Square D H300 Micro Split Core On Off Current Switch Installation Guide
- June 12, 2024
- SQUARE D
Table of Contents
Installation Guide
Current Monitoring H300
Micro Split-Core On/Off Current Switch US Patent 7,193,428
(other patents pending) Z205622-0C
H300 Micro Split Core On Off Current Switch
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
-
Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
-
This equipment must only be installed and serviced by qualified electrical personnel.
-
Read, understand and follow the instructions before installing this product.
-
Turn off all power supplying equipment before working on or inside the equipment.
-
Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION -
Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious
injury.
A qualified person is one who has skills and knowledge related to the
construction and operation of this electrical equipment and the installation,
and has received safety training to recognize and avoid the hazards involved.
NEC Article 100
No responsibility is assumed by Veris Industries for any consequences arising
out of the use of this material.
NOTICE
- This product is not intended for life or safety applications.
- Do not install this product in hazardous or classified locations.
- The installer is responsible for conformance to all applicable codes.
- Mount this product inside a suitable fire and electrical enclosure.
Product Overview
The H300 is a current-sensitive switching device that monitors current (amperage) in the conductor passing through it. A change in amperage in the monitored conductor that crosses the switch threshold causes the resistance of the FET status output to change state, similar to the action of a mechanical switch. In this model, the threshold is fixed at 150 mA AC max. The status output is suitable for connection to building controllers, or other appropriate data acquisition equipment operating at up to 30 volts. The H300 requires no external power supply to generate its output.
Specifications
Sensor Power | Induced from the monitored conductor |
---|---|
Amperage Range | 0.15 to 60 A continuous |
Status Output Ratings | N.O. 1.0 A @ 30 Vac/dc not polarity sensitive |
Insulation Class | 600 Vac RMS (UL); 300 Vac (CE) |
Setpoint | Fixed at 0.15 A max. (60 Hz) |
Frequency Range | 50/60 Hz |
Temperature Range | -15 to 60 °C (5 to 140 °F) |
Humidity Range | 10-90% RH non-condensing |
Hysteresis | 10% typical |
Off State Resistance | Open switch represents 1+ MΩ |
On State Resistance | Closed switch represents <200 mΩ |
Terminal Block Max. Wire Size | 16 to 22 AWG (1.3 to 0.3 mm²) |
Terminal Block Torque | 7 in-lb (0.8 N-m) |
Mounting Location | Not suitable for wet locations. For indoor use only. |
COMPLIANCE INFORMATION
Agency Approvals| UL508, CE: EN61010-1
Installation Category| Cat. III, pollution degree 2
For CE compliance, conductor shall be insulated according to IEC 61010‑1.
Product design provides for functional insulation only.
Dimensions
Installation
Disconnect and lock out power to the enclosure containing the conductor to be monitored.
- Locate a mounting surface for the removable mounting bracket that will allow the monitored conductor to pass through the center window when it is installed and that will keep the product at least ½” (13 mm) from any uninsulated conductors. Determine cable routing for the controller connection, allowing wiring to reach the mounting location.
- Drill holes to mount the bracket to the chosen surface using the included screws.
- Wire the output connections between the sensor and the controller (solid-state contact).
- Snap the sensor over the wire to be monitored and push the latch until it is securely closed. Clip the assembly to the mounting bracket. Important: If there is a paper inhibitor sheet between the contacts, remove before use.
- Secure the enclosure and reconnect power.
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) current transformer (CT) as shown. This technique
can be combined with wrapping (see below) to add range for a low current load
on a high current source.
DANGER: 5A CTs can present hazardous voltages. Install CTs in accordance with manufacturer’s instructions. Terminate the CT secondary before applying current.
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center window and around the sensor
body to produce multiple turns. This increases the current measured by the
transducer. Program the controller to account for the extra turns (e.g., if
four turns pass through the sensor (as shown) divide the normal reading by 4).
CAUTION
RISK OF EQUIPMENT DAMAGE
-
Derate the product’s maximum current for the number of turns through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor -
Failure to follow these instructions can result in overheating and permanent equipment damage.
Troubleshooting
Problem | Solution |
---|---|
No Reading at Controller | • Check for control voltage at sensor (<30V) |
• Check for amperage in monitored conductor (> 0.15A)
• Assure that sensor core mating surfaces are clean and that the core clamp is
completely closed.
Z205622-0C
©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 /
support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the
Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries,
L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their
respective owners.
0619
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>