Intesis NASA Compatible Air Conditioning Systems Server User Manual
- June 13, 2024
- Intesis
Table of Contents
Modbus Server
Samsung NASA compatible Outdoor Units
USER MANUAL
Issue date: 12/2020 r1.4 ENGLISH
Connecting Device
Important User Information
Disclaimer
The information in this document is for informational purposes only. Please
inform HMS Industrial Networks of any inaccuracies or omissions found in this
document. HMS Industrial Networks disclaims any responsibility or liability
for any errors that may appear in this document.
HMS Industrial Networks reserves the right to modify its products in line with
its policy of continuous product development. The information in this document
shall therefore not be construed as a commitment on the part of HMS Industrial
Networks and is subject to change without notice. HMS Industrial Networks
makes no commitment to update or keep current the information in this
document.
The data, examples and illustrations found in this document are included for
illustrative purposes and are only intended to help improve understanding of
the functionality and handling of the product. In view of the wide range of
possible applications of the product, and because of the many variables and
requirements associated with any particular implementation, HMS Industrial
Networks cannot assume responsibility or liability for actual use based on the
data, examples or illustrations included in this document nor for any damages
incurred during installation of the product. Those responsible for the use of
the product must acquire sufficient knowledge in order to ensure that the
product is used correctly in their specific application and that the
application meets all performance and safety requirements including any
applicable laws, regulations, codes and standards. Further, HMS Industrial
Networks will under no circumstances assume liability or responsibility for
any problems that may arise as a result from the use of undocumented features
or functional side effects found outside the documented scope of the product.
The effects caused by any direct or indirect use of such aspects of the
product are undefined and may include e.g. compatibility issues and stability
issues.
Gateway for the integration of Samsung NASA compatible systems into Modbus (RTU and TCP) systems.
ORDER CODE | LEGACY ORDER CODE |
---|---|
INMBSSAM004O000 | SM-ACN-MBS-4 |
INMBSSAM008O000 | SM-ACN-MBS-8 |
INMBSSAM016O000 | SM-ACN-MBS-16 |
INMBSSAM064O000 | SM-ACN-MBS-64 |
Description
1.1 Introduction
This document describes the integration of Samsung NASA compatible air
conditioning systems into Modbus compatible devices and systems using using
gateway the Intesis Modbus Server to Samsung NASA AC communication gateway.
The aim of this integration is to monitor and control Samsung NASA air
conditioning systems, remotely, from a Control Center using any commercial
SCADA or monitoring software that includes a Modbus Master driver (RTU and/or
TCP). To do it so, Intesa’s performs as a Modbus Server, allowing poll and
write requests from any Modbus master device.
Intesa’s makes available the Samsung NASA air conditioning system indoor
units’ data points through independent Modbus registers.
Up to 64 indoor units supported, depending on product version.
This document assumes that the user is familiar with Modbus and Samsung
technologies and their technical terms.
Integration of Samsung NASA’s compatible systems into Modbus systems
NOTE: Take following considerations into account for Samsung’s NASA R1/R2 network:
- Samsung NASA AC network allows for both automatic and manual addressing. Manual addressing of both indoor and outdoor units must be setup by Samsung installer in order that Intesis communicates properly. Manual addressing is setup by means of DIP switches in outdoor unit, and using the remote controller or DIP switches in the indoor unit.
- Samsung NASA indoor units need to be configured to accept ‘central control’. To do so, they need to be configured with so-called ‘installation option code’ in which segment 5 of this code needs to be set to value ‘1’ to allow central control.
1.1 Functionality
Intesa’s TM continuously monitors Samsung’s NASA R1/R2 network for all
configured signals and keeps the updated status of all of them in its memory.
It triggers updates on configured group addresses to KNX network on value
change.
Commands toward the R1/R2 indoor unit communication adaptor are permitted.
Each indoor unit is offered as a set of MBS objects.
Element | Object supported |
---|---|
Outdoor Unit | • Communication status |
• Addressing status
Indoor Unit| • Status
• Command
• Communication status
General signals
(all units)| • Command
1.2 Capacity of Intesis
Element | Max. | Notes |
---|---|---|
Number of indoor units | 64 * | Number of indoor units that can be controlled |
through Intesis
Number of Objects| 1124 *| Number of Samsung NASA objects available into
Intesis. (36 global signals + 64 x 17 individual unit signals)
- There are different models of Intesis MBS – Samsung NASA AC each one with different capacity. The table above shows the capacity for the top model (with maximum capacity).
Their order codes are:
-
* * INMBSSAM004O000: Model supporting up to 4 indoor units
- INMBSSAM008O000: Model supporting up to 8 indoor units
- INMBSSAM016O000: Model supporting up to 16 indoor units
- INMBSSAM064O000: Model supporting up to 64 indoor units
Modbus interface
In this section, a common description for all Intesis Modbus series gateways is given, from the point of view of Modbus system which is called from now on internal system. Connection with the Samsung NASA R1/R2 system is also called from now on external system.
1.3 Functions supported
This part is common for Modbus RTU and TCP.
Modbus functions 03 and 04 (Read Holding Registers and Read Input Registers)
can be used to read Modbus registers.
Modbus functions 06 and 16 (Single Multiple Holding Registers and Write
Multiple Holding Registers) can be used to write Modbus registers.
Configuration of poll records is possible between Modbus addresses 0 and
20000. Addresses that are not defined in section 2.2 (Modbus map of the
device) are read-only and will always report 0.
Modbus error codes are supported, they will be sent whenever a non-valid
Modbus address is queried.
All registers are 16-bit signed integer, in standard Modbus Big Endian
(MSB/LSB) format.
Intesis supports Modbus RTU and Modbus TCP and both interfaces can be used
simultaneously.
1.4 Modbus RTU
Both EIA485 and EIA232 physical layers are supported. Only the lines RX, TX and GND of the EIA232 connector are used (TX and RX for EIA485).
Baud rate can be selected between 1200, 2400, 4800, 9600, 19200, 38400, 56700
and 115200. Parity (none, even or odd) and stop bits (1 or 2) can be selected
as well.
Modbus slave number must be configured and the physical connection (RS232 or
RS485) can also be selected
1.5 Modbus TCP
TCP port to use (default is 502) and keep alive period must be configured.
IP settings of Intesis (DHCP status, own IP, net mask and default gateway)
must be configured as welL
1.6 Modbus Address Map
Modbus address from the formula is expressed in link layer format. This is,
first register address is 0.
Available signals depend on unit type, which must be selected in MAPS
configuration tool:
- IU: Indoor Unit
- HE: Hydro Heat ump system
- HT: Hydro Cascade cycle Heat ump system
- EHS: Eco-Heating-System, Air-to-Water Heat ump
- AHU: Air Handling Unit
- ERV: Energy Recovery Ventilation
- ERV+: Energy Recovery Ventilation Plus
- Chiller: Water/liquid circulating Cool/heat ump system
![Intesis NASA Compatible Air Conditioning Systems Server
- Figure 2](https://manuals.plus/wp-content/uploads/2023/09/Intesis-NASA- Compatible-Air-Conditioning-Systems-Server-Figure-2.png)
Connections
Find below information regarding the Intesis connections available.
Power Supply
Must use NEC Class 2 or Limited Power Source (LPS) and SELV rated power
supply.
If using DC power supply:
Respect polarity applied of terminals (+) and (-). Be sure the voltage applied
is within the range admitted (check table below). The power supply can be
connected to earth but only through the negative terminal, never through the
positive
terminal.
If using AC power supply:
Make sure the voltage applied is of the value admitted (24 Vac).
Do not connect any of the terminals of the AC power supply to earth, and make
sure the same power supply is not supplying any other device.
Ethernet
Connect the cable coming from the IP network to the connector ETH of the
gateway. Use an Ethernet CAT5 cable. If communicating through the LAN of the
building, contact the network administrator and make sure traffic on the port
used is allowed through all the LAN path (check the gateway user manual for
more information). Default IP is 192.168.100.246.
DHCP is enabled by default.
PortA / R1/R2 Samsung NASA
Connect the R1 (+) R2 (-) bus of Samsung NASA Outdoor Units to the connectors
A3 (+) A4 (-) of gateway’s PortA.
Respect the polarity.
PortB / Modbus-RTU RS485
Connect the EIA485 bus to connectors B1 (B+), B2 (A-) and B3 (SNGD) of
gateway’s PortB. Respect the polarity.
Remember the characteristics of the standard EIA485 bus: maximum distance of
1200 meters, maximum 32 devices connected to the bus, and in each end of the
bus it must be a termination resistor of 120 Ω. Bus biasing and termination
resistor for EIA485 can be enabled for PortB by means of a dedicated DIP:
SW1:
ON: 120 Ω termination active
OFF: 120 Ω termination inactive (Default setting).
SW2+3:
ON: Polarization active
OFF: Polarization inactive (Default setting).
If the gateway is installed in one bus end make sure that termination is active.
Console Port
Connect a mini-type B USB cable from your computer to the gateway to allow
communication between the Configuration Software and the gateway. Remember
that Ethernet connection is also allowed. Check the user manual for more
information.
USB
Connect a USB storage device (not a HDD) if required. Check the user manual
for more information.
Ensure proper space for all connectors when mounted (see section 6).
1.7 Power device
The first step to perform is to power up the device. To do so, a power supply working with any of the voltage range allowed is needed (check section 5). Once connected the ON led will turn on.
WARNING! In order to avoid earth loops that can damage the gateway and/or any other equipment connected to it, we strongly recommend:
- The use of DC power supplies, floating or with the negative terminal connected to earth. Never use a DC power supply with the positive terminal connected to earth.
- The use of AC power supplies only if they are floating and not powering any other device.
1.8 Connect to Samsung NASA installation
Use the PortA connector in the top corner of the Intesis device in order to
connect Samsung NASA bus to the Intesis. Remember to follow all safety
precautions indicated by Samsung.
To properly communicate with the Intesis, take into account following
considerations:
– Samsung NASA AC network allows for both automatic and manual addressing.
Manual addressing of both indoor and outdoor units must be setup by Samsung
installer in order that Intesis communicates properly. Manual addressing is
setup by means of DIP switches in outdoor unit and using the remote controller
or DIP switches in the indoor unit.
– Samsung NASA indoor units need to be configured to accept ‘central control’.
To do so, they need to be configured with so-called ‘installation option code’
in which segment 5 of this code needs to be set to value ‘1’ to allow central
control.
Connect the Samsung NASA bus to connectors A3 (R1/+), A4 (R2/-) of gateway’s
PortA. Respect the polarity.
1.9 Connection to Modbus
1.9.1 Modbus TCP
The gateways Ethernet port connection is used for Modbus TCP communication.
Connect the communication cable coming from the network hub or switch to the
Ethernet port of Intesis. The cable to be used shall be a straight Ethernet
UTP/FTP CAT5 cable.
TCP port to use (default 502) and keep alive period must be configured.
IP settings of the gateway (DHCP status, own IP, netmask and default gateway)
must be configured as well.
1.9.2 Modbus RTU
Connect the communication cable coming from the motbus network to the port
marked as Port B of the Intesis.
Connect the EIA485 bus to connectors B1 (-), B2 (+) and B3 (SNGD) of gateway’s
PortB. Respect the polarity.
Remember the characteristics of the standard EIA485 bus: maximum distance of
1200 meters, maximum 32 devices (without repeaters) connected to the bus, and
in each end of the bus it must be a termination resistor of 120 Ω. The gateway
has an internal bus biasing circuit that incorporates the termination
resistor. Bus biasing and termination resistor for EIA485 can be enabled for
PortB by means of a dedicated DIP switch.
1.10 Connection to PC (Configuration tool)
This action allows the user to have access to configuration and monitoring
of the device (more information can be found in the configuration tool User
Manual). Two methods to connect to the PC can be used:
- Ethernet: Using the Ethernet port of Intesis.
- USB: Using the console port of Intesis, connect a USB cable from the console port to the PC.
Set-up process and troubleshooting
1.11 Pre-requisites
It is necessary to have the Modbus RTU or TCP master/client device (BMS
side device) operative and properly connected to the corresponding port of the
gateway. 3.2 CONNECT TO SAMSUNG NASA VRF INSTALLATION to check that all the
requirements of the Samsung NASA system are set.
Connectors, connection cables, PC for the Configuration Tool usage and other
auxiliary material, if needed, are not supplied by Intesis for this standard
integration.
Items supplied by HMS Networks for this integration are:
- Intesis gateway.
- Link to download the configuration tool.
- USB Console cable to communicate with Intesis.
- Product documentation.
1.12 Intesis MAPS. Configuration & monitoring tool for Intesis Modbus series
1.12.1 Introduction
Intesis MAPS is a Windows® compatible software developed specifically to
monitor and configure Intesis new generation gateways.
The installation procedure and main functions are explained in the Intesis
MAPS User Manual. This document can be downloaded from the link indicated in
the installation sheet supplied with the Intesis device or in the product
website at www.intesis.com In this section, only
the specific case of Samsung NASA to Modbus systems will be covered.
Please check the Intesis MAPS User Manual for specific information about the
different parameters and how to configure them.
1.12.2 Connection
To configure the Intesis connection parameters press on the Connection button
in the menu bar.
1.12.3 Configuration tab
Select the Configuration tab to configure the connection parameters. Three
subsets of information are shown in this window: General (Gateway general
parameters), Modbus Slave (Modbus interface configuration) and Samsung NASA
(Samsung NASA interface parameters).
1.12.4 Modbus Slave configuration
Set parameters of Modbus Slave interface of Intesis.
-
Modbus Configuration
1.1. Modbus type selection. Select RTU, TCP or simultaneous RTU and TCP communication. -
TCP Configuration.
2.1. Modbus TCP Port: Modbus TCP communication port setting. Default port 502.
2.2. Keep Alive. Set the time of inactivity to send a keep Alive message. Default 10 minutes. -
RTU Configuration.
3.1. RTU bus connection type. Select the RTU connection type serial bus RS485
or 232.
3.2 Baud rate . Set the RTU bus communication speed. Default: 9600 bps.
- Available values: 1200, 2400, 4800, 9600,19200, 38400, 57600, 115200 bps.
3.3 Data Type. Set the Data-bit/parity/stop-bit. Default: 8bit/None/1.
- Available selection: 8bit/None/1, 8bit/Even/1, 8bit/Odd/1, 8bit/None/2.
3.4 Slave Number. Set the Modbus Slave address. Default slave address: 1.
- Valid address: 1..255.
1.12.5 Samsung NASA configuration
Set parameters for connection with Samsung NASA’s installation.
In Units Configuration section you need to enter, for each unit:
- Active. If it’s active (checkbox at Unit xx), ranging from 1 to 64 indoor units that will be integrated (maximum number of units will depend on Intesis model)
- Unit type. Type can be one of the following: IU, HE, HT, EHS, AHU, ERV, ERV+, CHILLER. Available signals will vary according to unit type.
- IU address. Address 0..63 of Unit in Samsung NASA R1/R2 bus. Remember that manual addressing of Samsung indoor units is required.
- OU address. Address 0..15 of Outdoor Unit in Samsung NASA R1/R2 bus. Remember that manual addressing of Samsung indoor units is required.
- Description. Descriptive name to ease identification of the unit (for example, ‘living room floor 1 unit’, etc).
Additional to manual entry of each unit, autodiscover of present units in an R1/R2 installation is possible. To do so, click the button Scan. The following window will appear:
By pressing the Scan button, connected Samsung NASA R1/R2 bus will be scanned
for available units. An Error window will appear if there is a problem in the
connection with R1/R2 bus (units not powered, bus not connected, …).
A progress bar will appear during the scan, which will take up to a few
minutes. After the scan is completed, the detected units will be shown in
available units as follows:
Select with its checkbox units to add (or replace) in installation, according
to selection Replace Units / Add Units.
After units to be integrated are selected, click button Apply, and changes
will appear in previous Units Configuration window.
1.12.6 Signals
All available KNX objects, its corresponding description and other main
parmaters are listed in the signals tab.
1.12.7 Sending the configuration to Intesis
When the configuration is finished, follow the next steps.
- Save the project (Menu option Project->Save) on your hard disk (more information in Intesis MAPS User Manual).
- Go to tab ‘Receive / Send’ of MAPS, and in Send section, press Send button. Intesis will reboot automatically once the new configuration is loaded.
After any configuration
change, do not forget to send the configuration
file to the Intesis using the Send button in the Receive / Send section.
1.12.8 Diagnostic
To help integrators in the commissioning tasks and troubleshooting, the
Configuration Tool offers some specific tools and viewers.
In order to start using the diagnostic tools, connection with the Gateway is
required.
The Diagnostic section is composed by two main parts: Tools and Viewers.
-
Tools
Use the tools section to check the current hardware status of the box, log communications into compressed files to be sent to the support, change the Diagnostic panels’ view or send commands to the gateway. -
Viewers
In order to check the current status, viewer for the Internal and External protocols are available. It is also available a generic Console viewer for general information about communications and the gateway status and finally a Signals Viewer to simulate the BMS behavior or to check the current values in the system.
More information about the Diagnostic section can be found in the Configuraion Tool manual.
1.12.9 Set-up procedure
-
Install Intesis MAPS on your laptop, use the setup program supplied for this and follow the instructions given by the Installation wizard.
-
Install Intesis in the desired installation site. Installation can be on DIN rail or on a stable not vibrating surface (DIN rail mounted inside a metallic industrial cabinet connected to ground is recommended).
-
If using Modbus RTU, connect the communication cable coming from the EIA485 port of the Modbus RTU installation to the port marked as Port B of Intesis (More details in section 3).
If using, Modbus TCP, connect the communication cable coming from the Ethernet port of the Modbus TCP installation to the port marked as Ethernet Port of Intesis (More details in section 3). -
Connect the communication cable coming from the Samsung NASA R1/R2 installation to the port marked as Port A of Intesis (More details in section 3).
-
Power up Intesis. The supply voltage can be 9 to 36 Vdc or just 24 Vac. Take care of the polarity of the supply voltage applied.
WARNING! In order to avoid earth loops that can damage Intesis and/or any other equipment connected to it, we strongly recommend:
• The use of DC power supplies, floating or with the negative terminal connected to earth. Never use a DC power supply with the positive terminal connected to earth.
• The use of AC power supplies only if they are floating and not powering any other device. -
If you want to connect using IP, connect the Ethernet cable from the laptop PC to the port marked as Ethernet of Intesis (More details in section 3).
If you want to connect using USB, connect the USB cable from the laptop PC to the port marked as Console of Intesis (More details in section 3). -
Open Intesis MAPS, create a new project selecting a copy of the one named INMBSSAM—O000.
-
Modify the configuration as desired, save it and download the configuration file to Intesis as explained in the Intesis MAPS user manual.
-
Visit the Diagnostic section, enable COMMS () and check that there is communication activity, some TX frames and some other RX frames. This means that the communication with the Centralized Controller and Modbus Master devices is OK. In case there is no communication activity between Intesis and the Centralized Controller and/or Modbus devices, check that those are operative: check the baud rate, the communication cable used to connect all devices and any other communication parameter.
Electrical & Mechanical Features
Dimensions
Recommended available space for its installation into a cabinet (wall or DIN rail mounting), with space enough for external connections
AC Unit Types compatibility
A list of Samsung unit model references compatible with INKNXSAM—O000and their
available features can be found in:
https://www.intesis.com/docs/compatibilities/inxxxsam0xxo000_compatibility
Error codes for Indoor and Outdoor Units
This list contains all possible values shown in Modbus register for “Error
Code” for each indoor unit and outdoor unit.
It must be taken into account that Outdoor Units are only able to reflect a
single error for each indoor / outdoor unit in the system. Thus, a unit having
two or more active errors from that list will only report a single error code
– the
one of the first error that has been detected.
Error
Code| Description
---|---
101| Indoor unit communication error. Indoor unit can not receive any data
from outdoor unit.
102| Communication error between indoor unit and outdoor unit. Displayed in
indoor unit.
108| Error due to repeated address setting (When 2 or more devices has same
address within the
110| Communication error between Hydro unit HT(Main PBA) and Control kit
PBA(Detection from the Control kit)
121| Error on indoor temperature sensor of indoor unit (Short or Open)
122| Error on EVA IN sensor of indoor unit (Short or Open)
123| Error on EVA OUT sensor of indoor unit (Short or Open)
128| EVA IN temperature sensor of indoor unit is detached from EVA IN pipe
129| EVA OUT temperature sensor of indoor unit is detached from EVA OUT pipe
130| Heat exchanger in/out sensors of indoor unit are detached
135| RPM feedback error of indoor unit’s cleaning fan
151| Error due to opened EEV of indoor unit (2nd detection)
152| Error due to closed EEV of indoor unit (2nd detection)
153| Error on floating switch of indoor unit (2nd detection)
154| RPM feedback error of indoor unit
161| Mixed operation mode error of indoor unit; When outdoor unit is getting
ready to operate in
cooling (or heating) and some of the indoor unit is trying to operate in
heating (or cooling) mode
162| EEPROM error of MICOM (Physical problem of parts/circuit)
163| Indoor unit’s remote controller option input is Incorrect or missing.
Outdoor unit EEPROM data error
180| Simultaneous opening of cooling/heating MCU SOL V/V (1st detection)
181| Simultaneous opening of cooling/heating MCU SOL V/V (2nd detection)
185| Cross wiring error between communication and power cable of indoor unit
186| Connection error or problem on SPi
190| No temperature changes in EVA IN during pipe inspection or changes in
temperature indoor unit with wrong address
191| No temperature changes in EVA OUT during pipe inspection or changes in
temperature is seen in indoor unit with wrong address
198| Error due to disconnected thermal fuse of indoor unit
201| Communication error between indoor and outdoor units (installation number
setting error, repeated indoor unit address, indoor unit communication cable
error)
202| Communication error between indoor and outdoor units (Communication error
on all indoor unit, outdoor unit communication cable error)
203| Communication error between main and sub outdoor units
205| Communication error on all PBA within the outdoor unit C-Box,
communication cable error
206| E206-0001: HUB PBA communication error / E206-0002: FAN PBA communication
errorE206- C003:INV1 PBA communication error / E206-0004: INV2 PBA
communication error
211| When single indoor unit uses 2 MCU ports that are not in series.
212| If the rotary switch (on the MCU) for address setting of the indoor unit
has 3 or more of the same address
213| When total number of indoor units assigned to MCU is same as actual
number of installed indoor units but there is indoor unit that is not
installed even though it is assigned on MCU
---|---
214| When number of MCU is not set correctly on the outdoor unit or when two
or more MCU was installed some of them have the same address
215| When two different MCU’s have same address value on the rotary switch
216| When indoor unit is not installed to a MCU port but the switch on the
port is set to On.
217| hen indoor unit is connected to a MCU port but indoor unit is assigned to
a MCU and the switch on the port is set to Off
218| When there’s at least one or more actual number of indoor unit connection
compared to number of indoor units assigned to MCU
219| Error on temperature sensor located on MCU intercooler inlet (Short or
Open)
220| Error on temperature sensor located on MCU intercooler outlet (Short or
Open)
221| Error on outdoor temperature sensor of outdoor unit (Short or open)
231| Error on COND OUT temperature sensor of main outdoor unit (Short or Open)
241| COND OUT sensor is detached
251| Error on discharge temperature sensor of compressor 1 (Short or Open)
257| Error on discharge temperature sensor of compressor 2 (Short or Open)
262| Discharge temperature sensor of compressor 1 is detached from the sensor
holder on the pipe
263| Discharge temperature sensor of compressor 2 is detached from the sensor
holder on the pipe
266| Top sensor of compressor 1 is detached
267| Top sensor of compressor 2 is detached
269| Suction temperature sensor is detached from the sensor holder on the pipe
276| Error on top sensor of compressor 1 (Short or Open)
277| Error on top sensor of compressor 2 (Short or Open)
291| Refrigerant leakage or error on high pressure sensor (Short or Open)
296| Refrigerant leakage or error on low pressure sensor (Short or Open)
308| Error on suction temperature sensor (Short or Open)
311| Error on temperature sensor of double layer pipe/liquid pipe(sub heat
exchanger) (Short or Open)
321| Error on EVI (ESC) IN temperature sensor (Short or Open)
322| Error on EVI (ESC) OUT temperature sensor (Short or Open)
323| Error on suction sensor 2 (Short or Open)
346| Error due to operation failure of Fan2
347| Motor wire of Fan2 is not connected
348| Lock error on Fan2 of outdoor unit
353| Error due to overheated motor of outdoor unit’s Fan2
355| Error due to overheated IPM of Fan2
361| Error due to operation failure of inverter compressor 2
364| Error due to over-current of inverter compressor 2
365| V-limit error of inverter compressor 2
366| Error due to over voltage /low voltage of inverter PBA2
367| Error due to unconnected wire of compressor 2
368| Output current sensor error of inverter PBA2
369| DC voltage sensor error of inverter PBA2
374| Heat sink temperature sensor error of inverter PBA2
378| Error due to overcurrent of Fan2
385| Error due to input current of inverter 2
386| Over-voltage/low-voltage error of Fan2
387| Hall IC connection error of Fan2
389| V-limit error on Fan2 of compressor
393| Output current sensor error of Fan2
396| DC voltage sensor error of Fan2
---|---
399| Heat sink temperature sensor error of Fan2
400| Error due to overheat caused by contact failure on IPM of Inverter PBA2
407| Compressor operation stop due to high pressure protection control
410| Compressor operation stop due to low pressure protection control or
refrigerant leakage
416| Compressor operation stop due to discharge temperature protection control
425| Phase reversal or phase failure (30 outdoor unit wiring, R-S-T-N ),
connection error on 3 phase input
428| Compressor operation stop due abnormal compression ratio
438| EVI (ESC) EEV leakage or internal leakage of intercooler or incorrect
connector insertion of EVI (ESC) EEV
439| Error due to refrigerant leakage
440| Heating mode restriction due to high air temperature
441| Cooling mode restriction due to low air temperature
442| Refrigerant c haring restriction in heating mode when air temperature is
over 15 °C
443| Operation prohibited due to the pressure drop
445| CCH is deatched
446| Error due to operation failure of Fanl
447| Motor wire of Fanl is not connected
448| Lock error on Fanl
452| Error due to ZPC detection circuit problem or power failure
453| Error due to overheated motor of outdoor unit’s Fan1
455| Error due to overheated IPM of Fan1
461| Error due to operation failure of inverter compressor 1
462| Compressor stop due to full current control or error due to low current
on CT2
464| Error due to over-current of inverter compressor 1
465| V-limit error of inverter compressor 1
466| Error due to over voltage /low voltage of inveter PBA1
467| Error due to unconnected wire of compressor 1
468| Output current sensor error of inverter PBA1
469| DC voltage sensor error of inver PBA1
474| Heat sink temperature sensor error of inverter PBA1
478| Error due to overcurrent of Fanl
485| Error due to input current of inverter 1
486| Error due to over voltage/low voltage of Fan
487| Hall IC error of Fanl
489| V-limit error on Fanl of compressor
493| Output current sensor error of Fanl
496| DC voltage sensor error of Fan1
499| Heat sink temperature sensor error of Fanl
500| Error due to overheat caused by contact failure on IPM of Inverter PBA1
503| Error due to alert the user to check if the service valve is closed
504| Error due to self diagnosis of compressor operation
505| Error due to self diagnosis of high pressure sensor
506| Error due to self diagnosis of low pressure sensor
560| Outdoor unit’s option switch setting error (when iinappropriate option
switch is on)
563| Error due to module installation of indoor unit with old version (Micom
version needs to be checked)
573| Error due to using single type outdoor unit in a module installation
601| Communication error between remote controller and the DVM Hydro unit /
Hydro unit HT
602| Communication error between master and slave remote controller
604| Tracking error between remote controller and the DVM Hydro unit / Hydro
unit HT
---|---
618| Error due to exceeding maximum numbers of Hydro unit installation (16
units)
627| Error due to exceeding maximum numbers of wired remote controller
installation (2 units)
633| Error caused by installing mixed models
653| Remote controller’s temperature sensor is disconnected or has problem
654| Data error on remote controller (Memory read/write error)
702| Error due to closed EEV of indoor unit (1st detection)
703| Error due to opened EEV of indoor unit (1st detection)
901| Error on the sensor of water inlet pipe (Short or Open)
902| Error on the sensor of water outlet pipe (Short or Open)
904| Error on water tank (Short or open)
907| Error due to pipe rupture protection
908| Error due to freeze prevention (Re-operation is possible)
909| Error due to freeze prevention (Re-operation is impossible)
910| Water temperature sensor on water outlet pipe is detached
911| Flow switch off error, When the switch Is turned off within 10 seconds
after a pump starts its operation (Re-operation Is possible)
913| Six times detection for Flow Switch Error (Re-operation is not possible)
914| Error due to incorrect thermostat connection
915| Error on DC fan(Non-operating)
573| Error due to using single type outdoor unit in a module installation
601| Communication error between remote controller and the DVM Hydro unit /
Hydro unit HT
602| Communication error between master and slave remote controller
604| Tracking error between remote controller and the DVM Hydro unit / Hydro
unit HT
618| Error due to exceeding maximum numbers of Hydro unit installation (16
units)
627| Error due to exceeding maximum numbers of wired remote controller
installation (2 units)
633| Error caused by installing mixed models
653| Remote controller’s temperature sensor is disconnected or has problem
654| Data error on remote controller (Memory read/write error)
702| Error due to closed EEV of indoor unit (1st detection)
703| Error due to opened EEV of indoor unit (1st detection)
901| Error on the sensor of water inlet pipe (Short or Open)
902| Error on the sensor of water outlet pipe (Short or Open)
904| Error on water tank (Short or open)
907| Error due to pipe rupture protection
908| Error due to freeze prevention (Re-operation is possible)
909| Error due to freeze prevention (Re-operation is impossible)
910| Water temperature sensor on water outlet pipe is detached
911| Flow switch off error, When the switch Is turned off within 10 seconds
after a pump starts its operation (Re-operation is possible)
913| Six times detection for Flow Switch Error (Re-operation Is not possible)
914| Error due to incorrect thermostat connection
915| Error on DC fan(Non-operating)
© HMS Industrial Networks S.L.U. – All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
References
- Intesis | Gateway solutions for Building Automation
- Intesis | Gateway solutions for Building Automation
- Intesis | Gateway solutions for Building Automation
- intesis.com/docs/compatibilities/inxxxsam0xxo000_compatibility
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>