | Installation instructions

SCOPE OF SUPPLY

6 Scope of supply

Standard components
All standard components are also available as spare parts. Further accessories and spare parts can be found in the separate accessories overview. Contact your local distributor to order components for your ventilation system.

Component

Product Number

iV-Twin+

1001-0203

iV-Twin+ Corner

1001-0238

iV-Twin+ Nordic

1001-0232

External termination: Weather protection hood incl. sealing tapes

Weather protection Compact, white RAL 9016

1508-0113 | 1508-01491)

Weather protection Compact, grey RAL 9006

1508-0114 | 1508-01471)

Weather protection Compact, grey RAL 7011

1508-0115

Weather protection Compact, anthracite RAL 7016

1508-0128 | 1508-01481)

Weather protection Compact, anthracite RAL 7016

1508-0116 | 1508-01551)

Wall sleeve with Styrofoam discs and mounting wedges

Wall sleeve R-D200x495

1506-0070

Wall sleeve R-D200x745

1506-0071

Thermal accumulator insert
Thermal accumulator insert iV-Twin+ [incl. Separating element 765 mm] Inner panel

1507-0023

Flair Twin+ V-233×233 inner panel, white

1505-0040

  1. Variant special: consisting of aluminium, with increased salt resistance

Ventilation device iV-Twin+ | Installation instructions

39

TROUBLESHOOTING

7 Troubleshooting

Troubleshooting

Fault

Possible cause

Remedy

Fan failure Fan does not switch off. Low flow rate
Noises Supply air is cold

No electrical power.
Installation error.
Fan defective. Controller/power supply defective. Faulty controller.
Panel closed. Dust filter heavily soiled
Pollen filter/activated carbon filter used.
The rotational speed of the fan is too low. Thermal accumulator soiled.
Foreign body in the fan
Thermal accumulatoris not correctly positioned in the wall sleeve. The rotational speed of the fan is very high.
Installation error.

Check fuse. Check wiring for correct polarity. Check all connectors for correct fit. Check the use of wire ferrules. Replace fan.
Switching controller/ power supply.
Replace controller.
Open panel. Clean/replace dust filter. Pollen or activated charcoal filter reduces the air volume flow. Only use filters during load periods. Replace the filter if it is heavily soiled.
Increase the output level.
Clean thermal accumulator. Remove foreign body from the fan. Clean the ventilation device. Slide the thermal accumulator out of the wall sleeve. Insert it again. Slide the thermal accumulator into the wall sleeve as far as the end-stop tape. Set a lower output level on the controller. Check the connector plug on the controller. The connector plug must be sitting firmly in the connector housing.

40

Ventilation device iV-Twin+ | Installation instructions

WARRANTY AND GUARANTEE
8 Warranty and guarantee
Warranty The warranty covers all defects that were present at the time of purchase. Observe the intended use in order to maintain the warranty claim. Outside Germany, the national warranty regulations of the country in which the system is sold apply. Contact the dealer of your home country. Guarantee: inVENTer GmbH gives a 5-year guarantee on all electronic components and the wall sleeve, as well as a 30-year guarantee on the ceramics of the thermal heat accumulator. This covers premature product wear. Warranty and guarantee claim For information on the guarantee provisions, see www.inventer.eu/garantie/guarantee. In the event of a warranty or guarantee claim, contact the dealer or factory representative responsible for you. In any case, send the complete unit back to the manufacturer. The warranty claim is an additional offer by the manufacturer and does not affect applicable law in any way.
9 Service
Complaints Check the delivery for completeness and transport damage upon receipt, using the delivery note. Report any missing items immediately, or at the latest within 14 days, to your supplier, dealer or factory representative. Accesories and spare parts To order components for your ventilation unit, contact your dealer or factory representative. Technical customer service: For technical advice, please contact our technical service staff:
+49 (0) 36427 211-333 service@inventer.de

Ventilation device iV-Twin+ | Installation instructions

41

inVENTer GmbH Ortsstraße 4a D-07751 Löberschütz www.inventer.eu
Subject to modifications No liability for printing errors
Product Number 5001-00XX Version: 1.0 ­ 09/2022