Victrix 3.034124 Pro V2 Expansion Kit for Cascade Regulator Instruction Manual
- June 13, 2024
- VICTRIX
Table of Contents
Cod. 1.048182 – Rev. ST.007527/000
VICTRIX PRO V2 EXPANSION KIT FOR
CASCADE REGULATOR
THIS SHEET MUST BE LEFT WITH THE USER ALONG WITH THE BOILER INSTRUCTION BOOKLET
GENERAL WARNINGS
All products are protected with suitable transport packaging.
The material must be stored in a dry place protected from the weather.
This instruction manual provides technical information for installing the kit.
As for the other issues related to kit installation (e.g. safety in the
workplace, environmental protection, accident prevention), it is necessary to
comply with the provisions specified in the regulations in force and with the
principles of good practice.
Improper installation or assembly of the appliance and/or components,
accessories, kits and devices can cause unexpected problems for people,
animals and objects. Read the instructions provided with the product carefully
to ensure proper installation.
Installation and maintenance must be performed in compliance with the
regulations in force, according to the manufacturer’s instructions and by
professionally qualified staff, meaning staff with specific technical skills
in the plant sector, as envisioned by the law.
SYFETY INSTRUCTIONS.
WARNING:
Danger due to live parts.
Some components are electrically live. Contact with live parts can result in
an electric shock, burns or even death. Before working on the electrical
system, observe the following points:
- Switch the system to a zero volts state.
- Secure to prevent switching back on.
- Check for zero volts state.
Key:
1 – EbV-Device bus
2 – A10V Outputs
3 – Adress switch
4 – Inputs EFI and EFI10V
5 – EbV- Device bus| 6 – 230V connection
7 – ARS Output
8 – ARS Output
9 – ARS Output
10 – ARSP Output
---|---
The heatcon! EM is an expansion for the inputs and outputs of a heatcon! EC inside the system, as shown in the technical data.
TECHNICAL DATA.
Installation | DIN rail installation |
---|---|
Outlets | EbV – device bus |
Connection technology | 4-wire technology, screw terminal connection |
Maximal zulassige Kabellange | 50 m |
Power supply | 230 V ±10 %, 50 Hz |
Power consumption | max. 9VA |
IP class | 0 (*) |
IP rating | IPOO |
Fusing | User-supplied |
Ambient conditions
• Storage temperature
• Operating temperature| -25 … +60 °C
-10 … +50 °C
Connections screw terminals| • Mains voltage L, N
• 1 x potential-free relay ARSP, max. 230V / 2A
• 3 x relay 230V ARS, max. 2A, sum current: max. 10A
• 2 x sensor pulse input EFI
• 2 x sensor pulse 0…10V input EFI 10V
• 2 x output 0..10V-PWM AIOVP
• 2 x EbV – device bus
Standards| DIN EN 60730
Dimensions| 106 x 90 x 61 mm (length x width x height) with hat rail
Weight| 240 g
Colour| Grey
*() Note**
The heatcon! EM 100 is supplied with a top hat rail housing.
Protection against contact and the IP 20 degree of protection must be ensured
by installation.
More information you will
find:
https://ebv-gmbh.eu/downloads/
WARRANTY CONDITIONS.
Improper use, non-observation of these instructions, use of inadequately qualified personnel and independent changes exclude any liability on the part of the manufacturer for the resulting damage. The manufacturer’s warranty becomes void.
Impairment of device function if incorrect spare parts are used!
If unauthorised parts are used correct functioning is not assured.
Use spare parts authorised by customer service.
DECLARATION OF CONFORMITY.
EbV Elektronikbau- und Vertriebs-GmbH assures that the product is produced
according to valid EU regulations. A complete version of the Declaration of
Conformity can be found in the installation manual at https://ebv-
gmbh.eu/downloads/
STD.010827/000
Documents / Resources
|
Victrix 3.034124 Pro V2 Expansion Kit for Cascade
Regulator
[pdf] Instruction Manual
3.034124 Pro V2 Expansion Kit for Cascade Regulator, 3.034124, Pro V2
Expansion Kit for Cascade Regulator, V2 Expansion Kit for Cascade Regulator,
Expansion Kit for Cascade Regulator, Kit for Cascade Regulator, Cascade
Regulator, Regulator
---|---