iV-Twin+ Ventilation Device
Installation instructions
iV-Twin+
Ventilation device
with heat recovery
www.inventer.eu
Trademarks, copyrights and industrial property rights
inVENTer®, Xenion®, inVENTron®, Inventin und Clust-Air® is a protected
trademark of inVENTer GmbH.
The copyright to this document remains with the manufacturer. Rights to all
content and images: © inVENTer GmbH 2022.
All trademarks used in this document are the property of their respective
manufacturers and are hereby acknowledged.
Disclaimer
This documentation represents a translation of the original German
installation instructions. It must be passed on to the user (tenant, owner,
property management, etc.) after completion of the installation. The contents
of this documentation have been checked for conformity with the hardware and
software described. Nevertheless, deviations cannot be excluded, so that no
guarantee can be given for complete conformity.
This documentation describes the functionality of the standard range. For
reasons of clarity, the documentation does not contain all detailed
information on all types of the product and cannot take into account every
conceivable case of operation, installation and assembly.
The illustrations in this documentation may differ slightly from the design of
the product you have purchased. The function remains the same despite the
difference in detail.
This documentation is updated regularly. Necessary corrections and appropriate
supplements are always included in subsequent editions. You can also find the
latest version at www.inventer.eu/ downloads.
Company Information
Publisher:
inVENTer GmbH Ortsstraße 4a D-07751 Löberschütz Germany
Telefon: Fax: E-Mail: Web:
+49 (0) 36427 211-0 +49 (0) 36427 211-113 info@inventer.de www.inventer.eu
CEO: Annett Wettig VAT ID number: DE 815494982 Jena District Court HRB 510380
2
Ventilation device iV-Twin+ | Installation instructions
TaBLE OF CONTENTS
Table of contents
1 User and Safety instructions…………………………………………………………………………………….. 4 1.1 User
information………………………………………………………………………………………………. 4 1.2 Safety
instructions……………………………………………………………………………………………. 5
2 System overview iV-Compact ventilation device ……………………………………………………….. 8 2.1
Construction ……………………………………………………………………………………………………. 9 2.2
Functions………………………………………………………………………………………………………… 10 2.3 Control elements
……………………………………………………………………………………………… 12
3 Preparing for installation ………………………………………………………………………………………….. 14 3.1
Installation Position ………………………………………………………………………………………….. 14 3.2 Position of
the wall opening ………………………………………………………………………………. 15 3.3 Dimensions
…………………………………………………………………………………………………….. 15 3.4 Sectional drawings ventilation
device …………………………………………………………………. 16 3.5 Dimensional drawings of the
components …………………………………………………………… 17
4 Installation and assembly…………………………………………………………………………………………. 18 4.1 Check
the scope of supply ………………………………………………………………………………… 18 4.2 Create wall opening
…………………………………………………………………………………………. 19 4.3 Laying cables to the wall opening
of the ventilation device ……………………………………. 20 4.4 Installing the wall sleeve
…………………………………………………………………………………… 22 4.5 External termination Ventilation
device Variante Standard montieren ……………………… 25 4.6 Inserting separating
element……………………………………………………………………………… 27 4.7 Slide-in thermal
accumulator(thermal accumulator and inVENTron Slim) ………………… 28 4.8 Insert
Xenion reversible fan, connect and check functions…………………………………….. 30 4.9
Fitting the inner panel……………………………………………………………………………………….. 34
5 Technical Data …………………………………………………………………………………………………………. 35 5.1 General
specifications………………………………………………………………………………………. 35 5.2 Specifications
according to ErP Directive, Regulation 1254/2014 …………………………… 36 5.3
Specifications according to ErP Directive, Regulation 1254/2014 …………………………… 37
6 Scope of supply……………………………………………………………………………………………………….. 39
7 Troubleshooting ………………………………………………………………………………………………………. 40
8 Warranty and guarantee……………………………………………………………………………………………. 41
9 Service…………………………………………………………………………………………………………………….. 41
Ventilation device iV-Twin+ | Installation instructions
3
USER AND SAFETY INSTRUCTIONS
1 User and Safety instructions
Thank you for purchasing this high quality product from inVENTer!
This section provides an overview of the basic safety precautions for safe and
proper operation of your ventilation system.
1.1 User information
Safety and warning instructions
The safety and warning instructions in these installation instructions have a uniform structure and are marked with a symbol on the left side of the instruction. A signal word in front of the text also indicates the hazard level. If several hazard levels occur, the safety note for the highest level is always used.
The safety instructions and warnings contain the following information:
SIGNAL WORD: Type and origin of the hazard. Possible consequences of the danger! · Measures to avoid hazard.
The signal word indicates the severity of the potential hazard unless the preventive measures are taken:
DANGER means: Imminent danger of serious injury or death.
WARNING means: Possible danger of serious injury or death.
CAUTION means: Direct danger or minor/significant injury.
NOTICE Means: Direct or possible risk of property damage due to an adverse event/state.
If you see these signs, follow the measures described to avoid possible danger and damage.
Other symbols used in this documentation
In addition to the safety and warning instructions, the following symbols are used:
i
A TIPsymbol indicates practical and useful tips for handing your ventilation device.
Additional tools and aids are required.
!
Red bar over a graphic: Illustration shows the outer wall.
Blue bar over a graphic: Illustration shows the outer wall.
Action required: This prompts the user to perform a specific action. Check
results: Requires user to check results ofthe action performed. Action focus:
To be taken into account in the corresponding assembly step.
4
Ventilation device iV-Twin+ | Installation instructions
USER AND SAFETY INSTRUCTIONS
1.2 Safety instructions
The operating instructions are part of your iV-Compact ventilation device and
must be available at all times (see www.inventer.eu/downloads). Before
carrying out any work on the system, read this documentation carefully and
observe all the instructions for installation, commissioning and maintenance
given in this chapter. In addition, observe the safety instructions that
precede the instructions described. Failure to observe the safety instructions
may result in personal injury and/or damage to property.
These installation instructions only cover the standard variant (referred to
as the “Standard variant” in the following text) of the iV-Twin+ ventilation
device. Information on the variants can be found in the separate installation
instructions for the respective components.
Intented use
The ventilation device is used to ventilate living rooms, rooms similar to
living rooms and other areas where people spend their time, e.g. living rooms
and bedrooms, offices, basements and attics. It is controlled via a controller
of the inVENTer system (also referred to as “controller” in the following
text).
General information
· Observe the applicable standards, regulations and directives when carrying
out work. In particular, also applicable building regulations, the fire
protection ordinance and accident prevention regulations of the employers’
liability insurance association.
· Only use the device/system in accordance with the applications described in
this documentation and only in conjunction with the components recommended and
approved byinVENTer GmbH and specified in this documentation. Modifications or
conversions to the unit/system are not permitted.
· Your ventilation device/system is exclusively designed for use in ambient
temperatures between -20 and 50°C.
· Faultless and safe operation of the unit/system requires proper transport,
storage and assembly as well as careful maintenance.
Installation and assembly
· CAUTION: The device may only be installed by qualified personel. · Before
starting the work, you should have a project that shows the number of
ventilation units, the location of the ventilation units, the ventilation
principle (cross ventilation, individual room ventilation, exhaust
ventilation) and the associated controllers. The exact positioning of the
individual units and control units must be checked on site and, if necessary,
adapted to the conditions on site with the involvement of the responsible
planner or the user. For optimal functioning, it is recommended that the unit
be installed at an appropriate location in the upper wall area. · WARNING: For
the joint operation of a ventilation unit with fireplaces, securing measures
must be taken to prevent the occurrence of negative pressure in the building.
The decision as to which measures should be carried out is made by the
responsible chimney sweep and/or building planner. · NOTICE: The ventilation
unit is not suitable for drying out buildings. Do not operate the device until
all construction work has been completed.
Ventilation device iV-Twin+ | Installation instructions
5
USER AND SAFETY INSTRUCTIONS
· NOTICE: Contamination of components by e.g. plaster residues will damage the
components! Seal the ventilation unit/air outlets of the ventilation unit
dust-tight during the entire construction work. Do not remove any thread locks
until final assembly.
· NOTICE: Do not install the unit near room air thermostats or in the
immediate vicinity/above sensitive pictures or furniture.
· NOTICE: The construction of the ventilation unit has a separation of air
volume flows in the wall sleeve. During and after installation, make sure that
vertical air volume separation is installed at all times!
· NOTICE: Observe the specified minimum distances on both sides of the wall
and frontally to avoid unintentional mixing of different air volume flows and
to ensure access to the device and its components. A minimum distance of 1.2 m
must be maintained between adjacent air openings. (, page 14 f.).
· NOTICE: The wall sleeve must be integrated into the building envelope
(airtightness level) in accordance with the current state of the art, taking
into account constructional and physical specifications (“RAL installation”).
The material for this is to be provided by the customer.
· NOTICE: When bringing the wall construction up to the wall sleeve, observe
the necessary blocking levels to avoid interrupting the composite thermal
insulation system. If uncertain, consult your planner before installation!
· NOTICE: Install the wall sleeve with aslope of 1 – 2° to the outer wall to
ensure that any condensation that may occur is drained off.
· NOTICE: The divce must not be used in locations where direct contact with
splashing water is possible over a long period of time and/or the device is
exposed to direct jets of water. Observe the specifications of VDE 0100 when
selecting the installation location.
· NOTICE: Store components standing upright outside the wall sleeve and do not
throw them to avoid damage and breakage of the components, especially the
thermal accumulator.
· NOTICE: To prevent algae from settling around the outer closures, the
installation instructions must be followed exactly (apply all sealing tapes!).
We recommend a biocide pre-setting/water-repellent pre-treatment of the façade
surface around the exterior finishes. Ask your planner about this!
· NOTICE: When mounting components in (exterior) walls with insulation, use
insulation anchors to ensure secure fastening of the components. Insulation
anchors are not included in the scope of delivery, they are optionally
available!
· NOTICE: Use only permanently elastic sealing compound suitable for outdoor
use to seal the joints at all outdoor terminations!
· NOTICE: The device has plastic surfaces that are sensitive to scratches. Do
not touch components with oily and/or dirty hands. Avoid contact with sharp or
pointed objects.
Electrical connection of the reversible fan
· DANGER: The device may only be installed by qualified personel.
· CAUTION: When using the ventilation device in protection area 1 according to
VDE 0100, all plug connections must be positioned in the wall sleeve at the
rear of the fan device.
· NOTICE: The ventilationdevice operates with protective extra-low voltage. It
muss not be connected directly to the 230 Vpower supply system.
· NOTICE: Laying cables whose sheathing under plaster is not plaster-resistant
leads to short circuits and cable fires! Lay cables without a plaster-
resistant cable sheath in the empty conduit.
· NOTICE: The use of a too small cable cross-section leads to a too high
voltage drop and/or the contacting is not guaranteed! Use a cable cross-
section of at least 0,75 mm² (stranded wire) for the fan BUS. Use wire end
ferrules with collars to connect the stranded wires.
6
Ventilation device iV-Twin+ | Installation instructions
USER AND SAFETY INSTRUCTIONS
· NOTICE:When using several ventilation units, controlled via several
controllers, you must ensure that the ventilation units are synchronised with
each other (see controller installation instructions). All controllers should
be connected via a mains fuse in the house distribution board.
If your device has a defect, contact the factory representative responsible
for you or our technical service.
Use contrary to the intended purpose leads to the exclusion of any liability
claims.
Improper use
Any use that is not mentioned in the chapter Intended use is considered
improper use.
Do not install/operate the equipment in areas where the following may enter or
occur:
· Environment with high oil or grease content. · Flammable gases, liquids or
vapours. · Extreme dust exposure. · Enviroment temperatures outside -20 50
°C · Obstacles preventing access to or removal of components of the
ventilation device.
The ventilation device is not to be used as an opening to the outside and/or
for the purpose of smoke discharge/smoke extraction in basements without
windows.
Qualified personnel
The device/system may only be set up, operated and cleaned in conjunction with
this documentation and the documentation for the controllers.
Assembly, electrical connection and initial commissioning of the device/system
may only be carried out by qualified personnel. Qualified personnel in the
sense of the safety instructions in this documentation are persons who are
authorized to install, commission and label devices, systems and circuits in
accordance with safety engineering standards.
Comformity
The ventilation device complies with the technical safety requirements and
standards of electrical appliances for domestic use. It is compliant with
applicable European Union and United Kingdom directives: The full text of the
EU Declaration of Conformity is available at the following Internet address:
https://www.inventer.eu/downloads/
Ventilation device iV-Twin+ | Installation instructions
7
SYSTEM OVERVIEW VENTILATION DEVICE IV-TWIN+
2 System overview Ventilation device iV-Twin+
The iV-Twin+ ventilation system was developed as a single room unit with heat recovery for separate ventilation of separate rooms or as a supplementary unit to existing ventilation devices. It is designed for the ventilation of living rooms and bedrooms in detached houses and apartment buildings, hotels and guesthouses, rooms in public facilities and workrooms in office buildings.
As a single room device, the iV-Twin+ does not require paired operation. The
creation of a spatial connection through overflow measures is not necessary.
The iV-Twin+ can therefore also be used in classic extract air rooms such as
kitchens, utility rooms, bathrooms and bathrooms. It is
suitable for installation in new buildings as well as for retrofitting in old
buildings. The installation is generally carried out in the outer wall.
A lockable inner panel discreetly covers the iV-Twin+ visually from the
interior. In the outdoor area, a freely selectable cover conceals the
components of the ventilation unit. The air volume
flow separators integrated into the inner panel and the outer cover ensure
that there is no mixing of different air flows outside the wall sleeve.
The standard lenght of the separating element is 765mm.The standard length of the wall sleeve is 495 mm. For larger wall thicknesses, a wall sleeve with a length of 745 mm or 495 can be ordered. Both versions can be shortened on site.
The ventilation unit is controlled via one of the following controllers1) of the inVENTer system:
· Pure
· MZ-Home
· sMove
Components · Separating element for the wall sleeve · Wall sleeve · External termination · Pollen and activated carbon filter (optional) · Inner panel
· Half cylinder heat accumulator (2x) · Fan unit with dust filter class
ISO Coarse 45% (G3) and reversing fan Mini-Xenion (2x),
connecting cable
Models
The ventilation devices of the iV-Twin+ product series differ in their
external terminations. This documentation only contains information on the
standard version of the ventilation device. Information on the variants can be
found in the separate installation instructions for the respective components.
· Standard variant: Ventilation device iV-Twin+ with driving rain-proof
weather protection hood Flex Twin+, incl. air volume separation
(white/grey/anthracite/special colour/nord).
· Corner variant: Ventilation device iV-Twin+ Corner (hereinafter referred to
as the “Corner variant”) for integration of the external closure in the window
reveal (white/grey/anthracite/special colour/ nord)
· Nordic variant: Ventilation device iV-Twin+ Nordic (in the further text
“Variant Nordic”) for integration of the external closure in clinker brick
walls (white/grey/anthracite/special colour/ north).
- The installation instructions for the controllers are not part of this documentation.
8
Ventilation device iV-Twin+ | Installation instructions
2.1 Construction C
SYSTEM OVERVIEW VENTILATION DEVICE IV-TWIN+
B A
D
14
98
18
10
12
11
17
15
13
16 Figure 1: iV-Twin+ ventilation device overview
5 6
7
4
180°
Standard variant:
1
3
2
Flex Twin+
Components
A External termination1):
Weather protection hood Flex
1 Weather protection hood base plate 2 Air volume flow separation
(pre-assembled) 3 Weather protection hood cover
B Wall sleeve
4 Wall sleeve R-D200 5 Interior wall mounting material 6 Recess fan BUS cable
C Thermal accumulator insert
(Thermal accumulator, fan unit)
7 Separator R-D200x765 8 Half cylinder heat accumulator (2x) 9 Thermal
accumulator handle 10 Dust filter G3 (ISO Coarse 45%) (2x) 11 Half-cylinder
fan unit with
Reversing fan Mini-Xenion (2x) 12 Knob fan unit (2x) 13 Plug fan Mini-Xenion
(2x) 14 Connecting cable iV-Twin+
D Flair Twin+ inner panel
15 Inner panel base plate 16 Spacer (4 x) 17 Inner panel cover 18 Air volume separation
- The description of the components of all other possible external finishes can be found in the separate installation instructions of the respective external finish.
Ventilation device iV-Twin+ | Installation instructions
9
SYSTEM OVERVIEW VENTILATION DEVICE IV-TWIN+
2.2 Functions
Ventilation device iV-Twin+
The iV-Twin+ ventilation device is used to ensure the ventilation of living
spaces. In addition, installation in classic extract air rooms is possible.
The integrated heat accumulator ensures optimum heat recovery at maximum air
volume flow.
As a single room device, the iV-Twin+ combines a supply air and extract air
device in one. To ensure that the ventilation system functions correctly and
that the pressure stability in the room is guaranteed, the supply air volume
must correspond to the exhaust air volume at all times. A separating element
vertically divides the wall sleeve into two airtight chambers. Each chamber
contains a fan unit and a heat accumulator in half-cylinder geometry.
Due to a high pressure build-up and the active speed control of the motor
(integrated wind pressure stabiliser) in the Mini-Xenion reversing fan, the
air volume flow in the system is kept almost constant even in the event of
pressure fluctuations caused by the weather.
In order to ensure the full functionality of the ventilation unit throughout
the year, a temperature monitor is integrated in the Mini-Xenion reversing
fan. This measures the temperature of the air flow at the fan. If the
temperature at the fan falls below + 5 °C, the reversible fan is automatically
switched to extract air mode for 4 cycles. This allows the thermal accumulator
to heat up again and prevents cooling of the interior due to cold supply air.
During this phase, the operating mode that has been set on the controller is
ineffective. Subsequently, the controller switches the ventilation device back
to the originally selected mode.
The most important components of the iV system are the ceramic thermal
accumulator, the reversing fan, air guiding vanes for straightening the air
volume flow, filters for different requirements, a closable inner panel and an
outer cover. A control device (controller) completes the system.
The operation of the iV ventilation systems is intuitive with the matching
inVENTer controllers. Different operating modes or air volume flows can be set
individually. The iV-Twin+ must be equipped with its own sMove or Pure
controller. It is also recommended to consider the MZ-Home Controller as a
separate zone.
The iV-Twin+ ventilation unit can be installed in area 1 according to VDE
0100. It meets the requirements of protection class IPX4. Please note the
different installation situations (chapter 4.8). If installed incorrectly, the
requirement will not be met.
In rooms with humidity entry, it is suggested to install a separate hygrostat
(sMove, Pure) or the humidity sensor (MZ-Home) in the room.
SYSTEM OVERVIEW VENTILATION DEVICE IV-TWIN+
Function of the iV-Twin+ in reverse mode In
70 s
Figure 2: Function of the iV-Twin+ in reverse mode The ventilation system
works according to the principle of regenerative heat recovery. The integrated
thermal accumulator is charged with the thermal energy of the room air as it
flows externally (extract air). After 70 seconds, the reversing fan changes
the direction of rotation each time. After the direction of rotation has
changed, the heat accumulator releases the stored heat energy to the incoming
fresh air (supply air). The two fans are each operated as a pair in push-pull
mode: One reversing fan conveys supply air into the interior, while the other
reversing fan conveys stale exhaust air out of the interior at the same time.
Function of the iV-Twin+ in exhaust air mode
If the ventilation mode is selected on the controller, the iV-Twin+
ventilation unit operates in extract air mode. Both reversing fans are
switched to extract air mode at the same time, i.e. both fans simultaneously
convey used extract air from the interior to the outside. In this operating
mode, there is no heat recovery. It is particularly recommended for the rapid
removal of moisture and odour load peaks.
Figure 3: Function of the ventilation unit iV-Twin+ in extract air mode
10
Ventilation device iV-Twin+ | Installation instructions
Ventilation device iV-Twin+ | Installation instructions
11
SYSTEM OVERVIEW VENTILATION DEVICE IV-TWIN+
2.3 Control elements
The ventilation device is operated via a controller of the inVENTer system.
Depending on the controller different operating modes and functions can be
set.
Basic controls
Designation
Pure
sMove
Number of controllable ventilation devices
Multi-zone control
Max. 2 No
Operating concept
· Switch
s4: Max. 2 s8: Max. 4 No
· Touch
Operating modes Functions
· Heat recovery · Through-ventilation · OFF (standard version only)
· Pause-Function (1 h)
· Heat recovery · Through-ventilation · OFF (standard version only)
· Pause-Function (1……8 h) · Boost-Funktion (15 min)
Fan speed Unit communication External interface
3 Output levels, predefined
Cable
1 potential-free switching contact per control module: · Pressure switch (NC)
· Other sensors (NO)
infinitely adjustable, 4 Output levels, predefined
Cable
1 potential-free switching contact per control controller: · Pressure switch
(NC) · Other sensors (NO)
12
Ventilation device iV-Twin+ | Installation instructions
SYSTEM OVERVIEW VENTILATION DEVICE IV-TWIN+
Multi-zone control Designation
MZ-Home
ON 12
Number of controllable ventilation devices Multi-zone control Operating
concept
Operating modes
Functions
Operating Unit & Clust-Air module
Max. 8 (excl. sensors)
max. 4 zones with ax. 2 devices [plus sensors] per zone
· Touch · Weekly timer
· Heat recovery · Through-ventilation · OFF
· Pause-Function (1…..8 h) (zonal) · Dehumidification with variable air volume
flow
Fan speed Unit communication External interface
4 Output levels, freely selectable
Cable
1 potential-free switching contact per Clust-Air module (max. 4) · Pressure
switch (NC/NO) · Other sensors (NO)
For detailed information, see the controller’s installation and operating instructions.
Ventilation device iV-Twin+ | Installation instructions
13
PREPARING FOR INSTALLATION
3 Preparing for installation
3.1 Installation Position
· The installation location can be derived from the positioning proposal of
the ventilation planning. The exact positioning of the individual devices and
control units must be checked by the customer and adjusted on site if
necessary. Consult the responsible planner about this! For optimum function,
it is recommended that the ventilation device is installed at an appropriate
point in the upper wall area (e.g. 1.80 m UEFF [upper edge of finished
floor]).
· Do not place the ventilation unit above radiators, room thermostats,
sensitive furniture and/or pictures.
· The divce must not be used in locations where direct contact with splashing
water is possible over a long period of time and/or the device is exposed to
direct jets of water.
Minimum distances of the wall opening for the ventilation device:
· Minimum distances to components / building elements on the internal and
external wall:
NOTICE: Malfunction due to incorrect positioning of the ventilation device. ·
Note insulation thickness and possible shutters! · Do not install near
radiators! · Observe minimum distance of 1.2 m to adjecent air openings!
A
1,2 m
B
1,0 m 1,4 m
1,0 m
C
1,2 m 0,75 y
y
1 between two ventilation units in a room to avoid mixing different air volume
flows: 2 to adjacent components on the outer wall (observe insulation
thickness/roller shutter):
upwards: 450 mm from centre axis wall opening/wall installation system Simplex
downwards/sideways: 250 mm from centre axis wall opening/wall installation
system Simplex
3 to adjacent building components on the inner wall: 250 mm from opening center.
4 to frontally adjacent building components:
300 mm for cleaning work.
5 between a weather protection hood and another ventilation system: 1.2 m
14
Ventilation device iV-Twin+ | Installation instructions
PREPARING FOR INSTALLATION
3.2 Position of the wall opening External termination Ventilation device
Variante Standard montieren
Ø225
250
5
1
250
5
148
148
1
249
4
4
2
165
165
3 279 Position wall opening
3
260
2
279
Position wall installation system Simplex
Figure 4: Dimensioned drawing wall opening iV-Twin+ (interior view)
1 Wall opening (Fig. 4, left) Wall installation system Simplex (Fig. 4, right)
2 Contour Weather Protection Hood3) 3 Soffit
4 Door-/Window frame 5 Bottom edge of lintel4)
- Minimum distance to adjacent components on the inner wall (from centre axis) 3)Fit weather protection hood at lintel level 2) Minimum distance to adjacent building components on the outer wall 4) Consider insulation thickness and possible shutters
3.3 Dimensions
Designation Wall thickness1) Wall opening for wall sleeve Wall sleeve
R-D200x495 (745 / 745) Weather protection hood Flex Twin+ Flair Twin+
V-233×233 inner panel
Depth/ Lenght [mm] > 270
Wide [mm] High [mm]
Wall thickness1)
Ø225
495 745
Ø200
23 88
279
313
233
233
- Standard variant: with exterior rendering, insulation, brickwork and interior rendering 2) open
Ventilation device iV-Twin+ | Installation instructions
15
PREPARING FOR INSTALLATION
3.4 Sectional drawings ventilation device
For sectional drawings of other variants of your ventilation unit, see the installation instructions for your specific external termination.
Schnittzeichnung Ventilation device iV-Twin+, Standard variant
10
9
10
11
1
Ø200 233
8
2
279
6 7
250 89
5
4
3
270
61
D
C
B
A
Figure 5: Sectional drawings ventilation device iV-Twin+ (Top view)
A Interior plaster/ interior structure B Masonry
C Insulation D Exterior plaster
1 Inner panel base plate 2 Separating element Flair Twin+ inner
panel (pre-assembled) 3 Inner panel panel 4 Separating element Flair Twin+
inner
panel (pre-assembled) 5 Wall sleeve R-D200 6 Separating element for the wall
sleeve
7 Weather protection hood Flex Twin+ 8 Separating element weather protection
hood Flex Twin+(pre-assembled) 9 Half cylinder heat accumulator 10 Dust filter
ISO Coarse 45% (G3)
(Part of the fan unit)
11 Fan unit half cylinder
16
Ventilation device iV-Twin+ | Installation instructions
3.5 Dimensional drawings of the components Flair Twin+ inner panel
A 7
6
PREPARING FOR INSTALLATION
A – A
3
1
5 UP
2
215 313
148
5
A
215
233
4 3 4xØ4,8
Figure 6: Dimensional drawing Flair Twin+ V-233×233 inner panel
4 61
1 Inner panel panel 2 Separating element (pre-assembled) 3 Spacer (4 x) 4 Inner panel base plate
5 Marking arrow
6 Interior wall fixing borehole 7 optional: Fixing hole outer wallØ 6 mm,
min 40 mm deep (4x)
Weather protection hood Flex Twin+
23
4 x Ø4,8
1
21
7
313
252
194,5
2 6
8 Weather prote27c9tion hood cover
Ø200
2
6
5
7
4
3
89
194,5
Weather protection hoo2d21base plate
Figure 7: Dimensional drawing weather protection hood Flex Twin+
1 Weather protection hood base plate 2 Separating element (pre-assembled) 3
Fixing hole outer wall (4 x)
Ø 8 mm, min. 50 mm deep (4 x) 4 Simplex mounting hole (4 x)
5 Sealing strip guide 6 Weather protection hood cover 7 Protective grid 8 Drip edge top
Ventilation device iV-Twin+ | Installation instructions
17
INSTALLATION AND ASSEMBLY
4 Installation and assembly
i
Read this chapter carefully before installation to avoid installation errors. The installtion and connection of the ventilation device must be carried out by qualfied personnel.
4.1 Check the scope of supply
Check the delivery for completeness and transport damage upon receipt, using
the delivery note. Report missing items immediately.
These assembly instructions describe the standard version of the product. The
scope of delivery of the wall sleeves for integrating the Connect controller
platform, as well as the interior termination variants, can be found in the
separately available installation instructions for the respective system
component.
1a 2
1b 1c
4x
11 External termination
1 a: Cover WSH1) Flex-Twin+
4x
1e
1 b: Baseplate WSH1) Flex-Twin+
1 c: Separating element Flex
4x
Twin+(pre-assembled)
1d: Sealing strip guide
1d
1 e: Interior wall mounting material
The Flex-Twin+ weather protection hood
is available in different colours and ma-
terials (stainless steel / aluminium [with
increased salt resistance]), must be
2a
ordered according to the desired colour
and texture.
3a 4 18
2d 4a
2b 2c 3b
3c 3d
4b
4x
22 Wall sleeve R-D200 2 a: Styrofoam discs 2 b: Mounting wedges set 2 c:
Recess for fan cable 2 d: Interior wall mounting material
33 Thermal accumulator iV-Twin+ 3 a: Separating element 3 b: Half cylinder
heat accumulator 3 c: Half cylinder fan unit 3 d: Connecting cable iV-Twin+
44 Inner panel Flair iV-Twin+ 4 a: Inner panel base plate
4c 4 b: Cover inner panel with divider (pre-assembled) 4 c: Interior wall
mounting material
- WSH: Weather protection hood
Ventilation device iV-Twin+ | Installation instructions
INSTALLATION AND ASSEMBLY
4.2 Create wall opening
CAUTION: Falling masonry when creating the wall opening can lead to physical
injuries and /or damage to property! · Install protection against falling
masonry on building exterior. · Remove objects from the inmediate vicinity of
the building´s exterior.
In new buildings/constructions we recommend the use of the optional Simplex
D200 wall mounting system, D230 wall block, or Woodplex for timber post and
beam construction.
Observe the minimum distances and the installation position of the ventilation
device. If uncertain, consult your planner before installation!
Create the wall opening through core drilling Drill with core drill attachment
or milling drill Ø 225 mm,
Ø 225
Requirements: · The masonry must be dry and in a load-bearing
condition. · No load-bearing elements in the position of the drill
hole.
Insert wall sleeve with a slope of 1 – 2° to the outer
! wall. The wall sleeve must have a slope of 1 2° to the exterior wall side.
Alternatively the drilling can be carried through with a slope.
The wall opening for the ventilation device has been created.
Ventilation device iV-Twin+ | Installation instructions
19
INSTALLATION AND ASSEMBLY
4.3 Laying cables to the wall opening of the ventilation device
CAUTION: Exposed electrical components. Electric shock and injury due to live
components (16 V DC)! · Installation and connection must only be carried out
by qualified and trained personnel.
Once the wall opening has been created, the cables necessary for operating the
ventilation system are laid to the wall opening for the ventilation device.
They connect the valve gate of the ventilation device with the control
components and thus establish the signal transmission and/or voltage
transmission between controller and Mini-Xenion reversing fan.
NOTICE: Cables to the wall opening of the ventilation device
not laid. No connection of the reversible fan possible!
Routing of the cables to the wall opeing of the ventilationdevice
must be done in this installtion step. Laying the connection cables
between the sMove/ Pure/ MZ-Home controllers and the Mini-Xe-
45°
nion reversing fan is not part of this documentation. For more
information, see the installation instructions of each contoller.
Cable to the ventilation device wall opening
The following cables, depending on the control device, are laid to the wall
opening for the ventialation device:
Pure sMove MZ-Home
Use
Cable type
Operating volatge fan Stranded cable
and
6 16 V DC,
device communication e.g.: LiYY 3×0.75 mm²
Cable origin
Pure control module
sMove operating device
Clust-Air module CAM17 in the ventilation zone
INSTALLATION AND ASSEMBLY
Principle diagrams for cable laying
The corresponding connection diagrams and assembly steps for installing the
controller are not part of this documentation! They can be found in the
installation instructions of the respective control unit (Pure, sMove, MZ-
Home).
Regler Pure, sMove and MZ-Home
6 16 V DC, 230 V AC
One after the other:
Cable Type LiYY, 3-wire, wire cross-section 0.75 mm² length see controller
Switch power supply unit
Star shaped:
Control device:
Pure: Control module sMove: Operating device MZ-Home: Clust-Air module
Ventilation devices 1)
Cable Type LiYY, 3-wire, wire cross-section 0.75 mm² length 33 mm max.
Ventilation devices 1)
Switch power supply unit
Control device:
Pure: Control module sMove: Operating device MZ-Home: Clust-Air module
Terminal blocks
- 4 ventilation devices only possible with sMove s8
20
Ventilation device iV-Twin+ | Installation instructions
Ventilation device iV-Twin+ | Installation instructions
21
INSTALLATION AND ASSEMBLY
4.4 Installing the wall sleeve
Measuring tape, angle grinder, spirit level, non-pressing 2K polyurethane foam, cutter, mounting wedge set and styrofoam discs.
Requirements: · The wall opening Ø 225 mm is finished. · The fan BUS is laid.
DC B
Y
X = ?
A
Determine the exact thickness X:
D = Exterior rendering, incl. other superstructures if
applicable.
C = Insulation, if necessary inl. air gap (optional)
B = Masonry, incl. relining if necessary.
A = Interior plaster.
Y = Protrusion of the
wall sleeve in the outer area (depending on the
installation situation exterior rendering or masonry)
External termination
Standard variant: Corner
Inner panel
X in [mm] =
Flex Twin+
A + B + C + D A + B
A + B
Nordic
double-skin Masonry (clinker)
single-skin Masonry (ETICS)
A + B A + B
Y in [mm] =
10 10
(for installation directly on the masonry)
UBP + 10
(for installation with substructure panel UBP)
C + D – 200
(min. 30 mm)
C + D – 95
(min. 30 mm)
X + Y
Cut the wall sleeve to the determined dimension X + a protrusion of Y on the
exterior wall. Be careful not to cut away the cut-out for
! the fan connecting cable.
File the edges.
12 h 9 h
3 h 6 h
1 2°
INSTALLATION AND ASSEMBLY
Remove the styrofoam discs from the wall sleeve.
Insert the wall sleeve into the wall opening so it is flush with the interior
wall. Note the thickness of the plaster.
The recess for the connection cables is
! located on the interior wall side and near the cables laid to the wall
opening.
Guide all connecting cables through the cut-out in the wall sleeve.
NOTICE: Anaccumulation of condensation-water in the wallsleeve. Damage to the
exterior wall and masonry and the building structure! · Insert wall sleeve
with a slope of
1 – 2° to the outer wall.
Attach the wall sleeve inside and outside with the mounting wedges so that
there is a slope of 1 2° to the exterior wall.
Check the angle of the wall sleeve using a spirit level.
NOTICE: Contamination of components by e.g. plaster residues will damage the
components of the wall sleeve! · Before foaming the free space between
the wall sleeve and the masonry, insert the Styrofoam discs. · Do not remove
the thread locks of the fastening elements until the inner panel is fitted.
Align the two lateral fastening elements of the wall sleeve horizontally.
22
Ventilation device iV-Twin+ | Installation instructions
Ventilation device iV-Twin+ | Installation instructions
23
INSTALLATION AND ASSEMBLY
24 h
24
Insert the styrofoam discs into the wall sleeve from the inside and outside.
NOTICE: Interruption of the thermal insulation composite system. Damage to the
building structure! · During installation, replace the wall structure as far
as the wall sleeve and if necessary guide the housing (flush-mounted inner
covers) towards it. · Observe the necessary barrier levels.
Foam-seal the gap between teh wall sleeve and masonry all the way around with
non-pressing 2K polyurethane foam.
Cut off the excess, hardened assembly foam and protruding assembly wedges as
follows: · Flush with the inner wall · Flush with the outer wall
! Make sure not to damage the connecting cable on the interior wall.
The wall sleeve set is installed.
Ventilation device iV-Twin+ | Installation instructions
INSTALLATION AND ASSEMBLY
4.5 Installing the external termination Standard variant
The assembly of any exterior termination variants is not part of this documentation! It can be found in the installation instructions of the respective external closure.
NOTICE Installing on an unfinished exterior wall leads to damage to the exterior wall! · Only install the external termination once the exterior wall is finished and fully dried .
NOTICE Penetration of condensation water and/or algae accumulation around the
weather protection hood leads to damage to the masonry/exterior wall and/or
discolouration of the façade! · Secure all sealing tapes on the weather
protection hood circumferentially before installing the
external termination. · Before installation, carry out a biocidal pre-
treatment/ water-repellent pre-treatment of the
surface around the external termiantion (consult your planner regarding this!)
Installing the external weather protection hood
Spirit level, pencil, power drill with Ø 8mm drill bit, cordless screwdriver,
wall anchors (wallplugs for insulation for insulated exterior walls),
permanently elastic external sealant, sealing tape, screws
Requirements: · The exterior wall is completed and even. · The wall sleeve set
is installed.
Remove the styrofoam disc on the outside wall side from the wall sleeve.
Simplex
Slide the base plate onto the projecting wall sleeve.
! The protective grille is directed towards the floor.
Level the base plate inner panel with a spirit level.
ø 8 mm
Mark the four drill holes: Outer holes (blue arrow) Masonry. Inner holes (green arrow) Simplex.
Drill the four holes Ø 8 mm, min 50 mm deep
Ventilation device iV-Twin+ | Installation instructions
25
INSTALLATION AND ASSEMBLY 4 x
26
i
TIP: Do not apply the sealing tape until inmediately before installing the base plate. This
prevents the sealing tape from swelling too
much and makes installation easier.
Attach the sealing tape, 9 mm, outside wall side and circumferentially along
the guide on the base plate.
! Do not seal the fixing holes!
Insert the wall anchors into the boreholes.
Screw the base plate weather protection hood into the wall anchors with 4 screws.
i
TIP: Use insulation dowels for fastening when attaching the base plate to external walls with
insulation or when using the wall installation
block/wall installation system Simplex. These
are not included in the scope of supply, they
are available as an option.
NOTICE: By wrong sealing of the joint between the base plate and the outer
wall the cover cannot be put on. · Seal only the upper joint between the base
plate and the outer wall.
Seal only the upper joint between the base plate and the outer wall.
Place the panel on the four spacers. Engage the panel downwards
! The guides on the cover hook behind the base plate.
The weather protection hood Flex Twin+ is installed.
Ventilation device iV-Twin+ | Installation instructions
INSTALLATION AND ASSEMBLY
4.6 Inserting separating element
NOTICE: IF the separating element is not positioned in the wall sleeve or is positioned incorrectly, there is a possibility of mixing different air volume flows! · A separating element vertically divides the wall sleeve into two airtight chambers. · Push the separating element into the separating bar of the weather protection hood!
Measuring tape, blade knife
Requirements: · The weather protection hood is installed.
Remove the styrofoam discs from the wall sleeve.
L = ?
L + 20
Shorten the partition element to the length of the wall sleeve + 20 mm.
NOTICE: Wrong/ No positioning of the separator element leads to mixing of
different air volume flows in the system! · Position the wider sealing lip
(red arrow)
on the separating element at the bottom of the wall sleeve. · Push the
separating element completely into the wall sleeve and the separating insert
of the weather protection hood!
Ventilation device iV-Twin+ | Installation instructions
Slide the power supply unit in the mounting socket.
! Push the separating element into the weather protection hood.
! The partition element has an inner wall projection of about 10 mm. The
separator is pushed in.
27
INSTALLATION AND ASSEMBLY
4.7 Insert the heat accumulator, shorten the fan BUS, strip the insulation and
connect it to the iV-Twin+ connection cable.
NOTICE Do not store/stack the thermal accumulator insert outside the wall
sleeve as doing so will damage the thermal accumulator’s ceramic. · Insert the
thermal accumulator immediately after removing it from the packaging.
Side cutters, stripping tool, connection cable (scope of delivery)
Requirements: · The weather protection hood is installed. · The separator is
pushed in.
Slide the thermal accumulator half cylinders each to the right and left of the
separating element from the interior as far as they will go in the direction
of the weather protection hood.
! · The handles face the interior. · The connecting cables protrude into the
interior. The thermal accumulator insert has been installed.
1
2
1 Shorten the fan BUS, 3-wire, to your determined wall thickness minus 260mm,
but at least to 150mm.
2 Strip approx. 7 mm of insulation from the cables on the fan BUS.
Connect the fan BUS with the iV-Twin+ connection cable.
INSTALLATION AND ASSEMBLY
NOTICE: · Ensure the correct sequence of the wire colours so that the fans
start.
(IV) (III) (V)
DIR2 (V) VOUT+ (IV) DIR1 (III)
Attach the three fan BUS cables in the free pole of the corresponding connection terminal according to the following table (do not use wire end ferrules):
Fan BUS (cable coming from the controller)
Connecting cable
Terminal block
Definition
Colour
Terminal block
Definition
Colour
DIR1 (III) Signal direction 1 White DIR1 (III) Signal direction 1 Yellow / Pink
VOUT+ (IV) Operating voltage Green VOUT+ (IV) Operating voltage Green / Rot
DIR2 (V) Signal direction 2 Brown DIR2 (V) Signal direction 2 Brown / Blue
The iV-Twin+ connection cable is connected to the fan BUS.
28
Ventilation device iV-Twin+ | Installation instructions
Ventilation device iV-Twin+ | Installation instructions
29
INSTALLATION AND ASSEMBLY
4.8 Insert Xenion reversible fan, connect and check functions
The mounting of the conversier fans varies depending on the place of use: ·
Use in protection zone 2 and higher (standard) · Use in protection zone 1
(IPX4)
Use in protection zone 2 and higher (standard)
Requirements: · Die Thermal accumulator sind in die Wall sleeve
eingeschoben. · The iV-Twin+ connection cable is connected to the
fan BUS. Slide the heat storage half cylinders each to the
right and left of the separating element from the interior as far as they will
go in the direction of the
! weather protection hood. ! · The filters are directed towards the heat
accumulator.
! · The finger guards face towards the interior. · The plug-in connections can
be reached.
Push both fan units up to the heat accumulators respectively.
Both fan units are mounted.
Pass one of the cables on the fan under the sealing lip so that all cables are
on the side with the fan BUS.
i
CHECK:
INSTALLATION AND ASSEMBLY
NOTICE: Incorrect electrical connection will damage the fan motor! · Always
connect the ventilation device to
the mains supply via a controller.
Insert the plugs of the cables on the fan into the sockets of the iV-Twin+
connection cable.
i TIP:The plugs are not assigned to the sockets and can be plugged together as
desired.
Place the cable in the wall sleeve.
The fan units are connected to the controller
Check that the fans start up and move. In heat recovery mode, the fans move in
opposite directions.
30
Ventilation device iV-Twin+ | Installation instructions
Ventilation device iV-Twin+ | Installation instructions
31
INSTALLATION AND ASSEMBLY
Use in protection zone 1 (IPX4) CAUTION: INcorrect positioning of the cables
and plug connections leads to personal injury and/or short-circuiting of the
fans! · Position all plug connections behind the fan unit to ensure IPX4
protection requirements.
Requirements: · The thermal accumulator are positioned in the wall
sleeve. · The iV-Twin+ connection cable is connected to the
fan BUS.
Insert a fan unit into the side of the wall sleeve where the fan BUS is not
located.
! · The filter is directed towards the heat accumulator.
! · The finger guard faces the interior. · The fan unit is only pushed in so
far that it is flush with the inner wall.
! · The plug-in connections can be reached.
Guide the cable with the plug connection over the upper sealing lip to the
side with the fan BUS. To do this, press the separating element slightly
downwards.
NOTICE: Incorrect electrical connection will damage the fan motor! · Always
connect the ventilation device to
the mains supply via a controller.
Insert the plug of the cable on the fan into a socket of the iV-Twin+ connection cable.
Insert the plug of the cable on the fan of the second fan unit into the second socket of the iV-Twin+ connection cable.
i
TIP: The plugs are not assigned to the sockets
and can be plugged together as desired.
INSTALLATION AND ASSEMBLY
The cables and plug connections are pushed into the wall sleeve and thus placed between the heat storage unit and the fan unit.
Slide the second fan unit into the still free side of the wall sleeve (the side where the fan BUS is located).
! · The filter is directed towards the heat accumulator.
! · The finger guard faces the interior. · The fan unit is only pushed in so far
!
that it is flush with the inner wall (no cable visible).
CHECK:
The fan is connected to the controller.
Check that the fans start up and move. In heat recovery mode, the fans move in
opposite directions.
32
Ventilation device iV-Twin+ | Installation instructions
Ventilation device iV-Twin+ | Installation instructions
33
INSTALLATION AND ASSEMBLY
4.9 Fitting the inner panel
The installation of the inner panel is illustrated using the example of the
fan units used in protection zone 2 and higher. If the fan units are installed
for use in protection zone 1 (close flush with the wall sleeve), the inner
cover is installed in the same way.
Spirit level, pencil, screwdriver
Requirements: · The thermal accumulator insert has been installed. · The reversing fans are connected.
Remove the thread locks from the fastening elements of the wall sleeve.
Place the base plate inner panel centric to the wall sleeve on the inner wall.
! · The position arrow on the base plate points upwards.
Screw the base plate weather protection hood into the wall anchors with 4
screws.
Place the panel on the four spacers.
! · The position arrows on the back of the inner panel cover point upwards.
! · Check: The inVENTer logo is located at the bottom right.
! · The separating element is inserted into the receptacle of the inner panel.
4x CLICK
The inner panel is fitted.
TECHNICAL DATA
5 Technical Data
5.1 General specifications
Feature Operating range [°C] Extract air/outdoor air Flow rate in reversed
mode [m³/h] Extract airflow [m³/h] (EN 13141-8) Sound pressure level, distance
2 m [dB (A)] Standard sound level difference [dB] Thermal efficiency of heat
recovery (‘w) Input voltage [V DC] Power consumption [W] Volume flow-related
electr. Specific fan power input [W/(m³/h)] Protection class (EN 61140)
Protection class (EN 60529) Standard filter class
ISO 16890 EN 779: 2012 Frost protection
Comformity
Energy efficiency class (SEC class)
Value -20 50 Without aggresive gases, dust and oils 5 23 10 45 14 38
Standard variant: 45 56 0.94 6 16 0.5 3 0.18 III IPX4
ISO Coarse 45% G3 Automatic by reversing operation (down to -20 °C)
A+ / A
34
Ventilation device iV-Twin+ | Installation instructions
Ventilation device iV-Twin+ | Installation instructions
35
TECHNICAL DATA
5.2 Specifications according to ErP Directive, Regulation 1254/2014
On the energy label you will find the following information from the product
data sheet: · Energy efficiency class (SEC class) · Sound power level Lwa ·
Maximum air flow (supply air)
iV-Twin+ iV-Twin+ Corner iV-Twin+ Nordic
Demand controlled
Pure with sensor sMove with sensor
MZ-Home
Manually controlled
Pure without sensor sMove without sensor
A+
A+
A
A
B
C
D
E
F
G
46
23 m3/h
dB (A)
ENERGIA · · · ENERGIJA · ENERGY · ENERGIE · ENERGI
2016
1254/2014
36
Ventilation device iV-Twin+ | Installation instructions
TECHNICAL DATA
5.3 Specifications according to ErP Directive, Regulation 1254/2014
iV-Twin+ ventilation device, demand controlled
iV-Twin+ product data sheet according to VO 1254/2014 EU dated 11 July 2014
Pt. Description a Supplier
b Model identifier
cold
c
EC class / Specific Energy Consumption (SEC) [kWh/(m²a)]
average
warm
d Ventilation type
e Type of drive
f
Type of heat recovery system
g Degree of temperature change t [%]
h Maximum air flow rate [m³/h]
i
Electrical input power (incl. control) [W]
j
Sound power level Lwa [dB (A)]
k
Reference air flow [m³/h]
l
Reference pressure difference [Pa]
m SEL [W/m³/h]
n Control factor
o Internal and external transfer [%]
p Mixing quota [%]
q
Position and description of the indicator for filter change
Instructions regarding controllable supply and extract
r
air grilles on the façade
(uni-directional ventilation devices only)
s Internet address
t
Sensitivity to pressure changes [%]
u Airtightness between interior and exterior [m³/h]
v
Annual power consumption [kWh/(m²a)]
cold
w
Annual savings Heating energy [kWh/(m²a)]
average
warm
Values
inVENTer GmbH
iV-Twin+ iV-Twin+ Corner iV-Twin+ Nordic
-90.439
A+
-44.95
-18.89
BVU
2
regenerative
94
23
3
46
16.1
0
0.18
0.65
1.8
0.6
Control device
none
www.inventer.eu 44.5 3.2 1.05 93.06 47.57 21.51
Ventilation device iV-Twin+ | Installation instructions
37
TECHNICAL DATA
Manually controlled
iV-Twin+ product data sheet according to VO 1254/2014 EU dated 11 July 2014
Pt. Description a Supplier
b Model identifier
cold
c
EC class / Specific Energy Consumption (SEC) [kWh/(m²a)]
average
warm
d Ventilation type
e Type of drive
f
Type of heat recovery system
g Degree of temperature change t [%]
h Maximum air flow rate [m³/h]
i
Electrical input power (incl. control) [W]
j
Sound power level Lwa [dB (A)]
k Reference air flow [m³/h]
l
Reference pressure difference [Pa]
m SEL [W/m³/h]
n Control factor
o Internal and external transfer [%]
p Mixing quota [%]
q
Position and description of the indicator for filter change
Instructions regarding controllable supply and extract
r
air grilles on the façade
(uni-directional ventilation devices only)
s Internet address
t
Sensitivity to pressure changes [%]
u Airtightness between interior and exterior [m³/h]
v Annual power consumption [kWh/(m²a)]
cold
w
Annual savings Heating energy [kWh/(m²a)]
average
warm
Values
inVENTer GmbH
iV-Twin+ iV-Twin+ Corner iV-Twin+ Nordic
-85.346
A
-40.596
-14.96
BVU
2
regenerative
94
23
3
46
16.1
0
0.18
1
1.8
0.6
Control device
none
www.inventer.eu 44.5 3.2 2.48 91.55 46.80 21.16
38
Ventilation device iV-Twin+ | Installation instructions
SCOPE OF SUPPLY
6 Scope of supply
Standard components
All standard components are also available as spare parts. Further accessories
and spare parts can be found in the separate accessories overview. Contact
your local distributor to order components for your ventilation system.
Component
Product Number
iV-Twin+
1001-0203
iV-Twin+ Corner
1001-0238
iV-Twin+ Nordic
1001-0232
External termination: Weather protection hood incl. sealing tapes
Weather protection Compact, white RAL 9016
1508-0113 | 1508-01491)
Weather protection Compact, grey RAL 9006
1508-0114 | 1508-01471)
Weather protection Compact, grey RAL 7011
1508-0115
Weather protection Compact, anthracite RAL 7016
1508-0128 | 1508-01481)
Weather protection Compact, anthracite RAL 7016
1508-0116 | 1508-01551)
Wall sleeve with Styrofoam discs and mounting wedges
Wall sleeve R-D200x495
1506-0070
Wall sleeve R-D200x745
1506-0071
Thermal accumulator insert
Thermal accumulator insert iV-Twin+ [incl. Separating element 765 mm] Inner
panel
1507-0023
Flair Twin+ V-233×233 inner panel, white
1505-0040
- Variant special: consisting of aluminium, with increased salt resistance
Ventilation device iV-Twin+ | Installation instructions
39
TROUBLESHOOTING
7 Troubleshooting
Troubleshooting
Fault
Possible cause
Remedy
Fan failure Fan does not switch off. Low flow rate
Noises Supply air is cold
No electrical power.
Installation error.
Fan defective. Controller/power supply defective. Faulty controller.
Panel closed. Dust filter heavily soiled
Pollen filter/activated carbon filter used.
The rotational speed of the fan is too low. Thermal accumulator soiled.
Foreign body in the fan
Thermal accumulatoris not correctly positioned in the wall sleeve. The
rotational speed of the fan is very high.
Installation error.
Check fuse. Check wiring for correct polarity. Check all connectors for
correct fit. Check the use of wire ferrules. Replace fan.
Switching controller/ power supply.
Replace controller.
Open panel. Clean/replace dust filter. Pollen or activated charcoal filter
reduces the air volume flow. Only use filters during load periods. Replace the
filter if it is heavily soiled.
Increase the output level.
Clean thermal accumulator. Remove foreign body from the fan. Clean the
ventilation device. Slide the thermal accumulator out of the wall sleeve.
Insert it again. Slide the thermal accumulator into the wall sleeve as far as
the end-stop tape. Set a lower output level on the controller. Check the
connector plug on the controller. The connector plug must be sitting firmly in
the connector housing.
40
Ventilation device iV-Twin+ | Installation instructions
WARRANTY AND GUARANTEE
8 Warranty and guarantee
Warranty The warranty covers all defects that were present at the time of
purchase. Observe the intended use in order to maintain the warranty claim.
Outside Germany, the national warranty regulations of the country in which the
system is sold apply. Contact the dealer of your home country. Guarantee:
inVENTer GmbH gives a 5-year guarantee on all electronic components and the
wall sleeve, as well as a 30-year guarantee on the ceramics of the thermal
heat accumulator. This covers premature product wear. Warranty and guarantee
claim For information on the guarantee provisions, see
www.inventer.eu/garantie/guarantee. In the event of a warranty or guarantee
claim, contact the dealer or factory representative responsible for you. In
any case, send the complete unit back to the manufacturer. The warranty claim
is an additional offer by the manufacturer and does not affect applicable law
in any way.
9 Service
Complaints Check the delivery for completeness and transport damage upon
receipt, using the delivery note. Report any missing items immediately, or at
the latest within 14 days, to your supplier, dealer or factory representative.
Accesories and spare parts To order components for your ventilation unit,
contact your dealer or factory representative. Technical customer service: For
technical advice, please contact our technical service staff:
+49 (0) 36427 211-333 service@inventer.de
Ventilation device iV-Twin+ | Installation instructions
41
inVENTer GmbH Ortsstraße 4a D-07751 Löberschütz www.inventer.eu
Subject to modifications No liability for printing errors
Product Number 5001-00XX Version: 1.0 09/2022
References
- Decentralized ventilation systems - invisible, energy-efficient, silent
- Decentralized ventilation systems - invisible, energy-efficient, silent
- Downloads - inVENTer
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>