Specifications

  • Power Supply: 230 V~
  • Power Consumption: 7 VA max (models with relay output), 70 VA (models with dosing-shot)
  • Environment: Operating temperature, storage temperature, RH max 90% noncondensing
  • Display: 2-row alphanumeric LCD with backlight
  • Digital Inputs: OFF/FLW input, AUX input, TC input
  • Relay Outputs: 2 independent outputs, max load 250 V~, 3 A resistive
  • Dosing-shot Output: Directly drives pump magnet, standard pulse 300 V and 90 msec, max frequency 120 pulses/minute
  • Current Output: 0-20 or 4-20 mA, max load 600 Ohm
  • Serial Output: RS232 port
  • Casing: ABS, water-tight housing, IP66 protection rate
  • Dimensions: 240 x 300 x h 120 mm; Weight approx. 1.5 kg

Product Usage Instructions

Installation:

  • Ensure the power supply matches the product’s requirements.
  • Mount the instrument securely on a wall using the provided template and screws.
  • Connect the necessary probes and inputs to the corresponding terminals.

Configuration

  • Power on the instrument and navigate through the configuration menu using the display.
  • Select the appropriate measurement ranges for each input based on your requirements.

Calibration

  • Perform calibration for pH, conductivity, and chlorine readings using standard calibration solutions.
  • Follow the calibration instructions provided in the user manual for accurate measurements.

Maintenance

  • Regularly check and clean the probes to ensure accurate readings.
  • Keep the instrument’s casing clean and free from any obstructions.

Instruction

  • Series of digital, single-parameter units, designed for wall installation.
  • All models feature an output configurable as “dosing-shot” for directly driving an electronic-free dosing pump. This function is very useful when the pump is installed in humid environments or in the presence of fumes, that may damage the electronic board.
  • Moreover, the instrument is equipped with two output relays (settable as set-point or alarm), one current output galvanically isolated, and one serial port to communicate with a PC/PLC (optional software).
  • All outputs can be temporary disabled (for example for maintenance purpose) through the START/STOP button.
  • The display language is user-selectable among the 4 available options (Italian, English, French or Spanish).
  • Errors and alarms are shown directly on the display, and configuration and calibration data are stored in the nonvolatile memory for at least 10 years.

The S507 series includes several models with input for pH/redox electrode, two-electrode CLE cell (for measuring chlorine, bromine, or chlorine dioxide), CAC series cell, conductivity probe, turbidity cell, and standard input.
All models feature an input for Pt100 temperature probe, for temperature measurement and compensation of pH, conductivity, and chlorine readings.

Model Description Code
S507-pH/RX/T Input for pH or ORP electrode + Pt100 probe 80050040
S507-CO Input for 2-electrode conductivity cell + Pt100 sensor;

measurement range selectable through configuration menu

| 80240040
S507-ACL| Input for CLE11 (or CLE12) cell; range to be specified
S507-CAC| Input for CAC cell; range to be specified
S507-TU| Input for turbidity cell| 85700026
S507-IN| Indicator with 0-20 or 4-20 mA input; range to be specified| 80710170

Note: The above part numbers refer to instruments with 230 V~ power supply. Versions with different power supply are also available upon request.

TECHNICAL DATA

Common Characteristics for All Models

  • Power Supply 230 V~ ±10% 50/60 Hz (115 or 24 V~, or 24 V- upon request)
  • Power Consumption 7 VA max (models with relay output) 70 VA (models with K1 configured as “dosing-shot”)
  • Protections PTC fuse appropriate to the power supply voltage. If K1=dosing-shot and 230 V~ power supply, F 250 mA, 5×20 fuse
  • Environment storage temperature -20 to +60 °C operating temperature -10 to +50 °C RH max 90% noncondensing
  • Display 2-row, alphanumeric LCD (16 digits per row), with backlight.
  • Digital Inputs 1 OFF/FLW input for disabling outputs; for voltage-free contact; 5 V voltage at terminals, current max 5 mA. 1 AUX (auxiliary) input, available on special models. 1 TC (temperature control) input, internal input, only for K1= dosing-shot
  • Relay Outputs 2 independent outputs on removable, 5-pole terminal block; max load 250 V~, 3 A resistive
  • Dosing-shot Output factory setting of K1 relay for directly driving of the pump magnet; standard pulse 300 V and 90 msec, max frequency 120 pulses/minute (not available for 24 V- or 24 V~ power supply versions)
  • Current Output 0-20 or 4-20 mA (selectable through software), max load 600 Ohm, error max 0.5% FS; provided with galvanic insulation.
  • Serial Output RS232 port on removable, 4-pole terminal block
  • Casing ABS, water-tight housing, for wall installation with 4 screws
  • Protection Rate IP66
  • Dimensions 240 x 300 x h 120 mm; fixing template 220 x 185 mm
  • Weight approx. 1.5 kg
  • Analogue Inputs precision better than 0.3% FS; repeatability better than 0.2% FS
  • Temperature Input removable, 2-pole terminal block, for connection of Pt100 sensor; standard range: -50…+200 °C

Analogic Input, depending on Model.

  • pH / ORP Input available on 4-pole removable terminal block (coaxial cable + reference); input impedance > 10^12 Ω standard ranges: 0…14 pH / ORP ±1000 mV
  • Input for CLE Cell available on 4-pole removable terminal block, for 2-electrode amperometric cell (copper/platinum + shield)
  • Input for CAC Cell available on 4-pole removable terminal block (power supply + signal)
  • Conductivity Probe available on removable terminal block, for 2-electrode cell + shield
  • Turbidity Cell available on removable terminal block, for CTS07 cell
  • Standardized Input available on 4-pole removable terminal block (specify input type, range, and transducer power supply, if any)

STEIEL ELETTRONICA Srl
tel. +39 049 8961488
[email protected]
www.steiel.it S507_scheda rev4.1-2023 GB.docx

FAQ

Q: How long is the data stored in the nonvolatile memory?

A: Configuration and calibration data are stored for at least 10 years in the nonvolatile memory.

Q: Can I use different power supply versions with this product?

A: Yes, versions with different power supply options are available upon request. Contact customer support for more information

Q: What is the maximum frequency for the dosing-shot output?

A: The maximum frequency for the dosing-shot output is 120 pulses per minute.

References