FANTECH ATMO200E Fresh Air Appliance Instruction Manual

June 13, 2024
fantech

FANTECH-logo

FANTECH ATMO200E Fresh Air Appliance

Product Information

The product is the ATMOTM Series Fresh Air Appliance. It comes with various parts and accessories, including 1 pc of Hanging Chain Kit, 1 pc of Hardware Kit, 1 pc of Drain Hose Kit, 1 pc of External Damper Wire harness, and 1 pc of Operation and Installation Manual. The product is not ENERGY STAR listed. It should be installed in compliance with provincial requirements or the National Building Code and ASHRAE’s Good Engineering Practices. Fantech reserves the right to modify its products’ features, designs, components, and specifications without notice.

Product Usage Instructions

Installation

Before installing the ventilation system, ensure compliance with the local building code or consult local authorities for jurisdiction requirements.

Table of Contents

  • Determining Your Airflow Requirement
  • Installation Examples
  • Exterior Ducting Installation
  • Interior Ducting Installation
  • FAA Installation
  • Airflow Adjustment & Balancing

Determining Your Airflow Requirement

  • 1 CFM (Cubic Feet per Minute) = 0.47 L/s (Liters per Second)
  • 1 L/s = 2.13 CFM
  • Installation Examples

Three installation examples are provided:

  1. Fully dedicated system
  2. Partially dedicated system
  3. Simplified installation

Exterior Ducting Installation

This section covers the weatherhood location and installing the ducting to the weatherhood.

Interior Ducting Installation

This section provides general tips for installation and covers installing duct to FAA (Fresh Air Appliance) and locating supply & exhaust air grilles.

FAA Installation

This section outlines the steps for installing the Fresh Air Appliance.

Airflow Adjustment & Balancing

This section provides instructions for adjusting and balancing the airflow of the ventilation system.

PARTS IN THE BOX

  • Fresh Air Appliance, 1 pc
  • Hanging Chain Kit, 1 pc
  • Hardware Kit, 1 pc
  • Drain Hose Kit, 1 pc
  • External Damper Wire harness, 1 pc
  • Operation and Installation Manual, 1 pc

Your ventilation system should be installed in conformance with the appropriate provincial requirements or, in the absence of such requirements, with the current edition of the National Building Code, and / or ASHRAE’s “Good Engineering Practices

United States
10048 Industrial Blvd., Lenexa, KS, 66215

  • Tel.: 800.747.1762
  • Fax: 800.487.9915

Canada
50 Kanalflakt Way, Bouctouche, NB, E4S 3M5

  • Tel.: 800.565.3548
  • Fax: 877.747.8116

Fantech reserves the right to modify, at any time and without notice, any or all of its products’ features, designs, components and specifications to maintain their technological leadership position. Please visit our website www.fantech.net for more detailed technical information

FANTECH-ATMO200E-Fresh-Air-Appliance-fig-1

PLEASE READ AND SAVE THESE INSTRUCTIONS
Before installation careful consideration must be given to how this system will operate if connected to any other piece of mechanical equipment, i.e. a forced air furnace or air handler operating at a higher static pressure. After installation, the compatibility of the two pieces of equipment must be confirmed by measuring the airflow of the Fresh Air Applliance using the balancing procedure found in this manual. It is always important to assess how the operation of any FAA may interact with vented combustion equipment (i.e. Gas Furnaces, Oil Furnaces, Wood Stoves, etc.)

Products are designed and manufactured to provide reliable performance, but they are not guaranteed to be 100% free of defects. Even reliable products will experience occasional failures, and this possibility should be recognized by the user. If these products are used in a life support ventilation system where failure could result in loss or injury, the user should provide adequate back-up ventilation, supplementary natural ventilation or failure alarm system, or acknowledge willingness to accept the risk of such loss or injury. Your ventilation system should be installed in accordance with the local building code that is in effect, in absence of such requirements, it is recommenced to check with local authorities having jurisdiction in your area prior to installing this product.

DETERMINING YOUR AIRFLOW REQUIREMENT

Room Count Method

Room classification          Number of rooms                      CFM (L/s) CFM Required

Master bedroom| | x 10 L/s (20 CFM)| =
Basement| yes or no| if yes add 10 L/s (20 CFM) if no = 0| =
Bedrooms| | x 5 L/s (10 CFM)| =
Living room| | x 5 L/s (10 CFM)| =
Others| | x 5 L/s (10 CFM)| =
Kitchen| | x 5 L/s (10 CFM)| =
Bathroom| | x 5 L/s (10 CFM)| =
Laundry room| | x 5 L/s (10 CFM)| =
Utility room| | x 5 L/s (10 CFM)| =

  • 1 CFM = 0.47 L/s
  • 1 L/s = 2.13 CFM

ASHRAE method

Ventilation Air requirements

Floor area| | | Bedrooms|
---|---|---|---|---
| 1| 2| 3| 4| 5
Ft2| m 2| CFM| L/s| CFM| L/s| CFM| L/s| CFM| L/s| CFM| L/s|
| | | | | | | | | | | |
< 500| < 47| 30| 128| 38| 18| 45| 21| 53| 25| 60| 28|
501-1000| 47-93| 45| 21| 53| 24| 60| 28| 68| 31| 75| 35|
1001-1500| 94-139| 60| 28| 68| 31| 75| 35| 83| 38| 90| 42|
1501-2000| 140-186| 75| 35| 83| 38| 90| 42| 98| 45| 105| 49|
2001-2500| 187-232| 90| 42| 98| 45| 105| 49| 113| 52| 120| 56|
2501-3000| 233-279| 105| 49| 113| 52| 120| 56| 128| 59| 135| 63|
3001-3500| 280-325| 120| 56| 128| 59| 135| 63| 143| 66| 150| 70|
3501-4000| 326-372| 135| 63| 143| 66| 150| 70| 158| 73| 165| 77|
4001-4500| 373-418| 150| 70| 158| 73| 165| 77| 173| 80| 180| 84|
4501-5000| 419-465| 165| 77| 173| 80| 180| 84| 188| 87| 195| 91|

ASHRAE 62.2-2016 Table 4.1, Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings

Bathroom: If the FAA is going to provide the required local exhaust ventilation for each bathroom with each a continuous 20 CFM (10 L/s), this ventilation rate can be considered as part of the whole-building ventilation rate.

INSTALLATION EXAMPLES

The way your heat/energy-recovery ventilator is installed can make a significant difference to the electrical energy you use. To minimize the electricity use of the heat/energy-recovery ventilator, a stand-alone fully ducted installation is recommended. If you choose a simplified installation that operates your furnace air handler for room-to-room ventilation, an electrically efficient furnace that has an electronically commutated (EC) variable speed blower motor will minimize your electrical energy consumption and operating cost. Example only – duct configuration may differ depending on the model

Suggested installation for:

  • Hydronic baseboard
  • Infloor heating
  • Electric baseboard
  • Mini split heat pump
    Benefits: Provides the best fresh air distribution in the house; lowest operation costsince the furnace/air handler unit is not needed.

FULLY DEDICATED SYSTEM
BEST FOR NEW CONSTRUCTION

  1. Stale air is drawn from key areas of the homerequiring local exhaust (bathroom, kitchen, laundry room).
  2. Fresh air is distributed directly to habitable rooms in the house (bedrooms, living room)
  3. The FAA’s airflow must be balanced after installation using the procedure found in the section “AIRFLOW

FAA ducting for fully Dedicated System

  • Ductwork layout may differ depending on modelFANTECH-ATMO200E-Fresh-Air-Appliance-fig-2
  • Unit air flow should be balanced while FAA is on “Normal” speed and furnace blower is running.

DIRECT CONNECTION of the FRESH air to living area to the RETURN PLENUM of the AIR HANDLER (Stale air drawn from key areas of home)

PARTIALLY DEDICATED SYSTEM (BETTER)

  1. In order to provide proper distribution of the fresh air, it is recommended that the furnace blower be set to run continuously or interconnected with FAA. See furnace electrical connection on page 16.
  2. Stale air is drawn from key areas of the home (bathroom, kitchen, laundry room).
  3. Fresh air is supplied to the return air plenum of the furnace.
  4. Due to the difference in pressure between the FAA and the equipment it is being connected to the FAA’s airflow must be balanced on site, using the procedure found in the section “AIRFLOW BALANCING”
    • In the case of a multi-zone system, please contact Fantech customer service prior to installing any installation type requiring the use of the furnace interlock”

Suggested installation for:

  • Central furnace (air handling unit or central air conditioners)
  • When ducting fresh air to living area is not possible or practical, i.e. expensive or when the central AHU will operate year-round.
    Benefits: Conditions the fresh air prior to distributing it throughout the house

Make sure the FAA iscapable of meeting the required airflow rate.

FAA/Furnace ducting for Partially Dedicated System

  • Ductwork layout may differ depending on modelFANTECH-ATMO200E-Fresh-Air-Appliance-fig-3

Fantech fresh air appliances (FAA) that use a supply fan shutdown for frost prevention do not include an outdoor air motorized damper. If you are using a simplified installation, i.e. connecting the FAA supply air duct to a furnace’s return air duct, the FAA must operate continuously. When the FAA is turned off, no warm exhaust air will flow through the FAA but the furnace’s fan will continue to draw in outdoor air directly into the furnace. If it’scold outside, cold air will be introduced, without re-heating, directly into the furnace. If the FAA is installed such that the homeowner may turn off the FAA during the winter, we recommend installing a motorized damper between the FAA’s supply air and the furnace’s return air duct that closes when the FAA is not operating. To install a damper accessory to the product, locate the auxiliary connector on the side of the electrical box. See Figure 1. Using the included wire harness, connect the damper accessory to the product.

DIRECT CONNECTION of both the FAA SUPPLY AIR STREAM and EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN

Suggested installation for:

  • When bathroom and kitchen already have local exhaust system
  • May be suitable for retrofitting
    Benefits: Least expensive installation type

SIMPLIFIED INSTALLATION (GOOD)
(RETURN/RETURN METHOD)

  1. Furnace blower must operate when ventilation from FAA is required. The furnace should be set to run continuously or interlocked with FAA. See furnace electrical connection on page 16.
  2. A minimum separation of 1m (39’’) is recommended between the two direct connections.
  3. In order to prevent exhausting any fresh air, the FAA’s exhaust air connection should be upstream of the FAA’s supply air connection when ducting to the furnace’s cold air return.
  4. Due to the difference in pressure between the FAA and the equipment it is being connected to the FAA’s airflow must be balanced on site, using the procedure found in the section “AIRFLOW BALANCING”
    • In the case of a multi-zone system, please contact Fantech customerservice prior to installing any installation type requiring the use of the furnace interlock”

FAA/Furnace ducting for Simplified Installation – Option 1FANTECH-ATMO200E-
Fresh-Air-Appliance-fig-5

Fantech fresh air appliances (FAA) that use a supply fan shutdown for frost prevention do not include an outdoor air motorized damper. If you are using a simplified installation, i.e. connecting the FAA supply air duct to a furnace’s return air duct, the FAA must operate continuously. When the FAA is turned off, no warm exhaust air will flow through the FAA but the furnace’s fan will continue to draw in outdoor air directly into the furnace. If it’s cold outside, cold air will be introduced, without re-heating, directly into the furnace. If the FAA is installed such that the homeowner may turn off the FAA during the winter, we recommend installing a motorized damper between the FAA’s supply air and the furnace’s return air duct that closes when the FAA is not operating. To install a damper accessory to the product, locate the auxiliary connector on the side of the electrical box. See Figure 1.Using the included wire harness, connect the damper accessory to the product.

EXTERIOR DUCTING INSTALLATION

WEATHERHOOD LOCATION

  • Decide where your intake and exhaust hoods will be located. Locating the Intake Weatherhood
  • Should be located upstream (if there are prevailing winds) from the exhaust outlet.
  • At a minimum distance to 900 mm (3′) away from dryer vents and furnace exhaust (medium or high efficiency furnaces), driveways, oil fill pipes, gas meters, or garbage containers.
  • At a minimum height of 460mm (18’’) above the ground, or above the level of expected snow accumulation.
  • Ideally, keep weatherhoods 1m (3′) from corners.
  • Do not locate in the garage, attic, crawl space, or underneath deck.

Locating the Exhaust Weatherhood

  • At least 460mm (18″) above ground or above the depth of expected snow accumulation
  • Ideally, keep weatherhoods 1m (3′) from corners.
  • Not near a gas meter, electric meter or a walkway where fog or ice could create a hazard
  • Do not locate in a garage, workshop or other unheated space

INSTALLING THE DUCTING TO THE WEATHERHOODS
A well designed and installed ducting system will allow the FAA to operate at its maximum efficiency. The inner liner of the flexible insulated duct must be secured to the  sleeve of the weatherhood (as close to the outside as possible) and to the appropriate ductconnection on the FAA. The insulation should remain full and not crushed. The outer liner, which acts as a vapor barrier, must be completely sealed to the outer wall and the FAA using tape and/or caulking. A good bead of high quality caulking (preferably acoustical sealant) will seal the inner flexible duct to both the FAA duct connection and the weatherhood prior to securing them. To minimize airflow restriction, the flexible insulated duct that connects the two outside weatherhoods to the FAA should be stretched tightly and be as short as possible. Twisting or folding the duct will severely restrict airflow. See “Installation Diagram Examples” for installation examples

STEPS FOR HOOD INSTALLATION:

  1. Using the duct connection of the outside hood, outline the intake & exhaust holes to be cut. The holes should be slightly larger than the duct connection to allow for the thickness of the insulated flexible duct. Cut a hole for both the intake and exhaust hoods.
  2. Pull the insulated flexible duct through the opening until it is well extended and straight. Slide the duct’s inner vinyl sleeve over the hood duct connection and secure. Pull the insulation over the duct and pull the vapor barrier over the sleeve. Secure with appropriate tape or sealant.
  3. Push the hood into the opening and then attach the hood to the outside wall with mounting screws. Repeat the installation procedure for both the supply and exhaust hoods.
  4. Using a caulking gun, seal around both hoods to prevent any leaks.

INTERIOR DUCTING INSTALLATION

  • To maximize airflow through the ductwork system, all ducts should be kept short and have as few bends or elbows as possible.
  • 45º elbows are preferable to 90º.
  • Use “Y“ ducts instead of “T” ducts whenever possible.
  • All duct joints must be fastened with screws or duct sealant and wrapped with aluminum foil duct tape to prevent leakage.
  • Galvanized ducting from the FAA to the living areas in the house is recommended whenever possible, although flexible ducting can be used in moderation when necessary.
  • To avoid possible noise transfer through the ductwork system, a short length (approximately 300 mm, 12’’) of nonmetallic flexible insulated duct should be connected between the FAA and the supply/exhaust ductwork system.
  • The main supply and return line to/from the FAA must have the same diameter as the duct connection or larger.
  • Branch lines to the individual rooms may be as small as 100 mm (4’’).

Installing ducting to FAA
Warning: Always fix and secure the 6″ collars with the screws supplied. Avoiding this critical step the unit will accumulate condensation.
Tip to Installer: To ensure a better installation and to avoid an undesired bend in the duct, align the duct with the collar before securing over the four hooks.The fresh air from outside and the Exhaust air to outside from the termination ducts to the FAA must be fully insulated of thermal insulation ducts to minimize heat loss and gain. All tapes, mastics, and nonmetallic clamps used for field installation of flexible ducts shall be listed and labeled to Standard UL 181B – Closure Systems for Use With Flexible Air Ducts and Air Connectors.
Air Connector A category of flexible duct not meeting the requirements of an Air Duct per UL 181 Standard (not tested for flame penetration, puncture and impact) and having limitations on use, length and location as defined by NFPA 90A and 90B. Air Connectors are identified by a “round shape” listing label of the listing agency.
Air Duct A category of flexible duct tested and classified as to the Surface Burning Characteristics in accordance with the UL 181 Standard. Air Ducts are identified by a “rectangular shape” listing label of the listing agency. To ensure quiet operation of ENERGY STAR qualified FAA, each product should be installed using sound attenuation techniques appropriate for the installation. Once insulated flex is attached to the collar, slide collar in keeper section, fixed collar to the unit with four screws supplied in installation kit to insure a proper seal.

  • Insert vinyl duct over the hooks and seal with a Tie wrap
  • Insert insulation inside the double collar.
  • Finish by taping the vapor barrier to the collar to insure proper seal
  • Slide collar on the unit
  • Fix and secure with four screws supplied and seal all joints.

Warning: To reduce air leakage in the final installation always seal the joint between all collars and keepers with aluminum tape or mastic.
Supply air grilles location
In homes without a forced air furnace, fresh air should be supplied to all habitable rooms, including bedrooms and living areas. It should be supplied from high wall or ceiling locations. Grilles that diffuse the air comfortably are recommended. In homes with a forced air furnace, you may want to connect the FAA to the furnace ductwork (see information below).
Exhaust air grilles location
The stale air exhaust system is used to draw air from the points in the house where the worst air quality problems occur. It is recommended that return air ducts be installed in the bathroom, kitchen, and laundry room. Additional return air ducts from strategic locations may be installed. The furnace return duct may also be used to exhaust from. In this method, the exhaust air is not ducted back from bathrooms, kitchens, etc to the HRV with “dedicated lines”.

As per building codes and installation requirements for combustion appliances: Air return ducts, or openings for air return, should not be placed in enclosed spaces containing combustion appliances that are subject to spillage.

FAA INSTALLATION

LOCATION
The FAA must be located in a conditioned space where it will be possible to conveniently service the unit. Typically the FAA would be located in the mechanical room or an area close to the outside wall where the weatherhoods will be mounted. If a basement area is not convenient or does not exist, a utility room may be used.
Attic installation must meet the following conditions:

  • Attic temperature must be above freezing conditions at all times and for best performance should be 12°C (54 °F).
  • The condensate drain (if included) must be installed so that the condensate drains and is protected from freezing.
  • The attic is easily accessible for equipment maintenance and inspection. Connecting appliances to the FAA is not recommended. These include:
  • Clothes dryer
  • Range top
  • Stovetop fan
  • Central vacuum system
  • Bathroom exhaust fans unless they are specifically designed for this purpose

These appliances may cause lint, dust or grease to collect in the FAA, damaging the unit

  • Have a nearby power supply (120 volts, 60Hz)
  • Choose a location which allows the possibility of mounting the unit to supporting beams.
  • The unit should be level in order to allow proper condensate drainage
  • To minimize noise, do not install unit in living area
  • Ensure proper drainage

Connecting any of these types of appliances to the FAA will void your warranty.

Mounting- Chain mount

  1. Place fastening hooks on the strapping board or the floor joists.
  2. Take flat screwdriver and slightly pull on punched out tab. Put chain link under hook.
  3. Hang the unit by slipping a link onto the hanginghooks, making sure the unit is level
  4. Install a spring on each chain. Hook the spring in the links so a loop is created in the chain. The spring will then support the unit’s weight and absorb vibrations

INSTALLING DRAIN LINE

Insert the threaded drain adapter thru the bottom of the FAA and hand tighten the plastic nut, and with a wrench tighten the nut another half turn to assure a better seal. Install the condensate line (included in drain kit). Insert condensate tubing by pushing clear plastic line over drain adapter. Make condensate trap by looping the clear plastic tubing. This procedure is to avoid foul odor to enter the FAA

The drain nipple is placed upside down in the unit to prevent it being damaged during shipping or the installation of the unit.

  • Make a loop in condensate line, not be subject to freezing temperatures.
  • Use a condensate pump if you don’t have access to a drain.FANTECH-ATMO200E-Fresh-Air-Appliance-fig-21

CAUTION
A Drain and Tubing (included) must be installed for all HRV units. For ERV units, drain is not required, however, it is recommended for climates where outdoor temperatures typically remain below -25°C (-13°F) combined with an indoor relative humidity higher than 40% for a period of 24 hours or serveral days in a row.

The Switch on the electrical box is used to toggle between STANDBY, REDUCED speed and NORMAL speed modes. Place the unit in NORMAL speed to perform the balancing

Airflow balancing
Balancing must be completed using the Fantech ECO-Touch® Programmable Touch Screen Wall Control
ENTERING BALANCING MODE
In the options menu during the initial 5 second countdown sequence, long press on “ECO” area for 5 seconds to enter basic balancing mode. The supply and exhaust fans are adjusted on high speed only and the offsets are proportionally applied to the medium and low speed automatically.

STAGE 1
(ADJUST LEVEL OF EXHAUST FAN IN HIGH SPEED):

  • In this step, balance exhaust fan and measure airflow on the exhaust air side

  • Pressing on “up” or “down” will adjust the fan speed in increments of 1%.

  • Once the desired exhaust airflow is reached, press on “next” and move on to the next stage

  • STAGE 2
    (BALANCE SUPPLY FAN ONLY IN HIGH SPEED):

  • In this step, balance supply fan and measure airflow on the supply air side

  • Pressing on “up” or “down” will adjust the fan speed in increments of 1%.

  • Once happy with the outcome, press on “next” to complete balancing

  • The supply and exhaust offset values will be proportionally applied to low and medium speed as well

WALL CONTROLS

  • Please see instruction manuals for individual controls for proper wiring and set up of control systems.
  • Installation of a user-accessible control with your product model will improve comfort and may significantly reduce the product model’s energy use
  1. Ensure that unit is not plugged when connecting the control
  2. Recirculation mode is only available with the Flex100H ES, HERO series and the models with the “R” suffix at the end of the model number.

The wiring connectors can be removed for easier connection

CENTRAL CONTROLS

These cannot be used with another central control
*Maintain polarity between control and FAA (+ → + ; – → -)

**ECO SERIES*** FEATURES CONNECT TO

ECO-Touch®

| •  Our most complete, yet easy-to-use control system

•  Sleek design with backlight touchscreen LCD

•  ECO mode selects the best operating mode and speed for the season, minimizing energy use associated with ventilation

•  Set preferred indoor relative humidity range and ventilation mode for day and night conditions

•  No battery to replace, all programmed settings are retained during power outages

•  Maintenance reminder indicator

•  Error code messages reduce troubleshooting time

|

ECO-TouchIAQ

| •  Integrated VOC Sensor

•  Our most complete, yet easy-to-use control system

•  Sleek design with backlight touchscreen LCD

•  ECO mode selects the best operating mode and speed for the season, minimizing energy use associated with ventilation

•  Set preferred indoor relative humidity range and ventilation mode for day and night conditions

•  No battery to replace, all programmed settings are retained during power outages

•  Maintenance reminder indicator

•  Error code messages reduce troubleshooting time

ECO-Feel

| •  ECO mode selects the best operating mode and speed for the season, minimizing energy use associated with ventilation

•  Integrated VOC Sensor

•  No battery to replace, all programmed settings are retained during power outages

EDF SERIES FEATURES CONNECTS TO

EDF7

| •  MODE button provides 3 modes of operations: Ventilation , Recirculation and Standby

•  User selected fan speed: Reduced, Medium, Normal and 20 minutes per hour

•  AUTO setting allows the homeowner to deactivate the dehumidistat

•  When the humidity exceeds the desired setpoint, the ventilation system operates at normal speed

•  Once the desired humidity level is achieved, your ventilation system resumes to its previous mode of operation.

|

EDF1

| •  Press button once for continuous Reduced speed

•  Press button twice and the unit will cycle 20 minutes ON/ 40 minutes OFF and repeat

•   EDF1 – Press button a third time and the system will run continuously on HIGH speed

AUXILIARY CONTROL –These controls can be paired with central controls or combined together.

*Maintain polarity between control and FAA (+ → + ; – → -)

RTS SERIES FEATURES CONNECTS TO
•  Wireless timer

•  Can only be paired with the ECO-Touch IAQ

•  20/40/60 minute timer with LED light

•  Boosts system to high speed with the touch of a button

•  Up to 5 can be used in one system

•  Use in bathroom, kitchen, laundry room

| Connects wireleslly to the

**RTS2***

| •  20- minute timer with LED light

•  Boosts system to high speed with the touch of a button

•  Up to 5 can be used in one system

•  Use in bathroom, kitchen, laundry room

|

**RTS5***

| •  20/40/60 minute timer with LED light

•  Boosts system to high speed with the touch of a button

•  Up to 5 can be used in one system

•  Use in bathroom, kitchen, laundry room

MDEH SERIES FEATURES CONNECT TO

MDEH1

| •  Rotary dial Dehumidistat

•  Multiple units can be used

•  We recommend setting the relative humidity above 80% during the summer

|

WIRING DIAGRAM

ATMO PRODUCT LINEFANTECH-ATMO200E-Fresh-Air-Appliance-
fig-42

WIRING DIAGRAM TO FURNACE

FOR A FURNACE CONNECTION TO A COOLING SYSTEM:
On some newer furnaces and older  thermostats, energizing the R andG terminal at the furnace has the effect of energizing the Y at the thermostat and thereby turning on the cooling system. If you identify this type of thermostat, you must use the“Alternate Furnace Interlock WiringFANTECH-
ATMO200E-Fresh-Air-Appliance-fig-43

As per building codes and installation requirements for combustion appliances: Air return ducts, or openings for air return, should not be placed in enclosed spaces containing combustion appliances that are subject to spillage.

TROUBLESHOOTING

Problem Causes Solutions
Air is too dry Dehumidistat control is set too low Increase the desired

level of humidity. Change ventilation mode from continuous mode to standby.
FAA out of balance| Have contractor balance FAA airflows
Air is too humid| Dehumidistat control is set too high| Reduce the desired level of humidity. Combine this with the use of continuous

exchange mode.

Sudden change in temperature| Wait until outside temperature stabilizes (winter). Heating will also improve

situation.

Storing too much wood for heating| Store a majority of your wood outside. Even dried, a cord of wood contains

more than 20 gallons of water.

Dryer vent exhaust is inside home| Make sure the dryer vent is exhausting outside.
Poor air circulation near windows| Open curtains or blinds.
FAA out of balance| Have contractor balance FAA airflows
Well sealed basement door is closed| Open the door or install a grill on the door.
Failed damper system may be stuck in recirculation

mode

| Check defrost damper. If damper is always blocking incoming fresh air, have

contractor verify damper system.

Persistent condensation

on window

| Improper adjustment of dehumidistat control| Reduce the desired level of humidity. Combine this step with use of continuous

exchange mode.

FAA out of balance| Have contractor balance FAA
Poor air circulation near windows| Open curtains or blinds.
Poor Air Flows| 1/4″ (6mm) mesh on the outside hoods is plugged| Clean exterior hoods or vents
Filters plugged| Remove and clean filter
Core obstructed| Remove and clean core
Indoor grilles closed or blocked| Check and open grilles
Inadequate power supply at site| Have electrician check supply voltage
Ductwork is restricting airflow| Check duct installation
Improper speed control setting| Increase the speed of the FAA (i.e. change unit control from REDUCED to NORMAL

speed)

FAA airflow improperly balanced| Have contractor balance FAA airflows
Ducting has fallen down or been disconnected from FAA| Have contractor reconnect ducting
Supply air feels cold| Poor location of supply grilles, the airflow may irritate

the occupant

| Locate the grilles high on the walls or under the baseboards, install ceiling

mounted diffuser or grilles so as not to directly spill the supply air on the occupant (eg. Over a sofa)

Turn down the FAA supply speed. A small duct heater (1kw) could be used to temper the supply air

Placement of furniture or closed doors is restricting the movement of air in the home

Outdoor temperature extremely cold| If supply air is ducted into furnace return, the furnace fan may need to run

continuously to distribute ventilation air comfortably

FAA and/or Ducts frosting up| FAA air flows are improperly balanced| Have HVAC contractor balance the FAA airflows
Malfunction of the FAA defrost system| Note: minimal frost build-up is expected on the core before unit initiates

defrost cycle functions

Condensation or Ice Build Up in

Insulated Duct to the Outside

| Incomplete vapor barrier around insulated duct| Tape and seal all joints
A hole or tear in outer duct covering| Tape any holes or tears made in the outer duct covering

Ensure that the vapor barrier is completely sealed.

LED is flashing

LED is not flashing

| Everything is in good operations|
No Power is being transmitted to the Control Board| Make sure unit is plugged. Transformer may need replacing.

FAA MAINTENANCE CHART

Check and Clean Filters| Every 3 months or if dirty| | | | | |
---|---|---|---|---|---|---|---
Check Heat Recovery Core| Every 6 months| | | | | |
Check Drain Pan and Lines| Every 3 months| | | | | |
Vacuum the Inside of the Unit| Annually| | | | | |
Clean and Un-block Outside

Hoods

| Annually| | | | | |
Clean and Inspect Duct Work| Annually| | | | | |
General Servicing by a Qualified Contractor| Annually| | | | | |
| | | | | | |
| | | | | | |

  • Schedule may be altered to meet your own needs. More frequent servicing may be required depending on the severity of your home’s indoor and outdoor environments.
Contractor Telephone Number Date Serviced

Make a scan of the QR code above to access Fantech’s warranty in English, French, or Spanish. Includes a 7y Motor, 5y on Electrical components and Core limited warranty

If additional support is needed to retrieve the warranty, visit fantech.net; call (800) 747–1762 (US), (800) 565–3548 (Canada), or +52 55 1328–7328 (Latin America); email support@fantech.net; or mail us at 10048 Industrial Blvd, Lenexa, KS 66215 United States or at 50 Kanalläkt Way, Bouctouche, NB E4S 3M5 Canada.

BOM #| Description| ATMO 150H (463888)| ATMO 200H (463889)| ATMO 150E (463890)| ATMO 200E (463891)
---|---|---|---|---|---
1| Motor| 428515| 428515| 428515| 428515
2| MERV3, Electrostatic Filter Kit| 463939| 463940| 463939| 463940
3| Heat or Energy Exchanger Cell| 463098| 463097| 463937| 463938
4| Capacitor 6uF| 411222| 411222| 411222| 411222
5| PC Board| 428252| 428252| 428252| 428252
6| Speed Switch| 410213| 410213| 410213| 410213
7| Transformer| 411963| 411963| 411963| 411963
8| Drain Fitting Kit| 463088| 463088| 463088| 463088
9| 6” Dia. Plastic Collar| 463102| 463102| 463102| 463102
10| 6” Dia. Plastic Keeper| 463103| 463103| 463103| 463103
11| Door Kit, ATMO Series| 463941| 463948| 463948| 463948
| Fuse, 8A, 250 VAC 3AB 3AG| 414736| 414736| 414736| 414736
| Temp Probe| 461102| 461102| 461102| 461102
| Kit, Chain| 404261| 404261| 404261| 404261
| Kit, Wall Bracket| 463942| 463942| 463942| 463942
| Wiring Diagram| 463927| 463927| 463927| 463927
| Installation Manual| 463913| 463913| 463913| 463913
| Filter MERV 8 (Pack of 2)| 463943| 463945| 463943| 463945
| Filter MERV 13 (Pack of 2)| 463944| 463946| 463944| 463946
| Kit, AUX. 24V Damper| 463947| 463947| 463947| 463947

FANTECH-ATMO200E-Fresh-Air-Appliance-fig-46

Fantech reserves the right to make technical changes. For updated documentation please refer to www.fantech.net

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>