BOSCH FMR-1000-RCMD Remote Command Center Installation Guide

June 13, 2024
Bosch

BOSCH FMR-1000-RCMD Remote Command Center

BOSCH FMR-1000-RCMD Remote Command Center

Notice

These instructions cover the installation of the Bosch FMR-1000-RCMD Remote Command Center in a fire system supervised by a Bosch FPA-1000 Analog Addressable Fire Panel or a Fire Alarm Control Panel with similar connection conditions.
Install, test and maintain the FMR-1000-RCMD according to these instructions, NFPA 72, Local Codes, and the Authority Having Jurisdiction. Failure to follow these instructions may result in failure of the device to operate properly. Bosch Security Systems Inc. is not responsible for improperly installed, tested or maintained devices.
Refer to FPA-1000- Installation and Operation Guide (P/N F.01U.174.607) for detailed wiring style requirements and complete programming instructions.

NOTICE!
NFPA 72 requires a complete system-wide functional test be performed following any modifications, repair, upgrades, or adjustments made to the system’s components, hardware, wiring, programming, and software/firmware.

CAUTION!
These instructions contain procedures to follow in order to avoid personal injury and damage to equipment.

Scope of Delivery

Description

One Remote Command Center (in back box with cover frame)
Tabs with different language versions for LED and key text
One hardware pack
One FMR-1000-RCMD Installation and Operation Guide

Device Description

The Remote Command Center FMR-1000-RCMD is a four-wire LCD annunciator with system control capability. It shows the LEDs and LCD display identically to the panel’s and includes a piezo, scrolling buttons, and operation keys for acknowledge [ACK], drill, reset and silence.
The scrolling functions and the acknowledge [ACK] key are accessible without restriction. The keys for reset, silence or drill can be enabled and disabled by the device key lock. In addition, the operation keys or all keys can be locked using DIP switches (refer to Table 7.1 on Page 11).
The Remote Command Center features tabs with different language versions for LED and key text. The device allows for surface and semi-flush mounting. Each FPA-1000 Analog Addressable Fire Panel supports up to a total of eight FMR-1000-RA Remote Annunciators and/or FMR-1000-RCMD Remote Command Centers.

Device Description

Mounting

The Remote Command Center should be mounted no higher than shoulder height of the shortest person operating the system.

Removing the Cover Frame

The device comes with the mounting material and language tabs in separate bags. For removing the device’s cover frame from the annunciator unit, hold the assembly and unlock the snap-fit hooks on one side. Pull the cover frame off.

Mounting

Surface Mounting

  1. The back box provides three knockouts for 1/2 in. diameter conduit connectors in the back, bottom and top side (refer to Figure 4.2, Item 1). To get a clean break, remove the knockout from the inside of the box.
    NOTICE!
    To get a clean break, remove the knockout from the inside of the box.

  2. Install the back box with the arrow pointing up (refer to Figure 4.2, Item 2).

  3. Use the back box as a template to mark the location of the mounting holes (refer to Figure 4.2, Item 3). Provide an opening in the mounting surface for the wiring. Pre-start the screws. Do not secure the screws at this point.

  4. The built-in bubble level allows you to level horizontally without extra tools when securing the base (refer to Figure 4.2, Item 4)

Before mounting the unit, follow the instructions in

  • Section 6 Inserting the Language Tab on Page 10
  • Section 7 Address Setting on Page 11
  • Section 5 Wiring on Page 9.
    Mounting

Legend

1| Knockout for 1/2 in. conduit connector in the in the back, bottom and top side
2| Arrow pointing up
3| Mounting holes for surface mounting
4| Bubble level
5| Fixing points for annunciator unit (4 screws)

Flush Mounting

For flush mounting, use a 3 gang electrical box. Refer to _Figure 4.3_to select the mounting holes. Before mounting the unit, follow the instructions in

  • Section 6 Inserting the _Language Tab_on Page 10
  • _Section 7 Address Setting_on Page 11
  • _Section 5 Wiring_on Page 9.

| Mounting
---|---
Legend
1| Mounting holes for flush mounting

Wiring

DANGER!
Explosion and burn hazard. Do not short terminals. Incorrect connections can result in damage to the unit and personal injury. Before servicing this equipment, remove all power connections.

Option Bus Circuit Wiring Distance

Use four conductor, 18 AWG (0.8 mm2 ) or larger wire to connect Option Bus devices to the FACP. The total length of wire connected to the Option Bus terminals must not exceed 4000 ft (1219 m), regardless of the wire gauge used. The maximum length between any one device and the panel terminals depends on the current drawn on the branch that the device is on. The current draw on a particular branch can be found by adding together the individual current draws of each device connected to the branch. Refer to FPA-1000 Installation and Operation Guide (P/N F.01U.173.607) for detailed wire length calculations.

Wiring Connections

The FMR-1000-RCMD is powered by either of the following power outputs from the FPA-1000:

  • 12 V DC power (Option bus)
  • 24 V FWR unfiltered Aux power output or UL listed external power supply with common reference ground with the FPA-1000:
  • 12 V DC power
  • 24 V DC power.

To wire the FMR-1000-RCMD:

  1. Power down the control panel.
  2. Route the wiring from the FACP to the annunciators.
  3. Bring the wiring through one of the knockouts in the annunciator’s base (surface mounting) or the 3 gang electrical box (flush mounting). Refer to Figure 4.2 on Page 8 for wire entrance location in the back box.
    Legend| Wiring
    ---|---
    GND| Ground
    V+/PWR| Power supply
    Y| Yellow, Data OUT
    G| Green, Data IN
    P3| Power supply connection
    P7| Data connection
  4. Connect the wiring to the FMR-1000-RCMD terminals. Refer to Figure 5.1.
  5. For surface mounting with back box: Secure the base. Use the bubble level to make sure that the back box is perfectly horizontal. Refer to Figure 4.2 on Page 8.
  6. Fasten the annunciator unit with the four mounting screws using a Phillips (crossheaded) screwdriver. Secure the screw for the earth ground connection. Refer to
  7. Place the cover frame onto the base along the top side. Press the bottom part until it snaps into place.
    Wiring
    When the device is powered on, the system performs a selftest. The routine includes checking of all interfaces, address switches, LEDs, LCD, buzzer, keys, current consumption, and lamp test.

Removing the Cover Frame for Service

For removing the device’s cover frame when the annunciator unit is already mounted, insert a small flathead screwdriver in each slot at the bottom or at the top of the frame. Press up and pull the cover frame off.

Wiring

Inserting the Language Tab

For different language versions of LED and key lettering, use the tabs provided with the FMR-1000-RCMD.

Inserting the Language Tab

  1. Insert the tab carefully in the slot at the top of the keypad.
  2. Slide the tab down carefully until it is completely flush with the keypad.
  3. For tab removal, carefully pull upwards at the strap.

Address Setting

Each FMR-1000-RCMD connected to the Option Bus of the FPA-1000 must be set to a unique Option Bus address ranging from 16 to 23. The devices must also be programmed at the control panel (refer to FPA-1000 Installation and Operation Guide (P/N F.01U.173.607). The address is set using the DIP switches at the main board of the annunciator unit. Refer to Table 7.1.

Address Setting

Option Bus Address

| DIP 1| DIP 2| DIP 3| DIP 4| DIP 5
---|---|---|---|---|---
16| OFF| OFF|

OFF

|

OFF position: Control keys are locked.
ON position: All keys are locked.

|

OFF position: Key lock active.
ON position: Key lock bypassed.

17

| ON| OFF| OFF
18| OFF|

ON

| OFF

19

| ON| ON| OFF
20| OFF| OFF|

ON

21

| ON| OFF| ON
22| OFF| ON|

ON

23

| ON| ON|

ON

Table 7.1 DIP Switch Function

The DIP switch 4 allows for locking the control keys (drill, reset and silence) in OFF position and for locking all keys in ON position.
The DIP switch 5 enables the device’s key lock in OFF position and bypasses the key lock in ON position.

NOTICE!
Each Option Bus device must have its own address, and each address can support only one device. Ensure that there are no duplicate addresses on the bus.

Programming

All Remote Annunciators and Remote Command Centers have to be configured as elements connected to the Option Bus.

The FPA-1000 enables various programming approaches:

  • On-site at the front panel to program another panel, but not all parameters can be programmed
  • On-site through a Web server using a laptop (connected to the panel with CAT5 cable)
  • Remote, using a Web page and a dial-up connection
  • Remote, using a Web page and an Ethernet connection. For front panel programming, the system provides an auto learn function, allowing the installer to configure the system quickly and easily in default mode. Using a local laptop or remote access through a communicator, the programming is carried out by means of browser-based user interface (virtual keypad). Refer to the FPA-1000 Installation and Operation Guide (P/N F.01U.173.607) for detailed programming instructions.

Operating

LEDs and LCD Keypad

The LEDs on the Remote Command Center follow the global system status (refer to Table 9.1). In addition, a communication fault on the Option Bus is indicated by the trouble LED flashing at 1 Hz (refer to Section 10 Troubleshooting on Page 15).

Legend| Operating| 1
4
5
---|---|---
1| LEDs
2| Device key
3| LCD screen
4| Scroll keys
5| Keys for Drill, Reset, Silenced,
| and Acknowledge [ACK]
LED| System Status|
---|---|---

Fire Red

| On| Whenever the system registers a fire alarm and is not reset|
Off|

  • If no alarm registered’
  • After resetting

|

Gas Alarm Blue

| On| When the system registers a gas alarm and is not reset|
Off|

  • If no gas alarm registered
  • After resetting

|

Power Green

| On| If AC power is applied to the panel|
Flashing 1)| When AC power fails and the unit operates from battery power|
Off| When no power (AC or battery) is applied|

Supervisory Yellow

| On| When the system registers a supervisory condition|
Off| When no supervisory condition is registered|

Silenced Yellow

| On|

  • When an alarm or trouble condition is silenced manually by the user
  • If the system auto-silence timer expires

|
Off|

  • When no condition is silenced
  • When a silenced condition is corrected

|

Trouble Yellow

| On|

  • When the panel is initializing
  • When the panel registers a trouble condition from a point, or the panel
  • When inputs or outputs or other elements are bypassed

|
Flashing 1)|

  • When the panel is not operating
  • When walk test is in progress

|
Off|

  • When no trouble condition exists
  • When the panel is resetting

|

  1. LED flash rate is 1 Hz (0.5 s on, 0.5 s off).

Table 9.1 LED Operation
Display

The FMR-1000-RCMD Remote Command Center uses an 80-character (4 lines x 20 characters) wide viewing-angle LCD display. The display includes a long-life LED backlight. The backlight is controlled by the panel, or locally turned on upon any key press and turned off after 30-second time-out without key press. Even when AC power is lost, the LED backlight remains lit if a user is operating the keypad.
Piezo Sounder
The FMR-1000-RCMD Remote Command Center has a piezo that provides audible indication of the system status. Refer to Table 9.2 for piezo modes when FMR-1000-RCMD is controlled by the panel:

Piezo Operation System Status
Silent The panel is in a normal state (no alarm, supervisory or trouble

condition). The panel was silenced or acknowledged after an off- normal condition.
Continuous beep| The panel is in fire alarm condition.
Periodic beep (0.5 s every 2 s)| The panel is in gas alarm condition.
Periodic beep (0.5 s every 4 s)| The panel is in supervisory condition.
Periodic beep (0.5 s every 10 s)| The panel is in trouble condition or a communication fault exists on the Option Bus.
Short beep| With every valid key press.

Table 9.2 Piezo Operation with FMR-1000-RCMD Panel Controlled
In case of multiple piezo activation, the system status with highest priority is indicated.
If the Remote Command Center is not controlled by the panel or during a communication fault, refer to Table 9.3 for piezo modes:

Piezo Operation System Status with FMR-1000-RA Controlled Locally
Periodic beep (0.5 s every 10 s) A communication fault exists on the Option

Bus.

Lamp Test

A lamp test is accomplished by pressing and holding the acknowledge [ACK] key for more than 3 seconds. All LEDs on the FMR-1000-RA are turned on and the LCD display is filled with black blocks when the lamp test starts. As soon as the acknowledge [ACK] key is released, the revision number, Option Bus address, and key lock status appear on LCD display for 3 seconds. Then the LEDs and the LCD display return to normal working mode (controlled by the panel).

Keypad Operations

With the key lock in the locked position, the user can use the scroll keys only for navigating the LCD display and operate the acknowledge [ACK] key. Upon an invalid key press, the display shows “KEY LOCKED” for 3 seconds. Refer to Table 7.1 on Page 11 for key lock bypass option.
With either the key lock in unlocked position or the DIP switch setting for the key lock bypassed, the user may operate any of the device’s keys.
View Status
With no alarms or troubles in the system, the display message is “SYSTEM NORMAL” or “SYSTEM NORMAL DAY” along with the current date and time.

During initialization by start-up or re-configuration, the screen indicates “System Initializing”. The panel shows the “System Resetting” screen upon reset, until the system returns to the normal supervising condition.
If PAS or Pre-signal is turned on, the screen indicates “SYSTEM NORMAL DAY”.
Any off-normal conditions are shown in groups classified as fire alarm, gas alarm, supervisory and trouble.
Use the arrow keys to view events or conditions in the same group. Up and down keys move the user to the previous or next event. The left and right keys switch to

NOTICE!
For system display information, refer to FPA-1000 Installation and Operation Guide (P/N F.01U.173.607).

Acknowledge
During an alarm, pressing the acknowledge [ACK] key turns off the piezo that is sounding on an annunciator. All the ongoing events or conditions are marked as “Acknowledged”. The 24-hour trouble reminder timer starts. Any trouble event not cleared within 24 hours is sent again and the piezo begins to beep again.
If a fire input point configured as “PAS enabled” (with global PAS enabled) is activated,
pressing the acknowledge [ACK] key within 15 seconds after a PAS activation starts the investigation timer. This allows the user to investigate the fire alarm or take other appropriate actions until the timer expires.
An acknowledgement operation can also be initiated by the activation of an input point configured as an acknowledge type.
Silence
Pressing the silence key performs all functions of the acknowledge operation.
When the silence operation is initiated, the panel goes into a “Silenced” status and the “Silenced” LED lights. The piezos on all keypads and annunciators turn off. All outputs are silenced if configured as “Silenceable”. NACs play the “Silenced” pulse for the programmed pattern, or they fully de-energize, as defined by the global option “Silence Config”. Strobes continue flashing.
If programmed, the panel transmits a silence report to the central station.
If the panel is already silenced, pressing [SILENCE] again causes an unsilence command in the panel. Silence operation does not reset the alarm status and does not return the activated input to normal service. Any new alarm reactivates any silenced outputs.

Trouble Reminder
If any events are not cleared within 24 hours after the [SILENCE] or [ACK] key was pressed,
the panel turns on the piezo again and events are transmitted to the central station again.
Reset
Pressing the reset key turns off the piezo and all activated or silenced outputs. The reset operation turns off auxiliary power AUX/RST for 5 seconds, and activates the global resetting zone. All alarms, supervisories, and troubles caused by activation of SLC points are cleared. Then the panel tries to reset all points that are in off-normal status. Not all system trouble conditions are affected by the reset operation. If programmed, the panel transmits a reset report to the central station.
Any alarm or trouble that exists after a reset causes the system to sound again.
Drill
To activate the drill operation, the [DRILL] key must be pressed twice to prevent accidental activation. Pressing the key once the system prompts for confirmation. Pressing the [DRILL] key again turns on all unbypassed NACs and drillable relay outputs.
The drill operation stops if the reset key is pressed, or it is automatically cancelled if the operation was started for a programmed time. A system reset is automatically performed by stopping the drill so that the panel and all field devices restore to their normal operation. If programmed, a drill start report and a drill stop report are transmitted to the central station.

Troubleshooting

Display LED Piezo Description
NOT PROGRAMMED 0.5 s on/

0.5 s off

| 0.5 s every 10 s| No communication activities on the device address.
NO COMMUNICATION| 0.5 s on/

0.5 s off

| 0.5 s every 10 s| After 60 seconds of no communication activities on any Option Bus address.
COMMUNICATION OK| off| off| Communication on the device address; no text received yet.

Specifications

Electrical
Operating voltage Nominal 12 V DC or 24 V DC/FWR
Current consumption at 12 V DC
  • Standby current

| 25 mA maximum (only Power LED on)

  • Alarm current

| 150 mA maximum (with annunciator lit and piezo on)
Current consumption at 24 V DC/FWR|

  • Standby current

| 30 mA maximum (only Power LED on)

  • Alarm current

| 120 mA maximum (with annunciator lit and piezo on)

Wiring Specification

Cable entries| 3 knockouts for 1/2 in. diameter conduit connectors in the back, bottom and top side
---|---
Connections| 2 connectors (4 terminals)
Wire gauge| AWG 12 to 18 (diameter 3.25 mm2 to 0.75 mm2)
Wire type| Non-shielded, four conductor wire
Maximum number of annunciators per system| 8 (FMR-1000-RA and/or FMR-1000-RCMD)
Distance allowed between FACP and annunciator| 2000 ft (610 m)
Maximum length of Option Bus wiring| 4000 ft (1219 m), depending on cable gauge and connected devices

Mechanics

Operating and display elements|
---|---

  • 6 LEDs

| Fire (red), Gas Alarm (blue), Power (green), Supervisory, Silenced and Trouble (3 x yellow)

  • LCD

| 4 line x 20 character LCD display, backlit

  • Keys

| Keys for Drill, Reset, Silenced, Acknowledge [ACK], 4 arrow keys

  • Piezo

| Built-in piezo sounder
Mounting holes back box| 2, spaced 5.5 in. (140 mm) apart
Housing material| ABS-FR
Color| Red
Dimensions (W x H x D)|

  • FMR-1000-RCMD

| 7.40 x 4.41 x 2.40 in. (188 x 112 x 61 mm)

  • Back box

| 7.40 x 4.41 x 1.89 in. (188 x 112 x 48 mm)
Weight| 19.4 oz (550 g)

Environmental Conditions

Environment Indoor, dry
Operating temperature 32 °F to 120 °F (0 °C to +49 °C)
Storage temperature -4 °F to 140 °F (-20 °C to +60 °C)
Relative humidity Up to 95%, non-condensing
Protection class per IEC 605029 IP 30
Trademarks

Phillips is a registered trademark of the Phillips Screw Co.

Logo

References