PRODUCT

Control Module Integration in TripSaver®II CutoutMounted Recloser
The S&C TripSaver® II Controller (Model Number TSII-CONTRL5 and TSII-CONTRL6) is an electronic control module integrated into to host product TripSaver® II cutout-mounted recloser which is a self-powered cutout-mounted electronically controlled single-phase re-closer. It uses a vacuum fault interrupter technology and is offered in system class voltage ratings of 15kV and 25kV. The Control module functions remain the same for all TripSaver® II cutout- mounted recloser configurations and are housed in the TripSaver® II recloser. The control module processes all electronic/electrical functions required for the proper operation of the TripSaver® II cutout-mounted recloser. Aside from its primary functions, the controller can be wirelessly accessed via the IEEE 802.15.4 protocol for performing TripSaver® II cutout-mounted recloser maintenance Control module’s design, hardware including transceiver and antenna, software, and communication protocol remains unaltered in all configurations of TripSaver® II cutout-mounted recloser. The Control module is an integral part of the TripSaver® II cutout-mounted recloser and will be integrated by S & C at the factory level. User WILL NOT integrate control module separately but will receive unit TripSaver® II cutout-mounted recloser with control module as an integral part of it. The information on 2.4GHz radio is given below.

Applicant S & C Electric Company
Brand Name TripSaver® II Cutout-Mounted Recloser
Product Model Name TripSaver® II Controller 5 and TripSaver® II

Controller 6
Product Model No.| TSII-CONTRL5 and TSII-CONTRL6
FCC Identifier| U3D-TSIICONTRL6
IC Identifier| 5349C-TSIICONTRL6
Type of transmission| Digital Transmission System (DTS)
Rated RF Output| 10 dBm (10 mW)
Frequency Range| 2405 – 2480 MHz
Type of modulation/data rate| GFSK / 1Mbit/s

O-QPSK / 250Kbit/s

Number of Channel(s)| 16 (from 11 to 26)
Antenna(s) & Gain| PCB antenna, Gain: +3.3 dBi
CT Voltage Input| CT input 230 V AC, 2A, 50/60 Hz J10 input 11-14.5 V DC, 1A
Environmental| – 40°C (-40°F) to +40°C (104°F).
Manufacturer Name & Address| S&C Electric Company 6601 N Ridge Blvd Chicago, IL 60626

This control module has been granted modular approval for TripSaver® II cutout-mounted recloser applications. The final host TripSaver® II cutout- mounted recloser and module combination have been evaluated in a certified lab for FCC Part 15B criteria for unintentional radiators to be properly authorized for operation as a Part 15 digital device. Test reports can be submitted upon request.
Control Module Models:
The Control module of the TripSaver® II cutout-mounted recloser provides controls and all logic functions for the proper functionality of TripSaver® II cutout-mounted recloser has 2 distinct models.

  1. TripSaver® II Controller 5 (TSII-CONTRL5) has the main control board that provides standard 5-second open intervals during TSII reclose sequence.
  2. TripSaver® II Controller 6 (TSII-CONTRL6) provides an Extended Open interval enabling 30-second open intervals during the TSII reclose sequence. The main control board has no sufficient storage energy to implement this feature. Therefore, the addition of a battery and battery charging/discharging circuitry has been added to supply the necessary energy to the control module

Both Control module of the TripSaver® II cutout-mounted recloser has no changes in the outer enclosure. Overall integration and assembly of the battery, battery board, and main control board are shown in fig. 1.