Fantini Cosmi CH193VMC Centralized control for VMC Unit User Guide
- June 13, 2024
- Fantini Cosmi
Table of Contents
- PRELIMINARY INFORMATION
- INTRODUCTION TO THE SYSTEM
- INSTALLATION
- ELECTRICAL CONNECTION
- VMC SIDE CONNECTION
- START-UP
- CONNECTION FOR REMOTE INTEGRATION AND DEHUMIDIFICATION
- DESCRIPTION OF DISPLAY KEYS
- LANGUAGE SELECTION
- DATE AND TIME SETTING
- DISPOSAL OF PRODUCTS
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Fantini Cosmi CH193VMC Centralized control for VMC Unit User Guide
PRELIMINARY INFORMATION
The complete English manual is available at the following link: pdf.fantinicosmi.it
INTRODUCTION TO THE SYSTEM
CH193VMC is an LCD remote panel for the advanced control of ventilation systems through VMC. Equipped with temperature, relative humidity and VOC sensors, it automatically controls ventilation and indoor air quality (IAQ)
INSTALLATION
ATTENTION!
Installation must be done by qualified personnelin compliance with the
requirements concerning installation of electrical equipment.
Installation operations must be done with the system’s power disconnected
The CH193VMC programmable thermostat must be installed on the wall or on a
flush mounting box, in 3 units, at a height of about 1.5m from the floor, in a
position to properly detect room temperature.
ELECTRICAL CONNECTION
CH193VMC is connected directly to the Fantini Cosmi VMC machines. The
connection changes based on the VMC code.
Please note: jump the terminals. Use a shielded cable and ground it on
the CH193VMC side.
VMC SIDE CONNECTION
AP20060
Make sure the jumper is inserted correctly
START-UP
At first switch-on, the CH193VMC must be coupled to a VMC. Choose the code of
the installed VMC
CONNECTION FOR REMOTE INTEGRATION AND DEHUMIDIFICATION
Only with the references AP20060 and AP20062.
DESCRIPTION OF DISPLAY KEYS
- Day of the week
- Heating/cooling coil activation state (if the VMC is set up for this)
- Room temperature (Celsius/ Fahrenheit) measured
- Multi-function touch icons
- VMC ventilation status
- Operating mode
- Bar graph to display messages and daily programming
Please note: the function of the multi-function keys varies depending on the situation and is described by the symbol that appears on the display next to the key
LANGUAGE SELECTION
DATE AND TIME SETTING
USER PROGR DATE AND TIME
TECHNICAL FEATURES
Rated power supply voltage | 9 – 24 Vcc |
---|---|
Absorbed current | 150 mA Max |
Backlight switch-off | 60s after last touch |
Temperature adjustment scale | 2 ÷ 40 °C,increase 0.1°C |
Measurement scale/ room T display | – 50 ÷ + 50 °C,resolution 0.1°C |
Relative humidity adjustment scale | 30 ÷ 70 %,resolution 1% |
Room relative humidity display scale | 0 ÷ 100 %, increase1% |
Air quality view | via VOC sensor |
Communication interface | RS485 |
Communication mode | ModBus RTU (master) |
Data formats | 9600bps, 8bit,no parity, 1 bit stop |
Maximum room temperature | 45°C |
Storage temperature | -10°C ÷ +60°C |
Pulse voltage | 4000V |
Software | Class A |
Insulation class | Class II |
--- | --- |
Degree of protection | IP30 |
Degree of pollution | 2 |
Number of operating cycles for manual actions | 3000 |
Number of operating cycles for automatic actions | 10000 |
Assembly | on wall or on flush mounting box |
Dimensions | 127 x 82 x 24 mm |
Weight | 0.100 Kg |
Compliant with
|
- EN 60730-1standards and second parts
- Directive 2014/30/ EU (EMC)
- Directive 2014/35/ EU (LVD)
Product made in Italy
DISPOSAL OF PRODUCTS
The crossed out wheeled dust bin symbol indicates that products must be
collected and disposed of separately from household waste. Integrated
batteries and accumulators can be disposed of with the product. They will be
separated at the recycling centres. The black bar indicates that the product
was placed on the market after August 13, 2005. By participating in separate
collection of products and batteries, you will help to assure the proper
disposal of products and batteries and thus help to prevent potential negative
consequences for the environment and human health. For more detailed
information about the collection andrecycling programmes available inyour
country, please contact your local city office or the shop where you purchased
the product.
FANTINI COSMI S.p.A.
Via dell’Osio, 6 20090 Caleppio di Settala, Milano – ITALY
Tel. +39 02 956821
Fax +39 02 95307006
info@fantinicosmi.it
www.fantinicosmi.it