SQUARE D HRB73152 QO and QOB Dual Function Instructions

June 6, 2024
SQUARE D

SQUARE - LOGOSQUARE - LOGO 2

Instruction Bulletin
Replaces

QO™ and QOB Dual Function (DF) (Combination AFCI and GFCI Circuit Breaker) (Pigtail and Plug-on Neutral)
Retain for future use.

 DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION,  OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, NOM-029-STPS or CSA Z462 or local equivalent.
  •  This equipment must only be installed and serviced by qualified electrical personnel.
  •  Turn off all power supplying this equipment before working on or inside the equipment.
  • Always use a properly rated voltage sensing device to confirm power is off.
  •  Circuit breakers must only be supplied by grounded neutral electrical systems.
  •  GFCI must be installed and wired correctly. The GFCI circuit breaker must switch both ungrounded (HOT) conductors in order to provide ground-fault protection. Incoming line must be connected to load center bus.
  • Replace all devices, doors, and covers before turning on power to this equipment.
  • A circuit breaker with a ground-fault circuit interrupter does not protect people who contact both power wires or either power wire and the neutral.

Failure to follow these instructions will result in death or serious injury.
NOTE:

  •  This product meets the requirements for Class A ground-fault circuit protection.
  •  The pigtail version of this circuit breaker is for us in all NQ panelboards and QO™ load centers, except all versions of QO2, QO2-4, and QO3-5. All QO6-12 and QO8-16 versions require the use of #3 AWG (25 mm 2 ) max. line conductors.
  •  This arc-fault and ground-fault detection device is not designed or intended for use on circuits in which the neutral conductor is shared with other circuits. The circuit breaker will nuisance trip in “shared neutral” circuits.
  • QO plug-on neutral dual function circuit breaker may only be used in plug-on neutral load centers. NOTE: To minimize nuisance tripping:
  •  Do not connect circuit breaker to swimming pool equipment installed before the adoption of the 1965 National Electrical Code.
  •  Do not connect circuit breakers to electric ranges or clothes dryers whose frames are grounded by connection to a neutral conductor.
  •  Do not connect the circuit breaker to more than 250 ft. (76 m) of load conductor for the total one-way run.

Installation

See Figure 1
1. Turn off all power supplying this equipment before working on or inside the equipment.
2. Turn off the circuit breaker (A).
3. Remove panel trim.

QO™ and QOB Dual Function (DF) (Combination AFCI and GFCI Circuit Breaker)

NOTE: If using plug-on neutral PDF (QO1XXPDF), go to step 5.
4. Connect panel neutral (pigtail wire B; applies to pigtail version only) to load center or panelboard neutral bar. See load center or panelboard for torque value.
5. Strip insulation off wires to length (C) shown.
6. Connect load power (D) and load neutral (E). See Figure 1 or side of circuit breaker for torque value.
NOTE: The load neutral wire (E) and panel neutral (pigtail wire B; applies to pigtail version only) must be connected according to the preceding instructions for proper unctioning of the arc-fault and ground fault detection device. If plug-on neutral DF is installed, circuit breaker neutral connector must be mounted on load center neutral bar for
the proper functioning of arc-fault and ground-fault detection device. See Figure 1A.
7. Install circuit breaker into the panel and re-torque wire connectors. For bolt-on circuit breakers, tighten screw (F).
8. Re-install panel trim and attach supplied label (G) to panel so that it is visible with panel trim installed.
NOTE: If using plug-on neutral DF, the circuit breaker must be mounted to load the center neutral bar. See Figure 1A below.
NOTE: When using QO Neutral kit (QONK1, 2, 3, or 4) in a QO enclosure, do not install the CAFI circuit breaker in space adjacent to the installed neutral kit. When installed, the neutral kits may interfere with the proper installation of these circuit breakers.

FIG. 1: Installation

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Test each circuit breaker monthly. If the circuit breaker handle does not move to the center (tripped) position, turn the circuit breaker off and contact a qualified electrician. Failure to follow these instructions will result in death or serious injury.
NOTICE
HAZARD OF EQUIPMENT DAMAGE Megger®, high-voltage or hi-pot tests will damage circuit breaker. Turn off all power supplying the equipment and isolate the circuit breaker before testing. Failure to follow these instructions can result in equipment damage.
QO™ and QOB Dual Function (DF) (Combination AFCI and GFCI Circuit Breaker)
See Figure 2

  1. Test circuit breaker after installation following the procedure below. Test monthly thereafter.
  2.  Turn off all loads downstream of the circuit breaker.
  3.  Turn on power to load center or panelboard.
  4. Turn circuit breaker handle (A) to ON.
  5.  Press the test button (B). If the circuit breaker handle does not move to the center (tripped) position (C), turn the circuit breaker off and contact a qualified electrician.

NOTE: For qualified electricians only. Press the test button (B). If the circuit breaker handle (C) does not move to the center (tripped) position, remove the load wires and repeat steps 1-5. If the circuit breaker handle (C) still does not move to the center (tripped) position, recheck circuit breaker wiring and installation. Replace the circuit breaker if no other issues are found. If the circuit breaker DOES trip after removing the load wires, do not remove the circuit breaker and troubleshoot the branch circuit.

6. Reset circuit breaker by moving handle fully to OFF position and then moving to ON position.
7. Turn loads downstream of circuit breaker back on.

FIG. 2 : Circuit Breaker TestingSQUARE D HRB73152 QO and QOB Dual
Function - FIG 2

Troubleshooting

PDF Fault Indication Procedure
The DF circuit breaker provides continuous fault protection. Should a fault occur during the indication procedure, the DF circuit breaker will interrupt the fault and protect the circuit.

  1.  Place the circuit breaker in the O/OFF position.
  2. Firmly press and continue holding the white ‘TEST’ button-through Step 4.
  3.  Move handle to I/ON position.
  4. The circuit breaker should trip at one of the following times.
Trips Instantly (less than 1 second) Fault to Ground
Trips at 2.0 seconds Arc Fault
Trips at 5.0 seconds Procedure Complete Includes: no-fault, thermal overload,

shortcircuit

To reset Fault Indication:
• Perform the CAFI Fault Indication Procedure a total of 6 times.
• Verify by performing CAFI Fault Indication
The procedure with a trip at 5.0 seconds (Procedure Complete) result.
An automatic reset of Fault Indication will occur if the CAFI circuit breaker has been powered continuously for 27 days.
Removal

  1.  Turn OFF (O) the circuit breaker. Remove the wires.
  2. To disconnect the plug-on jaw from the connector and mounting rail, lift the line-end (1) of the circuit breaker until the circuit breaker jaw disconnects from the bus bar. Continue lifting until the load-end (2) disengages from the mounting rail. See Figure 3A.
  3. If a circuit breaker is not replaced, install a QOFP filler plate (not provided) to fill an opening in the panel.
    NOTE: Do not use a twisting motion to remove the circuit breaker, or equipment damage may result. See Figure 3B.

SQUARE D HRB73152 QO and QOB Dual Function - FIG

NOTE: For additional troubleshooting information, please visit our website at www.Schneiderelectric.com or call our Product Support Team at 1-888-SquareD (1-888-778-2733). Federal Communications Commission Radio Frequency Interference Statement

Federal Communications Commission Radio
Frequency Interference Statement
This circuit breaker has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This circuit breaker generates, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there isno a guarantee that interference will not occur in a particular installation. If this circuit breaker does cause harmful interference to radio or television reception, the user is encouraged to try to correct the interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the circuit breaker and receiver.
  • Connect the receiver into an outlet on a circuit different from that to which the circuit breaker is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

Do not make changes or modifications to the device which are not expressly approved by Square D. Any changes or modifications may result in the loss of authority to operate the equipment.

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any  consequences  rising out of the use of this material. Schneider Electric and Square D are trademarks and the property of Schneider Electric SE, its subsidiaries, and affiliated companies. All other trademarks are the property of their respective owners.

Schneider Electric USA, Inc.
800 Federal Street
Andover, MA 01810 USA
888-778-2733
www.schneider-electric.us

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals