FIre-LITe ALarms BG-12LX Addressable Pull Station Instruction Manual
- June 13, 2024
- Fire-LITe Alarms
Table of Contents
FIre-LITe ALarms BG-12LX Addressable Pull Station
Product Information
The BG-12LX Addressable Pull Station is a dual-action pull station that can be surface mounted or semi-flush mounted. It includes a Single Pole, Single Throw (SPST) Normally Open (N/O) switch which closes upon activation. The pull station is designed for use with the FACP SLC system and can be wired to other addressable devices.
Product Usage Instructions
Installation:
- The BG-12LX can be surface mounted to an SB-10 or SB-I/O surface backbox or semi-flush mounted on a standard single-gang, double-gang, or 4 (10.16 cm) square electrical box.
- If semi-flush mounted, the optional BG-TR trim ring can be used.
Operation:
- To activate the pull station, push in and pull down on the handle. The word “ACTIVATED” will appear after the handle is pulled down.
- The pull station will remain activated until it is reset.
Resetting the Pull Station:
- Insert the key into the lock and rotate 1/4 turn counterclockwise.
- Open the door until the handle returns to normal.
- Close and lock the door.
Wiring:
Connect the pull station from the FACP SLC to the next addressable device
using the provided strip gauge. Follow the specified wiring configuration.
ADA Compliance:
For ADA compliance, ensure the clear floor space allows a forward approach
or parallel approach by a person in a wheelchair. The maximum reach heights
allowed are 48 inches (121.92 cm) for the forward approach and 54 inches
(137.16 cm) for the parallel approach.
Setting the Address:
- Turn the rotary address switches on the addressable module mounted inside the pull station to set the desired address. Only one device per address is allowed.
- Record the set address on the product ID label located inside the pull station.
LED Operation:
- Normal: The LED flashes red.
- Alarm: The LED remains steady red.
- The LED is visible through the translucent handle.
Description
The BG-12LX Addressable pull station is a non-coded, dual-action manual pull station with a key-lock reset feature. It provides Fire•Lite intelligent control panels with one addressable alarm initiating input. The addressable module is housed inside the pull station. The BG-12LX is compatible with all Fire•Lite intelligent panels. The BG-12LX meets the ADAAG controls and operating mechanisms guidelines (section 4.1.3[13]), and the ADA requirement for a 5 lb. maximum pull force to activate the pull station. Operating instructions are moulded into the pull station handle along with Braille text. Moulded Terminal numbers are also present. Conforms to ANSI/UL Standard 38 and ULC Standard S528.
Ratings
- Normal Operating Voltage : 24 VDC.
- Average Operating Current (LED Flash): 375 µA.
- Maximum Operating Current (LED On): 5 mA.
- Temperature Range: 32° F – 120° F (0° C – 49° C).
- Relative Humidity Range: 10% – 93% non-condensing.
Installation
The BG-12LX Addressable pull station can be surface mounted to an SB-10 or SB-I/O surface backbox or semi-flush mounted on a standard single-gang, double-gang or 4″ (10.16 cm) square electrical box. The optional BG-TR trim ring can be used if the BG-12LX is to be semi-flush mounted.
Operation
- To activate the dual-action pull station, push in and pull down on the handle. The word ‘ACTIVATED’ appears after the handle is pulled down. This will remain until the pull station is reset.
- The pull station includes one Single Pole, Single Throw (SPST) Normally Open (N/O) switch which closes upon activation of the pull station.
Resetting the Pull Station
- Insert the key into the lock and rotate 1/4 turn counterclockwise.
- Open the door until the handle returns to normal.
- Close and lock the door.
Wiring
NOTE : Closing the door automatically resets the switch to the ‘Normal’ position. Opening the door will not activate or deactivate the alarm switch.
CAUTION! Do not detach the door of the pull station during installation. The door of the pull station cannot be reattached to the backplate after the backplate has already been installed onto an electrical box.
CAUTION!
Install the FireLite BG-12LX addressable pull station according to these
instructions, applicable NFPA standards, national and local Fire and
Electrical codes and the requirements of the AHJ (Authority Having
Jurisdiction). Regular testing of the devices should be conducted by the
appropriate NFPA standards. Failure to follow these directions may cause the
device to report an alarm condition. FireLite is not responsible for devices
that have been improperly installed, tested or maintained.
ADA Compliance
For ADA compliance, if the clear floor space only allows a forward approach
to an object, the maximum forward reach height allowed is 48 inches (121.92
cm). If the clear floor space allows a parallel approach by a person in a
wheelchair, the maximum side reach allowed is 54 inches (137.16 cm).
Setting the BG-12LX Address
The BG-12LX Addressable pull station is factory preset with address ‘00.’ Set
the address for the pull station by turning the rotary address switches on the
addressable module mounted inside the pull station. Only one device per
address is allowed. Multiple modules may not be set to the same address on the
Signaling Line Circuit. Once the address is set, record it in the space
provided on the product ID label located inside the pull station.