legrand G3043GE Duplex Grounding Receptacle And Cover Installation Guide

June 13, 2024
Legrand

legrand G3043GE Duplex Grounding Receptacle And Cover

3000® Series Raceway provides wiring capacities for small to medium size installations. Power, communication, or A/V devices can be wired into the raceway for a flush appearance satisfying both aesthetic and functional requirements. 3000 Series Raceway is ideally suited for wiring applications in frequently changing environments such as labs, hospitals and other industrial applications.

FEATURES AND BENEFIT

  • Entrance knockouts are spaced at regular intervals along length of base. Allows power wiring, communication, or A/V cables to be brought in at a convenient point.
  • Mounts easily on walls, modular furniture, under raised floors, or over ceiling. Speeds installation; provides flexibility to bring wiring to points of use.
  • Removable cover. Provides access to wiring.
  • Accommodates a variety of receptacles, three-pole circuit breaker housings, and other protective devices. Provides flexibility for sophisticated wiring systems.
  • Complete line of fittings. Provides a complete wiring solution and allows for interconnection between raceway systems.
  • Available prewired. Manufactured to specified job site lengths, race way comes electrically prewired, ready to install. Jobs can be packaged by room, area, floor, or building and shipped per your job site requirements.
  • Electrical device identification for the prewired raceway. See page six for labeling options. Eliminates guesswork or time-consuming circuit tracing and speeds additions and renovations.
  • Compatible with A/V devices by using 5507 Series Faceplates.
  • Gray baked enamel and ivory ScuffCoat™ finish. Durable ivory ScuffCoat finish makes a scratch resistant surface.
  • Base and cover cutters. Manually operated cutters are lightweight and portable. Cutters offer labor savings for any size job and maintain a factory clean and square cut.
  • Datacom connectivity options. Accepts industry standard and proprietary devices from a wide range of manufacturers to provide a seamless and aesthetically pleasing interface for voice, data, audio, and video applications at the point of use.
  • UL Listed factory multioutlet assemblies. Listed by Underwriters Laboratories Inc. Multioutlet assemblies file number E15191 Guide (PVGT)/ Fittings file number E41751 Guide (RJPR).
  • UL5 and ADA compliant. Raceway and fittings meet UL5 specifications and can be installed in conformance with ADA requirements.
  • UL Listed and CSA Certified raceway. Listed by Underwriters Laboratories Inc. Raceway file number E4376 Guide (RJBT)/ Fittings file number E41751 Guide (RJPR) CSA Certified LR350.

3000 Series System Layoutlegrand G3043GE Duplex Grounding Receptacle
And Cover 1

NOTE : Illustration is for showing product applications only.

3000 Series Raceway Ordering Information

legrand G3043GE Duplex Grounding Receptacle And Cover
2

legrand G3043GE Duplex Grounding Receptacle And Cover
3 legrand G3043GE Duplex Grounding
Receptacle And Cover 4 legrand
G3043GE Duplex Grounding Receptacle And Cover 5

Add C prefix to denote Canadian version – CSA certified.

3000 Series Raceway Prewired Features


FEATURES| STANDARD| OPTIONS
Communication Devices| Ortronics or Activate Connectivity

System Devices

| Other manufacturers
Electrical Devices| Pass & Seymour| Other manufacturers and some International devices
Body Length| Longest = 10′ (2.54m), shortest = 1′ (305mm)| —
Installation| Surface mounted| —
Finish| Baked enamel finish

custom colors

| Standard colors of baked powder epoxy or
Wire Type| THHN stranded| Options per specification
Wiring Splices| Insulation displacement connectors| Continuous wiring or twist-on wire connector
Grounding Conductors| Wire gauge per National Electrical

Code (NEC) and shared grounding wires

| Oversized and/or separate grounding wires
Device Identification| Gray self-adhesive polyester label

with black letters devices available

| Self-adhesive engraved nameplate,

Interlink labeling software for communication

Neutrals| Shared neutral| Oversized and/or separate neutral wires
Pigtails| 12″ (305mm) feeds and receptacle leads| Per specification
Conduit Feeds| Raceway drilled at job site| Entrance end cap
Device Mounting| Steel plates| —
Record Drawings| Three sets and two copies of

marked-up blueprints

| Per job requirements
Submittal Services| Detailed submittal| Submittal free

3000 Series Ordering Specifications for Prewired Applications

Two options available when ordering a prewired job:

  1. Detailed Submittal
    The detailed submittal will show exactly how each raceway run will be built including lengths, number and type of receptacles, wiring schematics, circuiting information, etc. The contractor and/or distributor must review, clarify any information not clearly indicated on the drawings or specs, approve and return to the factory before production can begin.

  2. Submittal Free
    The Wiremold Prewired Checklist is filled out by the contractor or distributor and sent along with plans, casework and specs to the factory. No submittal is required and the project is scheduled for production upon receipt of all necessary information.

Device and Raceway Labeling Detail for Prewired Applications

  • Device labeling is available in the following materials: Gray self-adhesive polyester label with black lettering (standard). Other color self-adhesive polyester labels. Engraved phenolic nameplates with adhesive backing.
  • The back of the raceway is labeled with the raceway number and the room or area number(s).

3000 Series Raceway Wire Fill Capacities

3000 Series Raceway Wire Fill Capacities For Power

| | NUMBER OF CONDUCTORS (40% Fill)
WIRE SIZE THHN/THWN| O.D.

inches

| ****

(mm)

| WITHOUT DEVICES| WITH DUPLEX/ RECT. DEVICES 1.59 in. 2 (1025mm)| WITH SURGE/ GFCI DEVICES 2.30 in. 2 (1485mm)| LARGE SINGLE RECEPTACLES 3.00 in. 2 (1935mm)
14| AWG| 0.111| (2.8)| 152| 70| 40| 28
12| AWG| 0.130| (3.3)| 111| 51| 29| 21
10| AWG| 0.164| (4.2)| 70| 32| 18| 13
8| AWG| 0.216| (5.5)| 40| 18| 10| 7
6| AWG| 0.254| (6.5)| 29| 13| 7| 5

3000 Series Raceway Cable Fill Capacities for Communications

3000 Series Raceway Cable Fill Capacities for Communicatio ns
CABLE/WIRE SIZE O.D.

Inches (mm)

| 40% FILL
UNSHIELDED TWISTED PAIR| 4-PAIR, 24 AWG Cat 3

4-PAIR, 24 AWG Cat 5e

4-PAIR, 24 AWG Cat 6

4-PAIR, 24 AWG Cat 6a*

25-PAIR, 24 AWG

| 0.190                      (4.8)

0.210                      (5.3)

0.250                      (6.3)

0.354                      (8.9)

0.410                    (10.4)

| 52

42

30

15

11

COAXIAL| RG6/U| 0.270                       (6.9)| 25
FIBER| ZipCord

Round 4 Strand Fiber Round 6 Strand Fiber

| 0.118 x 0.236       (3 x 6)

0.187                       (4.5)

0.256                       (6.5)

| 53

53

28

Category 6 augmented (6a) cable for 10 gigabit ethernet – max allowed cable diameter per addenda No. 11 ANSI TIA/EIA 568-B.2.
NOTE : All brand and product names referenced in this document are registered trademarks or trademarks of their respective holders.
NOTE : The paper used to print this document is an environmentally responsible paper with 10% post consumer waste, with FSC and SFI Chain of Custody certifications, Lacey Act complaint. 100% of the electricity used to manufacture Flo sheets is generated with Green-e certified renewable energy.

Electrical Wiring Systems
60 Woodlawn Street
West Hartford, CT 06110
Phone: 1.877.BY.LEGRAND (295-3472)
www.legrand.us
570 Applewood Crescent
Vaughan, Ontario L4K 4B4
Phone:905.738.9195
www.legrand.ca

Documents / Resources

| legrand G3043GE Duplex Grounding Receptacle And Cover [pdf] Installation Guide
G3043GE Duplex Grounding Receptacle And Cover, G3043GE, Duplex Grounding Receptacle And Cover, Grounding Receptacle And Cover, Receptacle And Cover
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals