XTREME XBDM Bypass Distribution Module User Guide
- June 13, 2024
- Xtreme
Table of Contents
XTREME XBDM Bypass Distribution Module
INTORDUCTIONS
Repair or replace your UPS without power interruption by manually transferring critical loads from UPS power to utility power using the XBDM
The XBDM ensures continuous uptime for your critical electronics. This maintenance bypass module allows you to manually transfer critical loads from UPS power to utility power using a bypass switch, enabling UPS repair or replacement without power interruption to the load. Transferring back to protected UPS power is just as easy; simply return the bypass switch to the UPS position.
Read the Hot Swappable UPS white paper at www.xpcc.com/whitepaper For hardwired XBDM models, reference www.xpcc.com/xbdmhw
PRODUCT SNAPSHOT
› Available in: 15AMP, 20AMP, and 30AMP models
› Simplifies UPS repair or replacement and reduces costly downtime
› Easy cord connection to UPS
› Offers surge protection during UPS and utility mode
› Bypass switch provides transfer within 4–8ms
FEATURES
Power distribution— the XBDM adds up to ten output receptacles and
combines bypass functionality with power distribution capability in one
enclosure enclosure
Replace or service the UPS— while maintaining power to critical loads
Easy installation— both the UPS and utility power are connected to the
XBDM with the supplied cords
Simple to operate— LED indicators verify availability of UPS and utility
sources to confirm to the operator that power is available before transferring
critical loads Surge protection—loads are surge protected even when UPS is in
bypass mode; UPS electronics are protected during normal operation
Flexible mounting— supports horizontal 1U rack mount and vertical rack
mount installation
MODEL SELECTION GUIDE
For more information, visit www.xpcc.com/xbdm
MODEL NUMBER | XBDM-1015LV | XBDM-1020LV | XBDM-1030LV | XBDM-1020HV |
---|---|---|---|---|
POWER RATING | Voltage/current | 120VAC/15A | 120VAC/20A | 120VAC/30A |
INPUT | Utility input | 12 ft, 5–15P | 12 ft, 5–20P | 6 ft, L5–30P |
AC frequency | 50/60Hz | 50/60Hz | 50/60Hz | 50/60Hz |
OUTPUT | Maximum output | 12A | 16A | 24A |
RECEPTACLES | Front output | (6) 5–15R | (6) 5–20R | (5) 5–20R |
Rear output | (4) 5–15R | (4) 5–20R | (5) 5–20R | (4) C13 |
Rear UPS input | (1) 5–15R | (1) 5–20R | (1) L5–30R | (1) C19 |
TRANSFER SWITCH | Quantity and capacity | (1) 15A | (1) 20A | (2) 20A |
UPS OUTPUT | Cord to UPS output | 3 ft, 5–15P | 3 ft, 5–20P | 3 ft, L5–30P |
C20
AC SURGE| Max spike current| 6500A| 6500A| 6500A| 6500A
Energy dissipation| 114J| 114J| 114J| 220J
Max clamping voltage| 330VAC| 330VAC| 330VAC| 330VAC
INDICATORS| UPS available| Red LED
Utility available| Orange LED
Surge protection| Green LED
PHYSICAL| Dimensions (W x D x H)| 17 x 3.5 x 1.75 in (1U)
Weight| 3.5 lbs
INCLUDED IN BOX| 19″ rack mounting hardware, user manual, power cords (120VAC
models)
The XBDM features two modes of operation:
1 ) Utility mode CONNEC TED LOADS Utility power bypasses the UPS system
and is supplied to the load directly
2) UPS mode Power is routed through the UPS system to the connected load
Utility mode
UPS mode
Customer Service
Protect your business.
XPC USA / Denver, CO / sales@xpcc.com
XPC EMEA / Rotterdam, NL / emea@xpcc.com
www.xpcc.com
©2015 Xtreme Power Conversion Corporation. All Rights Reserved. XBDM.01U (Rev
3/16/15)
References
- Xtreme Power Conversion | Protect your business.
- White Papers | Xtreme Power Conversion
- XBDM Bypass Distribution Module | Xtreme Power Conversion
- XBDM HW Bypass Distribution Module | Xtreme Power Conversion
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>