Aeron® Window Control System – Window Actuator Installation Instructions
Q50294 Aeron Window Control System
Items Supplied
A | Actuator |
---|---|
B | Chain release tool |
C | Chain adjustor and module cover |
D | Actuator end caps (x2) |
E | Wire cover |
F | Wire cover screw |
G | Pivot bracket |
H | Pivot bracket screws (x4) |
I | Sash bracket screws (x2) |
J | Chain release cover |
Purchased Separately
- Synchronisation loom (1.8m)
- Rain sensor (cable length 2m)
- Rain sensor adaptor
Tools Required
- Marker
-
2 SQ driver bit
- Power drill
- 3.2mm drill bit
- Small flat screwdriver
- Silicon (If IP rating required)
-
Select Single or Double Actuators Per WindowRecommended dimensions only, for further information on chain restriction opening see QR code on the reverse page.
Double actuators require 1 x synchronisation loom -
Mounting Type
-
Retracting ChainUse chain release tool to extend chain to comfortable working length.
-
Removal of Sash BracketUse a small flat screwdriver to remove sash bracket.
-
Secure Sash BracketIf the sash bracket has not been removed from the chain, secure the sash bracket to the window sash with the screws supplied. Use the clutch tool to extend the chain if required. The chain can rotate at the sash bracket for ease of access to the fixing screws.
-
Position and Fix Pivot BracketAlign pivot bracket with sash bracket.
Note: notches in pivot bracket needs to align with centre of sash bracket. Once aligned, mark fixing screw locations for bracket and pivot. Use fixing screws provided. -
Set Chain Length and Module RemovaUse slide switch to select desired chain extension.
Note: preset chain extensions are printed on the circuit board. *for a double actuator installation the module must be removed from the slave actuator. For further information on chain restriction, refer to the website. -
Access to Chain Length Switch and ModuleClip the module cover in place. Ensure cover is located correctly and sits flush with actuator body.
-
Connect CablesInsert wiring into connector block and firmly push into placeConnect sync loom for a double actuator installation.
-
Cut CoverIf a different cable exit is desired, the wire cover can be cut to suit.
-
Wire CoverInstall wire cover and secure in place with screw provided.
-
IP30 RatingTo achieve IP30 rating, seal wire exit points with silicon.
-
Mount Actuator to Pivot BracketTilt actuator body and insert pivot post into the slotted upstand at one end of the pivot bracket. Once in place, repeat at the other end.
-
Install Actuator End CapsEnsure the tops of the caps are flush with the actuator body.
-
Fit Chain Release CoverPush the chain release cover into place.
WALL SWITCH CIRCUIT DIAGRAM
CALIBRATION AND BASIC FUNCTION
The system must be calibrated before use. Power up the system, after 10
seconds press the open/close switch. The windows will open 10mm and then
close. Wait at least 10 seconds once the window is closed, then operate the
unit to one full open and close cycle to complete the calibration.
Note: If a window stops during calibration, it means that it has ‘safety’
stopped due to too much load. Press the close switch.
Remove the obstruction. Then press the open switch to continue.
Wall Switch Basic Function:
Press the open switch for at least 2 seconds to open the windows.
Press the close switch for at least 2 seconds to close the windows.
Press any switch for at least 2 seconds to stop the windows.
POWER CABLE REQUIREMENTS
Length (m) | Wire Ø Min | AWG |
---|---|---|
12 | 0.7mm | 22 |
19 | 0.8mm | 20 |
29 | 1.0mm | 18 |
47 | 1.3mm | 16 |
74 | 1.6mm | 14 |
119 | 2.0mm | 12 |
LED OPERATIONAL INDICATOR
Fault | LED display |
---|---|
Actuator not calibrated | LED blink RED (0.1s ON 1.9s OFF) |
Obstruction detected | LED shines RED |
Voltage out of range | LED flashes RED @1Hz |
Motor unresponsive | LED flashes RED twice @1Hz, dwell for 1s |
Slide switch not read | LED flashes RED three times @1Hz, dwell for 1s |
Zigbee COMM | LED flashes RED four times @1Hz, dwell for 1s |
TECHNICAL SPECIFICATION
Input Voltage | 2432V DC |
---|---|
Maximum Current | 600mA per Actuator |
Opening Time (full ext) | Approx 30 sec |
Overall Dimensions | 310mm x 45mm x 36mm |
Operating Temperature | 0° – 50 °C |
Humidity | 0% – 95% |
Wall Switch Cable Length | 30m Max |
FREQUENTLY ASKED QUESTIONS
How many windows can I have in a system?
Hard wired/wall switch: 4 Wireless: 30
Can I use two actuators on one window?
Yes, windows wider than 900mm must use double actuators connected by a synchronisation loom.
Can I restrict the window opening?
Yes. See Step 7 “Set Chain Length and Module Removal” on opposite page.
How do I know which power lead goes where?
Refer to wiring diagram. Note: The actuators are not polarity sensitive.
What is the largest sash size for one actuator?
We recommend a maximum sash width of 900mm for a single actuator. For other sash constraints refer to “the selector chart” available on the website.
Can a Rain Sensor control individual windows?
A rain sensor will control all the windows on the hard wired system it is connected to.
Will my windows re-open automatically once the rain has stopped?
No. You will need to press the open button to reopen the windows.
Can I override a Rain Sensor that has closed the windows?
Yes. However the rain sensor will not reactivate until it has dried and reset.
GENERAL NOTES
Wall switch can operate a maximum of 4 actuators per circuit. A maximum of 1
rain sensor and Adaptor can be connected per system.
Smart Home Application:
“Smart Home” applications are NONSTANDARD and require particular features to
operate with this system. Replace wall switch connections with two relays.
Follow basic function steps to activate and control the system. Ensure
activation time is at least two seconds.
- Aeron Window Actuators should always be installed by a qualified professional.
- Only to be used on out of reach windows
ASSA ABLOY Australia Pty Ltd 235 Huntingdale Road
Oakleigh, Victoria, 3166 Australia
1300 LOCK UP (1300 562 587) lockweb.com.au
ASSA ABLOY New Zealand Ltd 6 Armstrong Road,
Albany, Auckland, 0632 New Zealand
www.assaabloy.com/nz
For customer feedback: nzsales@assaabloy.com