XTREME XBDM Bypass Distribution Module User Guide

June 13, 2024
Xtreme

XTREME XBDM Bypass Distribution Module

INTORDUCTIONS

Repair or replace your UPS without power interruption by manually transferring critical loads from UPS power to utility power using the XBDM

The XBDM ensures continuous uptime for your critical electronics. This maintenance bypass module allows you to manually transfer critical loads from UPS power to utility power using a bypass switch, enabling UPS repair or replacement without power interruption to the load. Transferring back to protected UPS power is just as easy; simply return the bypass switch to the UPS position.

Read the Hot Swappable UPS white paper at www.xpcc.com/whitepaper For hardwired XBDM models, reference www.xpcc.com/xbdmhw

PRODUCT SNAPSHOT

Available in: 15AMP, 20AMP, and 30AMP models
Simplifies UPS repair or replacement and reduces costly downtime
Easy cord connection to UPS
Offers surge protection during UPS and utility mode
Bypass switch provides transfer within 4–8ms

FEATURES

Power distribution— the XBDM adds up to ten output receptacles and combines bypass functionality with power distribution capability in one enclosure enclosure
Replace or service the UPS— while maintaining power to critical loads
Easy installation— both the UPS and utility power are connected to the XBDM with the supplied cords
Simple to operate— LED indicators verify availability of UPS and utility sources to confirm to the operator that power is available before transferring critical loads Surge protection—loads are surge protected even when UPS is in bypass mode; UPS electronics are protected during normal operation
Flexible mounting— supports horizontal 1U rack mount and vertical rack mount installation

MODEL SELECTION GUIDE

For more information, visit www.xpcc.com/xbdm

MODEL NUMBER XBDM-1015LV XBDM-1020LV XBDM-1030LV XBDM-1020HV
POWER RATING Voltage/current 120VAC/15A 120VAC/20A 120VAC/30A
INPUT Utility input 12 ft, 5–15P 12 ft, 5–20P 6 ft, L5–30P
AC frequency 50/60Hz 50/60Hz 50/60Hz 50/60Hz
OUTPUT Maximum output 12A 16A 24A
RECEPTACLES Front output (6) 5–15R (6) 5–20R (5) 5–20R
Rear output (4) 5–15R (4) 5–20R (5) 5–20R (4) C13
Rear UPS input (1) 5–15R (1) 5–20R (1) L5–30R (1) C19
TRANSFER SWITCH Quantity and capacity (1) 15A (1) 20A (2) 20A
UPS OUTPUT Cord to UPS output 3 ft, 5–15P 3 ft, 5–20P 3 ft, L5–30P

C20
AC SURGE| Max spike current| 6500A| 6500A| 6500A| 6500A
Energy dissipation| 114J| 114J| 114J| 220J
Max clamping voltage| 330VAC| 330VAC| 330VAC| 330VAC
INDICATORS| UPS available| Red LED
Utility available| Orange LED
Surge protection| Green LED
PHYSICAL| Dimensions (W x D x H)| 17 x 3.5 x 1.75 in (1U)
Weight| 3.5 lbs
INCLUDED IN BOX| 19″ rack mounting hardware, user manual, power cords (120VAC models)

The XBDM features two modes of operation:

1 ) Utility mode CONNEC TED LOADS Utility power bypasses the UPS system and is supplied to the load directly
2) UPS mode Power is routed through the UPS system to the connected load

Utility mode

UPS mode

Customer Service

Protect your business.
XPC USA / Denver, CO / sales@xpcc.com
XPC EMEA / Rotterdam, NL / emea@xpcc.com
www.xpcc.com
©2015 Xtreme Power Conversion Corporation. All Rights Reserved. XBDM.01U (Rev 3/16/15)
XTREME Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals