PRELIMINARY INFORMATION

The complete English manual is available at the following link: pdf.fantinicosmi.it

INTRODUCTION TO THE SYSTEM

CH193VMC is an LCD remote panel for the advanced control of ventilation systems through VMC. Equipped with temperature, relative humidity and VOC sensors, it automatically controls ventilation and indoor air quality (IAQ)

INSTALLATION

ATTENTION!
Installation must be done by qualified personnelin compliance with the requirements concerning installation of electrical equipment.

Installation operations must be done with the system’s power disconnected

The CH193VMC programmable thermostat must be installed on the wall or on a flush mounting box, in 3 units, at a height of about 1.5m from the floor, in a position to properly detect room temperature.
Dimension
Installation Instruction

ELECTRICAL CONNECTION

CH193VMC is connected directly to the Fantini Cosmi VMC machines. The connection changes based on the VMC code.
Electronic Connection
Please note: jump the terminals. Use a shielded cable and ground it on the CH193VMC side.

VMC SIDE CONNECTION

AP20060

Connection
Make sure the jumper is inserted correctly

START-UP

At first switch-on, the CH193VMC must be coupled to a VMC. Choose the code of the installed VMC
Control Panel

CONNECTION FOR REMOTE INTEGRATION AND DEHUMIDIFICATION

Only with the references AP20060 and AP20062.
ConnectionControl
Panel

DESCRIPTION OF DISPLAY KEYS

  1. Day of the week
  2. Heating/cooling coil activation state (if the VMC is set up for this)
  3. Room temperature (Celsius/ Fahrenheit) measured
  4. Multi-function touch icons
  5. VMC ventilation status
  6. Operating mode
  7. Bar graph to display messages and daily programming

Please note: the function of the multi-function keys varies depending on the situation and is described by the symbol that appears on the display next to the key

LANGUAGE SELECTION

Control Panel

DATE AND TIME SETTING

Control Panel
USER PROGR                                                  DATE AND TIME
Control Panel

TECHNICAL FEATURES

Rated power supply voltage 9 – 24 Vcc
Absorbed current 150 mA Max
Backlight switch-off 60s after last touch
Temperature adjustment scale 2 ÷ 40 °C,increase 0.1°C
Measurement scale/ room T display – 50 ÷ + 50 °C,resolution 0.1°C
Relative humidity adjustment scale 30 ÷ 70 %,resolution 1%
Room relative humidity display scale 0 ÷ 100 %, increase1%
Air quality view via VOC sensor
Communication interface RS485
Communication mode ModBus RTU (master)
Data formats 9600bps, 8bit,no parity, 1 bit stop
Maximum room temperature 45°C
Storage temperature -10°C ÷ +60°C
Pulse voltage 4000V
Software Class A
Insulation class Class II
--- ---
Degree of protection IP30
Degree of pollution 2
Number of operating cycles for manual actions 3000
Number of operating cycles for automatic actions 10000
Assembly on wall or on flush mounting box
Dimensions 127 x 82 x 24 mm
Weight 0.100 Kg

Compliant with

|

  • EN 60730-1standards and second parts
  • Directive 2014/30/ EU (EMC)
  • Directive 2014/35/ EU (LVD)

Product made in Italy

DISPOSAL OF PRODUCTS

The crossed out wheeled dust bin symbol indicates that products must be collected and disposed of separately from household waste. Integrated batteries and accumulators can be disposed of with the product. They will be separated at the recycling centres. The black bar indicates that the product was placed on the market after August 13, 2005. By participating in separate collection of products and batteries, you will help to assure the proper disposal of products and batteries and thus help to prevent potential negative consequences for the environment and human health. For more detailed information about the collection andrecycling programmes available inyour country, please contact your local city office or the shop where you purchased the product.
FANTINI COSMI S.p.A.

Via dell’Osio, 6 20090 Caleppio di Settala, Milano – ITALY
Tel. +39 02 956821
Fax +39 02 95307006
info@fantinicosmi.it
www.fantinicosmi.it

Fantini Cosmi Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals