legrand 6ATC2PAVSN Evolution Series 6 Poke Thru Surface Assembly Owner’s Manual

June 12, 2024
Legrand

legrand 6ATC2PAVSN Evolution Series 6 Poke Thru Surface Assembly

legrand-6ATC2PAVSN-Evolution-Series-6-Poke-Thru-Surface-Assembly-
PRODUCT`

Product Information

The EvolutionTM Series 6 Poke-Thru Devices are designed for both retrofit and new construction projects. These devices provide convenient access to power, communications, and audio/video services that are recessed below floor level, ensuring maximum device protection. The devices feature three gangs of capacity, allowing you to configure services according to the needs of your space. You can place services in any location within the unit. The low-profile durable metal covers are available in seven finishes, allowing them to seamlessly match any space. The covers also have sliding doors that enable cables to neatly egress from the unit, protecting cables and reducing tripping hazards. Evolution Series 6 Poke-Thru devices are suitable for meeting and training rooms, classrooms, healthcare facilities, and commercial buildings with open-space architecture.

Product Usage Instructions

Cabling Specifications
The copper cross-sectional area determines the wire fill capacity in a poke-thru device. The EvolutionTM Series 6 Poke-Thru Devices are UL Classified to U.S. and Canadian safety standards.

Copper Cross-Section Max # Conductors
Outer Channels: 0.0154 sq. in. (9.9mm2) (3) 12 AWG
Center Channel: 0.0387 sq. in. (24.97 mm2) (12) 14 AWG
Power Data Channel (Center): 0.0815 sq. in. (52.6mm2) (10) 10 AWG
Data Channel (Outside): 0.0187 sq. in. (12.1 mm2) (22) Cat. 6a
(5) Cat. 6a

Note: When using conductor sizes other than those listed above, ensure that the aggregate cross-sectional area of the copper conductors does not exceed the listed cross-sectional area.

Flooring Specifications
The EvolutionTM Series 6 Poke-Thru Devices are suitable for different floor types and core hole sizes:

  • Covered Floors (Carpet, Tile or Wood): Minimum core size of 6″ (152mm) and maximum core size of 6 1/8″ (154mm)
  • Bare Concrete or Terrazzo: Minimum and maximum core size of 6″ (152mm)

Caution: These devices are suitable for 1-, 1 1/2-, and 2-hour rated floor assemblies as described in the UL Fire Resistance directory for each service.

Evolution Series – The Most
Innovative Poke-Thru Devices in the Market Designed for retrofit and new construction, Evolution Series 6” Poke- Thru devices provide convenient access to power, communications, and audio/video services recessed below floor level – providing maximum device protection. With three gangs of capacity that allow you to configure services for the needs of your space, services can be placed in any location within the unit. The low-profile durable metal covers are available in seven finishes, designed to match any space. The cover also features sliding doors that allow cables to neatly egress from the unit, protecting cables while reducing tripping hazards.Evolution Series 6” Poke- Thru devices are the perfect fit for meeting and training rooms, classrooms, healthcare facilities or commercial buildings with open-space architecture

Features & Benefits

  • Recessed devices. Three (3) compartments for power, communications, and/or A/V devices, all recessed 4″ (102mm) below the floor level, providing maximum protection and device longevity.
  • Die-cast aluminum cover assemblies. The Evolution Series poke-thru design includes all metal die-cast aluminum cover assemblies, available in powder coated finishes of black, gray, bronze, and aluminum, as well as a brushed aluminum, satin brass plated and satin nickel plated finishes.
  • A/V compatible design. The 6AT Series devices are designed to work with with Legrand’s AVIP devices. Also compatible with most A/V manufacturers devices including their 1-gang decorator style design.
  • Flush tile version cover assemblies. A flush style cover for tile applications allows the Evolution Series Poke-Thru
  • Devices to be adjusted to the same level as the top surface of the floor covering. The tile cover is designed to be used in higher traffic applications, where a low profile is a must.
  • Auto-close egress doors. Egress doors lock in position when slid open and automatically close around cables, reducing the egress opening to the smallest size possible.
  • Improved hinge design. Provides greater durability while creating a more fluid, intuitive, opening and closing motion.
  • “Step-on-it” installation. Quick, easy installation without the need for additional fasteners or a second installer.
  • Added furniture feed capacity. The 6ATCFF Series Poke-Thru Device offers the largest dual service furniture feed capability on the market.
  • Pre-pour sleeve. Creates a cast-in-place core hole that allows the contractor to position poke-thru units before concrete is poured. Eliminates the cost and labor of coring the opening.
  • TopGuard™ Protection. All Evolution Series Poke-Thru Devices, like every Wiremold Poke-Thru Device, meet andexceed UL scrub water exclusion requirements for tile, carpet, and wood covered floors.
  • Meets ADA Accessibility Guidelines. Wide trim flange is designed to meet the ADA Accessibility Guidelines as it pertains to ADA Standard 4.5 which addresses changes in floor and ground surface levels. The poke-thru trim flanges are beveled so the slope is no greater than 1:2 ratio.
  • Suitable for use in air handling spaces. In accordance with Sec 300-22(C) of the National Electrical Code.
  • UL Listed and UL Fire Classified to U.S. and Canadian safety standards. UL Fire rated for up to 2-hour rated floors maintains the fire classification of the floor.

Vertical Markets

  • Commercial
  • Hospitality
  • Education
  • Entertainment
  • Healthcare
  • Retail

Compliance
WIREMOLD® Evolution™ Series 6″ Poke-Thru Devices cULus Listed, Metallic Outlet Box File Number E2961. Guide QCIT. cULus Listed Nonmetallic Outlet Boxes & Fittings Classified for Fire Resistance: File R8209, Guide CEYY.

Cabling Specifications

Copper Cross Section: The copper cross-sectional area determines the amount of wire fill capacity in a poke-thru device. Unlike other wire and cable management systems that utilize wire fill capacity, a poke-thru device is UL tested under fire conditions to determine themaximum amount of copper conductors that will pass through a poke-thru device, while maintaining the fire-rating of the floor assembly. All Legrand Poke-ThruDevices are UL Classified to U.S. and Canadian safety standards.

6AT COPPER CROSS-SECTION

OUTER                       CENTER

CHANNELS                  CHANNEL


Max Copper X-Section| 0.0154 sq. in. (9.9mm2)| 0.0387 sq. in.

(24.97 mm2)

Max # Conductors| (3) 12 AWG| (12) 14 AWG

6ATCFF COPPER CROSS-SECTION – FURNITURE FEED POKE-THRU DEVICES

POWER       DATA CHANNEL    DATA CHANNEL

CHANNEL          (CENTER)| (OUTSIDE)
Max Copper X-Section| 0.0815 sq. in. (52.6mm2)| 0.0686 sq. in.

(44.3 mm2)

| 0.0187 sq. in.

(12.1 mm2)

Max # Conductors| (10) 10 AWG| (22) Cat. 6a| (5) Cat. 6a

NOTE: When using conductor sizes other than listed above, the aggregate cross-sectional area of the copper conductors shall not exceed the cross- sectional area listed.

Copper Cross-Sectional Area of

Commonly Used Conductors


Size| Solid

24| 0.00032 sq. in.         (.206mm2)

23| 0.00040 sq. in.        (.258mm2)

22| 0.00050 sq. in.        (.322mm2)

14| 0.00323 sq. in.      (2.083mm2)

12| 0.00512 sq. in.       (3.303mm2)

10| 0.00815 sq. in.      (5.258mm2)

8| 0.01296 sq. in.       (8.361mm2)

NOTE: Use above values for solid or stranded conductors.

Flooring Specifications

6AT CORE HOLE SIZES

FLOOR                       CORE                         CORE

TYPE                     SIZE (Min.)                 SIZE (Max.)


Covered Floors (Carpet, Tile or Wood)| 6″| (152mm)| 6 1/8″| (154mm)
Bare Concrete or Terrazzo| 6″| (152mm)| 6 1/8″| (154mm)

CAUTION: These devices are suitable for 1-, 1 1/2-, and 2-hour rated floor assemblies as described in the UL Fire Resistance directory for each service. These devices meet all UL scrub water requirements, but are not suitable for wet or damp locations, or other areas subject to saturation with water or other liquids, such as commercial kitchens.

  • Floor Coverings: The poke-thru device is fire rated for concrete floor coverings. For floor coverings greater than 1″ (25mm), consult factory.
  • UL Certification: To view the UL certification, please visit www.UL.com/Database. Enter “Wiremold” as the company name and “CEYY” as the UL Category Code.

Poke-thru devices and abandonment fittings are for use with 1-, 1 1/2-, or 2-hour rated unprotected reinforced concrete floor and 1-, 1 1/2- or 2-hour rated floors employing unprotected steel floor units and concrete topping (D900-Series Designs), or concrete floors with suspended ceilings. (Fire resistive designs with suspended ceilings should have provisions for accessibility in the ceiling area below the poke-thru fittings.) The assembled Poke-Thru stem and service fitting or the abandonment fittings will not reduce the ratings of the floor assembly when the thickness and type of concrete (required for the specific rating) are within the specified limits and the fittings are installed as specified:

  1. Spacing – Minimum of 2′ (610mm) OC and not more than one unit per 65 square feet (6 square meters) of floor area in each span.
  2. Concrete – Minimum thickness of structural concrete topping of 2 1/4″ (57mm) over metal deck or a minimum 3″ thick reinforced concrete slab. Unit weight of concrete to be 110 to 155 pcf.
  3. Installation – Mounted in a 6″ (152mm) diameter core drilled hole in concrete per installation instructions accompanying the fittings or abandonment fittings. For use with power circuits, data and/or telephone cables as tabulated below

NOTE: The material that is used in Wiremold® poke-thru devices is not listed under the directory for Fire Stopping Material because the pokethrudevice is UL Classified as “Outlet Boxes and Fittings Classified For Fire Resistance (CEYY)”. The pass/fail criteria comes from UL263. The pass criteria is that the poke-thru unit cannot exceed 325° F. above ambient before the concrete slab (or deck) reaches this same temperature. Some poke-thru devices are tested for 2 hours while others are tested for 4 hours. The intumescent material has never been tested as a fire-stopping material as a stand-alone device. This material is designed to work as a unit with the entire poke-thru device.

Evolution Series

Evolution Series 6″ Poke-Thru Devices Ordering Informationlegrand-
6ATC2PAVSN-Evolution-Series-6-Poke-Thru-Surface-Assembly-FIG-1
\(2\)

NOTE: For more information on Device Plates and Bottom Feed Plates and on the additional options available, see the Device Plates and Bottom

  • Feed Plates sections found later in this document.
  • Tunneling extends from the 5BLH to 575CHA so that power cables from the 20A duplex receptacle mounted on the left side of the poke-thru device are run into the junction box attached to the 575CHA.
  • Also includes junction box attached to the 3/4″ conduit.

legrand-6ATC2PAVSN-Evolution-Series-6-Poke-Thru-Surface-Assembly-FIG-1
\(3\)

NOTE: For more information on Device Plates and Bottom Feed Plates and on the additional options available, see the Device Plates and Bottom

  • Feed Plates sections found later in this document.
  • Tunneling extends from the 5BLH to 575CHA so that power cables from the 20A duplex receptacle mounted on the left side of the poke-thru device are run into the junction box attached to the 575CHA.
  • Also includes junction box attached to the 3/4″ conduit.legrand-6ATC2PAVSN-Evolution-Series-6-Poke-Thru-Surface-Assembly-FIG-1 \(4\)

NOTE: For more information on Device Plates and Bottom Feed Plates and on the additional options available, see the Device Plates and Bottom

  • Feed Plates sections found later in this document.
  • Tunneling extends from the 5BLH to 575CHA so that power cables from the 20A duplex receptacle mounted on the left side of the poke-thru device are run into the junction box attached to the 575CHA.
  • Also includes junction box attached to the 3/4″ conduit.

legrand-6ATC2PAVSN-Evolution-Series-6-Poke-Thru-Surface-Assembly-FIG-1
\(5\)

NOTE: For more information on Device Plates and Bottom Feed Plates and on the additional options available, see the Device Plates and Bottom

  • Feed Plates sections found later in this document.
  • Tunneling extends from the 5BLH to 575CHA so that power cables from the 20A duplex receptacle mounted on the left side of the poke-thru device are run into the junction box attached to the 575CHA.
  • Also includes junction box attached to the 3/4″ conduit.

legrand-6ATC2PAVSN-Evolution-Series-6-Poke-Thru-Surface-Assembly-FIG-1
\(6\)

NOTE: For more information on Device Plates and Bottom Feed Plates and on the additional options available, see the Device Plates and Bottom

  • Feed Plates sections found later in this document.
  • Also includes junction box attached to the 3/4″ conduit.

legrand-6ATC2PAVSN-Evolution-Series-6-Poke-Thru-Surface-Assembly-FIG-1
\(7\)

NOTE: For more information on Device Plates and Bottom Feed Plates and on the additional options available, see the Device Plates and Bottom

  • Feed Plates sections found later in this document.
  • Also includes junction box attached to the 3/4″ conduit.

legrand-6ATC2PAVSN-Evolution-Series-6-Poke-Thru-Surface-Assembly-FIG-1
\(8\)

NOTE: For more information on Device Plates and Bottom Feed Plates and on the additional options available, see the Device Plates and Bottom

  • Feed Plates sections found later in this document.
  • Also includes junction box attached to the 3/4″ conduit.

legrand-6ATC2PAVSN-Evolution-Series-6-Poke-Thru-Surface-Assembly-FIG-1
\(9\)

NOTE: For more information on Device Plates and Bottom Feed Plates and on the additional options available, see the Device Plates and Bottom

  • Feed Plates sections found later in this document.
  • Also includes junction box attached to the 3/4″ conduit.

legrand-6ATC2PAVSN-Evolution-Series-6-Poke-Thru-Surface-Assembly-FIG-1
\(10\)

NOTE: For more information on Device Plates and Bottom Feed Plates and on the additional options available, see the Device Plates and Bottom

  • Feed Plates sections found later in this document.
  • Also includes junction box attached to the 3/4″ conduit.

legrand-6ATC2PAVSN-Evolution-Series-6-Poke-Thru-Surface-Assembly-FIG-1
\(11\)

NOTE: For more information on Device Plates and Bottom Feed Plates and on the additional options available, see the Device Plates and Bottom

  • Feed Plates sections found later in this document.
  • Also includes junction box attached to the 3/4″ conduit.

legrand-6ATC2PAVSN-Evolution-Series-6-Poke-Thru-Surface-Assembly-FIG-1
\(12\)

NOTE: For more information on Device Plates and Bottom Feed Plates and on the additional options available, see the Device Plates and Bottom

  • Feed Plates sections found later in this document.
  • Also includes junction box attached to the 3/4″ conduit.

legrand-6ATC2PAVSN-Evolution-Series-6-Poke-Thru-Surface-Assembly-FIG-1
\(13\)

NOTE: For more information on Device Plates and Bottom Feed Plates and on the additional options available, see the Device Plates and Bottom

  • Feed Plates sections found later in this document.
  • Also includes junction box attached to the 3/4″ conduit.

legrand-6ATC2PAVSN-Evolution-Series-6-Poke-Thru-Surface-Assembly-FIG-1
\(14\)

  • NOTE: All surface style poke-thru devices come with a transition angle to aid in the change in floor elevation.
  • NOTE: All surface style poke-thru devices come with a transition angle to aid in the change in floor elevation.

Evolution Series 6″ Poke-Thru Devices Cover Assemblies Ordering Information legrand-6ATC2PAVSN-Evolution-Series-6-Poke-Thru-Surface-Assembly-FIG-1
\(15\)

Evolution Series Heavy Duty 6″ Round Cover Assemblies Ordering Information legrand-6ATC2PAVSN-Evolution-Series-6-Poke-Thru-Surface-Assembly-FIG-1
\(16\)

Evolution Series 6″ Poke-Thru Devices Center Mount Device Plates Ordering Informationlegrand-6ATC2PAVSN-Evolution-Series-6-Poke-Thru-Surface-Assembly-
FIG-1 \(17\)

Evolution Series 6″ Poke-Thru Devices Side Mount Device Plates Ordering Informationlegrand-6ATC2PAVSN-Evolution-Series-6-Poke-Thru-Surface-Assembly-
FIG-1 \(18\)

Evolution Series 6″ Poke-Thru Devices Bottom Feed Device Plates Ordering Informationlegrand-6ATC2PAVSN-Evolution-Series-6-Poke-Thru-Surface-Assembly-
FIG-1 \(19\)

CAUTION: Receptacle supplied with this Poke-Thru is not suitable for direct field wiring. Contact manufacturer for replacement. Field modifications will void UL Listing and Classification. Replacement receptacle is limited to this manufacturers’ Catalog No 68REC.legrand-6ATC2PAVSN-Evolution-Series-6
-Poke-Thru-Surface-Assembly-FIG-1 \(20\)

NOTE: All brand and product names referenced in this document are registered trademarks or trademarks of their respective holders.

CONTACT

  • Legrand, North America
  • 60 Woodlawn Street
  • West Hartford, CT 06110
  • 1.877.BY.LEGRAND (295.3472)
  • www.legrand.us.
  • Canada
  • 905.738.9195
  • www.legrand.ca.

Download this product’s PEP ecopasport® environmental product declaration at www.legrand.us/resources-and-downloads. This declaration conforms with ISO 14025 and 14040 and is in alignment with EN 15804.
For more information or to configure your own Evolution™ Series Poke-Thru Device, visit our online configurator at: www.legrand.us/wiremold/evolution. CS3080 — Updated January 2023 — For latest specs visit www.legrand.us/wiremold. The interior of the Evolution™ Series 6″ Poke-Thru Device.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals