C S YO8 Super Yodalarm & Yodalight Series Instruction Manual

June 4, 2024
C S

C S YO8 Super Yodalarm & Yodalight Series

C-S-YO8-Super-Yodalarm-&-Yodalight-Series-product

Installation

  • Installation must be carried out in accordance with the latest codes of practice by a qualified electrician.
  • Check that the power supply is correct for the voltage rating of the alarm to be installed.
  • Ensure that the power supply is disconnected prior to installation or maintenance to avoid electrical shock.
  • The unit should be mounted to a wall or bulkhead formed of suitable material using the two mounting lugs projecting from the side of the enclosure.
  • The lugs have a 10mm diameter mounting hole & sit on 250mm centers. The minimum recommended length of fixing screw is 30mm (not supplied).
  • Avoid mounting the alarm where it could be subject to excessive vibration levels.

Ingress Protection

To maintain the IP rating of the product, the below points must be observed.

  • An IP66 cable gland is supplied with the product. This gland (or other suitably rated) must be used.
  • When replacing the front cover, each of the four retaining screws must be torqued to 0.6Nm ±0.1Nm

Sound selection

  • Ensure the supply is OFF before proceeding.
  • All DC and AC units have selectable alarm sounds (see table on the back of the installation sheet for details) and are selectable via switch SW1.
  • A second stage tone is made available via a third wire connected to terminal TB1/3 as shown in Fig. 1.
  • Alternatively, for DC units only, the 1st and 2nd stage sound signals can be generated by supply reversal see Figure 1, Option 2.
  • Manually selectable second-stage tones are available for YO8 units by using switch SW2.

Line integrity on DC systems

  • For 3 wire 2-stage alarm system, monitor via reverse polarity.
  • For 2 wire 2 stage alarm system, monitor via threshold, (applied voltage<1v) an end-of-line (E.O.L) resistor is required for line monitoring and should have a minimum resistance of 3k3 ohms and 0.5watts, wire-wound or metal film type.

AC Systems

  • As with the DC units, the AC units have a selectable tone via the SW1 DIP switch, see Figure 2.
  • A second stage can be activated by applying an additional “N” connection to the TB3 terminal on the PCB, as shown in Figure 2.

Additional Voltage Options

  • The Clifford and Snell YO8 Super series is also available in a 48vDC (F).
  • The wiring for this voltage is the same as for the 24vDC units shown in Figure 1.
  • Always confirm correct voltage is applied to relevant terminals.C-S-YO8-Super-Yodalarm-&-Yodalight-Series-fig-1

YO8 Super Yodalarm/Yodalight Series

Consists of either the YA80 Super (Audible Unit only) or the YL80 Super (Combined Audible & Visual unit) Connections for the YL80 Super units are made via a 6-way Terminal Block mounted in the base of the unit as shown in Figure 3 (DC) & Figure 4 (AC) diagrams below. Using the connections shown, it is possible to independently control both Sounder and Beacon sections.C-S-YO8
-Super-Yodalarm-&-Yodalight-Series-fig-2

Features Include

  • Termination: Upto 2.5mm2 cable
  • Operating Temperature: Standard Variants -25oC to +70oC EN54-3 Appr oved -25oC to +55oC
  • Enclosure Material: Fire Resistant & UV Stable UL94-5VB rated ABS
  • Lens Material: Fire Resistant & UV Stable Polycarbonate
  • Ingress Protection: Weatherproof to IP66
  • Sound Pressure Level: 120dB(A) Max.
  • Volume Control Adjustment: -18dB
  • AC Supply: 50/60 Hz

Tone Table

| | Frequency| Rept.| ****

Second

| | Switches| | | dB(A)
---|---|---|---|---|---|---|---|---|---
Tone| Description| (Hz)| rate| Stage| 1| 2| 3| 4| 5| Special Application| @ 1m

(± 3dB)

1| Alternating| 800-1000| 0.5| 3| I| I| I| I| I| Fire Alarms| 116
2| Alternating| 2500-3100| 0.5| 4| O| I| I| I| I| Security Alarms| 111
3| Alternating (fast)| 800-1000| 0.25| 7| I| O| I| I| I| Increased urgency| 117
4| Alternating (fast)| 2500-3100| 0.25| 8| O| O| I| I| I| Security deterrent| 111
5
| Alternating| 440-554| 0.4/0.1| 14| I| I| O| I| I| AFNOR, France (NFS 32001)| 109
6| Alternating| 430-470| 1| 14| O| I| O| I| I| | 109
7| Alternating (v.fast)| 800-1000| 0.13| 12| I| O| O| I| I| | 118
8| Alternating (v.fast)| 2500-3200| 0.07| 13| O| O| O| I| I| | 111
9| Alternating| 440-554| 2| 10| I| I| I| O| I| Turn-out, Sweden| 111
10| Continuous note| 700| –| 1| O| I| I| O| I| All-clear, Sweden| 112
11| Continuous note| 1000| –| 31| I| O| I| O| I| | 118
12| Continuous note| 1000| –| 7| O| O| I| O| I| | 118
13| Continuous note| 2300| –| 2| I| I| O| O| I| | 113
14| Continuous note| 440| –| 9| O| I| O| O| I| | 107
15
| Interrupted tone| 1000| 2| 31| I| O| O| O| I| | 118
16| Interrupted tone| 420| 1.25| 30| O| O| O| O| I| AS2220, Australia| 108
17| Interrupted tone| 1000| 0.5| 1| I| I| I| I| O| | 117
18| Interrupted tone| 2500| 0.25| 4| O| I| I| I| O| | 113
19| Interrupted tone| 2500| 0.5| 2| I| O| I| I| O| | 113
20| Interrupted tone| 700| 6/12| 10| O| O| I| I| O| Pre-vital mess, Sweden| 115
21| Interrupted tone| 1000| 1| 32| I| I| O| I| O| | 118
22| Interrupted tone| 700| 4| 10| O| I| O| I| O| Air-raid, Sweden| 115
23| Interrupted tone| 700| 0.25| 10| I| O| O| I| O| Local warning, Sweden| 115
24| Interrupted tone| 720| 0.7/0.3| 10| O| O| O| I| O| Industrial alarm, Germany| 115
25| Int,fast,rising volume| 1400| 0.25| 26| I| I| I| O| O| | 114
26| Fast siren| 250-1200| 0.085| 11| O| I| I| O| O| | 116
27| Rising constant, fall| 1000| 10/40/10| 17| I| O| I| O| O| Industrial alarm, Germany| 120
28
| ISO 8201 Evacuation| 800-1000| as std| 11| O| O| I| O| O| Int’l evacuation alarm| 118
29| Fast whoop| 500-1000| 0.15| 32| I| I| O| O| O| | 116
30| Slow whoop| 500-1200| 4.5| 12| O| I| O| O| O| Evacuation, The Netherlands| 120
31
| Reverse sweep| 1200-500| 1| 11| I| O| O| O| O| Evacuation, Germany| 118
32| Siren| 500-1200| 3| 26| O| O| O| O| O| | 118

Note: EN54-3 Compatible Tones are marked above.

Moflash Signalling Limited accepts no liability for any consequences following the use of this document. Any technical specifications and products referred to within this document are subject to change without notice due to continual improvement and product development policies. All dB(A) figures are subject to environmental conditions. The units are sold under Moflash standard conditions of sale, available on request. Additional resources, including installation sheet translations, certificates, and DoCs are available from the www.moflash.co.uk website.