Product Information
Product Name: Presence detector 353-751021-1 Product Type: Manual SnapFit mounting presence detector Model Number: P47/P48 DALI-2 (master), P46 DALI-2 (secondary/BMS) Dimensions: L = 2000 mm, 44 mm x 69 mm x 56.9 mm Wiring: Fixed ceiling (9.5 – 40 mm) or suspended ceiling (0.2 – 9 mm) LED Behavior: Green LED continuous on (connection OK), Green LED flashing (warming up*), Red LED continuous on (error), Blue LED flashing (walk test active)
Product Usage Instructions
- Mounting:
- For fixed ceiling installation, ensure the wiring is correct and the detector is securely mounted on a surface with a thickness of 9.5 – 40 mm.
- For suspended ceiling installation, ensure the wiring is correct and the detector is securely mounted on a surface with a thickness of 0.2 – 9 mm.
- Connection: – After installation, check the LED behavior to ensure proper connection.
- Green LED continuous on indicates a successful connection.
- Green LED flashing indicates the detector is warming up*.
- Red LED continuous on indicates an error.
- Blue LED flashing indicates that the walk test is active.
- App Settings:
- The product can be configured using the app settings.
- By default, the factory settings are applied.
- The switch can be turned ON/OFF using the app.
- The lux level for detection can be set to 500 lux. – The time delay for load activation can be set to 15 minutes.
- Troubleshooting: – If the load does not turn on or off, check the wiring scheme to ensure it is correct.
- If the detector receives false triggers, check for any objects in the detection range that may cause false triggering and remove them or lower the sensitivity.
Note: For more detailed information and troubleshooting, refer to the user manual. * “Warming up” is an optional feature and may not be available on all models.
Presence detector P46LR, DALI-2, secondary and BMS, 32-37 m, 360°, SnapFit,for flush mounting, WAGO WINSTA® MIDI 2 m cable with 5-pol. connector
Wiring
- WAGO WINSTA® mounting plate, 770-625
- WAGO WINSTA® distribution connector, 770-618
Dimensions
Installation
App settings
| | | __
---|---|---|---
Factory settings| Switch ON/OFF| 500 lux| 15 min
Settings by BMS software
Table memory bank 2
Address| Description| Default value| Memory type
0x00| Address and last accessible memory location| 0x03| ROM
0x01| Indicator byte (manufacture definable)| 0x00| any
0x02| Memory bank lock byte (<>0x55 = Read Only else Read/ Write)| 0xFF| RAM
0x03| PIR sensitivity segment A (MR, LR and HC detectors) 4 = MAX 3 = HIGH 2 =
LOW 1 = MIN 0 = OFF| 0x03| NVM
0x04| PIR sensitivity segment B (LR and HC detectors)
4 = MAX 3 = HIGH 2 = LOW 1 = MIN 0 = OFF
| 0x03| NVM
0x05| PIR sensitivity segment C (LR and HC detectors)
4 = MAX 3 = HIGH 2 = LOW 1 = MIN 0 = OFF
| 0x03| NVM
0x06| LUX range
0 = NORMAL 0 – 1023 lux, 10-bit
1 = HIGH 0 – 10360 lux, 14 bit
| 0x00| NVM
0x07| Bluetooth® communication 0 = enabled, 1 = disabled| 0x00| NVM
Note: The detector reboots when Bluetooth® communication is disabled or re-enabled. This lasts for approximately 100 – 500 ms.
LED behaviour
When Bluetooth® communication is disabled, the green LED does not flash while warming up.
Specifications
- Article number………………………………………………………………………………………. 353-751021-1
- Configuration……………………………………………………………………………… DALI-2 secondary/BMS
- Input voltage………………………………………………………………………………………… via the DALI bus
- Maximum current consumption………………………………………………………………………..28.1 mA
- Nominal current consumption (12 V, 25°C) Bluetooth® enabled……………………………. 8.1 mA
- Nominal current consumption (12 V, 25°C) Bluetooth® disabled…………………………… 5.0 mA
- Maximum startup time DALI…………………………………………………………………………< 1200 ms
- Maximum PIR detection startup time…………………………………………………………………….. 70 s
- Light intensity range………………………………………………. 0 – 10360 lux (see DALI BMS settings)
- Detection angle…………………………………………………………………………………………………… 360°
- Detection range (PIR)……………………………………………………………. ø 37 m from a height of 3 m
- Ambient temperature………………………………………………………………………………. -25 – +40 °C
- Mounting method………………………………………….. flush mounting with SnapFit mounting bracket
- Mounting height…………………………………………………………………………………………… 2 – 3.5 m
- Drill diameter…………………………………………………………………………………………………… 76 mm
- Minimum flush mounting depth………………………………………………………………………. 56.9 mm
- Colour………………………………………………………………………………………………… white (RAL 9010)
- Dimensions visible (HxWxD)………………………………………………………….. 100 x 100 x 42.2 mm
- Dimensions (HxWxD)…………………………………………………………………….. 120 x 120 x 99.1 mm
- Wire capacity…………………………………………………………………………………………….1.5/2.5 mm²
- Protection degree………………………………………………………………………………………………… IP20
- Impact resistance………………………………………………………………………………………………… IK04
- Modification of settings… app (iOS/Android) and 2-way Bluetooth® communication/BMS software
- Maximum range Bluetooth® (free field, depending on the device)…………………………… 50 m
- Operating frequency………………………………………………………………………………………… 2.4 GHz
- Maximum radio frequency power…………………………………………………………………….. – 2 dBm
- Halogen-free…………………………………………………………………………………………………………. yes
- Marking…………………………………………………………………………………………………………………CE
Troubleshooting
Support & contact
nv Niko sa
Industriepark West 40
9100 Sint-Niklaas, Belgium
www.niko.eu
EN +32 3 778 90 80 support@niko.eu
Niko prepares its manuals with the greatest care and strives to make them as complete,
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>