FW MURPHY LP1095 M-VIEW 12 Inch Touch Display Owner's Manual
See the FW Murphy website at www.fwmurphy.com for full user manual, M-VIEW DESIGNER 3.1 software and software manual.
SAFETY SUMMARY
All safety related regulations, local codes as well as instructions that
appear in this document or on equipment must be observed to ensure personal
safety and to prevent damage to either the device or equipment connected to
it.
Do not use these products to replace proper safety interlocking. No software-
based device (or any other solid-state device) should ever be designed to be
responsible for the maintenance of personnel safety or consequential equipment
not equipped with safeguards. FW Murphy disclaims any responsibility for
damages, either direct or consequential, that result from the use of this
equipment in a manner not consistent with these specifications.
⚠ WARNING – EXPLOSION HAZARD – DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS
BEEN SWITCHED OFF OR AREA IS KNOWN TO BE NON-HAZARDOUS.
⚠ WARNING – EXPLOSION HAZARD – SUBSTITUTION OF COMPONENTS MAY IMPAIR
SUITABILITY FOR CLASS I, DIVISION
ORDERING INFORMATION
SPECIFICATIONS
Must use a Class 2 circuit according to National Electrical Code (NEC),
NFPA-70 or Canadian Electrical Code (CEC), Part I, C22.1 or a Limited Power
Supply (LPS) according to IEC/EN 60950-1 or Limited-energy circuit according
to IEC/EN 61010-1. Power connection via removable three position terminal
block.
BATTERY: Lithium coin cell. Typical lifetime of 6 years nominal. To maintain
UL rating, replacement battery must be: Rayovac BR2032-BA or Panasonic BR2032.
DIMENSIONS In inches (mm)
ENVIRONMENTAL
CONDITIONS: Operating Temperature Range: -20 to 60 °C, or lowest range among
equipment used in your M-VIEW system. Consult the user manual for further
details. Storage Temperature Range: -20 to 70 °C Vibration to IEC 68-2-6:
Operational 5-500 Hz, 4 g Shock to IEC 68-2-27: Operational 40 g (10 g,
modules w/relays) Operating and Storage Humidity: 0 to 85% max. RH non-
condensing Altitude: Up to 2000 meters Installation Category II, Pollution
Degree 2 as defined in IEC/EN 60664-1.
CERTIFICATIONS AND COMPLIANCES: CE Approved EN 61326-1 Immunity to Industrial
Locations Emission CISPR 11 Class A IEC/EN 61010-1 RoHS Compliant ATEX
Approved II 3 G Ex ic nA IIC T4 Gc II 3 D Ex tc IIIC T135°C Dc DEMKO 14 ATEX
1387X
EN 60079-0, -11, -15, -31 IECEx Approved
Ex ic nA IIC T4 Gc Ex tc IIIC T135°C Dc IECEx UL 15.0035X
IEC 60079-0, -11, -15, -31 UL Listed: File #E302106 UL Hazardous: File
E317425 Type 4X Indoor/Outdoor Enclosure rating (Face only) IP20 Enclosure
rating (Rear of unit) ABS Type Approval for Shipboard Applications
CONNECTIONS: High compression cage-clamp terminal block Wire Strip Length:
0.3″ (7.5 mm) Wire Gauge Capacity: One 14 AWG (1.63 mm) solid,
two 18 AWG (1.02 mm) or four 20 AWG (0.81 mm) CONSTRUCTION: Cast aluminum
enclosure with NEMA 4X/IP66 rating
when correctly fitted with the gasket provided. These devices have only been
evaluated for low risk of mechanical impact. WEIGHT: 5.06 lb. (2.29 Kg)
OPERATOR INTERFACE INSTALLATION
MOUNTING INSTRUCTIONS
For hazardous location installation the following shall be taken into
consideration:
– When used in a Zone 22 environment, the device shall be panel mounted in at
least Zone 22 IECEx/ATEX-Certified tool accessible enclosure with a minimum
ingress protection rating of at least IP64 as defined in IEC/EN 60529.
– When used in a Zone 2 environment, the device shall be panel mounted in at
least Zone 2 IECEx/ATEX-Certified tool accessible enclosure with a minimum
ingress protection rating of at least IP54 as defined in IEC/EN 60529.
– This device is open-type and must be mounted in a suitable dust-tight end-
enclosure in accordance with articles 500 and 502 of the NEC and positioned so
only the face of the display is exposed.
– Must be wired using Division 2 wiring methods as specified in article
501-4(b), 502-4(b), and 503-3(b) of the National Electric Code, NFPA 70 for
installation within the United States, or as specified in section 19-152 of
Canadian Electrical Code for installation in Canada.
PANEL CUT-OUT
CONNECTING TO EARTH GROUND
Each operator panel has a chassis ground terminal on the back of the unit.
Your unit should be connected to earth ground. Steps should be taken beyond
connecting to earth ground to eliminate the buildup of electrostatic charges.
The chassis ground is not connected to signal common of the unit. Maintaining
isolation between earth ground and signal common is not required to operate
your unit. But, other equipment connected to this unit may require isolation
between signal common and earth ground. To maintain isolation between signal
common and earth ground care must be taken when connections are made to the
unit. For example, a power supply with isolation between its signal common and
earth ground must be used. Also, plugging in a USB cable may connect signal
common and earth ground.1
1 USB’s shield may be connected to earth ground at the host. USB’s shield in
turn may also be connected to signal common.
POWER SUPPLY REQUIREMENTS The MV-12T requires a 10-30 VDC power supply. Your
unit may draw
considerably less than the maximum rated power depending upon the features
being used. As additional features are used your unit will draw increasing
amounts of power. Items that could cause increases in current are modules,
additional on-board communications, SD card, and other features programmed
through M-VIEWTM DESIGNER 3.1.
To ensure you do not exceed the capacity of your M-VIEW host power supply,
calculate the total power consumption required for all of your planned
modules. Each module’s maximum power consumption is listed in the
Specifications of their Product Bulletin. The total power available for
modules is listed in the specifications of the M-VIEW host.
In any case, it is very important that the power supply is mounted correctly
if the unit is to operate reliably. Please take care to observe the following
points:
The power supply must be mounted close to the unit, with usually not more
than 6 feet (1.8 m) of cable between the supply and the operator interface.
Ideally, the shortest length possible should be used.
The wire used to connect the operator interface’s power supply should be at
least 22-gage wire suitably rated for the temperatures of the environment to
which it is being installed. If a longer cable run is used, a heavier gage
wire should be used. The routing of the cable should be kept away from large
contactors, inverters, and other devices which may generate significant
electrical noise.
A power supply with an NEC Class 2 or Limited Power Source (LPS) and SELV
rating is to be used. This type of power supply provides isolation to
accessible circuits from hazardous voltage levels generated by a mains power
supply due to single faults. SELV is an acronym for “safety extra-low
voltage.” Safety extra-low voltage circuits shall exhibit voltages safe to
touch both under normal operating conditions and after a single fault, such as
a breakdown of a layer of basic insulation or after the failure of a single
component has occurred. A suitable disconnect device shall be provided by the
end user.
I/O MODULE INSTALLATION
The physical order of all installed modules must match the modules order in M-VIEW DESIGNER 3.1. Torque screws to 6.0 pound-force inch [96 ounce-force inch] (0.68 N m).
COMMUNICATING WITH THE MV-12T
CONFIGURING AN MV-12T
The MV-12T is configured using M-VIEWTM DESIGNER 3.1 software, which is
available as a no charge download from FW Murphy’s website. The software
updates for new features and drivers are posted on the website as they become
available. By configuring the MV-12T using the latest software version, you
are assured that your unit has the most up to date feature set. The software
can configure the MV-12T through the RS232 PGM port, USB port, or SD card.
The USB port is connected using a standard USB cable with a Type B connector.
The driver needed to use the USB port will be installed with the software.
The RS232 PGM port uses a programming cable made by FW Murphy to connect to
the DB9 COM port of your computer. If you choose to make your own cable, use
the “MV-12T Port Pin Out Diagram” for wiring information.
The SD card can be used to program an MV-12T by placing an image file on the
SD card. The card is then inserted into the target MV-12T and powered. Refer
to the M-VIEW DESIGNER 3.1 literature for more information on the proper names
and locations of the files.
USB, DATA TRANSFERS FROM THE SD CARD
WARNING – DO NOT CONNECT OR DISCONNECT CABLES WHILE POWER IS APPLIED UNLESS
AREA IS KNOWN TO BE NON-HAZARDOUS. USB DEVICE PORT IS FOR SYSTEM SET-UP AND
DIAGNOSTICS
In order to transfer data from the SD card via the USB port, a driver must be
installed on your computer. This driver is installed with M-VIEW DESIGNER 3.1
and is located in the folder C:Program FilesFW MuprhyM-VIEW DESIGNER 3.1Device
after the software is installed.
This may have already been accomplished if your MV-12T was configured using
the USB port.
Once the driver is installed, connect the MV-12T to your PC with a USB cable,
and follow “Mounting the SD” instructions in the M-VIEW DESIGNER 3.1 User
Manual.
INSERTION/REMOVAL OF THE SD CARD
Insert the SD card into the slot provided with the card oriented as shown. The
card is inserted properly when the end of the card is flush with the MVIEW
case. To remove the SD card, push in slightly on the card.
BATTERY & TIME KEEPING
WARNING – EXPLOSION HAZARD – DISCONNECT POWER AND ENSURE THE AREAS IS KNOWN TO BE NON-HAZARDOUS BEFORE SERVICING/REPLACING THE UNIT AND BEFORE INSTALLING OR REMOVING I/O WIRING AND BATTERY.
CAUTION: Lithium battery. Danger of explosion if battery is incorrectly
replaced. Replace only with the same or equivalent type recommended by the
manufacturer.
A battery is used to keep time when the unit is without power. Typical
accuracy (at 25°C) of the M-VIEW time keeping is less than one minute per
month drift. The battery of an M-VIEW unit does not affect the unit’s memory,
all configurations and data is stored in non-volatile memory.
Changing the Battery To change the battery of an M-VIEW, first remove power to
the unit.
Remove the battery cover. Grasp the top edge of the battery and push to the
left to remove the battery from the holder. Lift the battery out and replace
with a new battery.
Replace the battery cover, and re-apply power. Use the unit keypad, or follow
the procedure described in the “Setting the Time and Date” section of the
M-VIEW DESIGNER 3.1 User Manual to enter the correct time and date.
- Please note that the old battery must be disposed of in a manner that complies with your local waste regulations. The battery must not be disposed of in fire, or in a manner whereby it may be damaged and its contents could come into contact with human skin.
Warranty – A limited warranty on materials and workmanship is given with this FW Murphy product. A copy of the warranty may be viewed or printed by going to http://www.fwmurphy.com/warranty
FW MURPHY PRODUCTION CONTROLS
SALES, SERVICES & ACCOUNTING
4646 S. HARVARD AVE.
TULSA, OK 74135
CONTROL SYSTEMS & SERVICES
105 RANDON DYER ROAD
ROSENBERG, TX 77471
MANUFACTURING
5757 FARINON DRIVE
SAN ANTONIO, TX 78249
DOMESTIC SALES & SUPPORT
FW MURPHY PRODUCTS
PHONE: 918 957 1000
EMAIL: INFO@FWMURPHY.COM
WWW.FWMURPHY.COM
FW MURPHY CONTROL SYSTEMS & SERVICES
PHONE: 281 633 4500
EMAIL: CSS-SOLUTIONS@FWMURPHY.COM
INTERNATIONAL SALES & SUPPORT
CHINA
PHONE: +86 571 8788 6060
EMAIL: INTERNATIONAL@FWMURPHY.COM
LATIN AMERICA & CARIBBEAN
PHONE: +1918 9571000
EMAIL: INTERNATIONAL@FWMURPHY.COM
SOUTH KOREA
PHONE: +82 70 7951 4100
EMAIL: INTERNATIONAL@FWMURPHY.COM