SIGMA 8 Inch Ductile Iron Wedge Action Flanged Universal Joint SBR Rubber O-Ring Instructions
- June 13, 2024
- SIGMA
Table of Contents
SIGMA 8 Inch Ductile Iron Wedge Action Flanged Universal Joint SBR Rubber
O-Ring
SIGMAFLANGETM Adapter
The SIGMAFLANGETM Adapter is a component used for connecting PVC or ductile
iron pipes. It is designed to be used in conjunction with the SIGMA ONE-LOK
restraining gland, which provides additional security and stability to the
joint.
Installation Instructions
To install the SIGMAFLANGETM Adapter, please follow these steps:
- Ensure you have the appropriate SIGMA installation instructions for PVC or ductile iron pipe.
- Prepare the pipe ends by cleaning and ensuring they are free from any dirt, debris, or damage.
- Apply a suitable lubricant or sealing compound to the gasket surfaces of the SIGMAFLANGETM Adapter.
- Align the SIGMAFLANGETM Adapter with the pipe ends, ensuring a proper fit.
- Tighten the bolts evenly, alternating between them, to secure the SIGMAFLANGETM Adapter in place.
- Refer to the specific SIGMA installation instructions for PVC or ductile iron pipe to properly install the SIGMA ONE-LOK restraining gland.
- Inspect the joint for any leaks or irregularities.
Please note that these installation instructions are general guidelines.
Always refer to the specific SIGMA installation instructions for PVC or
ductile iron pipe for detailed and accurate
installation procedures. For more information about SIGMA products, please
visit the official SIGMA Corporation website:
www.sigmaco.com.
April 2014 SIGMA Corporation
Installation Instructions
-
Examine the SIGMAFLANGE adapter sleeve to insure that all parts are free of damage and the SIGMA provided O-ring is properly secured in the cavity located on the face of the flanged end. Clean the pipe end thoroughly of any dirt or debris to facilitate the assembly of the mechanical joint gasket and provide a proper seal. Slide the SIGMA ONE-LOK™ restraining gland over the pipe end with the frontal lip facing the pipe end. Thoroughly apply soapy water or approved pipe lubricant per the ANSI/AWWA C111/A21.11 standard to the UL recognized mechanical joint gasket and the plain end of the pipe and slide the gasket over the plain end pipe making sure the tapered side of the gasket is facing the pipe end.
-
Install the SIGMAFLANGE adapter sleeve against the mating flanged outlet and insert the flange bolts in the corresponding bolt holes. Completely assemble the flanged joint (flange bolts are not included with the SIGMAFLANGE adapter). Insert the plain end pipe with the mechanical joint gasket and ONE-LOK restraining gland into the mechanical joint end of the adapter sleeve The pipe must be inserted into the SIGMAFLANGE sleeve a minimum distance of 2.125” on 3”-4”, 2.5” on 6”-12”, and 3” on 14”-24” in order to accommodate the maximum deflection in the joint.
-
Ensure that the pipe is centered and the spacing of the pipes outside diameter and adapter sleeve’s inside diameter are even throughout the entire circumference of the joint. Slide the mechanical joint gasket forward and seat evenly inside the mechanical joint cavity of the adapter sleeve, followed by the ONE-LOK restraining gland and hand tighten the necessary t-head bolts and nuts in the corresponding bolt holes. If joint deflection is required, make deflection following joint assembly but before tightening the bolts.
-
Install the SIGMA ONE-LOK restraining gland in accordance with the SIGMA installation instructions as appropriate for PVC or ductile iron pipe.