SLOAN G2 Advanced Electronic Flushometers Owner’s Manual
- June 13, 2024
- SLOAN
Table of Contents
- SLOAN G2 Advanced Electronic Flushometers
- Product Information
- Product Usage Instructions
- SENSOR MODULE COMPONENT PARTS
- ABOUT PRODUCT
- ITEM 10. FLEX TUBE DIAPHRAGM KIT
- O-RING
- REGULATORS
- REGULATOR (SOLD 6 PER PACKAGE)
- ITEM 16A. SLIP JOINT GASKETS AND RINGS
- SOLENOID REPLACEMENT
- BATTERY REPLACEMENT
- RANGE ADJUSTMENT (ADJUST ONLY IF NECESSARY)
- TROUBLESHOOTING AND MAINTAINING THE SLOAN G2 OPTIMA PLUS® FLUSHOMETER
- CARE AND CLEANING INSTRUCTIONS
- SENSOR MODULE COMPONENT PARTS
- OTHER VALVE COMPONENT PARTS
- ITEM 13A. SLIP JOINT GASKETS AND RINGS
- ELECTRONIC MODULE ASSEMBLY CHART
- BATTERY REPLACEMENT
- FLEX TUBE DIAPHRAGM ASSEMBLY
- FLEX TUBE DIAPHRAGM KITS
- REGULATORS
- OLD STYLE DIAPHRAGM INSIDE PARTS
- SOLENOID REPLACEMENT
- TROUBLESHOOTING GUIDE
- BATTERIES
- CARE AND CLEANING OF CHROME AND SPECIAL FINISHES
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SLOAN G2 Advanced Electronic Flushometers
Product Information
Item No. | Code No. | Part No. | Description |
---|---|---|---|
1A | 0325160 | EBV-138-A | Sensor Module Component Part |
1A | 0325161 | EBV-139-A | Sensor Module Component Part |
Product Usage Instructions
-
1. For battery door replacement, refer to the instructions on Page 58.
- To replace the flex tube diaphragm kit, follow these steps:
- Identify the desired color and corresponding part number from the Flex Tube Diaphragm Kit table on Page 84.
- Remove the old flex tube diaphragm by unscrewing it from the valve body.
- Install the new flex tube diaphragm by screwing it onto the valve body.
- Ensure that the flex tube diaphragm is securely attached.
SENSOR MODULE COMPONENT PARTS
ABOUT PRODUCT
- Sloan introduced its Optima Plus® battery powered sensor flushometer in 1992, revolutionizing the flushing of water closets and urinals. In both new construction and retrofit applications, the use of the Optima Plus has become the standard method for many facilities to improve restroom hygiene and ensure handicap accessibility compliance.
- In May, 2003 Sloan introduced the G2 Optima Plus®.
- The G2 Optima Plus® builds on the success of the original product and offers many technological advancements to further improve on performance and reliability expected of sensor activated plumbing. In addition to a new aesthetic design, the G2 Optima Plus® features a new state-of-the-art electronic and optical package and a solenoid operator. The G2 Optima Plus replaces the original Optima Plus® product, which was phased out of production in mid-2003.
- The Sloan G2 Optima Plus® automatic battery powered flushometer relies on an infrared sensor to detect a user and activate a flushing cycle. No physical contact with the flushometer surface is necessary, assuring sanitary protection. G2 Optima Plus® flushometers are ADA compliant devices.
- The flushometer is triggered by means of an active infrared sensor. The Optima Plus® sensor emits a continuous invisible light beam. When a user enters the beam’s effective range, the beam is reflected into the Optima Plus scanner window. The user is now detected. After the user moves out of the effective range of the sensor, a signal is sent to the flushometer solenoid and, after appropriate arming and/or flush delays, the flush cycle is initiated.
ITEM 10. FLEX TUBE DIAPHRAGM KIT
- EBV-1020-A and EBV-1022-A are supplied with multiple regulators.
- A 0.5 gpf (1.9 Lpf) urinal kit can be converted to a 1.0 gpf (3.8 Lpf) by cutting and removing the smooth A-164 flow ring from the guide.
- For a 4.5 gpf (17 Lpf) water closet flush use EBV-1020-A with the white regulator, and cut and remove the A-164 flow ring from the guide.
- Color of regulator to be used with flex tube diaphragm to obtain the listed flush volume. EBV-1025-A includes H-1015A Flow Control
O-RING
REGULATORS
The flush volume of the flex tube diaphragm kit is controlled by the regulator. Regulators are identified by color. Some flex tube diaphragm kits are supplied with multiple regulators. The installer must make sure the proper regulator is used when installing the flex tube diaphragm kit.
REGULATOR (SOLD 6 PER PACKAGE)
ITEM 16A. SLIP JOINT GASKETS AND RINGS
SOLENOID REPLACEMENT
-
Turn off water and relieve pressure by loosening Tailpiece coupling and re-tighten. Loosen and remove top screws along with the outer cover assembly.
-
Disconnect wire clip from battery door and remove module from inner metal cover assembly
-
Remove Solenoid by turning counter clockwise. Remove any remaining O-rings or parts in orifice.
-
Remove black plastic Housing from the threaded end of new Solenoid Operator by unscrewing (counterclockwise). It is normal to find fluid inside this housing.
-
Make sure all O-rings (2) are installed on the grey End cap of the new Solenoid Operator. Install Solenoid Operator by threading it (clockwise) into the Housing. Tighten with fingers beyond just snug.
-
Mount module on inner cover assembly. Reconnect the plastic clip on the battery door.
-
Assemble outer cover assembly.
- Turn on water at control stop. Installation complete.
BATTERY REPLACEMENT
-
When G2 Optima Plus® has approximately 4,000 flushes left, the same red light that appears at start-up will flash four (4) times quickly whenever an object is detected. When this occurs, we recommend changing the batteries as follows:
-
When required, replace batteries with four (4) type AA batteries.
Note: Water does not have to be turned off to replace batteries. -
Loosen the two (2) screws on top of unit. Remove the complete cover assembly. Lift the sensor module from its plate. Unplug the electrical connector from battery compartment cover. Loosen the retaining screw on battery compartment cover and remove battery compartment cover. Install four (4) alkaline type AA batteries exactly as illustrated at right. Install battery compartment cover and secure with retaining screw. Make certain that battery compartment cover is fully compressed against gasket to provide a seal; Do not overtighten. Plug the electrical connector into the battery compartment cover. Reinstall the sensor module onto the plate.
-
Reinstall the complete cover assembly onto the plate. Tighten the two (2) screws on top of the unit.
RANGE ADJUSTMENT (ADJUST ONLY IF NECESSARY)
-
The Optima Plus has a factory set sensing range:
- Water Closet Models – 22” to 42” (559 mm to 1067 mm)
- Urinal Models – 15” to 30” (381 mm to 762 mm)
-
The Factory setting should be satisfactory for most installations.
-
If the range is too short (i.e., not picking up users) or too long (i.e., picking up opposite wall or stall door) the range can be adjusted.
Note: Water does not have to be turned off to adjust range. -
Make sure to remove all the non-permanent targets in sensor view area. Push manual override button for 25 seconds. the Red LED in the G2 sensor starts slow blinking. Release the button during the LED blinking. The G2 will enter into distance setting mode. The setting mode will run for one (1) minute.
IMPORTANT !!!
WHEN ADJUSTING RANGE FOR URINAL SENSOR, MAKE SURE TO SETUP A PROPER TARGET IN FRONT OF URINAL SENSOR.
TROUBLESHOOTING AND MAINTAINING THE SLOAN G2 OPTIMA PLUS® FLUSHOMETER
IMPORTANT:
- This product contains mechanical and/or electrical components that are subject to normal wear. These components should be checked on a regular basis and replaced as needed to maintain the valve’s performance.
- Never open Control Stop to where the flow from the valve exceeds the flow capability of the fixture. In the event of a valve failure, the fixture must be able to accommodate a continuous flow from the valve.
ATTENTION INSTALLERS:
- With the exception of the control stop inlet,
- DO NOT USE pipe sealant or plumbing grease on any valve component or coupling! To protect the chrome or special finish of Sloan flushometers,
- DO NOT USE toothed tools to install or service these valves. Use our A-50 Super-Wrench™ or other smooth-jawed wrench to secure couplings.
- Regulations for low consumption fixtures (1.6 gpf/6.0 Lpf closets and 1.0 gpf/3.8 Lpf urinals) prohibit use of higher flush volumes.
-
Sensor flashes continuously only when user steps within range.
Unit in start-up mode; no problem. This feature is active for the first ten (10) minutes of operation. -
Valve does not flush; sensor not picking up user.
Range too short; increase the range. -
Valve does not flush; sensor picking up opposite wall or surface, or only flushes when someone walks by. Red light flashes continuously for first ten 10 minutes even with no one in front of the sensor.
Range too long; shorten range. -
Valve does not flush even after adjustment.
- Range adjustment potentiometer set at full “max” or full “min” setting.
- Readjust potentiometer away from full “max” or “min” setting.
- Batteries completely used up; replace batteries.
- Problem with electronic sensor module; replace electronic sensor module.
-
Unit flashes 4 quick times when user steps within range.
Batteries low; replace batteries. -
Valve does not shut off.
-
By-pass orifice in diaphragm is clogged with dirt or debris, or by-pass is clogged by an invisible gelatinous film due to “over-treated” water. Remove flex tube diaphragm and wash under running water.
Note: Size of orifice in the by-pass is of utmost importance for the proper metering of water by the valve. DO NOT ENLARGE OR DAMAGE THIS ORIFICE. Replace flex tube diaphragm if cleaning does not correct the problem. -
Dirt or debris fouling stem or flex tube diaphragm. Remove flex tube diaphragm and wash under running water.
-
O-ring on stem of flex tube diaphragm is damaged or worn. Replace O-ring if necessary.
-
Problem with solenoid. If cleaning does not correct problem, replace with new solenoid operator.
-
-
Not enough water to fixture.
-
Wrong flush volume regulator installed in flex tube diaphragm kit.
Install the correct regulator. -
Wrong Optima Plus® model installed; i.e., 1.0 gpf urinal installed on 3.5 gpf closet fixture. Replace with proper Optima Plus model.
-
Enlarged by-pass in diaphragm. Replace flex tube diaphragm.
-
Control stop not adjusted properly. Readjust control stop.
-
Inadequate volume or pressure at supply. Increase water pressure or supply (flow) to valve. Consult factory for assistance.
-
-
Too much water to fixture.
- Wrong flush volume regulator installed in flex tube diaphragm kit. Install the correct regulator.
- Control stop not adjusted properly. Readjust control stop.
- Wrong Optima Plus model installed; i.e., 3 gpf model installed on 1.0 or 1.5 gpf urinal fixture.
- Dirt in diaphragm by-pass. Clean under running water or replace flex tube diaphragm.
Note: The EBV-46-A beam deflector is no longer required or available for the G2 Optima Plus.
CARE AND CLEANING INSTRUCTIONS
- DO NOT USE abrasive or chemical cleaners to clean the flushometer, they may dull the luster and attack the plastic cover and the chrome finish of the flushometer. Use ONLY mild soap and water, then wipe dry with clean cloth or towel.
- While cleaning the bathroom tile, the Optima Plus should be protected from any splattering of cleaner. Acids and cleaning fluids can discolor or remove chrome plating.
- When assistance is required, please contact
- Sloan Technical Support at: 1-888-SLOAN-14 (1-888-756-2614).
SENSOR MODULE COMPONENT PARTS
OTHER VALVE COMPONENT PARTS
ITEM 13A. SLIP JOINT GASKETS AND RINGS
ELECTRONIC MODULE ASSEMBLY CHART
- The electronic and optical improvements of the G2 Optima Plus® have been incorporated into the electronic modules for use with older Optima Plus products.
- Optima Plus® modules can be identified by color.
- Old style modules are black and have a wire that runs along the side of the unit.
- G2 modules are blue and have a wire only on the back of the unit.
- There are now only two electronic module assembly variations for use with older Optima Plus valves:
- EBV-146-A-U Urinal
- EBV-146-A-C Water closet
- This chart cross references the part numbers and code numbers of our new electronic modules over from our old module numbers.
- The modules include the solenoid, inner cover and electronic module.
- These modules are for use with older Optima Plus and Regal Pro® Optima
- Plus® valves only.
BATTERY REPLACEMENT
- When Optima Plus has approximately 4,000 flushes left, the same red light that appears at start-up will flash four (4) times quickly whenever an object is detected. When this occurs, we recommend changing the batteries. On Optima Plus, shut off water and relieve pressure.
- Separate locking ring, cover and diaphragm from electronic sensor module.
- Loosen retaining screw on battery compartment door and remove battery compartment door. Install four (4) AA batteries exactly as illustrated. Install battery compartment door and secure with retaining screw. Make certain that battery compartment door is fully compressed against gasket to provide a seal; do not overtighten.
FLEX TUBE DIAPHRAGM ASSEMBLY
- In early 2003 Sloan introduced the flex tube diaphragm kit into the Optima Plus. This design completely replaced the old Optima Plus diaphragm kit that featured the metal shaft with the quad Ring. This change further improvedthe reliability of the Optima Plus as it replaced a wearable dynamic seal (the Quad Ring) with a non-moving static O-ring seal.
- The flex tube diaphragm kit also features Sloan’s exclusive dual-filter diaphragm. The dual-filter diaphragm helps to protect the valve from waterborne sediment that can cause the valve to stick open and run on. The dual-filter diaphragm is also made from Sloan’s Permex® synthetic rubbermaterial for resistance against chloramines and other water treatment chemicals.
- The flex tube diaphragm can be used to replace all generations of Sloan Optima Plus® diaphragm kits. The same flex tube diaphragm kits are used in the G2 Optima Plus® valve.
FLEX TUBE DIAPHRAGM KITS
REGULATORS
The flush volume of the flex tube diaphragm kit is controlled by the regulator. Regulators are identified by color. Some flex tube diaphragm kits are supplied with multiple regulators. The installer must make sure the proper regulator is used when installing the flex tube diaphragm kit.
OLD STYLE DIAPHRAGM INSIDE PARTS
SOLENOID REPLACEMENT
-
Remove battery cover and batteries from existing sensor module.
-
Disconnect the white plastic connector that connects the black and red wires on the side of the module.
-
Unscrew (counterclockwise) the existing solenoid valve from the base plate.
-
Remove white plastic seat and O-rings that are located inside the housing.
- Remove clear plastic housing from the threaded end of new operator by unscrewing (counterclockwise). It is normal to find water inside this housing.
-
Make sure O-ring is installed on the gray housing of the new operator. Install solenoid operator by threading it (clockwise) into the housing. Tighten with fingers beyond just snug.
-
Reinstall batteries in the correct position and reattach battery door.
-
Reconnect the white plastic connectors on the side of the module. Slide the white connector into the clip to secure. Tuck wiring in close to module. If valve runs, tighten solenoid further.
TROUBLESHOOTING GUIDE
IMPORTANT:
- The OPTIMA PLUS® flushometer is engineered for quiet operation. Excessive water flow creates noise, while too little water flow may not satisfy the needs of the fixture. Proper adjustment is made when plumbing fixture is cleansed after each flush without splashing water out from the lip AND a quiet flushing cycle is achieved.
- Never open Control Stop to where the flow from the valve exceeds the flow capability of the fixture. In the event of a valve failure, the fixture must be able to accommodate a continuous flow from the valve.
ATTENTION INSTALLERS: With the exception of the control stop inlet, DO NOT USE pipe sealant or plumbing grease on any valve component or coupling! To protect the chrome or special finish of Sloan flushometers, DO NOT USE toothed tools to install or service these valves. Use our A-50 Super-Wrench™ or other smooth-jawed wrench to secure couplings. Regulations for low consumption fixtures (1.6 gpf/6.0 Lpf closets and 1.0 gpf/3.8 Lpf urinals) prohibit use of higher flush volumes.
-
Sensor flashes continuously only when user steps within range.
Unit in start-up mode; no problem. This feature is active for the first ten (10) minutes of operation. -
Valve does not flush; sensor not picking up user.
- Range too short; increase the range.
- Optima Plus installed on a high rough-in fixture (beam is shooting over the user’s head). Install the EBV-46-A beam deflector (black modules only).
-
Valve does not flush; sensor picking up opposite wall or surface, or only flushes when someone walks by. Red light flashes continuously for first ten 10 minutes even with no one in front of the sensor.
-
Range too long; shorten range.
-
Sensor is picking up mirror or highly reflective wall or surface in front of fixture. Install Optima Plus® slightly “off-center” (2 to 5 degrees) to eliminate direct reflection off of mirror or opposite wall or surface.
-
-
Valve does not flush even after adjustment.
- Range adjustment potentiometer set at full “max” or full “min” setting. Readjust potentiometer away from full “max” or “min” setting.
- Batteries completely used up; replace batteries.
- Problem with electronic sensor module; replace electronic sensor module.
-
Unit flashes 4 quick times when user steps within range.
Batteries low; replace batteries. -
Valve does not shut off.
- By-pass orifice in diaphragm is clogged with dirt or debris, or by-pass is clogged by an invisible gelatinous film due to “over-treated” water. Remove diaphragm and wash under running water. Replace with new diaphragm if cleaning does not correct the problem.
- Dirt or debris fouling stem or flex tube diaphragm. Remove flex tube diaphragm and wash under running water.
- Solenoid problem. If cleaning does not correct the problem, replace with new solenoid operator.
-
Not enough water to fixture.
- Wrong Optima Plus flex tube diaphragm installed; i.e., 1.0 gpf urinal installed on 3.5 gpf closet fixture. Replace with proper diaphragm assembly.
- Enlarged by-pass in diaphragm. Replace with flex tube diaphragm kit.
- Control stop not adjusted properly. Readjust control stop.
- Inadequate volume or pressure at supply. Increase water pressure or supply (flow) to valve. Consult factory for assistance.
-
Too much water to fixture.
- Control stop not adjusted properly. Readjust control stop.
- Wrong Optima Plus flex tube diaphragm installed; i.e., 3.0 gpf model installed on 1.0 or 1.5 gpf urinal fixture. Replace with proper Optima Plus diaphragm assembly.
- Dirt in diaphragm by-pass. Clean under running water or replace with new flex tube diaphragm.
-
Men’s room closet bowls unflushed.
Closet being used as urinal. Angle sensor slightly off fixture centerline to detect standing person in front of fixture.
BATTERIES
When required, replace batteries with four (4) alkaline type AA batteries.
CARE AND CLEANING OF CHROME AND SPECIAL FINISHES
DO NOT USE abrasive or chemical cleaners to clean flushometers as they may
dull the luster and attack the chrome or special decorative finishes. Use ONLY
mild soap and water, then wipe dry with clean cloth or towel. While cleaning
the bathroom tile, the flushometer should be protected from any splattering of
cleaner. Acids and cleaning fluids can discolor or remove chrome plating.
When assistance is required, please contact Sloan Technical Support at:
1-888-SLOAN-14 (1-888-756-2614).