niko P48LR Presence Detector Flush Mounting SnapFit White Instruction Manual

June 13, 2024
niko

niko P48LR Presence Detector Flush Mounting SnapFit White Instruction Manual
niko P48LR Presence Detector Flush Mounting SnapFit
White

Presence detector P48LR, DALI-2, master, 32-37 m, 360°, SnapFit, for flush mounting, WAGO WINSTA® MIDI 2 x 2 m cable with 5-pol. connectors

Wiring

Wiring

230 V – OFF

Dimensions

Dimensions

Installation

Installation

**NOT REMOVABLE (fixed ceiling)

Installation

**

**REMOVABLE (suspended ceiling)

Installation

**

App settings

Factory settings __ __ __
Switch ON/OFF 500 lux 15 min

App settings
Application

230 V – ON

LED behaviour

Green LED continuous on| | Connection OK|
---|---|---|---
Green LED breathing| | Connection OK, overrule ON|
Green LED flashing| | Warming up| Wait
Red LED continuous on| | Error| More info – >
Application
detector tool
Red LED breathing| | Warning
Blue LED flashing| | Walk test active

230 V – ON

Specifications

  • Article number……………………………………………………………………………………… 353-751421-2

  • Configuration ………………………………………………………………………………………….DALI-2 master

  • Input voltage………………………………………………………………………………230 Vac ± 10 %, 50 Hz

  • Maximum power consumption …………………………………………………………………………… 0.6 W

  • Maximum power consumption wireless link active ……………………………………………. 0.65 W

  • Short circuit behaviour shutdown trigger……………………..voltage below 12 V, exceeding 1.3 s

  • Short circuit behaviour restart period …………………………………………. every 14 s until success

  • Detector output………………………………………………………………. DALI Broadcast/DALI Adressable

  • Circuit breaker………………………………………………………………………maximum MCB rating 16 A*

  • Relay contact………………………………………………………………….. NO (max. µ10 A), potential-free

  • Maximum load incandescent and halogen lamps (cosφ = 1)………………………………… 2300 W

  • Maximum load fluorescent lamps (cosφ ≥ 0.5) …………………………………………………… 1200 VA

  • Maximum load economy lamps (CFLi) ……………………………………………………………….. 350 W

  • Maximum load LED lamps 230 V ……………………………………………………………………….. 350 W

  • Maximum load LED driver………………………………………………………………………………… 500 VA

  • Maximum load electronic transformer …………………………………………………………………. 500 VA

  • Maximum capacitive load ………………………………………………………………………………… 140 µF

  • Maximum switching current………………………………………………..165 A/20 ms – 800 A/200 µs

  • Maximum voltage on the DALI bus ……………………………………………………………………..15 Vdc

  • Maximum guaranteed current on the DALI bus ………………………………………………….200 mA

  • Maximum supply current…………………………………………………………………………………250 mA

  • Maximum startup time DALI ………………………………………………………………………..< 1200 ms

  • Maximum PIR detection startup time……………………………………………………………………. 70 s

  • Maximum number of dimmable zones ……………………………………………………………………….4

  • Maximum number of control gear on the DALI bus ……………………………………………………64

  • Light intensity range …………………………………………………………………………..20 – 2000 lux, ∞

  • Switch-off delay ……………………………………………………………………… pulse, 20 s – 120 min, ∞

  • Detection angle………………………………………………………………………………………………….. 360°

  • Detection range (PIR) …………………………………………………………… ø 37 m from a height of 3 m

  • Ambient temperature ………………………………………………………………………………-25 – +40 °C

  • Mounting method …………………………………………. flush mounting with SnapFit mounting bracket

  • Mounting height ……………………………………………………………………………………………2 – 3.5 m

  • Drill diameter………………………………………………………………………………………………….. 76 mm

  • Minimum flush mounting depth………………………………………………………………………. 100 mm

  • Colour……………………………………………………………………………………………….. white (RAL 9010)

  • Dimensions visible (HxWxD) …………………………………………………………. 100 x 100 x 42.2 mm

  • Dimensions (HxWxD)………………………………………………………………….. 120 x 120 x 142.2 mm

  • Wire capacity ……………………………………………………………………………………………1.5/2.5 mm²

  • Protection degree ……………………………………………………………………………………………….. IP20

  • Impact resistance……………………………………………………………………………………………….. IK04

  • Modification of settings …………………… app (iOS/Android) and 2-way Bluetooth® communication

  • Maximum range Bluetooth® (free field, depending on the device) ………………………….. 50 m

  • Operating frequency……………………………………………………………………………………….. 2.4 GHz

  • Maximum radio frequency power………………………………………………………………………-2 dBm

  • Halogen-free …………………………………………………………………………………………………………yes

  • Marking ………………………………………………………………………………………………………CE Cable specifications

  • Cable 1 colour………………………………………………………………………………………………… grey

  • Cable 2 colour………………………………………………………………………………………………… grey

  • Length……………………………………………………………………………………………………………..2 m

  • Wire cross-section……………………………………………………………………………………. 1

  • Voltage………………………………………………………………………………………………………….400 V

  • Rated current ………………………………………………………………………………………………….16 A

  • Halogen-free …………………………………………………………………………………………………….yes

  • Ambient temperature…………………………………………………………………………….-5 – +40 °C

  • Type of connector cable 1……………………………………………………… male, 5-pole, light green

  • Type of connector cable 2……………………………………………………………….male, 5-pole, pink

  • The MCB rating is limited by national installation rules.

Detection area

Detection area

H| A
Walking| B
Across| C
Towards| D
Presence
---|---|---|---|---
| | | |
2.5 m| ø 32 m| ø 28 m| ø 10 m| ø 8 m
3.0 m| ø 37 m| ø 30 m| ø 8 m| ø 4 m

Measured according to EN/IEC63180

Troubleshooting

Problem Possible cause Proposed solution
Load does not turn on The wiring is not correct Check the wiring scheme
The ambient light is too strong Check the response value luminosity and raise

the value if necessary
Load does not turn of| The switch-off delay is too long| Check the switch-off delay and shorten the delay if necessary
The detector receives false triggers| Check for any objects that may cause false triggering and remove them from the detection range or lower the sensitivity
App cannot connect to the detector| Bluetooth® has been disabled on your mobile device| Enable Bluetooth® on your mobile device

Support & contact

nv Niko sa
Industriepark West 40
9100 Sint-Niklaas, Belgium

+32 3 778 90 80 support@niko.eu

Niko prepares its manuals with the greatest care and strives to make them as complete, correct and up to date as possible. Nevertheless, some deficiencies may subsist. Niko cannot be held responsible for this, other than within the legal limits. Please inform us of any deficiencies in the manuals by contacting Niko customer services at support@niko.eu.