Zeta SCM-4-20 4-20mA Gas Detector Module Instruction Manual
- June 12, 2024
- ZETA
Table of Contents
- General
- Installation
- TRM RJ45 Port Address Designation
- Securing the modules
- Before Powering the Panel On
- Power on Procedure
- Field Wiring
- Wiring recommendations
- Configuring Detectors
- Preset
- Custom
- Front Unit LED Indications
- Configuring Cause and Effect
- Pre-alarm
- Alarm
- Specifications
- Appendix A: Compatible detectors
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Zeta SCM-4-20 4-20mA Gas Detector Module Instruction Manual
General
The SCM-ZMM is a six zone monitor module that is designed to be DIN mounted inside of a Smart Connect Multiloop control panel. It’s powered and interfaced to the Smart Multi-loop via a RJ45 connection. The module has six zone monitor circuits which can be typically used for conventional devices and/or for special detectors that are not available in addressable form such as UV detectors, aspiration and beam detectors etc. The module monitors and transmits the status (normal, open, short, or alarm) of a zone with the detectors to a control panel. Each zone input can be programmed to either give an alarm or technical alarm signal when active
Installation
ATTENTION: THE PANEL MUST BE POWERED DOWN AND DISCONNECTED FROM THE BATTERIES BEFORE INSTALLING OR REMOVING ANY MODULES.
-
Ensure that the installation area is free from any cables or wires that may get caught, and that there is enough space on the DIN rail to mount the module. Also ensure that the DIN clip underneath the module is in the open position.
-
Place the module onto the DIN rail, hooking the metal earth clip underneath onto the rail first.
-
Once the earth clip is hooked, push the bottom of the module onto the rail so that the module sits flat.
-
Push the plastic DIN clip (located at the bottom of the module) upwards to lock and secure the module into position
-
Once the module is secured to the DIN rail, simply connect the supplied CAT5E cable to the module’s RJ45 port.
-
Connect the other end of CAT5E cable to the nearest unoccupied RJ45 port on the termination PCB.
TRM RJ45 Port Address Designation
Each RJ45 port on the Smart Connect Multi-loop termination has its own unique port address. This port address is important to keep note of as it is displayed on Alarm/Fault messages and is used when configuring or setting up cause and effects on the panel (See SCM operation manual GLT-261-7-10).
Securing the modules
The modules are designed to clip together to make them more secure. In addition, the SCM panel is supplied with Din rail stoppers. These should be fitted before the first module, and after the last module on each rail.
Before Powering the Panel On
- To prevent the risk of a spark, do not connect the batteries. Only connect the batteries after powering on the system from its main AC supply.
- Check that all external field wiring is clear from any open, shorts and ground faults.
- Check that all the modules have been installed properly, with correct connections and placement
- Check that all switches and jumper links are at their correct settings.
- Check that all interconnection cables are plugged in properly, and that they are secure.
- Check that the AC power wiring is correct.
- Ensure that the panel chassis has been correctly earth grounded.
Before powering on from the main AC supply, make sure that the front panel door is closed
Power on Procedure
- After the above has been completed, turn the panel on (Via AC Only). The panel will follow the same power up sequence described in initial power up section above
- The panel will now display one of the following messages
Message | Meaning |
---|---|
Panel has not detected any modules fitted during its power up check. |
Power down the panel and check that the expected modules are fitted, and that all module cables are correctly inserted.
Note that the panel will need at least one module fitted to run.
| The panel has detected a new module added to a port that was previously empty.
This is the usual message seen the first time a panel is configured
| The panel has detected a
different type of module fitted to a port that was previously occupied.
| The panel has detected a module
fitted to a port that is the same type, but it`s serial number has changed.
This could happen if a loop module was swapped with another one, for example.
| The panel has detected no
module fitted to a port that was previously occupied.
| The panel has detected no
module changes, so has powered up and started running
- Check that the module configuration is as expected using the and to navigate the through the port numbers. Press the ✓ icon to confirm the changes.
- The new module is now configured into the panel and is ready for use.
- Since the batteries are not connected, the panel will report them as removed, lighting the yellow “Fault” LED, intermittently sounding the Fault buzzer, and displaying battery removed message on the screen.
- Connect the batteries, ensuring that the polarity is correct (Red wire = +ve) & (Black wire = -ve). Acknowledge the Fault event via the display screen, and reset the panel to clear the battery fault.
- The panel should now remain in the normal condition, and you can configure the panel as normal.
Field Wiring
NOTE: The terminal blocks are removable to make wiring easier.
ATTENTION: DO NOT EXCEED POWER SUPPLY RATINGS, OR MAXIMUM CURRENT RATINGS.
Class B Wiring
NOTE: Any unused circuits should have a 5k6, 1 Watt dummy load fitted between + and S terminals, to prevent a fault being reported.
NOTE: Only one 4-20mA detector per circuit
Wiring recommendations
It is reccomended that the distance between panel and detector does not exceed 500m.
Configuring Detectors
The SCM-4-20 Module is optimised for connecting Zeta`s range of 4-20mA detectors. These have a stepped output and the module has preset options for each detector. It also has a custom setting that is fully adjustable so can be configured for any detector.
Preset
The Smart Connect Multiloop has preset settings for the range of gas detectors
supplied by Zeta Alarms Limited.
These detectors have a stepped output, giving currents of 4, 12 or 20mA for
normal, pre-alarm, and alarm conditions. (See appendix A for the list of
available detectors)
Custom
In addition to the preset detectors, the smart Connect multiloop has the
option of custom settings, where the user can enter:-
Detector description,
Measurement units (%vol, ppm, %LEL)
Full scale Range (EG 0-30ppm)
Output current range (to allow for detectors that output more than 20mA)
Pre alarm current
Alarm current
Front Unit LED Indications
LED Indication| Description| LED Indication| LED
Indication
---|---|---|---
ALARM| | Pre-Alarm|
Fault| Flashing when a short circuit condition has been detected.| |
Pulses to show communication between the module and the motherboard.
Configuring Cause and Effect
The SCM-4-20 reports events on screen as a Technical alarm / Gas Alarm, or Technical Alarm / Gas Pre Alarm. To operate an output on one of these events, it is programmed as follows:
Pre-alarm
To Operate an output on a gas pre-alarm, use the Tech alarm ON cause. This can be made on a panel, zone, or local I/O level.
If the system is being run as a mixed system (EG, combined fire and gas detection), the local I/O Level (Individual gas Detectors), or zone level (With only related gas detectors in a zone) should be used. This avoids confusion between a fire alarm, and a gas detection alarm.
Alarm
To Operate an output on a gas alarm, use the Alarm cause. This can be made on a panel, zone, or local I/O level.
If the system is being run as a mixed system (EG, combined fire and gas detection), the local I/O Level (Individual gas Detectors), or zone level (With only related gas detectors in a zone) should be used. This avoids confusion between a fire alarm, and a gas detection alarm.
Specifications
Specification | SCM-4-20 |
---|---|
Design Standard | EN54 Part 2 |
Approval | LPCB (pending) |
Circuit Voltage | 24V DC |
Circuit Type | Power limited & Supervised |
Wiring Class | Class B |
Maximum Line Impedance | 50Ω |
Maximum Current | 250mA per circuit |
Wiring Class | 2 x Class B circuits |
Recommended cable sizes | 22 AWG to 14 AWG (0.3mm2 to 2.5mm2) |
Dummy Load (If circuit not used) | 5K6Ω, 1W |
Maximum Detectors Per Circuit | 1 |
Operating Temperature | -5°C (23°F) to 40°C (104°F) |
Max Humidity | 93% Non-Condensing |
Size (mm) (HxWxD) | 103mm x 97mm x 46mm |
Weight | 0.2KG |
Appendix A: Compatible detectors
Analogue gas detectors GS-220.BC.V.ZETA for combustible gases
Model – ordering code | Detected gas | Gas concentration |
---|---|---|
GS-220.BC.V.ZETA.MET.100 | METHANE | 0 – 100% LEL |
GS-220.BC.V.ZETA.PRO.100 | PROPANE | 0 – 100% LEL |
GS-220.BC.V.ZETA.BUT.100 | N-BUTANE | 0 – 100% LEL |
GS-220.BC.V.ZETA.PEN.100 | N-PENTANE | 0 – 100% LEL |
GS-220.BC.V.ZETA.HEX.100 | N-HEXTANE | 0 – 100% LEL |
GS-220.BC.V.ZETA.HEP.100 | N-HEPTANE | 0 – 100% LEL |
GS-220.BC.V.ZETA.OCT.100 | N-OCTANE | 0 – 100% LEL |
GS-220.BC.V.ZETA.MNL.100 | METHANOL | 0 – 100% LEL |
GS-220.BC.V.ZETA.ETL.100 | ETHANOL | 0 – 100% LEL |
GS-220.BC.V.ZETA.PRO.100 | ISO-PROPANOL | 0 – 100% LEL |
GS-220.BC.V.ZETA.ACE.100 | ACETONE | 0 – 100% LEL |
GS-220.BC.V.ZETA.MEK.100 | METHYL ETHYL KETONE | 0 – 100% LEL |
GS-220.BC.V.ZETA.TOL.100 | TOLUENE | 0 – 100% LEL |
GS-220.BC.V.ZETA.EAC.100 | ETHYL ACETATE | 0 – 100% LEL |
GS-220.BC.V.ZETA.HYD.100 | HYDROGEN | 0 – 100% LEL |
GS-220.BC.V.ZETA.AMM.100 | AMMONIA | 0 – 100% LEL |
GS-220.BC.V.ZETA.UPT.100 | UNLEADED PETROL | 0 – 100% LEL |
GS-220.BC.V.ZETA.ETH.100 | ETHYLENE | 0 – 100% LEL |
Analogue gas detectors GS-220.BC.V.ZETA for toxic gases
Model – ordering code | Detected gas | Gas concentration |
---|---|---|
GS-220.BC.V.ZETA.CO.500 | CARBON MONOXIDE | 0 – 500ppm |
GS-220.BC.V.ZETA.NO2.30 | NITROGEN DIOXIDE | 0 – 30ppm |
GS-220.BC.V.ZETA.H2S.100 | HYDROGEN SULPHIDE | 0 – 100ppm |
GS-220.BC.V.ZETA.AMM.100P | AMMONIA | 0 – 100ppm |
GS-220.BC.V.ZETA.CL2.10 | CHLORINE | 0 – 10ppm |
GS-220.BC.V.ZETA.O2.25 | OXYGEN | 0 – 25%VOL |
Analogue gas detectors GS-220.BC.V.ZETA for refrigerant gases
Model – ordering code | Detected gas | Gas concentration |
---|---|---|
GS-220.BC.V.ZETA.AMM.2000 | AMMONIA | 0 – 2000ppm |
GS-220.BC.V.ZETA.134A.2000 | R-134a | 0 – 2000ppm |
GS-220.BC.V.ZETA.404A.2000 | R-404a | 0 – 2000ppm |
GS-220.BC.V.ZETA.407C.2000 | R-407c | 0 – 2000ppm |
GS-220.BC.V.ZETA.410A.2000 | R-410a | 0 – 2000ppm |
GS-220.BC.V.ZETA.290.2000 | R-290 | 0 – 2000ppm |