ICP DAS tSG-3781B, tSG-3781L Signal Conditioner User Manual
- June 12, 2024
- ICP DAS
Table of Contents
ICP DAS tSG-3781B, tSG-3781L Signal Conditioner
Introduction
The tSG-3781B/tSG-3781L is a device with setting buttons located on the left side of the LCD screen (tSG-3781L).
Appearance
Version: Ver1.002023 Mar. 1
Applications
- Heating system in buildings
- Ventilation system
- Controlling servo-assisted diaphragm valve
Version: Ver1.002023 Mar. 2
PIN Assignment
- Wire Connection:
- Iin Input PWM Output
- Version: Ver1.002023 Mar. 3
Block Diagram
PWM Duty Cycle and Frequency setting:
The following figures show the button switch positions used to configure the channel PWM duty cycle and frequency range. The PWM frequency configuration button switches are located on the left side of the module for front view.
PWR Mode Up Down Set
The power LED of the module Press MODE to modify the channel frequency, the
channel frequency flashes. Press UP to increase the frequency, long press to
increase quickly. Press DOWN to decrease the frequency, long press to decrease
quickly. Press SET to save
the modified value. Press MODE during the modification to stop the
modification.
Version: Ver1.002023 Mar. 4
Dimensions
No specific information provided.
Technical Service
Please E-mail your problem description to service@icpdas.com when you have any questions.
More detail information: www.icpdas.com
Version: Ver1.002023 Mar. 5
Introduction
The tSG-3781B/L is a 1-channel DC current input signal conditioning module
which can convert 4 ~ 20 mA current input to PWM output. This provides an
economical solution when the 4 to 20mA current need to be converted to PWM
output. The duty cycle, 0% to 100%, of the PWM output is a linear
transformation of the 4 to 20mA current input. The frequency of the PWM signal
can be in the range 600Hz to 800Hz and it can be adjusted by buttons.
The tSG-3781B/L includes a monochrome graphic LCD display which shows the duty
cycle and frequency of the 1-channel PWM output signal. 4 kV ESD and 4 kV EFT
protection are also provided to enhance noise protection capabilities in
industrial environments.
Note1: The setting buttons are at the bottom of the LCD. (tSG-3781B)
The setting buttons are on the left side of the LCD. (tSG-3781L)
Appearance
Applications
- Heating system in buildings
- Ventilation system
- Controlling servo-assisted diaphragm valve
PIN Assignment
Wire Connection
Block Diagram
PWM Duty Cycle and Frequency setting
The following figures show the button switch positions used to configure the channel PWM duty cycle and frequency range. The PWM frequency configuration button switches are located left side the module for front view.
PWR | The power LED of the module |
---|---|
Mode | **Press MODE to modify the channel frequency, the channel |
frequency flashes.
Up| Press UP to increase the frequency, long press to increase
quickly.
Down| Press DOWN to decrease the frequency, long press to decrease
quickly.**
Set
| Press SET to save the modifi ed value.
Press MODE during the modifi cation to stop the modification.
Dimensions
Technical Service
Please E-mail your problem description to
service@icpdas.com when you have any questions.
More detail information: www.icpdas.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>