Fantech VER 100 Energy Recovery Ventilator Instruction Manual

June 13, 2024
fantech

Fantech VER 100 Energy Recovery Ventilator

Fantech VER 100 Energy Recovery Ventilator

PARTS IN THE BOX

  • Energy Recovery Ventilator, 1 pc
  • Hanging Chain Kit, 1 pc
  • Drain Hose Kit, 1 pc
  • Operation and Installation Manual, 1 pc

Your ventilation system should be installed in conformance with the appropriate provincial requirements or, in the absence of such requirements, with the current edition of the National Building Code, and / or ASHRAE’s “Good Engineering Practices”.

Safety Precaution

Safety precaution

PLEASE READ AND SAVE THESE INSTRUCTIONS

Before installation careful consideration must be given to how this system will operate if connected to any other piece of mechanical equipment, i.e. a forced air furnace or air handler operating at a higher static pressure. After installation, the compatibility of the two pieces of equipment must be confirmed by measuring the airflow of the Energy Recovery Ventilator using the balancing procedure found in this manual. It is always important to assess how the operation of any ERV may interact with vented combustion equipment (i.e. Gas Furnaces, Oil Furnaces, Wood Stoves, etc.)

Products are designed and manufactured to provide reliable performance, but they are not guaranteed to be 100% free of defects. Even reliable products will experience occasional failures, and this possibility should be recognized by the user. If these products are used in a life support ventilation system where failure could result in loss or injury, the user should provide adequate back-up ventilation, supplementary natural ventilation or failure alarm system, or acknowledge willingness to accept the risk of such loss or injury.

Your ventilation system should be installed in accordance with the local building code that is in effect, in absence of such requirements, it is recommenced to check with local authorities having jurisdiction in your area prior to installing this product.

DETERMINING YOUR AIRFLOW REQUIREMENT

Room Count Method

Room classification| Number of rooms| CFM (L/s)| CFM Required
---|---|---|---
Master bedroom| | x 10 L/s (20 CFM)| =
Basement| yes or no| if yes add 10 L/s (20 CFM) if no = 0| =
Bedrooms| | x 5 L/s (10 CFM)| =
Living room| | x 5 L/s (10 CFM)| =
Others| | x 5 L/s (10 CFM)| =
Kitchen| | x 5 L/s (10 CFM)| =
Bathroom| | x 5 L/s (10 CFM)| =
Laundry room| | x 5 L/s (10 CFM)| =
Utility room| | x 5 L/s (10 CFM)| =

ASHRAE method

Ventilation Air requirements

Floor area Bedrooms
1 2
Ft2 m 2
L/s CFM
< 500 < 47
501 -1000 47- 93
1001- 1500 94- 139
1501- 2000 140- 186

49
2001- 2500| 187- 232| 90| 42| 98| 45| 105| 49| 113| 52| 120| 56
2501- 3000| 233- 279| 105| 49| 113| 52| 120| 56| 128| 59| 135| 63
3001- 3500| 280- 325| 120| 56| 128| 59| 135| 63| 143| 66| 150| 70
3501- 4000| 326- 372| 135| 63| 143| 66| 150| 70| 158| 73| 165| 77
4001- 4500| 373- 418| 150| 70| 158| 73| 165| 77| 173| 80| 180| 84
4501- 5000| 419- 465| 165| 77| 173| 80| 180| 84| 188| 87| 195| 91

  • ASHRAE 62.2-2016 Table 4.1, Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings.

Bathroom: If the ERV is going to provide the required local exhaust ventilation for each bathroom with each a continuous 20 CFM (10 L/s), this ventilation rate can be considered as part of the whole-building ventilation rate.

INSTALLATION EXAMPLES

Example only – duct configuration may differ depending on the model.

FULLY DEDICATED SYSTEM

BEST FOR NEW CONSTRUCTION

  1. Stale air is drawn from key areas of the home requiring local exhaust (bathroom, kitchen, laundry room).
  2. Fresh air is distributed directly to habitable rooms in the house\ (bedrooms, living room)
  3. The ERV’s airflow must be balanced after installation using the procedure found in the section “AIRFLOW BALANCING”.

Suggested installation for:

  • Hydronic baseboard
  • Infloor heating
  • Electric baseboard
  • Mini split heat pump

Benefits: Provides the best fresh air distribution in the house; lowest operation cost since the furnace/air handler unit is not needed.

ERV ducting for fully Dedicated System

ERV ducting for fully Dedicated System

DIRECT CONNECTION of the FRESH air to living area to the RETURN PLENUM of the AIR HANDLER (Stale air drawn from key areas of home.

PARTIALLY DEDICATED SYSTEM (BETTER)

  1. In order to provide proper distribution of the fresh air, it is recommended that the furnace blower be set to run continuously or interconnected with ERV. See furnace electrical connection on page 18.
  2. Stale air is drawn from key areas of the home (bathroom, kitchen, laundry room).
  3. Fresh air is supplied to the return air plenum of the furnace.
  4. Due to the difference in pressure between the ERV and the equipment it is being connected to the ERV’s airflow must be balanced on site, using the procedure found in the section “AIRFLOW BALANCING”
    • In the case of a multi-zone system, please contact Fantech customer service prior to installing any installation type requiring the use of the furnace interlock”

Suggested installation for:

  • Central furnace (air handling unit or central air conditioners)
  • When ducting fresh air to living area is not possible or practical, i.e. expensive or when the central AHU will operate year-round.

Benefits: Conditions the fresh air prior to distributing it throughout the house

ERV/ Furnace ducting for Partially Dedicated System

ERV/ Furnace ducting for Partially Dedicated System

Fantech energy recovery ventilators (ERV) that use a supply fan shutdown for frost prevention do not include an outdoor air motorized damper. If you are using a simplified installation, i.e. connecting the ERV supply air duct to a furnace’s return air duct, the ERV must operate continuously. When the ERV is turned off, no warm exhaust air will flow through the ERV but the furnace’s fan will continue to draw in outdoor air directly into the furnace. If it’s cold outside, cold air will be introduced, without re-heating, directly into the furnace.

If the ERV is installed such that the homeowner may turn off the ERV during the winter, we recommend installing a motorized damper between the ERV’s supply air and the furnace’s **return air duct that closes when the ERV is not operating. See wiring diagram (figure 1).

**

DIRECT CONNECTION of both the ERV SUPPLY AIR STREAM and EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN.

SIMPLIFIED INSTALLATION (GOOD)

(RETURN/RETURN METHOD) – OPTION 1

  1. **** Furnace blower must operate when ventilation from ERV is required. The furnace should be set to run continuously or interlocked with ERV. See furnace electrical connection on page 18.
  2. A minimum separation of 1m (39’’) is recommended between the two direct connections.
  3. In order to prevent exhausting any fresh air, the ERV’s exhaust air connection should be upstream of the ERV’s supply air connection when ducting to the furnace’s cold air return.
  4. Due to the difference in pressure between the ERV and the equipment it is being connected to the ERV’s airflow must be balanced on site, using the procedure found in the section “AIRFLOW BALANCING”
  • In the case of a multi-zone system, please contact Fantech customer service prior to installing any installation type requiring the use of the furnace interlock”

Suggested installation for:

  • When bathroom and kitchen already have local exhaust system
  • May be suitable for retrofitting

Benefits: Least expensive installation type..

ERV/ furnace for Simplified Installation – Option 1

ERV/ furnace for Simplified Installation – Option 1

Fantech energy recovery ventilators (ERV) that use a supply fan shutdown for frost prevention do not include an outdoor air motorized damper. If you are using a simplified installation, i.e. connecting the ERV supply air duct to a furnace’s return air duct, the ERV must operate continuously. When the ERV is turned off, no warm exhaust air will flow through the ERV but the furnace’s fan will continue to draw in outdoor air directly into the furnace. If it’s cold outside, cold air will be introduced, without re-heating, directly into the furnace.

If the ERV is installed such that the homeowner may turn off the ERV during the winter, we recommend installing a motorized damper between the ERV’s supply air and the furnace’s _ **return air duct that closes when the ERV is not operating. See wiring diagram (figure 1).

**_

DIRECT CONNECTION of the ERV SUPPLY AIR STREAM to the SUPPLY AIR SIDE on the FURNACE & EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN.

OPTION 2

  1. **** Furnace blower must operate when ventilation from ERV is required. The furnace should be set to run continuously or interlocked with ERV. See furnace electrical connection on page 18.
  2. Due to the differences in pressure between the ERV and the equipment it is being connected to, the ERV‘s airflow must be balanced on site, using the procedure found section “AIRFLOW BALANCING”.
  • In the case of a multi-zone system, please contact Fantech customer service prior to installing any installation type requiring the use of the furnace interlock”.

Suggested installation for:

  • When bathroom and kitchen already have local exhaust system
  • May be suitable for retrofitting

Benefits: Least expensive installation type.

**** In the case of a simplified installation, Option 1 is recommended.

ERV/Furnace ducting for Simplified Installation – Option 2

ERV/Furnace ducting for Simplified Installation - Option
2

Fantech energy recovery ventilators (ERV) that use a supply fan shutdown for frost prevention do not include an outdoor air motorized damper. If you are using a simplified installation, i.e. connecting the ERV supply air duct to a furnace’s return air duct, the ERV must operate continuously. When the ERV is turned off, no warm exhaust air will flow through the ERV but the furnace’s fan will continue to draw in outdoor air directly into the furnace. If it’s cold outside, cold air will be introduced, without re-heating, directly into the furnace.

If the ERV is installed such that the homeowner may turn off the ERV during the winter, we recommend installing a motorized damper between the ERV’s supply air and the furnace’s return air duct that closes when the ERV is not operating. See wiring diagram (figure 1).

EXTERIOR DUCTING INSTALLATION

WEATHERHOOD LOCATION

  • Decide where your intake and exhaust hoods will be located.

Locating the Intake Weatherhood

  • Should be located upstream (if there are prevailing winds) from the exhaust outlet.
  • At a minimum distance to 900 mm (3′) away from dryer vents and furnace exhaust (medium or high efficiency furnaces), driveways, oil fill pipes, gas meters, or garbage containers.
  • At a minimum height of 460mm (18’’) above the ground, or above the level of expected snow accumulation.
  • Ideally, keep weatherhoods 1m (3′) from corners.
  • Do not locate in the garage, attic, crawl space, or underneath deck.

Locating the Exhaust Weatherhood

  • At least 460mm (18″) above ground or above the depth of expected snow accumulation
  • Ideally, keep weatherhoods 1m (3′) from corners.
  • Not near a gas meter, electric meter or a walkway where fog or ice could create a hazard
  • Do not locate in a garage, workshop or other unheated space

INSTALLING THE DUCTING TO THE WEATHERHOODS

A well designed and installed ducting system will allow the ERV to operate at its maximum efficiency. The inner liner of the flexible insulated duct must be secured to the sleeve of the weatherhood (as close to the outside as possible) and to the appropriate duct connection on the ERV. The insulation should remain full and not crushed. The outer liner, which acts as a vapor barrier, must be completely sealed to the outer wall and the ERV using tape and/or caulking. A good bead of high quality caulking (preferably acoustical sealant) will seal the inner flexible duct to both the ERV duct connection and the weatherhood prior to securing them.
To minimize airflow restriction, the flexible insulated duct that connects the two outside weatherhoods to the ERV should be stretched tightly and be as short as possible.
Twisting or folding the duct will severely restrict airflow.

See “Installation Diagram Examples” for installation examples.

STEPS FOR HOOD INSTALLATION:

  1. Using the duct connection of the outside hood, outline the intake & exhaust holes to be cut. The holes should be slightly larger than the duct connection to allow for the thickness of the insulated flexible duct. Cut a hole for both the intake and exhaust hoods.

  2. Pull the insulated flexible duct through the opening until it is well extended and straight. Slide the duct’s inner vinyl sleeve over the hood duct connection and secure. Pull the insulation over the duct and pull the vapor barrier over the sleeve. Secure with appropriate tape or sealant.

  3. Push the hood into the opening and then attach the hood to the outside wall with mounting screws.
    Repeat the installation procedure for both the supply and exhaust hoods.

  4. Using a caulking gun, seal around both hoods to prevent any leaks.

INTERIOR DUCTING INSTALLATION

  • To maximize airflow through the ductwork system, all ducts should be kept short and have as few bends or elbows as possible.
  • 45º elbows are preferable to 90º.
  • Use “Y“ ducts instead of “T” ducts whenever possible.
  • All duct joints must be fastened with screws or duct sealant and wrapped with aluminum foil duct tape to prevent leakage.
  • Galvanized ducting from the ERV to the living areas in the house is recommended whenever possible, although flexible ducting can be used in moderation when necessary.
  • To avoid possible noise transfer through the ductwork system, a short length (approximately 300mm, 12’’) of nonmetallic flexible insulated duct should be connected between the ERV and the supply/exhaust ductwork system.
  • The main supply and return line to/from the ERV must have the same diameter as the duct connection or larger.
  • Branch lines to the individual rooms may be as small as 100mm (4’’).

INSTALLING DUCT TO ERV

For flexible duct installation, slide flexible ducting onto duct connection. Then install a cable tie over flexible duct to prevent leakage between the ducting and the duct connection.
In the case of solid ducting, slide duct over duct connection, screw in place and seal.

SUPPLY AIR GRILLES LOCATION
In homes without a forced air furnace, fresh air should be supplied to all habitable rooms, including bedrooms and living areas. It should be supplied from high wall or ceiling locations. Grilles that diffuse the air comfortably are recommended. In homes with a forced air furnace, you may want to connect the ERV to the furnace ductwork (see information below).

EXHAUST AIR GRILLES LOCATION
The stale air exhaust system is used to draw air from the points in the house where the worst air quality problems occur. It  is recommended that return air ducts be installed in the bathroom, kitchen, and laundry room. Additional return air ducts from strategic locations may be installed. The furnace return duct may also be used to exhaust from. In this method, the exhaust air is not ducted back from bathrooms, kitchens, etc to the ERV with “dedicated lines”.

__ As per building codes and installation requirements for combustion appliances:
Air return ducts, or openings for air return, should not be placed in enclosed spaces containing combustion appliances that are subject to spillage.

ERV INSTALLATION

LOCATION

The ERV must be located in a conditioned space where it will be possible to conveniently service the unit. Typically
the ERV would be located in the mechanical room or an area close to the outside wall where the weatherhoods will
be mounted. If a basement area is not convenient or does not exist, a utility room may be used.

  • Have a nearby power supply (120 volts, 60Hz)
  • Choose a location which allows the possibility of mounting the unit to supporting beams.
  • The unit should be level in order to allow proper condensate drainage
  • To minimize noise, do not install unit in living area
  • Ensure proper drainage

Attic installation must meet the following conditions:

  • Attic temperature must be above freezing conditions at all times and for best performance should be 12°C (54 °F).
  • The condensate drain (if included) must be installed so that the condensate drains and is protected from freezing.
  • The attic is easily accessible for equipment maintenance and inspection.

Connecting appliances to the ERV is not recommended. These include:

  • Clothes dryer
  • Range top
  • Stovetop fan
  • Central vacuum system
  • Bathroom exhaust fans unless they are specifically designed for this purpose

These appliances may cause lint, dust or grease to collect in the ERV, damaging the unit.

**** Connecting any of these types of appliances to the ERV will void your warranty. 

MOUNTING – WALL MOUNT

BRACKET MOUNTING KIT INCLUDES

  • Mounting bracket, 1 pc
  • Rubber vibration isolators, 4 pcs
  • Screws, 4 pcs
  • Washers, 4 pcs
  • Safety screws, 2 pcs
  1. Attach bracket to wall using 4 screws and washers provided.

  2. Lift unit and slide into slots on the bracket

  3. Insert the safety screws on both sides to secure the unit.

Mounting- Chain mount

Optional

  1.  Place fastening hooks on the strapping board or the floor joists.

  2. Attach a hanging chain (provided) to each 19 mm (3/4″) bolt (provided) in the top 4 corners of the unit and tighten.

  3. Hang the unit by slipping a link onto the hanging hooks, making sure the unit is level.

  4. Install a spring on each chain. Hook the spring in the links so a loop is created in the chain. The spring will then support the unit’s weight and absorb vibrations.

INSTALLING DRAIN LINE

Through normal operation and during its defrost mode, the ERV may produce some condensation. This water should flow into a nearby drain, or be taken away by a condensate pump. The ERV and all condensate lines must be installed in a space where the temperature is maintained above the freezing point.
A “P” trap should be made in the drain line. This will prevent odors from being drawn back up into the unit.

The drain nipple is placed upside down in the unit to prevent it being damaged during shipping or the installation of the unit.
For both drain and drainless installation the drain nipple needs to be flipped.

  1. Remove the nutsert.

  2. Invert the drain nipple. Make sure to place gasket between the unit and the drain nipple inside the unit.

  3. Secure the drain nipple using the nutsert.

  4. Install the drain hose making a “P” trap, secure the condensate line drain connection using the tube clamp provided.
    Fill the condensate line with water.

Caution:
A Drain and Tubing (included) must be installed for all HRV units. For ERV units, drain is not required, however, it is recommended for climates where outdoor temperature typically remains below -25°C (-13°F) combined with an indoor relative humidity higher than 40% for a period of 24 hours or several days in a row.

AIRFLOW ADJUSTMENT & BALANCING

BALANCING THE AIRFLOWS IS CRUCIAL TO ENSURE OPTIMAL OPERATION OF THE UNIT. IF THE AIRFLOW IS NOT PROPERLY BALANCED, THE FOLLOWING ISSUES MAY OCCUR:

  • SIGNIFICANT POSITIVE OR NEGATIVE PRESSURE INSIDE THE HOUSE
  • UNIT’S EFFICIENCY MAY BE NEGATIVELY AFFECTED
  • UNIT’S DEFROST MAY NOT WORK EFFECTIVELY
  • CAN LEAD TO AIR LEAKS OR BACKDRAFTING OF ANY COMBUSTION APPLIANCES.

The airflow adjustment and balancing procedure consists of adjusting the fresh airflow to make sure it meets the requirements for the building and then balance the system to make sure there is an equal amount of stale air being exhausted. In the case that the airflow is not exactly the same, it is recommended to have a higher stale airflow of up to 10% in colder climates to ensure that the temperature of the fresh airflow coming from the outside is as close to the room temperature as possible.

GENERAL PREPARATION:

Before performing the adjustment and balancing for unit, make sure to check the following:

  • Seal all the ductwork
  • Fully open all dampers (if present)
  • Turn off all other exhaust appliances such as range hood, dryers, bathroom fans, etc.
  • If performing balancing during cold weather, make sure the unit is not operating in defrost mode.
  • If the installation type is Simplified or Partially Dedicated, make sure that the furnace/air handler blower is operating at normal speed during the balancing sequence.
  • When reading with a mechanical type manometer (Magnehelic), make sure the manometer is placed on a level surface

For optimal performance, ERV unit should be re-balanced after a major renovation or after the installation of extra grilles or registers.

  • In cold climates, continuous excessive positive pressure inside the house may drive moisture inside the external walls of the house. Moisture present inside the external wall may condense if the outside temperature is cold enough and can cause damage to structural components. A symptom of excessive positive pressure inside a house is frozen door locks.
  • Continuous excessive negative pressure can have undesirable effects. In some geographic locations, negative pressure can increase the infiltration of soil gases such as methane and radon. Negative pressure is also undesirable where combustion equipment is present and may cause back drafting of the combustion gases.

ADJUSTING AIRFLOWS USING INTEGRATED BALANCING SYSTEM

Adjustable dampers are integrated into the Fresh Air to Building and the Stale Air to Outside duct connections. Those dampers replace the installation of separate back draft and balancing dampers in the duct line.

The integrated dampers are preset at the fully opened position. In order to reduce the amount of airflow, turn the adjustable lever using a flat screw driver by turning it counter clock wise. Turning the lever clockwise may damage the plastic screw head. Follow the balancing steps to properly adjust the airflow.

BALANCING STEPS

Use balancing chart located on the door of the ERV.

STEP #1 : Identify the desired airflow using the provided chart. From the desired airflow (left column) identify the pressure reading needed by simply following the line. Make sure to set the unit at the Normal speed before performing the next step.
STEP #2 : Measure the pressure reading by connecting a manometer on the LOW and HIGH pressure ports located on the duct connection. Refer to Illustration #1. If the pressure reading is LOWER than the desired value, adjust the balancing dampers by turning the adjustable arm counter clockwise until the correct corresponding pressure value is reached. Refer to Illustration #2 Do the same for both the SUPPLY and EXHAUST airflows. If the pressure reading is HIGHER than desired when the damper is fully opened, please check the distribution system for any anomalies that could increase the resistance in the distribution system.

BALANCING CHART (example only)

Airflow Normal Speed Reduced Speed
CFM L/s ∆In W.G. Pressure read ng
110 52 0.36
100 47 0.46
90 42 0.55
80 38 0.64
70 33 0.74
65 31 0.78
60 28 0.83
55 26 0.87
50 24 0.92
  • If the house is tightly sealed, adjusting one airflow may affect the other airflow as well. It is recommended to check each airflow again to make sure the value did not change dramatically during the balancing procedure. Make adjustments as necessary.
  • The pressure reading from the duct connection refers to the total pressure loss from the distribution system. A well designed distribution system should have a total pressure loss between 0.4” (100Pa) and 0.6” (150Pa). The pressure reading can therefore be used to troubleshoot distribution system. If the pressure reading is higher than 0.6” (150Pa), we recommend that you inspect the system and check for closed grilles, blocked exterior hoods or twisted flexible duct.

STEP #3: Secure the adjustable arm by tightening the set screw as shown in Illustration#3.
Balancing Steps

LOW VOLTAGE CONTROL SYSTEMS

* Please see instruction manuals for individual controls for proper wiring and set up of control systems.

  1. . Ensure that unit is not plugged when connecting the control
  2.  Recirculation mode is only available with the Flex100H ES, HERO series and the models with the “R” suffix at the end of the model number.

The wiring connectors can be removed for easier connection.

CENTRAL CONTROLS

These cannot be used with another central control
*Maintain polarity between control and ERV (+ → + ; – → -)

ECO **SERIES*** FEATURES CONNECT TO

ECO- Touch®

|

  • Our most complete, yet easy-to-use control system
  • Sleek design with backlight touchscreen LCD
  • ECO mode selects the best operating mode and speed for the season, minimizing energy use associated with ventilation
  • Set preferred indoor relative humidity range and ventilation mode for day and night conditions
  • No battery to replace, all programmed settings are retained during power outages
  • Maintenance reminder indicator
  • Error code messages reduce troubleshooting time

|

ECO- TouchIAQ

|

  • Integrated VOC Sensor
  • Our most complete, yet easy-to-use control system
  • Sleek design with backlight touchscreen LCD
  • ECO mode selects the best operating mode and speed for the season, minimizing energy use associated with ventilation
  • Set preferred indoor relative humidity range and ventilation mode for day and night conditions
  • No battery to replace, all programmed settings are retained during power outages
  • Maintenance reminder indicator
  • Error code messages reduce troubleshooting time

ECO- Feel

|

  • ECO mode selects the best operating mode and speed for the season, minimizing energy use associated with ventilation
  • Integrated VOC Sensor
  • No battery to replace, all programmed settings are retained during power outages

EDF SERIES| FEATURES| CONNECTS TO

EDF7

|

  • MODE button provides 3 modes of operations: Ventilation , Recirculation and Standby
  • User selected fan speed: Reduced, Medium, Normal and 20 minutes per hour
  • AUTO setting allows the homeowner to deactivate the dehumidistat
  • When the humidity exceeds the desired setpoint, the ventilation system operates at normal speed
  • Once the desired humidity level is achieved, your ventilation system resumes to its previous mode of operation.

|

EDF1

|

  • Press button once for continuous Reduced speed
  • Press button twice and the unit will cycle 20 minutes ON/ 40 minutes OFF and repeat
  • EDF1 Press button a third time and the system will run continuously on HIGH speed

AUXILIARY CONTROL –These controls can be paired with central controls or combined together.

*Maintain polarity between control and ERV (+ → + ; – → -)

RTS SERIES FEATURES CONNECTS TO
  • Wireless timer
  • Can only be paired with the ECO-Touch IAQ
  • 20/40/60 minute timer with LED light
  • Boosts system to high speed with the touch of a button
  • Up to 5 can be used in one system
  • Use in bathroom, kitchen, laundry room

| Connects wireleslly to the

**RTS2***

|

  • 20- minute timer with LED light
  •  Boosts system to high speed with the touch of a button
  • Up to 5 can be used in one system
  • Use in bathroom, kitchen, laundry room

|

**RTS5***

|

  • 20/40/60 minute timer with LED light
  • Boosts system to high speed with the touch of a button
  • Up to 5 can be used in one system
  • Use in bathroom, kitchen, laundry room

MDEH SERIES| FEATURES| CONNECT TO

MDEH1

|

  • Rotary dial Dehumidistat
  • Multiple units can be used
  • We recommend setting the relative humidity above 80% during the summer

|

WIRING DIAGRAM

WIRING DIAGRAM

WIRING DIAGRAM TO FURNACE

FOR A FURNACE CONNECTION TO A COOLING SYSTEM:

On some newer furnaces and older thermostats, energizing the R and G terminal at the furnace has the effect of energizing the Y at the thermostat and thereby turning on the cooling system. If you identify this type of thermostat, you must use the “Alternate Furnace Interlock Wiring.
Standard Accessory Control Contact

As per building codes and installation requirements for combustion appliances: Air return ducts, or openings for air return, should not be placed in enclosed spaces containing combustion appliances that are subject to spillage.

TROUBLESHOOTING

Problem Causes Solutions
Air is too dry Dehumidistat control is set too low Increase the desired

level of humidity. Change ventilation mode from continuous mode to standby.
ERV out of balance| Have contractor balance ERV airflows
Air is too humid| Dehumidistat control is set too high| Reduce the desired level of humidity. Combine this with the use of continuous

exchange mode.

Sudden change in temperature| Wait until outside temperature stabilizes (winter). Heating will also improve

situation.

Storing too much wood for heating| Store a majority of your wood outside. Even dried, a cord of wood contains

more than 20 gallons of water.

Dryer vent exhaust is inside home| Make sure the dryer vent is exhausting outside.
Poor air circulation near windows| Open curtains or blinds.
ERV out of balance| Have contractor balance ERV airflows
Well sealed basement door is closed| Open the door or install a grill on the door.
Persistent condensation on window| Improper adjustment of dehumidistat control| Reduce the desired level of humidity. Combine this step with use of continuous

exchange mode.

ERV out of balance| Have contractor balance ERV
Poor air circulation near windows| Open curtains or blinds.
Poor Air Flows| 1/4″ (6mm) mesh on the outside hoods is plugged| Clean exterior hoods or vents
Filters plugged| Remove and clean filter
Core obstructed| Remove and clean core
Indoor grilles closed or blocked| Check and open grilles
Inadequate power supply at site| Have electrician check supply voltage
Ductwork is restricting airflow| Check duct installation
Improper speed control setting| Increase the speed of the ERV (i.e. change unit control from REDUCED to NORMAL

speed)

ERV airflow improperly balanced| Have contractor balance ERV airflows
Ducting has fallen down or been disconnected from ERV| Have contractor reconnect ducting
Supply air feels cold| Poor location of supply grilles, the airflow may irritate the occupant| Locate the grilles high on the walls or under the baseboards, install ceiling

mounted diffuser or grilles so as not to directly spill the supply air on the occupant (eg. Over a sofa)

Turn down the ERV supply speed. A small duct heater (1kw) could be used to temper the supply air

Placement of furniture or closed doors is restricting the movement of air in the home

Outdoor temperature extremely cold| If supply air is ducted into furnace return, the furnace fan may need to run

continuously to distribute ventilation air comfortably

ERV and/or Ducts frosting up| ERV air flows are improperly balanced| Have HVAC contractor balance the ERV airflows
Malfunction of the ERV defrost system| Note: minimal frost build-up is expected on the core before unit initiates

defrost cycle functions

Condensation or Ice Build Up in

Insulated Duct to the Outside

| Incomplete vapor barrier around insulated duct| Tape and seal all joints
A hole or tear in outer duct covering| Tape any holes or tears made in the outer duct covering Ensure that the vapor barrier is completely sealed.

Note: It is best to get the unit checked by a certified HVAC Contractor/Technician.

ERV CORE WASHING INSTRUCTIONS

For proper maintenance of your energy recovery core please follow these instructions.

  1. Remove both filters by sliding them out.

  2. Remove the core from the unit.

  3. With one of your core’s air inlets facing down, place it in a large sink, bathtub, or shower.

  4. Pour clean tap water through the face of the core facing upwards until it runs clear.
    Ensure the entire surface is rinsed.

  5. Rotate the core so that its other air inlet is facing down and repeat step 5.

  6. With plates still oriented vertically allow the core to dry, normally 2-3 hours.

  7. Slide back the core into the unit

  8. Replace both filters.

Limited Warranty

  • The Energy recovery core has limited 5Y warranty.
  • The warranty is limited to 5Y on parts and 7Y on fans from the date of purchase, including parts replaced during this time period. If there is no proof of purchase available, the date associated with the serial number will be used for the beginning of the warranty period.
  • The fans found in all Fantech ERVs require no lubrication, and are factory balanced to prevent vibration and promote silent operation.
  • The limited warranty covers normal use. It does not apply to any defects, malfunctions or failures as a result of improper installation, abuse, mishandling, misapplication, fortuitous occurrence or any other circumstances outside Fantech’s control.
  • Inappropriate installation or maintenance may result in the cancellation of the warranty.
  • Any unauthorized work will result in the cancellation of the warranty.
  • Fantech is not responsible for any incidental or consequential damages incurred in the use of the ventilation system.
  • Fantech is not responsible for providing an authorized service centre near the purchaser or in the general area.
  • Fantech reserves the right to supply refurbished parts as replacements.
  • Transportation, removal and installation fees are the responsibility of the purchaser.
  • The purchaser is responsible to adhering to all codes in effect in his area.
  • This warranty is the exclusive and only warranty in effect relative to the ventilation system and all other warranties either expressed or implied are invalid.

PARTS LIST

Parts List

BOM #| Description| VER 100

(463235)

---|---|---
1| LXFB2E190 Repl. motor kit| 463995
2| Electrostatic Filters Kit| 405577
3| Energy Recovery Cell 8.5″ x 8.5″ x 12″| 427928
4| Capacitors 8uF,250V,REC| 410012
5| Kit, PCB  Replacement, Board, AC| 428252
6| Auto-Transformer| 411963
7| Control Switch| 410213
8| Kit Drain Plug| 40315
9| Collar 5”, Oval, w/Stop| 412826
10| Collar 5”, Oval, wo/Stop| 412827
11| Screw, Set, Slotted, 8-32 x 5/16”| 412836
12| Cap, w/Tab, Plastic, Tapered| 412839
13| Damper, 5”, Oval| 412831
14| Temperature Probe| 40286
15| Door Assembly| 428470
| Kit, Chain| 404261
| Kit, Wall Bracket| 428471
| KIT,FILTER,2XMERV6, 8.4”X12.4”| 414645
| Wiring Diagram| 428464
| Installation Manual| 428465

Customer Support

United States
10048 Industrial Blvd., Lenexa, KS, 66215
Tel.: 800.747.1762
Canada
50 Kanalflakt Way, Bouctouche, NB, E4S 3M5
Tel.: 800.565.3548
Fantech reserves the right to modify, at any time and without notice, any or all of its products’ features, designs,
components and specifications to maintain their technological leadership position.
Please visit our website fantech.net for more detailed technical information

Fantech reserves the right to make technical changes.
For updated documentation please refer to www.fantech.net
Fantech®
 www.fantech.net

Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals