Schneider Electric HDPM6000 METSEHDP150A30H Split Core Current Transformer Installation Guide

June 13, 2024
Schneider Electric

Power Logic™ HDPM6000 Series Current Transducer Models
Installation Guide

HDPM6000 METSEHDP150A30H Split Core Current Transformer

** The Power Logic ™** HDPM6000 series low-voltage current transducers (LVCT) provide secondary AC voltage proportional to the primary (sensed) alternating current. For use with the HDPM6000 platform only, these current transducers provide a means to transform electrical service amperages to a voltage compatible with monitoring equipment.
www.se.com
HDPM6000 Series Current Transducer Models
Refer to the following installation guides (part number):
HDPM6000B (Z208131), HDPM6000 Head Unit (Z208128), HDPM6000 I/O Module (Z208142),
HDPM6000R (Z208129), HDPM6000S24 (Z208449) and HDPM6000S (Z208130).

Safety Information

Important Information
Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of either symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Please Note
Electrical equipment should be installed, operated, serviced and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. A qualified person is one who has skills and knowledge related to the construction, installation and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.

Safety Precautions

Installation, wiring, testing and service must be performed in accordance with all local and national electrical codes.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E in the USA or applicable local standards.
  • This equipment must only be installed and serviced by qualified electrical personnel.
  • Turn off all power supplying equipment before working on or inside the equipment.
  • Product may use multiple voltage/power sources. Disconnect all sources of power before servicing.
  • Always use a properly rated voltage sensing device to confirm power is off.
  • Do not depend on this product for voltage indication.
  • Products rated for basic insulation must be installed on insulated conductors.
  • Replace all doors, covers and protective devices before powering the equipment.
  • Install device in an appropriate electrical and fire enclosure per local regulations
  • This product is not intended for life or safety applications.

Failure to follow these instructions will result in death or serious injury.
WARNING
RISK OF INJURY OR EQUIPMENT DAMAGE
Do not apply current transducer to circuits having a phase-to-phase voltage greater than their voltage rating unless adequate additional insulation is applied between the primary conductor and the current transducers.
Failure to follow these instructions can result in injury, fire or equipment damage.
Schneider Electric assumes no responsibility for damage of equipment or personal injury caused by products operated on circuits above their published ratings.

Ordering Information

CTs Compatible With HDPM6000 Head Unit, HDPM6000R Retrofit Module and I/O Module

Commercial Reference / Model| Lead Length| Weight| Form Factor| Accuracy| Description| Type of CT
METSEHDPM20A12H| 12 ft (3.66 m)| 1.088 lb (0.494 kg)| SUN2| 0.2%| 20 A CT| Split-Core
METSEHDPM20A30H| 30 ft (9.14 m)| 1.946 lb (0.883 kg)
METSEHDPM75A12| 12 ft (3.66 m)| 0.350 lb (0.159 kg)| CTMF| 1.0%| 75 A CT
METSEHDPM75A12H| 12 ft (3.66 m)| 1.137 lb (0.516 kg)| SUN3| 0.2%
METSEHDPM75A30| 30 ft (9.14 m)| 0.710 lb (0.322 kg)| CTMF| 1.0%
METSEHDPM75A30H| 30 ft (9.14 m)| 1.996 lb (0.905 kg)| SUN3| 0.2%
METSEHDPM75A60| 60 ft (18.29 m)| 2.305 lb (1.046 kg)| CTMF| 1.0%
METSEHDPM125A12| 12 ft (3.66 m)| 0.350 lb (0.159 kg)| CTTG| 0.1%| 125 A CT| Solid-Core
METSEHDPM125A30| 30 ft (9.14 m)| 0.710 lb (0.322 kg)
METSEHDP150A12H| 12 ft (3.66 m)| 1.187 lb (0.538 kg)| SUN3| 0.2%| 150 A CT|

Split-Core

METSEHDP150A30H| 30 ft (9.14 m)| 2.046 lb (0.928 kg)
METSEHDPM150A12| 12 ft (3.66 m)| 1.137 lb (0.516 kg)| SUS4| 0.5%
METSEHDPM150A30| 30 ft (9.14 m)| 1.996 lb (0.905 kg)
METSEHDPM150A60| 60 ft (18.29 m)| 2.595 lb (1.177 kg)
METSEHD150A12| 12 ft (3.66 m)| 1.167 lb (0.529 kg)| SUSF (Small)| 1.0%| 150 A CT, 1 in x 1 in (2.54 cm x 2.54 cm)
METSEHD150A30| 30 ft (9.14 m)| 2.026 lb (0.919 kg)
METSEHD150A60| 60 ft (18.29 m)| 2.625 lb (1.190 kg)
METSEHDP300A12H| 12 ft (3.66 m)| 1.287 lb (0.584 kg)| SUN4| 0.2%| 300 A CT
METSEHDPM300A12| 12 ft (3.66 m)| 1.187 lb (0.538 kg)| SUS4| 0.5%
METSEHDPM300A30| 30 ft (9.14 m)| 2.046 lb (0.928 kg)
METSEHDPM300A30H| 30 ft (9.14 m)| 2.146 lb (0.973 kg)| SUN4| 0.2%
METSEHDPM300A60| 60 ft (18.29 m)| 2.645 lb (1.200 kg)| SUS4| 0.5%
METSEHD300A30| 30 ft (9.14 m)| 2.096 lb (0.951 kg)| SUSF (Small)| 1.0%|

300 A CT, 1 in x 1 in (2.54 cm x 2.54 cm)

METSEHD300A60| 60 ft (18.29 m)| 1.646 lb (0.747 kg)
METSEHD300A12| 12 ft (3.66 m)| 1.237 lb (0.561 kg)
METSEHD300A12L| 12 ft (3.66 m)| 1.646 lb (0.747 kg)| 300 A CT, 2 in x 2 in (5.08 cm x 5.08 cm)
METSEHD300A30L| 30 ft (9.14 m)| 2.505 lb (1.136 kg)
METSEHD300A60L| 60 ft (18.29 m)| 3.104 lb (1.408 kg)
METSEHDP300A08H| 8 ft (2.44 m)| 1.996 lb (0.905 kg)| CTTB| 0.2%| 300 A CT| Solid-Core
METSEHDPM400A12| 12 ft (3.66 m)| 1.287 lb (0.584 kg)| SUS4| 0.5%| 400 A CT|

Split-Core

METSEHDPM400A12H| 12 ft (3.66 m)| 1.387 lb (0.629 kg)| SUN4| 0.2%
METSEHDPM400A30| 30 ft (9.14 m)| 2.146 lb (0.973 kg)| SUS4| 0.5%
METSEHDPM400A30H| 30 ft (9.14 m)| 2.245 lb (1.018 kg)| SUN4| 0.2%
METSEHDPM400A60| 60 ft (18.29 m)| 2.744 lb (1.245 kg)| SUS4| 0.5%
METSEHD400A12| 12 ft (3.66 m)| 1.297 lb (0.588 kg)| SUSF (Small)| 1.0%| 400 A CT, 1.25 in x 1.25 in (3.17 cm x 3.17 cm)
METSEHD400A30| 30 ft (9.14 m)| 2.156 lb (0.978 kg)
METSEHD400A60| 60 ft (18.29 m)| 2.754 lb (1.249 kg)
METSEHD400A12L| 12 ft (3.66 m)| 1.856 lb (0.842 kg)| 400 A CT, 2.5 in x 2.5 in (6.35 cm x 6.35 cm)
METSEHD400A30L| 30 ft (9.14 m)| 2.714 lb (1.231 kg)
METSEHD400A60L| 60 ft (18.29 m)| 3.313 lb (1.503 kg)
METSEHDPM600A12| 12 ft (3.66 m)| 1.387 lb (0.629 kg)| SUS4| 0.5%| 600 A CT
METSEHDPM600A30| 30 ft (9.14 m)| 2.305 lb (1.046 kg)
METSEHDPM600A60| 60 ft (18.29 m)| 2.305 lb (1.046 kg)
METSEHD600A30| 30 ft (9.14 m)| 2.535 lb (1.150 kg)| SUSF (Small)| 1.0%| 600 A CT, 3 in x 3 in (7.62 cm x 7.62 cm)
METSEHD600A60| 60 ft (18.29 m)| 3.133 lb (1.421 kg)
METSEHD600A12| 12 ft (3.66 m)| 1.676 lb (0.760 kg)
METSEHD800A30| 30 ft (9.14 m)| 2.934 lb (1.331 kg)| 800 A CT, 4 in x 4 in (10.16 cm x 10.16 cm)
METSEHD800A60| 60 ft (18.29 m)| 3.533 lb (1.603 kg)
METSEHD800A12| 12 ft (3.66 m)| 2.075 lb (0.941 kg)
METSEHD1000A30| 30 ft (9.14 m)| 2.934 lb (1.330 kg)| 1000 A CT, 4 in x 4 in (10.16 cm x 10.16 cm)
METSEHD1200A30| 30 ft (9.14 m)| 3.054 lb (1.385 kg)| 1200 A CT, 4 in x 6 in (10.16 cm x 15.24 cm)
METSEHD1600A30| 30 ft (9.14 m)| 3.173 lb (1.439 kg)| SUSF (Medium)| 1.0%| 1600 A CT, 4 in x 6 in (10.16 cm x 15.24 cm)
METSEHD1600A30L| 30 ft (9.14 m)| 3.173 lb (1.439 kg)| 1600 A CT, 4.5 in x 4.5 in (11.43 cm x 11.43 cm)
METSEHD2000A30| 30 ft (9.14 m)| 4.650 lb (2.109 kg)| SUSF (Medium)| 1.0%| 2000 A CT, 4 in x 6 in (10.16 cm x 15.24 cm)
METSEHD2000A30L| 30 ft (9.14 m)| 4.480 lb (2.032 kg)| 2000 A CT, 6 in x 3 in (15.24 cm x 7.62 cm)
METSEHD3000A30| 30 ft (9.14 m)| 4.271 lb (1.937 kg)| SUSF (Large)| 1.0%| 3000 A CT, 4 in x 4 in (10.16 cm x 10.16 cm)
METSEHD3000A30L| 30 ft (9.14 m)| 4.430 lb (2.009 kg)| 3000 A CT, 4 in x 6 in (10.16 cm x 15.24 cm)
METSEHD3000A30XL| 30 ft (9.14 m)| 5.289 lb (2.399 kg)| 3000 A CT, 5 in x 12 in (12.7 cm x 30.48 cm)
METSEHD4000A30| 30 ft (9.14 m)| 5.289 lb (2.399 kg)| 4000 A CT, 5 in x 12 in (12.7 cm x 30.48 cm)
CTs Compatible With HDPM6000S and HDPM6000S24 Strip Modules

Commercial Reference /
Model| Lead Length| Weight| Form Factor| Accuracy| Description| Type of CT
METSEHDPM50Al2P| 12 in (30.48 cm)| 0.101 lb (0.046 kg)| CTTA| 0.2%| 50 A CT, with connector, for use with 24 circuit strip module only| Solid-Core
METSEHDPM50A18P| 18 in (45.72 cm)| 0.104 lb (0.047 kg)
METSEHDPM75A4| 4 in (10.16 cm)| 0.629 lb (0.285 kg)| CTMF| 1.%| 75 A CT, for use with 21 circuit with connector,
strip module only| Split-Core
METSEHDPM125A10| 10 in (25.4 cm)| 0.130 lb (0.059 kg)| CTTG| 0.1%| 125 A CT, with connector, for use with 21 circuit strip module only| Solid-Core
METSEHDPM125A4| 4 in (10.16 cm)| 0.130 lb (0.059 kg)
METSEHDPM150A5| 5 in (12.7 cm)| 0.918 lb (0.416 kg)| SUS4| 0.5%| 150 A CT, for use with 21 circuit with connector,
strip module only| Split-Core
METSEHDPM250AT12| 12 ft (3.66 m)| 0.500 lb (0.227 kg)| SUST| 0.5%| 250 A CT, without connector| Solid-Core
METSEHDPM300A5| 5 in (12.7 cm)| 0.968 lb (0.439 kg)| SUS4| 0.5%| 300 A CT, with connector, for use with 21 circuit
strip module only| Split-Core
METSEHDPM400A5| 5 in (12.7 cm)| 1.068 lb (0.484 kg)| 400 A CT, with connector, for use with 21 circuit strip module only
METSEHDPM500AT12| 12 ft (3.66 m)| 0.500 lb (0.227 kg)| SUST| 0.5%| 500 A CT, without connector| Solid-Core
METSEHDP600A5| 5 in (12.7 cm)| 1.167 lb (0.529 kg)| SUS4| 0.5%| 600 A CT, for use with 21 circuit with connector,
strip module only| Split-Core
CTs Compatible With HDPM6000B Busway Module

Commercial Reference / Model| Lead Length| Weight| Form Factor| Accuracy| Description| Type of CT
METSEHDPM75A16| 16 in (40.64 cm)| 0.639 lb (0.290 kg)| CTMF| 1.%| 75 A CT| Split-Core
METSEHDPM125A16| 16 in (40.64 cm)| 0.140 lb (0.064 kg)| CTTG| 0.1%| 125ACT| Solid-Core
METSEHDPM150A16| 16 in (40.64 cm)| 0.928 lb (0.421 kg)| SUS4| 0.5%| 150 ACT| Split-Core
METSEHDPM300A16| 16 in (40.64 cm)| 0.978 lb (0.444 kg)| 300 A CT
METSEHDPM400A16| 16 in (40.64 cm)| 1.078 lb (0.489 kg)| Split-Core 400 A CT
METSEHDP600A16|  16 in (40.64 cm)| _ 1.177 lb (0.534 kg)|  600 A CT

Application Diagram

Schneider Electric HDPM6000 METSEHDP150A30H Split Core Current Transformer -
Diagram

Specifications

Form Factor| Accuracy| Operating Temperature
Range| Storage Temperature
Range| Leads| Altitude of Operation| Installation Category| Agency Approvals
---|---|---|---|---|---|---|---
SUN2| 0.2%| -40 °F to 131 °F
(-40 °C to 55 °C)| -58 °F to 158 °F
(-50 °C to 70 °C)| Black and white twisted
pair 18 AWG, AWM, UL1015, 600 V, 221 °F (105 °C)| 6561.68 ft (2000 m) max| Cat Ill, Pollution
Degree 2| UL2808, CE
SUN3
SUN4| Cat Ill, Pollution
Degree 3
SUS4| 0.5%
SUSF| 1%| -40 °F to 158 °F
(-40 °C to 70 °C)| -58 °F to 221 °F
(-50 °C to 105 °C)| Cat IV, Pollution
Degree 3
CTMF| 1%| -40 °F to 131 °F
(-40 °C to 55 °C)| -58 °F to 140 °F
(-50 °C to 60 °C)| Cat III, Pollution
Degree 2| IEEE C57.13,
CAN / CSA-C61869-1:14,
CAN / CSA-C61869-2:14, CE
CTTG| 0.1%| -40 °F to 185 °F
(-40 °C to 85 °C)| -58 °F to 221 °F
(-50 °C to 105 °C)| 3280.84 ft
(1000 m) max| UL2808 (Lead Length 4.92 ft (1.5 m)) or
UL Recognized (Lead Length < 4.92 ft (1.5 m)), CE
SUST| 0.5%| -40 °F to 131 °F
(-40 °C to 55 °C)| -58 °F to 158 °F
(-50 °C to 70 °C)| 6561.68 ft (2000 m) max| UL2808, CE
CTTA| 0.2%| -40 °F to 185 °F
(-40 °C to 85 °C)| -40 °F to 185 °F
(-40 °C to 85 °C)| Black and white twisted
pair 24 AWG, AWM1901,
600 V, 392 °F (200 °C)| UL Recognized, CE
CTTB| 0.2%| Black and white twisted
pair 18 AWG, AWM1015,
600 V, 221 °F (105 °C)

Following specifications are common for all form factors:
Output at Rated Current: 0.25 VAC
Frequency Range: 50/60 Hz
Humidity Range: 0 to 95% noncondensing
Continuous Current Rating Factor: 1
Max. Voltage L-N Sensed Conductor: 600 VAC

Dimensions

SUN2, SUN3, SUN4 and SUS4

Model| W Window| A Dimension| B Dimension| C Dimension
---|---|---|---|---
SUN2| 0.4 in (10.17 mm)| 2.4 in (60.69 mm)| 1.65 in (41.91 mm)| 1.15 in (29.21 mm)
SUN3| 0.7 in (17.80 mm)| 3.0 in (76.19 mm)| 2.4 in (60.96 mm)| 1.17 in (29.72 mm)
SUN4| 1.25 in (31.75 mm)| 3.3 in (83.81 mm)| 3.1 in (78.74 mm)| 1.3 in (31.04 mm)
SUS4| 1.25 in (31.75 mm)| 3.3 in (83.81 mm)| 3.1 in (78.74 mm)| 1.3 in (31.04 mm)

Schneider Electric HDPM6000 METSEHDP150A30H Split Core Current Transformer -
Dimensions1

Schneider Electric HDPM6000 METSEHDP150A30H Split Core Current Transformer -
Dimensions2

Installation

Turn off and lock out power to the primary circuit before installing these CTs. Use a properly rated voltage sensing device to confirm that power is off.
NOTICE
INCORRECT POLARITY OR CT WIRE MISCONNECTION

  • Align CT arrow to point in the direction of the power flow.
  • Paired lead wires must be kept together.
  • Do not install CTs in a panel where they exceed 75% of the wiring space of any cross-sectional area within the panel.
  • Do not install CTs in areas of breaker arc venting.
  • Do not install CTs using Class 2 wiring methods or connect to Class 2 equipment (NFPA 70)
  • Secure CTs and route conductors so that they do not contact live terminals or bus.

Failure to follow this instruction can result in incorrect readings or loss of data or damage to equipment.
Connect the transducer output leads to the meter inputs. Refer the wiring diagram in the installation guide for the appropriate module for details.
SUN2, SUN3, SUN4, SUS4, and SUSF Installation
Busbar and Phase Orientation

  • The white mark ensures orientation every time the top is attached.
  • The white mark is on the top right side when looking at the product label.
  • Refer to label for correct CT orientation.

Proper Size and Fitting

  • The window of the CT should be big enough to fit the busbar without excess space.
  • A split-core CT should not be oversized around the bus/conductor, resulting in an inaccurate/bad reading.
  • The busbar should also be in the center of the CT window to allow the coils to energize evenly.

Schneider Electric HDPM6000 METSEHDP150A30H Split Core Current Transformer -
Fig2

Installation

  1. Remove the screws (or push-pins) from the CT and take the top off.

  2. Slide the body of the CT over the busbar.
    NOTE: Refer to label for correct CT orientation.

  3. Re-attach the top to the body of the CT, using the white mark to orient how the top will fit.

  4. Place the screws/push-pins back to secure the top to the CT.

  5. Terminate the leads to the metering device before turning on the power.

Schneider Electric HDPM6000 METSEHDP150A30H Split Core Current Transformer -
Fig3

CTMF Installation

  1. Release the clasp on one side of the CT and open it on the hinge.
    NOTE: Check the core ends on both sections of the CT to ensure there is no rust or debris in the closure areas. A label on the product indicates the source side. In the illustrated diagram, the arrow indicates the current flow (i.e., the label faces away from the circuit breaker).

  2. Wrap the CT around the primary lead.

  3. Close the CT until the clasp clicks into place to ensure that the contact surfaces are firmly seated.

  4. Reconnect power to the panel.
    CTs may be simply hung on the wire on which they snap around. An alternative is the use of VELCRO ® strips on the bottom or hinged side of the unit, to allow for ease of mounting and removal as necessary. VELCRO is non-conductive.

Schneider Electric HDPM6000 METSEHDP150A30H Split Core Current Transformer -
Fig4

CTTA, CTTB, CTTG, and SUST Installation

  1. Route the primary conductor through the center of the CT and complete the conductor connections.
    NOTE: A label on the product indicates the source side. All solid-core CT models should be oriented such that the wire leads face the source.

  2. Reconnect power to the panel.

Schneider Electric HDPM6000 METSEHDP150A30H Split Core Current Transformer -
Fig5

Note: Form factor is indicative, it may vary in actual.

Schneider Electric HDPM6000 METSEHDP150A30H Split Core Current Transformer -
qr codeZ208152-0D
Schneider Electric
35, rue Joseph Moniker
92500 Ruel Malmaison
France
+33 (0) 1 41 29 70 00
www.se.com
Schneider Electric Limited
Stafford Park 5
Telford TF3 3BL
United Kingdom
Z208152-0D